1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

Embed Size (px)

Citation preview

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    1/180

    ARMY TM 5-683NAVY NAVFAC MO-116

    AIR FORCE AFJMAN 32-1083

    FACILITIES ENGINEERINGELECTRICAL INTERIOR FACILITIES

    APPROVED FOR PUBLIC RELEASE: Distributioni s un l imi ted

    DEPARTMENTS OF THE ARMY, THE NAVY, AND THE AIR FORCENOVEMBER 1995

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    2/180

    REPRODUCTION AUTHORIZATION/RESTRICTIONS

    This manual has been prepared by or for the Government and is

    public property and not subject to copyright.

    Reprints or republication of this manual should include a credit sub-

    stantially as follows: J oint Departments of the Army, the Navy andthe Air Force, USA, Technical Manual TM 5-683/NAVFAC

    MO-116/AFJ MAN 32-1083, Electrical Interior Facilities, 30 November

    1995.

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    3/180

    TM 5-68NAVFACMQ-11

    AFJMAN 32-108

    TECHNICAL MANUAL NO. 5-683 H E A D Q U A R T E R S

    NAVY MANUAL NAVFAC MO-116 DEPARTMENT OF THE ARMY,

    THE NAVY, AND THE AIR FORC

    AIR

    FORCE

    MANUAL

    AFJ MAN 32-1083W A S H I N G T O N, DC, 30 November 199

    ELECTRICAL INTERIOR FACILITIES

    cHAPTER 1.

    2.

    3.

    4.

    5.

    6.

    7.

    8.

    I N T R O D U C T I O NP urpose a nd s cope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Codes a nd s pecifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Ma inten a nce requiremen ts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Records . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    P riority a nd schedu ling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Ha za rds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    SWITCHG EAR ASSE MBLI ES 600V OR LES S

    P eriodic maint ena nce . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Meta l enclosures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    B us ba r a nd t ermina l conn ections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Un der floor ducts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Bu swa ys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    P ower circuit br eakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Netw ork protectors.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Auxiliar y sw itch gea r equipmen t. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Switchgear trouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .TRANSFORMERS

    Sm all pow er tr an sformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Dr y-type t ra nsform ers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    ELECTRIC MOTORS

    Ma inten a nce of electric motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Altern at ing curr ent (AC) motors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Dir ect current (DC) motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Motor operat ing considera tions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Motor insu lat ion testin g . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Motor t rouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    MOTOR CONTROLS

    Fun ctions o motor contr ols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Types of motor contr ols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Component s a nd m a intena nce of motor contr ols. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    P reventive ma intena nce an d tr ouble-shooting guid e . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    POWER CABLES

    Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Visua l inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Cable insulation testing ...... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Over potentia l testin g. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Ca ble trouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    SOLID-STATE ELECTRONIC EQUIPMENT

    Solid-sta te ma inten an ce. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Solid-state components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Electrical disturbances (power quality) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Dist urba nce meas urement a nd m onitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Volta ge surge su ppression . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    G R O U NDI NG

    G round m ain tena nce. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Types of ground ing sy stems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    G round fa ult int errupt ing meth ods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    P a r a g r a p h

    11

    1-2

    1-3

    1-41-5

    1-61-7

    2-1

    2-22-32-42-52-62-72-82-9

    3-13-2

    4-14-24-3

    4-44-54-6

    5-15-25-35-4

    6-16-26-36-46-5

    71

    7-27-37-47-5

    8-l8-18-3

    P a g e

    11

    1-1

    111-1

    1-11-21-2

    2-1

    2-12-22-22-22-32-102-122-16

    3-13-1

    4-14-14-13

    4-204-244-24

    5-15-15-66-15

    6-l6-l6-16-26-5

    7 17-17-77-77-8

    8-18-18-9

    *This manual supersedesTM 5-683/NAVFAC MO-116/AFM 91-17, dated 2 March 1972

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    4/180

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    5/180

    TM 5-683/NAVFAC MO-116/AFJMAN 32-108

    LIST OF FIGURES(cont'd)

    Figure 211. Lar ge cell for a st at ionar y ba tt ery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3-1. Dry-type tr a nsform er. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-1. Cut a wa y view of squirr el-cage ind uction motor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-2. Cut aw ay view of w ound-rotor induction m otor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-3. Cut aw a y view of syn chronous mot or . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-4. Pr ima ry pa rts of an AC induction m otor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-5. Clean ing a nd dr ying m otors in pla ce . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-6. Bea ring in sta llat ion precaut ions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-7. Constr uction of ball a nd r oller bea rings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-8. Gr eas ing bea rings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-9. Typical sleeve bear ings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-10. Cuta wa y view of a typica l DC motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-11. Main t ypes a nd connections of D Cmot ors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-12. Arma tur e of a la rge DC motor on st an ds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-13. Inspecting a nd inst alling br ushes on a larg e DC motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-14. Cuta wa y section of a commut a tor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-15. Bru sh " cha tt eract ion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-16. Poor commuta tor conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-17. Good commutator films.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-18. Exam ple of eccentric commuta tor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-19. Dial ga uge to mea sure commut a tor concentricity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-20. Common und ercuttin g mist a kes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4-21. Connections for test ing mot or insula tion resist a nce. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-1. Man ua l sta rt ers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-2. Typical ma gnetic st a rter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-3. Combina tion st a rter s in NE MA enclosures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-4. Coordination of motor overload relay and current limiting fus e. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-5. Autot ra nsform er sta rter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-6. Resista nce sta rt er. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-7. Pa rt-Winding s ta rt er. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-8. Solid St at e sta rt er . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-9. Typical motor control center . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-10. Cuta wa y view of typical molded case circuit breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-11. Molded cas e circuit brea ker tim e-current curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-12. Fuse ma inten an ce practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-13. Underwriters Laboratories Cartridge fuse classification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-14.Typica l t herm al overloa d . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-15. Typical hea ter s election t a ble for therm al overload device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5-16. A NE MA size 6 ma gnet ic conta ctor (courtesy of Siemen s-Allis) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6-1. Connections for test ing low volta ge cable insulat ion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    71. Typical ca pacitor t ypes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    7-2. Diodes a nd SC Rs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    73. Cha ra cterist ics of diodes an d Zeners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    7-4. Testing Zener volta ge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    75. Tra nsist or test ing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    8-1. Typical equipm ent g round . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    8-2. Typical grounding sy stem for a building an d its a ppara tus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    8-3. Methods of system ground ing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    8-4. Methods o fsolidly groundin g th e neutra l of three-phase syst ems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    8-5. Methods of resistance grounding the neut ra l of three-phase sy stems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    8-8. Gr ounding for electronic a nd ADP syst ems.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    8-7. Gr ound fa ult circuit int errupt er operat ion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    9-1. Prehea t fluorescent lam p an dfixture components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    9-2. Mercury la mp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    9-3. Trouble-shooting flu orescent lightin g . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    10-1. Sa mple comput er-ba sed fire detection sys tem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    10-2. Cla ss A a nd B fire detection circuits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    121. P a dlock and mult iple lock ad apt er . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    122. Typical safety tag. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    123. Ground cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    12-4. Grounding clamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    125. Ey e an d fa ce protection selection guide.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-1. Set-up for mea surin g AC volta ge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    13-2. Set-up for measuring resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    P a g e

    2-1

    3-2

    4 -8

    4 -9

    4-14-1

    4-1

    4-1

    4-1

    4-1

    4-1

    4-1

    4-1

    4-1

    4-1

    4-1

    4-2

    4-2

    4-2

    4-24-2

    4-2

    4-2

    5 -2

    5-2

    5-3

    5-4

    5-5

    5 -6

    5-7

    5 -8

    5-9

    5-1

    5-1

    5-15-1

    5-1

    5-1

    5-1

    6 -2

    7 -3

    75

    7 -6

    7-6

    7-8

    8 -3

    8-4

    8-5

    8 -6

    8 -6

    8-1

    8-1

    9-2

    9-3

    9-4

    10-2

    10-3

    122

    122

    123

    12-4

    12-6

    13-4

    13-5

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    6/180

    TM 5-683/NAVFAC MO-116/AFJMAN 32-1083

    LIST OF FIGURES (contd)

    Figure 13-3.

    13-4.

    13-5.

    14-1.14-2.

    14-3.

    14-4.

    14-5.

    14-6.

    14-7.

    14--6.

    14-9.

    14-10.

    14-11.

    Ta ble 2-1.2-2.

    4-1.

    4-2.

    4-3.

    4-4.

    4-5.

    5-1.

    5-2.

    6-1.

    6-2.

    71.

    9-1.

    10-1.

    111.

    13-1.14-1.

    14-2.

    15-1.

    15-2.

    15-3.

    1.54.

    Set-up for testin g pha se sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Megohmmeter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..........

    Diagram of megohmmeter connections.... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Comp a r i s on o f wa t e r f low w i t h e le c t r i c c u r re n t . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Curves showing components of measured current during insulation testing . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Typical curves show ing dielectric absorption effect in a time-resistence or double-read ing t est . . . . . . . . . . .

    Resistive components of a made electrode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    S o i l r e s i s t i v i t y v s m o i s t u r e c o n t e n t o f r e d c l a y s o i l . . . . . . . . . . . . . . . . . . . . . . . . -

    Soil resistance vs temperature of clay soil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Soil resistance vs depth of electrode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Ea rth electrode w ith h emispheres . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Fall-of-potential method graph. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Sampling the cell electrolyte . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Reading the hydrometer f loat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    LIST OF TABLES

    U.S. s ta ndard bolt t orgues for bus connections heat t reated steel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Trouble-shooting procedures for switchgear equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Motor application guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Nam eplate voltage ra tings of sta nda rd induction motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    AC synchronous motor trouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..........

    DC motor generator trouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Motor control preventat ive maintenance guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Motor control trouble-shooting chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -

    Condu ctor sizes, insula tion th ickness, test voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Cable maintenance overheating problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    P ower q ua lity problems su mm ar y .. ...--. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Lamp trouble-shooting guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....

    Comparison of fire detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Common tra de nam es for P CB by ma nufa cturers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Tools an d equipment for effective electrical m ain tena nce . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..Interpreting insulation resistance test results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Condit ion of insu lat ion indicat ed by dielectric absorption r at ios . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    P ercenta ge of failure cau se since ma inta ined.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Equipment fa ilure rate mult ipliers vereus maintenance quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Int erior wirin g a nd light ing sys tem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Electric motors a nd controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    P a g e

    13-6

    13-7

    13-7

    14-2

    14-2

    14-3

    14-5

    14-5

    14-6

    14-6

    14-6

    14-7

    14-s

    14-9

    P a g e

    2 -32-17

    4 -2

    4-24

    4-26

    4-33

    4-36

    5-17

    5-19

    6 -6

    6-7

    79

    9 -6

    10-4

    112

    12-2

    14-3

    14-4

    15-2

    15-2

    15-3

    15-5

    i v

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    7/180

    TM5-683/NAVFAC MO-116/AFJMAN 32-1083

    CHAPTER 1

    INTRODUCTION

    1-1. Purpose and scope.

    This ma nua l provides guidance to facil i t ies ma inte-

    na nce personnel in the ma intena nce of interior elec-

    trical systems of 600 volts and less. These systems

    include such components as illumination, low volt-

    age syst ems, rotat ing equipment, motor control cen-

    te r s , so l id-s t a te equ ipment , t r ans f o rmers , and

    switchgear . It also a pplies to low volta ge controlled

    devices on high-voltage systems. The procedures

    presented in this manual are basic and can be ap-

    plied to the equipment of any manufacturer. De-

    tailed information and instructions should be ob-

    tained from the instruction book for the particulartype of equipment being serviced.

    1-2. References.

    Appendix A cont a ins a list of references used in this

    m a nu a l .

    1-3. Codes and specifications.

    Maintenance on electrical systems and equipment

    must ad here to the codes and specif icat ions a s they

    apply to the work to be performed. Also, manufac-

    turers maintenance instructions which accompany

    select electrica l components m ust be applied in con-

    junction with the codes and specifications listed be-

    low and the departmental specif ications l isted in

    appendix A.

    a. The National Electrical Code [National Fire

    P rot ection Associat ion #70 (NF P A 70)]. This code is

    the most w idely a dopted set of electrical sa feguard-

    ing practices. It defines approved types of conduc-

    tors and equipment, acceptable wiring methods,

    mandatory and advisory rules, operating voltages,

    limitations on loading of conductors, required work-

    ing spaces, methods of guarding energized parts ,

    interrupting capacity requirements of system pro-tective and control devices, requirements for con-

    nections and splices, insulation resistance require-

    ments, a nd grounding requirements.

    b. Recommended Practice for Electrical Equip-

    ment Maintenance (NFPA 70 B).

    C. A m e r i c a n N a t i o n a l S t a n d a r d s I n s t i t u t e /

    Insti tute of Electrical and Electronics Engineers

    St a nda rd (ANS I/IE EE St d.) cha pter 15, 242-1986,

    IEEE Recommended Pract ice for Protect ion and Co-

    ordinat ion of Industria l and Commercial Power Sys-

    tems. This code provides preventive maintenance

    practices for electrical systems a nd equipment usedin industrial-type applications.

    1-4. Maintenance requirements.

    Preventive maintenance should not be confused

    with repairs af ter a breakdown. The definition of

    maintenance implies that the equipment or system

    is inspected to discover i ts weaknesses and then

    repair or replace the necessary elements before a

    breakdown occurs. A maintenance program for pro-

    tective devices and the electric system could be di-

    vided into the following steps: inspecting, cleaning,

    tightening, lubricat ing, testing, a nd r ecording.

    a. The effectiveness of the distribution system is

    measured in t erms of volta ge regula tion, power fac-

    tor, load balance, reliability, efficiency of operation,

    and costs. To ensure the systems efficiency, lessen

    failures, and maximize safety, an effective mainte-

    nance program must be employed. This program

    should in clude an d/or consider t he follow ing:

    (1) Scope of work.

    (2) Intervals of performance.

    (3) Meth ods of a pplica tion.(4) Safety requirements, practices and proce-

    dures.

    (5) Adherence to codes, specifications and di-rectives.

    (6) Maintenance management procedures re-

    garding tools, records, and follow-up procedures.

    (7) Ha zar ds associat ed with w ork and the fa cil-

    i ty .

    (8) Emergency operating instructions.

    (9) Requirements for periodic review to deter-

    mine addit iona l loading in circuits such a s in fam ily

    housing, bachelor quarters, and maintenance and

    administrat ive bui ldings.

    b. A well executed maintenance program will

    provide benefits in t erms of:

    (1) Economic operation.

    (2) Improved safety.

    (3) Longer equipment life.

    (4) Reduced repair and overhaul time.

    (5) Fewer unplanned outages.

    (6) Early detection of undesirable changes in

    the power syst em.

    (7) Improved operation of the facility.

    1-5. Records.

    A good record keeping system is essential for safe,

    efficient a nd economical operat ion of electr ical fa cil-

    i t ies and for planning and executing an effective

    1-1

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    8/180

    TM5-683/NAVFAC MO-116/AFJMAN 32-1083

    prevent ive maintenance program. I t i s recom-

    mended to use the Work Information Management

    Syst em (WIMS) or other da ta -aut omated systems t o

    keep records rather than paperwork f i les. Suitable

    forms and reports requirements should be devel-

    oped to suit local needs. When facilities are built,

    instruction documents and spare parts l is ts for al lequipment installed should be obtained prior to

    beneficial occupancy acceptance.

    a. In addition to charts , work orders, and real

    property records, the following records have been

    found useful in analysis and correction of recurring

    trouble areas.

    (1) Diagrams. Accurate single-line and sche-ma tic diagra ms of the distribution system should be

    readily accessible in the electrical shop. These are

    essential references when switching circuits and re-

    routing electric power in emergencies. Such dia-

    grams also provide a simple means of locating facil-

    ities and determining the characteristics of electricsupply to buildings requiring maintenance. Electri-

    cal personnel must have access to latest "as-built "

    building drawings for use in tracing out circuitry

    within buildings.

    (2) Equi pment l i sts/ logs. These lists should bemaintained on all i tems of equipment such as mo-

    tors, motor controllers, meters, panelboards, electri-

    cal controls, and switchgear. Lists should reflect

    detailed information such as the density of al l l ike

    it em s, i t e m r a t i n g s a n d p h y si ca l l oc a t i on s .Lists/logs w ill fa cilita te scheduling of in spections

    and maintenance services.

    (3) Equipment maintenance records. Theserecords should be maintained on every individual

    i tem of electrical equipment that requires mainte-

    nance services. Records should include detailed in-

    formation such as scheduled maintenance and in-

    spect ion requ i rements , p rev ious tes t resu l t s ,

    maintenance repairs performed and any other re-lated information that would facil i tate analyzing

    the equipment performance. Maintenance records

    should be retained on file for as long as needed to

    allow collection of sufficient data to perform the

    equipment performance analyses. By observing the

    equipment performance, downward trends can be

    identified and problem areas corrected before majorbreakdowns occur.

    (4) Em er gency opera t i ng i nst ru ct i ons. E m e r -

    gency operation of electrical facilities is safer and

    quicker when instructions are prepared and posted

    in advance. There should be instructions for each

    genera l type of an ticipated emergency, sta ting w ha t

    each employee in the electrical section should do,

    setting up a lternat ives for key personnel, and estab-

    lishing follow-up procedures for use after an emer-gency has passed. Instructions should be posted in

    the electrical shop, security guard office, all em

    gency generating or opera ting a reas, a nd other lo

    tions as the responsible supervisor deems necessa

    Employees should be listed by name, title, offi

    telephone number, home address and home te

    phone number (where permissible). These instr

    tions should emphasize safety under conditionsstress, power interruptions and similar emerg

    cies.

    1-6. Priority and scheduling.

    In regard to the support of the instal led phys

    facilities, it is the policy of the Military Dep

    ments t hat , in order of priority , ma intenance sho

    be second only to operations. It must be system

    and timely. Subsequent sections in this docum

    provide generaI suggestions on service frequenc

    and procedures. Although these proposed acti

    and frequencies may appear to be excessive, th

    suggestions are based upon experience and equment manufacturers recommendations. They

    not intended to supersede instructions that elec

    cal manufacturers normally provide. Every reali

    effort should be made to adhere to these suggesti

    considering existing manpower levels and availa

    test equipment. It is generally good practice to

    spect equipment three to six months af ter i t is f

    put into service and then to inspect and maintai

    every one to three years, depending on its serv

    and operating conditions. Conditions that make quent maintenance and inspection necessary a

    a. High humidity and high ambient temperatu

    b. Corrosive atmosphere.c. Excessive dust and dirt .

    d. High repeti t ive duty.

    e. Frequent fault interruption.

    f. Older equipment.

    1-7. Hazards.

    Material specifications, construction criteria, ins

    l a t ion s t andards , and s a f e work ing procedu

    should be applied to minimize hazards. All w

    should be performed by qualified electricians

    conform to the latest accepted procedures and s

    dards .

    a. Building electrical systems. Fi re and s a fhazards in building electrical systems often re

    from tampering by unqualif ied personnel. Proba

    the greatest example of tampering is the unaut

    rized changing or replacing of fuses. Careful ob

    vation by maintenance personnel is needed to c

    trol excessive use of items such as extension cor

    heaters, air conditioners, and improper ground

    which cause over loading o f the wir ing sys te

    Whenever possible, installation of additional rectacles is preferable to the use of extension cor

    1-2

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    9/180

    Each building should be inspected for loose wires,

    poor connections, bare conductors, unauthorized or

    nonstand ard at ta chment cords, use of wiring or f ix-

    tures as support for extraneous i tems, any condi-

    tions likely to cause f ires and la mps larger tha n th e

    sta nda rd size prescribed for outlets .

    b. Hazardous locations. Special occupancy areasinclude gara ges, aircraf t h an gars, ga soline dispens-

    ing and service stations, bulk storage plants , and

    TM5-683/NAVFAC MO-116/AFJMAN 32-1083

    health care facil i t ies . Such areas designed as "Haz-

    ards Locations," as specified in Article 500 of the

    Na tional E lectrical C ode, require special an d equip-

    ment considerations. These considerations include

    the use o f specia l f i t t ings , r ig id condui t , and

    explosion-proof apparatus. Maintenance personnel

    must ensure that a l l work performed in a hazardousarea complies with the code requirements for the

    areas particular hazard classif ication.

    1-3

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    10/180

    TM 5-683/NAVFAC MO-116/AFJMAN 32-1083

    CHAPTER 2

    SWITCHGEAR ASSEMBLIES 600V OR LESS

    2-1. Periodic Maintenance.

    A periodic maintenance schedule must be estab-

    l i s h e d t o o b t a i n t h e b e s t s e r v i c e f r o m t h e

    switchgear. Annual check should be made on all

    major switchgear devices af ter instal lation. After

    trends have been established regarding the equip-

    ment condition a nd reliabil ity , t he ma intenance in-

    terval may be extended (1836 months) in keeping

    with the operating conditions. A permanent record

    of all maintenance work should be kept. The record

    should include a list of periodic checks and tests

    made (including date of test), condition of the equip-

    ment, repairs or adjustments performed, and test

    da t a tha t w ould faci li ta te per forming a t rend analy-

    sis. Maintenance personnel must follow all recog-

    nized safety pract ices , both the nat ional ly publ ished

    standards and mili tary regulations. Some specif ic

    suggestions in dealing with switchgear mainte-

    na nce are given below:

    a. Tools designed for slowly closing switchgear

    circuit breakers or other devices during mainte-

    na nce are not suita ble for use on an energized sys-

    tem. The speed necessary for device closing is as

    important as its speed in opening; therefore, a

    wrench or other manual tool is not fast enough.

    b. Before working on a switchgear enclosure,verify that the enclosure is de-energized by check-

    ing for volta ge using a volta ge detector.

    c. Disconnect all drawout or tilt-out devices such

    as circuit breakers, instrumentation transformers,

    an d control power tra nsformers.

    d. Do not lay tools on the equipment w hile work-

    ing. It is al l too common to forget a wrench when

    closing up an enclosure. Dont take the chance.

    e. Never rely upon the insulat ion surrounding a n

    energized conductor t o provide protection t o person-

    nel. Use suitable safety clothing and equipment.

    f. Always use the correct maintenance forms and

    equipment. When performing maintenance the fol-lowing should be a vaila ble:

    (1) Forms for recording th e condit ions as found

    an d w ork done.

    (2) Control power connections, test couplers,and spare parts recommended by the manufacturer

    to facil i tate repair and maintenance of each type ofcircuit breaker.

    (3) Special tools, such as lifting mechanismsfor removing an d t ra nsporting power circuit break-

    ers, relay test plugs for testing a nd calibrat ing pro-

    tective relays, a low resistance ohmmeter for mea-

    s u r i n g t h e r e s i s t a n c e o f c o n t a c t s , a m m e t e r s ,

    voltmeters, m egohmm eters, low voltag e/high cur-

    rent t est sets for testing power circuit breakers, a nd

    other special test equipment.

    (4) Manufacturers instruction books regarding

    the maintenance of switchgear devices such as cir-

    cuit breakers, relays, bus bars, meters, etc. The

    fundamentals that are presented in the upcoming

    sections are designed to supplement these instruc-

    tions, giving the elements of the overall mainte-

    nance program ra ther t han the deta i ls.

    2-2. Metal enclosures.

    Maintenance is recommended below:a. With power off and the bus properly grounded,

    open the enclosure and remove any accumulated

    dust and dirt . Vacuum cleaning is recommended;

    blowing with compressed air is not.

    b. Check structure and anchor bolts for t ight-

    ness . For bus and breaker connect ions ensure

    manufacturers specified torques are used.

    c. Clean and lubricate circuit breaker racking

    mechanisms with a non-hardening, non-conductive

    grease.

    d. Inspect operation and adjustment of safety

    shutters, mechanical and key interlocks, auxil iary

    and l imit sw itches.e. Clean and inspect strip heaters.

    f . Clean any a i r f i l ters tha t are ins ta l led in the

    ventilation openings.

    g. Inspect all relays, contractors, switches, fuses,

    and other auxiliary devices for correct operation

    an d cleanliness.

    h. Tighten control wiring connections.

    i . Inspect al ignment and contacting of primary

    disconnecting devices, checking for signs of abnor-

    ma l wea r or other dam age. Discolora tion of these or

    other si lvered surfaces is not usually harmful un-

    less caused by sulphide deposits, which can be re-

    moved by a solvent , such a s a lcohol, or silver polish.j . A f t e r c l e a n i n g , m e a s u r e t h e r e s i s t a n c e t o

    ground and between phases of the bus with a

    megohmmeter (para 14-2). It is not possible to give

    definite l imits for sat isfactory insulation resista nce

    values, so that a change in the reading from one

    inspection period to another is the best indication of

    any weakening tendency. The readings should be

    taken under similar conditions each time, and the

    record should include temperature and humidity.

    k. B efore replacing th e breaker, wipe the primar y

    disconnecting device contacts. Apply a thin coat of

    2-1

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    11/180

    TM 5-683/NAWAC MO-116/AFJMAN 32-1083

    contact lubricant to the s ta t ionary s tuds and to the

    primary disconnects on the breaker.

    l . Ensure that all metal shields are securely in

    place. These shields must be installed to confine any

    blast in the event of circuit breaker failure.

    (1) A n ote on l ubr icants. One of the most useful

    lubricants for motors is an extreme pressure (EP)

    lithium-base petroleum grease. As the usage of

    Class F winding temperat ure rat ings has increased ,

    however, others have adopted synthetic greases to

    withstand higher bearing temperatures .

    (2) Synt hetic oil s and greases. Synthetic oi ls

    and greases compounded from various silicones,

    alkyl benzene, diesters, and fluorinated ethers, are

    available for extremely high-temperature service

    that would cause premature oxidation of petroleum

    lubricants. Some synthetics also suit extremely low

    temperature, down to 40 or 50 degrees below zero.

    The main uses for synthetic lubricants in motorbear ings a re reduced f r i c t ion and res i s tance to

    moisture and chemical contamination. Such appli-

    cations must be carefully worked out with bearing

    a nd lubricant suppliers, beca use no universal lubri-

    cant formulation will apply to all environments.

    However, i t is not unusual for lubricant to vary

    little more than brand name. Thus substitutions are

    often possible. Consult with t he man ufactur er of the

    switchgear to determine the importa nt characteris-

    tics of the lubricant prior to specifying a substitute

    lubricant. Carefully selected substitutes will reduce

    the cost of procurement, stocking and dispensing.

    2-3. Bus bar and terminal connections.

    Many fa i lures a re a t tr ibutable to improper termina-

    tions, poor workmanship, and different characteris-

    tics of dissimilar metals. Loose bus bar or terminal

    connections will cause overheating which can be

    easily spotted by a discoloration of the bus bar. A

    thermographic survey can be conducted to detect

    overheating before discoloration occurs (para 14-7).

    An overheating condition will lead to deterioration

    of the bus system a s well as t o equipment connected

    to the bus; i.e. protective devices, bus stabs, etc.

    Therefore, bus ba r a nd t ermina l connections should

    be regularly checked to ensure that they are prop-

    erly tightened without damaging the conductors.

    Special attention should be given where excessive

    vibration may cause loosening of bolted bus and

    terminal connections. Tightening torque values for

    electrical connections are provided in table 21.

    This information should be used for guidance only

    wh ere no tight ening informat ion on t he specific con-

    nector is available. I t should not be used to replace

    manufacturers instructions which should always be

    followed. Do not assume that once a connection has

    been torqued to its proper value that i t remains

    2-2

    tight indefinitely. I f signs of arcing ar e evident, t hen

    the connections should be broken and the connect-

    ing surfaces cleaned. Because of the different char-

    a cteristics of copper an d a luminum, t hey should not

    be intermixed in a terminal or splicing connector

    wh ere physica l conta ct occurs between t hem, unless

    th e device is suita ble for t he purpose and conditions

    of use. Materials such as solder and compounds

    shall be suitable for the use and shall be of a type

    which will not adversely affect the conductors.

    a. Al um in um connectors. Special considerations

    must be given to aluminum connections. Aluminum

    connectors are plated and should not be cleaned

    with abrasive. I f these connectors are damaged,

    they should be replaced. I t should be noted that

    when making connections with aluminum conduc-

    tors, be sure to use a joint compound made for the

    purpose. To assist in the proper and safe use of solid

    aluminum wire in making connections to wiringdevices, refer to the National Electrical Code. Make

    aluminum connections with solderless circumferen-

    tial compression-type, aluminum-bodied connectors

    U L list ed for AL/CU . Remove sur fa ce oxides from

    aluminum conductors by wire brushing and imme-

    diately apply oxide-inhibiting joint compound and

    insert in connector. After joint is made, wipe away

    excess joint compound and insulate splice.

    b. Bus in sulators and barr iers. Bus bar support

    insulat ors an d/or barr iers should be wiped w ith a

    clean cloth. Do not use steel wool or oxide papers to

    remove dirt; use a cleaning solvent that will not

    leave trace deposits. While cleaning, check insula-tors for cracks and signs of arc tracking. Defective

    units should be replaced. Loose mounting hardware

    should be tightened.

    2-4. Underfloor ducts.

    All undefloor duct systems require checks for evi-

    dence o f o i l and wa ter . Entrances and f i t t ings

    should be checked and corrected as necessary to

    prevent entrance of l iquids, insects, and rodents.

    Cockroaches, ants, beetles and rodents have been

    known to a t t ack cab le insula t ion , espec ia l ly i f

    greases or oi ls are present . External heat and heat

    caused by overloaded circuits can cause cracking of

    cable insulation and drying of taped splices. Mois-

    ture can then penetrate the cable and could cause a

    fault. Therefore, underfloor conduits and duct sys-

    tems should be kept sufficiently clear of electrical

    and hot water f loor-heating systems to prevent un-

    due heating of the enclosures.

    2-5. Busways.

    Feeder busway, trolley busway and plug-in busway

    (fig 21) require annual cleaning and removal of oil

    substances and dirt. Ventilated-type busway should

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    12/180

    TM 5-683/NAWAC MO-116/AFJMAN 32-1083

    NOTE : REDUCE TORQUE BY 20% WHEN CADMIUM PLATED BOLTS ARE USED.

    have the bus bars cleaned annually with clean, dry

    compressed a i r a t a maximum pressure o f 50

    pounds per square inch. Plug-in devices should be

    s e r v i c e d u s i n g t h e s a m e p r o c e d u r e s a s o t h e r

    switches or breakers. The plug-in bus or prongs

    should be checked annually for annealing or corro-

    sion on all connections which are rated in excess to

    75 percent of the rating of the bus duct. Connections

    should not be retorqued as part of a routine main-

    tenance procedure unless visibly loose or shown to

    be loose by an infrared scan. All busway connections

    should be torqued according to manufactures rec-

    ommendations. If this information is not available,

    use the torque specifications in table 2-1. Inspect toensure tha t :

    a. Ventilation continues to be adequate.

    b. Clearances are maintained and encroachment

    from other equipment facilities has not occurred.

    2-6. Power circuit breakers.

    Power circuit breakers encompass all breakers ex-

    cept molded case breakers and breakers used for

    control applications. It is recommended that power

    circuit breakers be inspected once a year after in-

    stallation. More frequent inspections are recom-

    mended where severe load conditions, dust, mois-

    ture or other unfavorable conditions exist, or if the

    vital nature of the load warrants i t . Any breaker

    that has in terrupted a f aul t a t or near i ts shor t

    circuit ra ting should be inspected immediately a f ter

    the in terrupt ion and serviced i f necessary . Re-

    energize equipment completely before working on

    any devices , connect ions , bus work, breaker orf eeder cab le compar tmen ts . Th is inc ludes de-

    energizing any connections to outside primary or

    secondary sources such as transformers, tie lines,

    etc. Manufacturers instruction documents should

    also be obta ined and read carefully before disassem-

    bly or adjustments are performed.

    a. Drawout circu i t breakers. A d r a w o u t - t y p e

    breaker should be tested and inspected for proper

    operation as follows:

    (1) Withdraw the breaker to the test position.This position disconnects the primary power circuit

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    13/180

    TM 5-683/NAVFAC MO-116/AFJMAN 32-1083

    FEEDERBUSWAY

    PLUG-IN

    N>

    BUSWAY

    F i gu r e 2 -1 . Typ i ca l busway i n s ta l l a t i o n .

    but leaves the control circuits energized (fig 2-2). If

    a test position is not provided, then complete-

    ly withdraw the circuit breaker from its compart-

    ment and use a test coupler to provide control

    power.

    (2) Test for voltage to make sure that all pathsof potential backfeed from control power circuits, as

    well as outside sources, are disconnected. This is

    especia lly importa nt if an externa l source of control

    power is being used for t esting.

    (3) Operate the breaker and check all func-tions. Use both the electrical means (when pro-

    vided) and the mechanical means to charge, close

    and trip the breaker. This is particularly important

    for breakers that normally remain in ei ther the

    opened or closed position for long periods of time.

    (4) Remove the breaker from its compartment

    to a c lean maintenance area . Close the compart-

    ment door and cover the breaker cutout to prevent

    access t o live part s.

    (5) Check and lubricate all safety rollers andauxiliary contacts. Check all mechanical clearances

    to ensure they are within manufacturer specified

    tolerances. Also inspect a nd lubricate bus st a bs an d2-4

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    14/180

    TM 5-683/NAVFAC M116/AFJMAN 32-1083

    ~DISCONNECTED

    ALL POWER DISCON-NECTED

    WITHDRAWNBREAKER WITHDRAWNREADY FOR REMOVAL

    F i gu r e 2-2. D raw ou t c i r c u i t b r ea ke r pos i t i o n s .

    a c/dc cont rol block cont a cts. Verify corr ect opera tion

    of trip free and anti-pump mechanisms.

    b. Fi xed circui t br eakers. Maintenance on fixed-

    or bol ter-type c ircui t breakers is normally per-

    formed with the breaker in place inside its cubicle.

    Special precautions must be exercised to assure

    equipment is de-energized and the circuit in which

    it is connected is properly secured from a safety

    s tandpoin t . Al l contro l c i rcu i t s should be de-

    e n e r g i ze d . S t o r e d e n e r g y c l o s i n g m e c h a n i s m sshould be discharged.

    c. Power cir cuit breaker comp onent s. M a i n t e -

    nance on all power circuit breakers will encompass

    maintenance on the following components.

    (1) Insulat ion. The general rule for insulationis keep it clean an d dry. Remove interpha se barriers

    and clean them and all other insulating surfaces

    with dry compressed air and a vacuum cleaner.

    Wipe insulation with clean lint-free rags and sol-

    vents as recommended by the manufacturer if hard-

    ened or encrusted contamination must be removed.

    Repair moderate damage to bushing insulation by

    sanding smooth and refinishing with a clear insu

    lating varnish. Check insulating parts for evidence

    of overheating a nd for cracks tha t indica te excessive

    thermal aging.

    (2) Contacts. Th e major function of the powe

    circuit breaker depends among other things upon

    correct operation of i ts contacts. These circui

    breakers normally have at least two distinct sets o

    contacts on each pole, main and arcing (fig 2-3)Some have an intermediate pair of contacts which

    open after the main contacts and before the arcing

    contacts.

    (a) M ain contacts. When the b reaker i s

    closed, practically the entire load current passes

    through the main contacts. Also, short circuit cur

    rent must pass through them during opening or

    closing faulted lines. If the resistance on these con

    tacts becomes high, they will overheat. Increased

    contact resistance can be caused by pitted contac

    surfaces, foreign ma terial embedded on conta ct sur

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    15/180

    TM 5-683/NAVFAC MO-116/AFJMAN 32-1083

    FIXED ARCING CONTACT

    MOVABLECONTACT

    MOVABLE MAIN

    CONTACT

    ARCI

    F i gu r e 2 -3 . Power c i r c u i t b r ea ke r m a i n a nd a r c i n g con ta c t s .

    faces, or weakened contact spring pressure. This (c) Contact maintenance. The general rules

    will cause excessive current to be diverted through

    the arcing contacts, with consequent overheatingand burning.

    (b) Ar cin g contacts. Arcing contacts are the

    last to open; any arcing normally originates on

    them. In circuit interruption, they carry current

    only momenta ri ly , but tha t current may be equal t o

    the interrupting rating of the breaker. In closing

    aga inst a short c ircui t , they may momenta ri ly carry

    considerably more than the short circuit interrupt-

    ing rating. Therefore, they must make positive con-

    tact when they are touching. I f not, the main con-

    tacts can be badly burned or may result in a failure

    to interrupt a faul t .

    for maintaining contacts on all types of breakers

    a re: keep them clean, a ligned and w ell adjusted. Toinspect the circuit breaker contacts, the arc chutes

    must be removed. When doing this, check the arc

    chutes for evidence of damage, and replace dam-

    aged parts. I f not damaged, then blow off dust or

    loose particles. Once the main contacts are exposed,

    inspect their condition. Slight impressions on the

    sta tionary conta cts cau sed by the pressure a nd wip-

    ing a ction of the mova ble conta cts is tolerable. Con-

    ta cts w hich h ave been roughened in service should

    not be f i led but large projections, caused by u nusua larcing, should be removed by filing. When filing,

    take care to keep the contacts in their original de-

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    16/180

    TM 5-683/NAVFAC MO-116/AFJMAN 32-1083

    sign. That is, i f the contact is a l ine type, keep the

    a rea of conta ct l inear , and if ball ty pe, keep the ball

    shaped out. Discoloration of silver-plated surfaces is

    not usually harmful unless caused by insulating

    deposits. These deposits should be removed with

    alcohol or a silver cleaner. Whether cleaned or not,lubricate the main contacts by applying a thin f i lm

    of slow aging, heat resistant grease. All excess lubri-

    cant should be removed with a clean cloth to avoid

    accumulation of dirt and dust. Under no circum-

    stances should the arcing contacts be lubricated.

    Where serious overheating is indicated by discolora-

    tion of metal and surrounding insulation, the con-

    tact and spring assemblies should be replaced in

    accorda nce with ma nufacturers instructions. While

    careful ly c losing the c ircui t breaker , check for

    proper gap, wipe and contact alignment. Contact

    gap is the d is ta nce betw een t he s ta t ionar y a nd mov-

    able contacts with the circuit breaker in the fully

    open position. I f the a rcing conta ct ga p is too small ,

    a circuit breaker may not be able to interrupt a

    fault. I f the main contact gap is too small , the mainconta cts wi l l interrupt the faul t a long with t he arc-

    ing contacts and possibly burn the main contacts.

    Contact wipe is the amount of over travel between

    the stationary and movable contacts from the time

    when the contacts are just touching to the time

    when the circuit breaker is fully closed (figs 24,

    25, and 26). Check that all contacts make and

    break at approximately the same t ime. Make ad-

    justments in accordance with the manufacturers

    recommendat ions. La mina ted copper or brush st yle

    b

    F i g u r e 2-4. Arc i n g con ta c t gap and w i pe.

    CONTACT WIPE

    2-7

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    17/180

    TM 5-683/NAVFAC MO-116/AFJMAN 32-1083

    ACRING CONTACTS

    TOUCHING

    CON

    F i gu r e 2-5 In t e rmed i a t e con ta c t gap .

    contacts found on older circuit breakers should be

    replaced when badly burned. Repairs are not prac-

    tical because the laminations tend to weld togetherwhen burning occurs, and contact pressure and

    wipe are greatly reduced. These contacts may be

    filed to remove large projections or to restore their

    original shape. They should be replaced when theyare burned sufficiently to prevent adequate circuit

    breaker operation or when half of the contact sur-

    face is burned aw a y. Ca rbon conta cts, used on older

    circuit breakers, require very li ttle maintenance.

    However, inadequate contact pressure caused by

    erosion or repeat ed f il ing m ay cause overhea ting or

    interfere with their function as arcing contacts.

    (3) Operating mechanism. The purpose of theoperating mechanism is to open and close the

    breaker contacts. This usually is done by linkages

    connected, for most power breakers, to a power op-

    erating device such as a solenoid or closing spring

    2-8

    for closing, and contains one or more small sole-

    noids or other types of electro-magnets for tripping.

    Tripping is accomplished mechanically, independent

    from the closing device, so tha t the brea ker conta cts

    will open even though the closing device still may be

    in the closed position. This combination is called a

    mechanically trip-free mechanism. After closing,the prima ry function of the opera ting mechan ism is

    to open the breaker when it is desired, which is

    wh enever t he tr ipping coil is energized at above its

    rated minimum operating voltage. The breaker op-

    erating mechanism should be inspected for loose or

    broken par ts; m issing cott er pins or reta ining keep-

    ers; and missing nuts and bolts. I t should also be

    examined for damage or excessive wear on cam,

    latch, and roller surfaces. Excessive wear usually

    results in loss of travel of the breaker contacts. I t

    can affect operation of latches; they may stick or

    slip off and prematurely trip the breaker. Adjust-

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    18/180

    TM 5+583/NAVFAC MO-1 16/AFJMAN 32-1083

    11L 1 3CONTACT WIPE16 32

    Figure 2-6. Main contact wipe.

    menta for excessive wear are possible for certain lubricate pins and bearings not disassembled. Useparts . For others, replacement is necessary. The non-ha rdening a nd non-conductive grease lub

    closing and tripping action of a breaker should be cate the ground or polished surfaces of cam

    quick and positive. While documenting, operate the rollovers, latches and props, pins and bearings th

    breaker several times, checking for obstructions or are removed for cleaning. Check the breaker ope

    excessive friction. Any binding, slow a ction, dela y in a t ing mechanism adjustments and readjust as d

    speration, or failure to tr ip or latch must be con- scribed in th e ma nufa cture%inst ruction book.

    rected prior to returning to service. Clean and these adjustments cannot be made within specifie

    relubricate the operating mechanism. Use a tolerances, it will usually indicate excessive we

    nondetergent light machine oil (SAE-20 or 30) to and the need for a complete overhaul.

    2

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    19/180

    TM 5-683/NAVFAC MO-116/AFJMAN 32-1083

    (4) T r i p devi ces. The t rip devices on low volta ge

    circuit breakers provide the electrical decisions

    needed to detect th e difference between norma l an d

    abnormal conditions of current flow. The mainte-

    nance and adjustment of these devices is just as

    important as the work performed on the main con-

    tacts and operating mechanism. The trip devices

    are either electro-mechanical or solid-state. Both

    types are responsible for providing various degrees

    of fixed, short, or inverse time delays ba sed on the

    a m o u n t o f c u r r e n t t h e y s e n s e . T h e e l e c t r o -

    mechanical type, with an air or f luid dashpot for

    time delay, should be tested as part of the mainte-

    na nce work performed. A dash pot is a pneumat ic or

    hydraulic device used for cushioning or damping of

    movement to a void mechanical sh ock a nd consisting

    essentially of a cylinder conta ining air or l iquid a nd

    a pis ton moving in i t . Test ing of the electro-

    mechanical devices requires th e use of a low volta ge

    (about 0-20V) but h igh current (usua l ly O-

    50,000A) prima ry injection t est set designed specifi-cally for this purpose. Calibration tests should be

    ma de to verify th at the performa nce of the device is

    within the values shown on the manufacturers pub-

    l ished curves; taking into account that the time-

    current curves are plotted as a band of values

    rather than a single l ine (fig 27). Pay careful at ten-

    t ion to how the manufacturer has presented the

    curve data. There is a wide variety of formats.

    Check to see tha t t he current is in amperes or mul-

    tiples of a pickup value and whether temperature

    ranges or previous conditions will affect results.

    Usually, the trip devices are tested one unit at a

    time. There ar e some devices which ma y use a ther-mal element for time delay. These may have to be

    tested all at once to get results similar to those

    published by the ma nufa cturer. Check the t est con-

    ditions carefully. I f the trip devices do not operate

    properly, the calibration and timing components

    should be adjusted or replaced per the ma nufa ctur-

    ers recommendations. If repair or replacement of

    the electro-mechanical devices is being considered,

    then thought should be given toward retrofitting

    the existing breaker with solid-state trip devices.

    This newer technology is generally more reliable

    beca use the part s used to make th e trip unit do not

    drif t out of a djustm ent or suffer th e effects of a ging

    or contamina t ion to the same degree as the i r

    electro-mechanical forerunners. I f the breakers a re

    a lready equipped w ith solid-sta te t rip devices, they

    should also be checked for proper operation and

    time delay in accordance with the manufacturers

    published curves. The test procedure recommended

    by th e ma nufa cturer should be followed.

    (5) Au xil ia ry devi ces. Inspect the closing motoror solenoid, shunt trip coil and mechanism, alarm

    2-10

    mechanisms, and the control wiring for correct op-

    erations, insulation condition and tightness of con-

    nections. Check on-off indicators, spring-charge in-

    dicators, mechanical and electrical interlocks, key

    interlocks, and lock-out fixtures for proper opera-

    tion and lubricate where required. In particular,

    test the positive interlock feature which prevents

    the insertion or removal of the breaker w hile it is in

    the closed position. Check control devices for free-

    dom of operation. Replace contacts when badly worn

    or burned. After the breaker has been serviced,

    manually operate it slowly with a closing device to

    check for tightness or friction and to see that the

    contacts move to their fully open and fully closed

    positions. Electrically operate the breaker several

    times to check the performance of the electrical ac-

    cessories using the TEST position, an external

    test /cont rol cabinet , or a test coupler.

    2-7. Network protectors.

    The current-carrying parts, main contacts, and op-erating mechanism of a network protector are very

    similar to those of the air circuit breaker. This simi-

    larity usually ends with the principal mechanical

    devices. Unlike the usual feeder circuit breaker, the

    network protector is more like a tie circuit breaker;

    that is, i t is almost always energized on both sides.

    This condition requires that extreme care be taken

    during installation or removal of the unit from ser-

    vice. The netw ork protector is equipped with specia l

    relays t ha t sense the netw ork circuit conditions and

    command the mechanism to either open or close

    automatically in response to those conditions. Net-

    work protectors are used where large amounts ofpower must be distributed to high density load ar-

    eas such as commercial buildings and office com-

    plexes. To form a network, several incoming power

    sources may be connected. As a result, a short cir-

    cuit a t a ny point in t he system usua lly involves very

    high fault currents.

    a. Safety precautions. Due to the construction

    and purpose of the network protector, taking it out

    of service or placing it ba ck in service is a procedure

    that must be done while the circuit is energized.

    During this work, always use the special insulated

    tools provided with the particular model to be ser-

    viced. Alternate or make-shift tools are not recom-

    mended unless they have been laboratory tested

    and are known to have good safety performance.

    Electrical grade, safety gloves should stil l be worn

    by the person servicing the unit regardless of the

    type or condition of the tools used.

    b. M ai ntenance. A routine maintenance schedulefor network protectors should be observed. The fre-

    quency of inspection w ill vary based on the location

    and environment in which the unit is installed, and

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    20/180

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    21/180

    TM 5-683/NAVFAC MO-116/AFJMAN 32-1083

    the number of operat ions the uni t has made. In a l l

    cases, open the circuit first. This is done by moving

    t h e c o n t r o l h a n d l e f r o m A U T O M A T I C t o

    MANUAL and then manually opening the circuit.

    The cont rol ha ndle a nd/or opera tin g mecha nism

    should then be locked in th e OP EN position beforefurther work is done. Maintenance should include

    cleaning an y a ccumula tion of dust, dirt or corrosion

    deposits, a thorough visual inspection, and overall

    performance tests. Should the operation of any part

    be suspect, refer to the manufacturers instructions

    describing operation, adjustment, and replacement

    of these parts. I f the network sensing relays are out

    of calibration, they should be recalibrated by com-

    petent shop personnel. The network protector is

    housed in a cell or enclosure similar to those used

    for air circuit breakers (fig 2-8). The circuit breaker

    mechanism and the network relay panel assembly

    of a network protector are usually constructed aa anintegral , drawout uni t which must be withdrawn

    fmm the housing for proper maintenance. Removal

    is done by unbolting the fuses at the top (usually)

    and the disconnecting links at the bottom (some

    models have bolt-actuated disconnecting f ingers at

    the bottom). After removing any additional lock-

    down bol ts or la tches , the drawout uni t may be

    carefully withdrawn using the rails provided for

    suppor t . Al though th i s prov ides a compara t ive

    measure of safety, work should be done cautiously

    since there is voltage present within the enclosure.

    I t is better to move the unit completely away fromth e enclosure (fig 29). The following inspection a nd

    maintenance operations can be done on the drawout

    unit :

    (1) Clean the breaker assembly. Use of avacuum cleaner is preferred. Use cloth rags free of

    oil or grease for removing clinging dirt.

    (2) Remove arc quenchers. Replace if damaged.

    (3) Inspect main contacts (fig 2-10). Smooth

    any heavily frosted area with a very f ine f i le or a

    burnishing stone which does not shed abrasive par-

    ticles. Protect hinged joints from falling particles

    during f iling.

    (4) File smooth any especially high projections

    of metal on arcing contacts.

    (5) See that all electrical connections are tight.

    (6) Look for any abrasion of wire insulation

    an d repair .(7) Check for signs of overheating of control

    wire and current carrying parts .

    (8) See that all springs are in good condition

    and are properly seated in place.

    (9) See that all nuts, pins, snap rings or retain-

    ers, and screws are in place and tight.

    (10) Replace any broken or missing barriers.(11) With the rollout unit still set aside, per-

    form the following maintenance operations inside

    the enclosure:

    **WARNING**Both source and load terminals are probably still energized. Use insulated tools and safety

    protective equipment for this work. Do not remove any barriers from the enclosure.

    (a) Look for loose hard wa re on the enclosurebottom or beneath the frame. I f any is found, trace

    to source and correct problem or replace.

    (b) Clean stand-off bus insulators.

    (c) Remove oxide f ilm from t erminal conta ctsi f necessary.

    ( 1 2 ) M a n u a l l y c l o s e a n d t r i p t h e b r e a k e r

    mechanism according to instructions furnished for

    the particular model.(13) Perform an operational test using a net-

    work protector test kit .

    (14) Conduct insulation resistance tests, di-

    electric test and electrical operating test in accord-

    ance with the manufacturers recommendations.

    (15) Carefully replace the drawout unit in theenclosure. Make a f inal inspection to be sure no

    control wiring has become snagged, and that no

    plugs or connecting surfa ces ha ve been bent or dam -

    aged.

    2-8. Auxiliary switchgear equipment.

    Auxiliary equipment includes devices such as fuses,

    capaci tors , meters , relays , etc . This equipment

    should be serviced along with the major switchgear

    components, unless there is some indication that a

    device is being heavily or improperly used, in which

    case it should be inspected more often. Protective

    relays and meters should be inspected and cali-brated on a scheduled basis. Critical service equip-

    ment should have the protective relays checked at

    every maintenance turn (annually or according to

    manufacturers recommendations). Relays applied

    to other general distribution circuits may be done

    less frequently (see para 2-8h).

    a. Fuses. Fuse maintenance is covered as a sepa-

    rate category of electrical equipment (para 5-4d).

    b. Capaci tors.

    power capacitor

    The maintenance requirement on

    instal la t ions is so smal l that i ts

    2-12

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    22/180

    TM 5-683/NAVFAC MO-116/AFJMAN 32-1083

    )INGs

    BREAKER UNIT J COUPLING

    F i gu r e 2 -8 . Typ i ca l d r a wou t n etwo r k p r o tec t o r and enc l o su r e .

    Holes For

    M o u n t i n g

    Screws

    ( Two OnEach Side

    F i gu r e 29 . Netwo r k p r o tec t o r r emovab l e un i t .

    importance is often overlooked. The voltage of the

    system at the capacitor location should be checked

    at l ight load periods to determine if an overvoltage

    condition exists. Any changes in circuit connections,

    which may increase vol tage levels , warrant a re-

    check of operating conditions. The conductor sizes

    should provide for not less than 135 percent of ca-

    pacitor current at rated voltage and WA. As a gen-

    eral rule, i f the side of the capacitor unit casing is

    operating at a temperature above 55 degrees C (131

    degrees F a temperature almost too hot for bare-

    hand contact) , then a more complete investigationof operating conditions should be made. The case

    temperatures should never exceed 65 degrees C

    (149 degrees F) under any conditions. Adequate

    ventilation is therefore necessary to remove the

    heat generated by continuous full-load duty. Re-

    move any obstructions at ventilation openings in

    capacitor housings to ensure that this ventilation is

    maintained. A disconnected capacitor retains its

    electrical charge for some time and may even retain

    the full-line voltage across its terminals. Therefore

    always discharge a capacitor before handling or

    making connections. An insulat ion short c ircui tjumper may be used for this purpose; however, it

    should only be applied with full knowledge of the

    circuit, and with the use of appropriate protective

    equipment. Power capacitors are generally provided

    with individual fuses to protect the system in case

    of a short circuit within the capacitor. In addition to

    a faul ty capaci tor , a fuse may be blown by a n a bnor-

    mal voltage surge. Check for blown fuses and re-

    place them with a type recommended by the manu-

    facturer. Do not remove fuses by hand until the

    capacitor has been completely discharged. Clean the

    case of a capacitor, the insulating bushings, and any

    2-13

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    23/180

    TM 5-683/NAVFAC MO-1 16/AFJMAN 32-1083

    ARCQUENCHER

    BLOWOUT

    COIL

    ARC

    QUENCHERSUPPORTINGSCREWS

    SCREWS FORMOVABLE

    ARCING

    CONTACT

    LOCKING

    PLATE

    FLEXIBLECONNECTION

    STOP PINFOR MOVABLE

    ARCINGCONTACT

    CONTACT

    SUPPORT

    CROSS BAR

    UPPER

    CONTACT BAR

    MOLDED

    SUPPORTFOR ARC

    QUENCNER

    INSULATION

    STATIONARYARCING

    CONTACT

    MOVABLEARCING

    CONTACT

    UPPER MAIN

    SILVERCONTACTS

    STOP SCREW

    MAINBRIDGING

    CONTACT

    BLOCK

    LOWERCONTACTBAR

    F i g u r e 210. Typ i ca l con t a c t con s t r u c t i o n f o r a n etwo r k p r o t e ct o r .

    connections that are dirty or corroded. Inspect the posed connections, and safety gear and tools must

    case of each capa citor for lea ks, bulges, or discolora-

    tion. I f any of these conditions exist, then replace

    th e capa citor (pa ra 112).

    c. Ba tt er y suppl i es. Th e contr ol bat tery is such an

    importa nt i tem in sw itchgear operat ion t hat i t must

    be given strict attention in the maintenance pro-

    gra m. The bat tery cha rger plays a critica l role sinceit supplies norma l direct current (DC) power to t he

    stat ion and maintains the bat ter ies a t a high level

    of charge. The batteries, in addition to supplying

    temporary heavy demands in excess of the charger

    capacity, serve a s a back-up source to tr ip breakers

    upon loss of alternating current (AC) power. Failure

    of the charger or i ts AC supply transfers al l DC load

    to the batteries. Each battery cell electrolyte levelshould be checked. While a single cell may not pro-

    duce a serious shock hazard, when the cells are

    connected in a battery bank, a severe shock hazard

    may be possible. Also, there are usually many ex-

    2-14

    be used to the best degree of safety such as face

    shields, a cid/caust ic resista nt gloves, emergency

    eyewash, etc. Electrolyte is the f luid contained in

    each battery cell (fig 211). Low electrolyte levels

    indicate too high a charging rate. In this case, the

    float-voltage setting of the charger should be

    checked against the battery manufacturers recom-mendations. The specific gravity of the battery elec-

    trolyte should be taken using a hydrometer (para

    14-6). I f the readings between battery cells vary

    more than fif ty points on the hydrometer scale, the

    battery probably has a bad cell which should be

    replaced. If all cells read consistently low (within 50

    points), the batt ery should be fully cha rged a nd th e

    battery charger checked for proper operation. The

    battery top surface should be clean. Surface con-

    tamina t ion can produce leakage currents tha tpresent a drain on the charger and the battery. Vent

    holes in t he cell ca ps should be open. Ba tt ery t ermi-

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    24/180

    nal connections should be tight and free of corro-

    sion. I f the termina l connections a re corroded, they

    should be cleaned with bica rbonat e of soda. B a tt ery

    terminals and cable ends should be cleaned thor-

    oughly. I f stranded cable is used it is advisable to

    cut off the corroded end. If this is not possible, the

    stra nds should be separa ted a nd c leaned interna l ly .

    Any dus t accumula t ion on the ba t tery charger

    should be blown off or wiped clean. Ventilation

    openings should be clear of obstruction. Terminal

    connections should be checked for tightness. All re-

    lays, l ights or horns for indicating such abnormal

    conditions as grounds, loss of AC power supply, and

    high or low voltage should be checked to ensure that

    they are operating properly. During maintenance

    outages of the AC supply, th ere may be times when

    it is necessar y to provide a t empora ry supply to the

    TM 5-683/NAVFAC MO-1161AFJMAN 32-1083

    charger. While being charged, a battery produces

    and emits a mixture of hydrogen and oxygen gases

    which is very explosive. Open flames or sparks must

    not be permitted in close proximity t o the ba tt eries.

    The room or compartment in which operating bat-

    teries are located should be well ventilated. Smok-

    ing should be prohibited in these rooms or compart-

    men ts .

    d. I nstrum ent tran sform ers. I n s t r u m e n t t r a n s -

    formers are used to step down a current or voltage

    in order to operate a meter or a relay. Indoor-type

    instrument transformers are normally dry type, ex-

    cept potentia l tra nsformers (P Ts) which ma y be en-

    closed in compound-filled metal cases. The more

    common transformer constructions have the com-

    plete transformer molded into one solid mass with

    only the t erminals exposed.

    I ** CAUTION** I

    INever open circui t the secondary winding of a current transformer while energized . To do so

    may resul t in component damage or persona l in jury . IVENT AND ELECTROLYTE

    FILLING FUNNEL

    NEGATIVE (-) TERMlNAL/

    POSITPLATE

    RUBBER

    SEPARAT

    IVE-

    OR

    POSITIVE (+) TERMINAL

    ELECT

    LEVEL

    ROLYTE

    LINES

    NEGATIVE PLATE

    F i gu r e 2 -11. La r ge cel l f o r a s ta t i o na r y ba t t e r y .

    2-15

    WWW.SURVIVALEBOOKS.COM

  • 8/13/2019 1995 Us Army Facilities Engineering Electrical Interior Facilities 180p

    25/180

    TM 5-683/NAVFAC MO-116/AFJMAN 32-1083

    (11) Verify connection of seconda ry P T leads by

    applying a low volta ge to the leads a nd checking for

    voltage contribution at applicable devices.

    (12) Check for PT secondary load with second-

    ary voltage and current measurements. Make sure

    load is less t ha n volt a mps (VA) of P T.f. M eteri ng. Most of the buildings in a typical

    mili tary instal lation are unmetered. Meters (both

    recording and indicating), relays, and associated

    equipment are usually part of a substation, main

    dis tr ibut ion swi tchboard equipment , or specia l

    equipment. Indust rial sh ops a nd other buildings oc-

    casionally uti l ize kilowatt hour demand meters,

    power factor meters, ammeters, and voltmeters. In

    an effort to determine whether the maintenance or

    operat ion of these meters is adequa te demands t ha t

    the m etering instruments be of th e specif ied ra nge,

    accurately calibrated, and adequately serviced. In-

    strument accuracy is always expressed in terms ofthe percentage of error at the full-scale point. Maxi-

    mum accuracy, consequently, is obtainable by keep-

    ing the rating as high on the scale as possible, and

    requires a properly rated instrument. An instru-

    ment with an accuracy of 1 percent, with a scale

    reading of 100 divided into 100 divisions, is accurate

    to plus or minus one division. Hence, a reading of 20

    has a margin of error of plus or minus one division,

    which in th is ins tance means tha t the t rue va lue

    could be between 19 or 21an actual variation of 10

    percent. If the maximum indicating meter reading

    is less tha n 50 percent of the meter r an ge, indicat-

    ing meters should be recalibra ted, and ra tchets anddials changed. How often an instrument is cali-

    brat ed depends on i ts use and the desired accuracy.

    I f ca l ibra t ion s tandards and equipment are not

    available, instruments of nearly the same rating

    ma y be checked aga inst ea ch other. If w ide discrep-

    an cies are n oted, the suspect instrum ent should be

    checked by a competent laboratory or returned to

    the manufacturer. For many mili tary establish-

    ments, the uti l i ty company will best perform this

    work. Take care to prevent entrance of dirt or lint

    into an instrument because this dirt could hinder

    the actuation of the instrument pointer. Clean the

    glass with a damp cloth because a dry cloth mayinduce a static charge on the glass and af fect the