Upload
kjansa
View
92
Download
3
Embed Size (px)
Citation preview
Installation Instructions
ControlLogix Redundancy Module
Catalog Number 1756-RM, Series A
Topic Page
Important User Information 3
North American Hazardous Location Approval 4
Environment and Enclosure 5
Preventing Electrostatic Discharge 6
Optical Ports 6
About the Module 7
ControlLogix Redundancy System Overview 9
Installation Requirements 10
Configuring a Redundancy Installation 11
Module Placement and Partnering 11
Install the Primary and Redundant Modules 12
Connect the Fiber-optic Communication Cable 13
Check Power Supply and Module Status Indicators 16
Apply Chassis Power 16
Flash Upgrade the Modules 17
Designating the Primary Chassis 18
Designate the Primary Chassis and Qualify the System 18
Qualify the System 19
2 ControlLogix Redundancy Module
Conversion from a Nonredundant to a Redundant Configuration 19
1756-RM Configuration Tool 21
Auto-Synchronization Parameter 21
Reset the 1756-RM Module 22
Remove or Replace the Module 22
Status Indicators 23
Module Status Display 23
Health Status Indicators 24
Inter-1756-RM Module Communication Status Indicator 25
Chassis State Status Indicator 25
1756-RM Module Chassis States 26
1756-RM Module Scrolling Display Messages 27
1756-RM Module Fault Codes and Display Messages 28
Alpha Numeric Error Codes 30
Recovery Messages 31
Specifications 32
Environmental Specifications 33
Certifications 34
Topic Page
Publication 1756-IN092B-EN-P - July 2008
ControlLogix Redundancy Module 3
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.
Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures.
SHOCK HAZARD
BURN HAZARD
Publication 1756-IN092B-EN-P - July 2008
4 ControlLogix Redundancy Module
North American Hazardous Location ApprovalThe following information applies when operating this equipment in hazardous locations.
Informations sur l’utilisation de cet équipement en environnements dangereux.
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
Les produits marqués “CL I, DIV 2, GP A, B, C, D” ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
WARNING EXPLOSION HAZARD -• Do not disconnect equipment unless
power has been removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Substitution of components may impair suitability for Class I, Division 2.
• If this product contains batteries, they must only be changed in an area known to be nonhazardous.
AVERTISSEMENT RISQUE D’EXPLOSION – • Couper le courant ou s'assurer
que l'environnement est classé non dangereux avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
• S'assurer que l'environnement est classé non dangereux avant de changer les piles.
Publication 1756-IN092B-EN-P - July 2008
ControlLogix Redundancy Module 5
Environment and Enclosure
ATTENTION This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 m (6561 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, for additional installation requirements, Allen-Bradley publication 1770-4.1.
• NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.
Publication 1756-IN092B-EN-P - July 2008
6 ControlLogix Redundancy Module
Preventing Electrostatic Discharge
Optical Ports
ATTENTION This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.• Wear an approved grounding wriststrap.• Do not touch connectors or pins on component boards.• Do not touch circuit components inside the equipment.• Use a static-safe workstation, if available.• Store the equipment in appropriate static-safe packaging when
not in use.
ATTENTION Under certain conditions, viewing the optical port may expose the eye to hazard. When viewed under some conditions, the optical port may expose the eye beyond the maximum permissible-exposure recommendations.
Publication 1756-IN092B-EN-P - July 2008
ControlLogix Redundancy Module 7
About the ModuleTwo 1756-RM ControlLogix redundancy modules working together supervise the operating states and state transitions, which establish the basic framework for redundancy operations. The redundancy pairs provide a bridge between chassis pairs that allow other modules to exchange control data and to synchronize their operations. Use this illustration to identify the external features of the module.
Redundancy Module
PRI COM OK
Front View
Top View
Backplane Connector
Backplane Connector
Bottom View
LC Single-mode Connector
Side View
44487
Publication 1756-IN092B-EN-P - July 2008
8 ControlLogix Redundancy Module
The 1756-RM module lets you commission the redundant system in a plug-and-play manner without any programming. You connect a 1756-RM module pair with the default configuration in the redundant chassis pair and set up the redundant system with a communication cable.
You are not required to develop any programming to allow a 1756-L6x controller to migrate to a redundant system from a nonredundant system. Controller programs can input to the 1756-RM module’s management of redundancy states.
You can apply power to the chassis pair either simultaneously or sequentially. You can also set up the system by inserting a 1756-RM module pair in an already powered-up chassis pair containing redundancy compliant modules or inserting redundancy compliant modules, in a powered-up chassis pair containing only a 1756-RM module.
Once you have set up your redundancy configured hardware containing a chassis pair, a 1756-RM module pair and other redundancy compliant modules, and you have applied power, no further tasks are required in the 1756-RM module to activate redundancy in the system. The 1756-RM modules automatically determine the operation state of each of the chassis pair and are ready to accept commands and provide system monitoring.
Before You Begin
Before you install the module, make sure you: • know how to handle the module.
See Preventing Electrostatic Discharge on page 6.• understand redundant systems and redundant media.
For additional information, see the ControlLogix Redundancy System User Manual, publication 1756-UM523.
Publication 1756-IN092B-EN-P - July 2008
ControlLogix Redundancy Module 9
ControlLogix Redundancy System OverviewBy using a pair of 1756-RM modules you can create redundancy state control to supervise the operating states and state transitions. Chassis bridging by using the back-up communication cable provides communication between chassis that allows other modules to exchange control data and to synchronize their operations.
EtherNet Switch
DC INPUT DC OUTPUT Analog Input Analog Output
STATSTAT
Diagnostic
STATSTAT
Diagnostic
STATSTAT
Diagnostic
STATSTAT
Diagnostic
Relay Module
Digi
tal I
nput
Logix5563 Redundancy Module ControlNet
Cont
rolN
et
EtherNet/IP
Ethe
rNet
1756
-RM
1756
-Lxx
Logix5563 Redundancy Module ControlNetEtherNet/IP
1756
-RM
1756
-Lxx
ControlNet
Cont
rolN
et S
cann
er
Rela
y Ou
put
Anal
og O
utpu
t
Anal
og In
put
Digi
tal O
uput
Supervisory Node
Communication Cable
ControlNet
EtherNet/IP
Control Chassis
Control Chassis
I/O Chassis
PRI COM OK
PRI COM OK
Cont
rolN
et
Ethe
rNet
44492
Supervisory Node
Control Chassis
Control Chassis
I/O Chassis
Publication 1756-IN092B-EN-P - July 2008
10 ControlLogix Redundancy Module
Installation RequirementsWhen you assemble the primary and secondary chassis for redundancy, you assemble them just as you would any ControlLogix chassis, except that for redundancy you need to assemble two identical chassis. Specifically, these items must match:
• Primary and secondary (redundant) control chassis, with all modules in the exact same order (slot for slot)
• Firmware revisions of all module partners
IMPORTANT If the primary and secondary (redundant) systems are not assembled identically, and are not comprised of modules with matching firmware revisions, the 1756-RM module cannot qualify the secondary chassis to the primary chassis.
ATTENTION If you are adding redundancy to an already operational ControlLogix system, shut off your process to install the 1756-RM module and designate the primary system.
You may also have to use RSNetWorx software to configure keeper information in the secondary ControlNet communication module if the master keeper for ControlNet communication is in the primary chassis.
You may also need to enable redundancy in your RSLogix 5000 software application and remove any I/O modules from the chassis.
Publication 1756-IN092B-EN-P - July 2008
ControlLogix Redundancy Module 11
Configuring a Redundancy Installation
You configure a redundant system by using two ControlLogix chassis labeled as Chassis A and Chassis B. Each module in Chassis A (including the 1756-RM module) must be partnered by a compatible module in the same slot in Chassis B. You connect the redundant pair with a communication cable.
For more information on permitted configurations, refer to these publications:
• ControlLogix Enhanced System Redundancy Release Notes, publication 1756-RN650.
• ControlLogix/ProcessLogix Standard Redundancy Release Notes publication 1756-RN628.
You connect each partnered communication module in either chassis to the same or different networks depending on the communication module type. ControlNet communication modules can be connected to the same network while Ethernet communication modules can be connected to either the same subnet or different subnets. This system configuration of modules in dual chassis is called a redundant chassis pair (RCP).
Module Placement and Partnering
You can place modules in any slot order within the control chassis, but the 1756-RM module enforces these positioning rules:
• The 1756-RM module pair must occupy the same slots in their respective chassis. The 1756-RM module pair does not consider the chassis pair to be partnered if the 1756-RM modules are placed in different slots, even if the partners of other modules are present in the same slot.
Publication 1756-IN092B-EN-P - July 2008
12 ControlLogix Redundancy Module
• Each pair of ControlLogix controllers and communication modules must be comprised of compatible partner modules. Two modules in the same slot are considered as compatible partners only if they contain compatible hardware and firmware and other rules that may be enforced by the module itself. The compatibility status (Compatible or Incompatible) is determined by either the module in the primary chassis or its partner in the secondary chassis.
• The 1756-RM module prevents certain redundancy operations, such as Qualification, if incompatible modules reside in the redundant-control chassis pair.
Install the Primary and Redundant ModulesPlace a 1756-RM module in corresponding slots in the primary and redundant chassis. For example, if you place a module in slot five of the primary chassis, you must place the second module in slot five of the redundant chassis.
1. Align the circuit board with top and bottom guides in the chassis.
2. Slide the module into the chassis, making sure the module backplane connector properly connects to the chassis backplane.
The module is properly installed when it is flush with other installed modules.
WARNING When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.
IMPORTANT To remove the module, push down on the locking clips at the top right and bottom left of each module. Slide the module out of the chassis.
Publication 1756-IN092B-EN-P - July 2008
ControlLogix Redundancy Module 13
Redundancy Module Cable
The network connections are made by using an LC single-mode style duplex fiber connector assembly.
The cable connection is made at the bottom of the module in a downward orientation. There is enough space between the transmit and receive connectors so you can use the LC connector coupler. Using this coupler keeps the fiber-optic cable from bending so you can connect and disconnect the cable without removing the module from the chassis. Fiber cable catalog numbers available are the 1756-RMC1 (1 m, 3.28 ft); 1756-RMC3 (3 m, 9.84 ft); and 1756-RMC10 (10 m, 32.81 ft).
Connect the Fiber-optic Communication CableFollow this procedure to install the communication cable.
1. Remove the black protective plug on the first redundancy module in the redundant chassis pair.
2. Remove the protective caps from the cable.
ATTENTION The 1756-RM module contains a single-mode transmitter. Connecting this module to a multi-mode port will damage any multi-mode devices.
ATTENTION Under certain conditions, viewing the optical port may expose the eye to hazard. When viewed under some conditions, the optical port may expose the eye beyond the maximum permissible-exposure recommendations.
ATTENTION The redundancy module communication cable contains optical fibers. Avoid making sharp bends in the cable. Install the cable in a location where it will not be cut, run over, abraded, or otherwise damaged.
Publication 1756-IN092B-EN-P - July 2008
14 ControlLogix Redundancy Module
3. Attach an LC connector coupler.
Using the coupler keeps the fiber-optic cable from bending so you can connect and disconnect the cable without removing the module from the chassis.
4. Plug the cable connector into the redundancy module.
5. Plug the remaining cable-connector end to the second redundancy module.
TIP The connectors on the cable and the module are keyed for correct installation.
Logix5563 Redundancy Module
44493
Publication 1756-IN092B-EN-P - July 2008
ControlLogix Redundancy Module 15
Fiber-optic Communication Cable
Optical Power Budget
You can determine the maximum optical-power budget in decibels (dB) for a fiber-optic link by computing the difference between the minimum transmitter-output optical power (dBm avg) and the lowest receiver sensitivity (dBm avg).
The optical-power budget provides the necessary optical-signal range to establish a working fiber-optic link. You must account for the cable lengths and the corresponding link penalties. All penalties that affect the link performance must be accounted for within the link optical power budget.
Optical Power Budget Ranges
Attribute Value
Connector LC-type (fiber-optic)
Cable type 8.5/125 micron single-mode fiber-optic cable
Channels 1 (transmit and receive fiber)
Length, max 4000 km(1)
(1) Longer distances can be supported based on the systems’ optical power budget. See the section Optical Power Budget.
Transmission Less than or equal to 100 Mbps
Wavelength 1300 nm
Transmitter Minimum Typical Maximum Unit
Output optical power -15 -8 dBm
Wavelength 1261 1360 nm
Receiver
Receiver sensitivity -38 -3 dBm avg
Receiver overload -8 dbm avg
Input operating wavelength 1261 1580 nm
Publication 1756-IN092B-EN-P - July 2008
16 ControlLogix Redundancy Module
Apply Chassis PowerOpen the chassis panel and apply power.
Check Power Supply and Module Status IndicatorsCheck the status indicators and alphanumeric display to determine if the power supply and module are operating properly.
Logix5563 Redundancy Module
44490
Logix5563
Redundancy Module
Redundancy Module
Alphanumeric Display
OK indicator is red during self-test, then green.
COM
Power Supply indicator is green.
PRI
44491
Publication 1756-IN092B-EN-P - July 2008
ControlLogix Redundancy Module 17
Flash Upgrade the Modules
To flash upgrade the modules to the latest firmware revision, perform this procedure.
1. Go to http://support.rockwellautomation.com and download the latest firmware revision for your 1756-RM module.
2. Apply power to only one redundant chassis.
3. Wait for the module to scroll display: APPLICATION UPDATE REQUIRED.
4. Start your ControlFLASH firmware upgrade kit and apply the latest firmware to the module.
For additional information on identifying and upgrading your 1756-RM module, see the ControlFLASH Firmware Upgrade Kit Quick Start, publication 1756-QS105.
5. Verify that the module displays PRIM, indicating a successful flash upgrade.
6. Turn off the power to the redundant chassis used in step 2.
7. Apply power to the other redundant chassis.
8. Wait for the module to scroll display: APPLICATION UPDATE REQUIRED.
9. Start your ControlFLASH firmware upgrade kit and apply the latest firmware to the module.
IMPORTANT Back up any programs or data that you have saved to a device. When you upgrade firmware, all old data is overwritten.
IMPORTANT Make sure you know the serial number from your original firmware disk. To upgrade to the latest firmware revision, such as 2.x, you need to provide the original serial number. If you don’t have the serial number, refer to Rockwell Automation Support on the back cover.
Publication 1756-IN092B-EN-P - July 2008
18 ControlLogix Redundancy Module
Designate the Primary Chassis and Qualify the SystemOnce you assemble the chassis, you must designate the primary chassis. Usually, the first chassis you apply power to is the primary chassis. After you have applied power, qualify the system so that all module pairs are at compatible firmware-revision levels.
Designating the Primary Chassis
The chassis that you apply power to first is automatically designated as the primary chassis. The 1756-RM module displays PRIM on the module’s four-character display to acknowledge that this chassis is the primary control chassis.
If both modules have power applied to them simultaneously, the module with the lowest serial number is designated as the primary chassis and displays PRIM on the module’s four-character display. In addition, the PRI status indicator on the primary 1756-RM module is green. The secondary chassis displays either DISQ or SYNC, depending on the state of the secondary chassis. In addition, the PRI status light on the secondary 1756-RM module is not illuminated.
ATTENTION Do not apply power to the chassis until you have read the instructions for designating the primary chassis. Applying power to the chassis is crucial to designating the primary and secondary chassis.
Do not attempt to designate a primary chassis before loading in an application image. Refer to Flash Upgrade the Modules on page 17 before you designate the primary chassis and qualify the system.
Publication 1756-IN092B-EN-P - July 2008
ControlLogix Redundancy Module 19
Conversion from a Nonredundant to a Redundant Configuration
You can upgrade the standalone chassis to a redundant chassis pair, by inserting a 1756-RM module in the standalone chassis and setting up an identical chassis with compatible modules (including the 1756-RM module) in the same slot as the standalone chassis.
If the partnered chassis, containing nonredundant modules or nonredundancy compliant firmware, is designated as the secondary chassis, it will stop functioning.
Qualify the System
When you first apply power to the designated primary and secondary chassis, the redundant system begins to qualify them. During qualification, the primary modules are compared with the secondary module partners to verify that the hardware and firmware are compatible.
If the 1756-RM module displays Then
SYNC after the chassis has been started and qualified.
The chassis configuration and the firmware revision levels are compatible.
DISQ
Important: The secondary 1756-RM module initially displays DISQ until it completes the qualification process. This may take 1…3 minutes.
A issue exists:
• with the chassis configuration.• with incompatible firmware-revision levels
between the primary and secondary modules.See Flowchart of Starting a Chassis with a
Healthy 1756-RM Module on page 20.
• if the ControlNet-module partners’ Keeper parameters are not the same.
• if the ControlNet MAC ID’s are not set to the same node address.
Publication 1756-IN092B-EN-P - July 2008
20 ControlLogix Redundancy Module
Flowchart of Starting a Chassis with a Healthy 1756-RM Module
1756-RM module is started
Lock backplane to stall faster starting modules
Perform Self Test display:Txxx
Pass Self Test?Assert SYS_FAIL
YesThe 1756-RM module waits up to five seconds for a more slowly starting 1756-RM module.
Is another 1756-RM module
present?
Other 1756-RM module out of Power-up or in a lower slot
Release backplane lock Yes
No
Release backplane lock
Begin search for other module
Major Unrecoverable Fault State display:Exxx
1756-RM module reports faults and status via Health Status, four-character display, and/or backplane.
Ten-second startup search period
No
Module found?
Redundancy compliant?
Notify module of 1756-RM presence
Yes
No
No
Yes
After the release of the backplane lock, the 1756-RM module has 200 ms to notify any waiting modules.
Alone (no partner chassis)?
Partner also during start?
Partner already
primary?
No
No
No Partner Chassis display:PRIM
Partner also in Powerup display:????
Partner is Primary display:DISQ
Partner is disqualified secondary display:PRIM
Yes
No
No
No
YesYes
Yes
Yes
No
Publication 1756-IN092B-EN-P - July 2008
ControlLogix Redundancy Module 21
1756-RM Configuration ToolThe 1756-RM configuration tool is available through RSLinx software. This tool provides you with these configuration options:
• Assign primary and secondary chassis ID's• Display redundancy-compliant modules• Issue commands and monitor redundancy status• Modify configuration options• Display module names and revision levels by reading information
from modules that are not 1756-RM redundancy module compliant• Provide system event history
For additional information about the configuration tool, see the ControlLogix Redundancy System User Manual, publication 1756-UM523.
Auto-Synchronization Parameter
You can configure the Auto-Synchronization parameter to control whether the 1756-RM module automatically initiates qualification whenever the control chassis powers up or the 1756-RM module encounters changes to the system that triggers a re-qualification attempt.
Auto-Synchronization has two states: ENABLED or DISABLED. If DISABLED, you must manually synchronize the secondary chassis. If ENABLED, the primary 1756-RM module attempts to automatically qualify the system.
For additional information about triggers, see the ControlLogix Redundancy System User Manual, publication 1756-UM523.
Publication 1756-IN092B-EN-P - July 2008
22 ControlLogix Redundancy Module
Installing or Removing the Module Under PowerYou can install or remove the module while chassis power is applied. You can remove and insert the primary or secondary 1756-RM module from the chassis or disconnect the inter-RM cable for maintenance without losing control.
Reset the 1756-RM Module
There are two ways to reset the module. You can either cycle power to the chassis or remove the module from the chassis and reinsert the module.
Remove or Replace the Module
1. Push on upper and lower module tabs to disengage them.
2. Slide the module out of the chassis.
WARNING When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.
IMPORTANT Only choose to cycle power to the module if you will not loose control of your process.
IMPORTANT If you want to resume system operation with an identical module, you must install the new module in the same slot.
Publication 1756-IN092B-EN-P - July 2008
ControlLogix Redundancy Module 23
Status IndicatorsThe 1756-RM module has these diagnostic status indicators.
Module Status DisplayThe module status display provides diagnostic information.
Display Cause
Testing four-character display at startup
DISQ Disqualified secondary chassis
ERAS Boot mode - erasing firmware
Exxx(1) Major fault situation
PRIM Primary chassis
message The shifted message string alternates with the error ID code
PROG Boot mode - loading new firmware
QFNG Qualifying Secondary
SYNC Qualified secondary chassis
PRI COM OK
REDUNDANCY MODULE
PRI COM OK
E V N TModule Status Display, see page 23.
Health Status Indicator, see page 24.
Communication Status Indicator, see page 25.
Chassis State Status Indicator, see page 25.
Publication 1756-IN092B-EN-P - July 2008
24 ControlLogix Redundancy Module
Health Status IndicatorsThe Health status indicator reveals if power has been applied to a module and if it is operating correctly.
Txxx(2) 1756-RM module self test at startup
TEST Module is running on-board diagnostics during powerup.
ICPT A test line on the backplane is asserted.
!Cpt The modules in one or both of the chassis in the redundant pair do not belong to the same platform.
WAIT Application firmware is starting up.
XFER Application firmware load in progress.
ICPT A test line on the backplane is asserted.
???? Resolving transition state
!Cpt The modules in one or both of the chassis in the redundant pair do not belong to the same platform.
(1) xxx represents an error or fault code, with the two least-significant characters in decimal.
(2) xxx represents a hexadecimal test identification number.
Status Conditions
Off No power has been applied to the 1756-RM module.
Solid red • The module is conducting a self test while it is being started.
• The 1756-RM module has experienced a critical failure.
Flashing red • The 1756-RM module is experiencing an NVS update.
• The 1756-RM module has experienced a noncritical failure.
• The 1756-RM module has been configured improperly.
Solid green The 1756-RM module is operating normally.
Flashing green The 1756-RM module is operating normally but is not communicating with other modules.
Display Cause
Publication 1756-IN092B-EN-P - July 2008
ControlLogix Redundancy Module 25
Inter-1756-RM Module Communication Status IndicatorThe Inter-1756-RM module communication status indicator indicates activity on the Inter-1756-RM module communication link.
Chassis State Status IndicatorThe Chassis State status indicator identifies whether the chassis is primary.
Status Conditions
Off • No power has been applied to the 1756-RM module.
• There is no Inter-1756-RM module communication activity.
Red < 1 second The 1756-RM module has been started and has established partner communication.
Solid red The 1756-RM module has experienced a critical communication failure.
Flashing green • Communication activity is present.
• Sampled every 250 ms.
Status Conditions
Off • No power has been applied to the 1756-RM module.
• The 1756-RM chassis state is in secondary or failed state.
Green < 1 second Power up with partner 1756-RM module determining primary state.
Solid green 1756-RM chassis state is in a primary state.
Publication 1756-IN092B-EN-P - July 2008
26 ControlLogix Redundancy Module
1756-RM Module Chassis States
Status Conditions
PWRUP Power up
PwNS Primary with No Secondary Partner
PwDS Primary with Disqualified Secondary Partner
Primary with Qualifying Secondary Partner
PwQS Primary with Qualified Secondary Partner
DSwNP Disqualified Secondary with No Partner
DSwP Disqualified Secondary with Primary Partner
Qualifying Secondary
QSwP Qualified Secondary
PLgU Primary Locking for Update
PLU Primary Locked for Update
SLgU Secondary Locking for Update
SLU Secondary Locked for Update
Publication 1756-IN092B-EN-P - July 2008
ControlLogix Redundancy Module 27
1756-RM Module Scrolling Display Messages
Message Description Action
EEPROM Update Required
Module in Boot mode and requires an image to be loaded in the EEPROM.
Replace Module.
BOOT Erase Error Module in Boot mode and unable to erase the nonvolatile memory device.
Cycle power to the module and attempt to reflash the module. If error persists, replace the module.
BOOT Program Error Module in Boot mode and unable to erase the nonvolatile memory device.
APP Erase Error Module in App mode and unable to erase the nonvolatile memory device.
APP Program Error Module in App mode and unable to erase the nonvolatile memory device.
EEPROM Write Error Module in Boot mode and unable to erase the nonvolatile memory device.
Publication 1756-IN092B-EN-P - July 2008
28 ControlLogix Redundancy Module
1756-RM Module Fault Codes and Display MessagesThe 1756-RM module faults fall into four categories.
All fault types are logged in the 1756-RM module’s event log, which is stored in nonvolatile memory. You can access the event log through the configuration tool, refer to the ControlLogix Controllers Users Manual, publication 1756-UM523.
Fault Type Description
Minor Recoverable • The fault does not stop redundancy operations and provides you with a recovery mechanism.
• The 1756-RM module may clear some minor recoverable faults on its own.
Minor Nonrecoverable • The fault does not stop redundancy operations.
• No recovery mechanism is available.
Major Recoverable The fault impacts redundancy operations, although the effect may not be immediate. For example, if the fault occurred in the secondary 1756-RM module, it may not affect control until the primary 1756-RM module fails.
Major Nonrecoverable • This is a critical fault. Redundancy operations will cease.
• A switchover may occur.
• No recover mechanism is available.
• The module may need to be replaced.
Publication 1756-IN092B-EN-P - July 2008
ControlLogix Redundancy Module 29
In addition to the event log, the 1756-RM module displays major faults on the module’s four-character status display in one of two ways; two through four-character word abbreviations and alpha numeric codes.
1st Word
2nd Word
3rd Word
4th Word
Error Description Actions
CFG LOG ERR Configuration log error. No action is required.
COMM RSRC ERR Communication resource error.
Reset the 1756-RM module.
COMM RSRC ERR PRT1 Port1 Communication resource error on Backplane.
Reset the 1756-RM module and check the rack.
COMM RSRC ERR PRT2 Port2 Communication resource error on Inter-1756-RM link.
1. Reset the 1756-RM module.
2. Check the cable.
COMM ERR PRT1 Port1 Communication error, Backplane communication.
Check or replace the rack.
COMM ERR PRT2 Port2 Communication error, Inter-1756-RM module communication link.
Check or replace the single-mode cable.
COMM ERR General Communication Error.
No action is required.
DUPL RM Duplicate 1756-RM module. This module is not in control.
Remove this 1756-RM module.
EVNT LOG ERR Event Log Error. No action is required.
FMWR ERR Firmware error. Re-flash firmware.
HDW ERR Hardware failure. Replace the 1756-RM module.
OS ERR Operating system error. Replace the 1756-RM module.
Publication 1756-IN092B-EN-P - July 2008
30 ControlLogix Redundancy Module
Alpha Numeric Error Codes
The fault code is a four-character alpha-numeric string. Valid characters are 0…9 and A through Z, except S and O. The first character is always E. Each firmware subsystem within the 1756-RM module is assigned a range of fault codes. Each subsystem assigns fault codes within its range.
RM PWR DOWN 1756-RM module Power Down, Module detected a DC_Fail condition.
Check the other modules in the rack.
WDOG ERR Watchdog time out. Reset the 1756-RM module.
WDOG FAIL Watchdog task failed its status check.
Replace the 1756-RM module.
Valid Character String Indication
E Error.
x1 The subsystem in which the error was detected.
x2 The subsystem function or group of functions in which the error was detected.
x3 The specific error.
1st Word
2nd Word
3rd Word
4th Word
Error Description Actions
Publication 1756-IN092B-EN-P - July 2008
ControlLogix Redundancy Module 31
If you encounter one of these error codes, write the Exxx code down and contact Rockwell Automation Product Support by using one of the methods described in the Rockwell Automation support section on the back cover.
Recovery Messages
For certain faults, the module status display provides recovery instructions. Up to four, four-character words are displayed.
Range Subsystem Range Subsystem
E 0 _ _ Backup Control Object E C _ _ Object Communication
E 1 _ _ OS Board Support Package E D _ _ Wall Clock Time Object
E 2 _ _ Chassis Profile Object E E _ _ Non-maskable Interrupt Service Routine
E 3 _ _ Coordinated System Time Object
E F _ _ Nonvolatile Storage Object
E 4 _ _ Device Object E G _ _ RM Fault Handler
E 5 _ _ Extended Log Object E H _ _ Self Test Object
E 6 _ _ Event Log Object E I _ _ Workstation Display Object
E 7 _ _ Backup Communication Object
E J _ _ Industrial Control Platform Object
E 8 _ _ ICP Toolkit E K _ _ RM Watchdog Manager
E 9 _ _ Indicator Device Driver E L _ _ Instrumentation Object
E A _ _ RM State Machine E M _ _ File Object
E B _ _ Event Log Device Driver
Recovery Instruction Code Description
RPLC MOD Replace the module.
RSET MOD Reset the module.
REMV MOD Remove the module.
SEAT MOD Reinsert the module into the chassis.
Publication 1756-IN092B-EN-P - July 2008
32 ControlLogix Redundancy Module
SpecificationsRedundancy Module - 1756-RM
Attribute Value
Backplane current 4 mA @ 1.2V dc 120 mA @ 24V dc 1.2 A @ 5.1V dc
Mounting ControlLogix chassis, single slot module
Enclosure type rating None (open-style)
North American temperature code T4
Power dissipation, max 9.0 W
Thermal dissipation 31 BTU/hr
Publication 1756-IN092B-EN-P - July 2008
ControlLogix Redundancy Module 33
Environmental Specifications Attribute Value
Temperature, operating
0…60 °C (32…140 °F)IEC 60068-2-1 (Test Ad, Operating Cold),IEC 60068-2-2 (Test Bd, Operating Dry Heat),IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
Temperature, nonoperating
–40…85 °C (–40…185 °F)IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
Relative humidity 5…95% noncondensing IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration IEC 60068-2-6 (Test Fc, Operating): 2 g @ 10…500 Hz
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):30 g
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock):50 g
Emissions CISPR 11: Group 1, Class A
ESD immunity IEC 61000-4-2:6 kV contact discharges8 kV air discharges
Radiated RF immunity IEC 61000-4-3:10V/m with 1 kHz sine-wave 80%AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz 3V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz
Publication 1756-IN092B-EN-P - July 2008
34 ControlLogix Redundancy Module
Certifications Certification Value
Certifications (when product
is marked)(1)
(1) See the Product Certification link at http://ab.com for Declarations of Conformity, Certificates, and other certification details.
UL UL Listed Industrial Control Equipment. See UL File E65584.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radio Communication Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
Publication 1756-IN092B-EN-P - July 2008
ControlLogix Redundancy Module 35
Additional ResourcesThese documents contain additional information concerning related Rockwell Automation products.
You can view or download publications at http://literature.rockwellautomation.com. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.
Resource Description
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Contains general guidelines for installing a Rockwell Automation industrial automation system.
ControlLogix Redundancy System User Manual, publication 1756-UM523
Contains information about ControlLogix redundancy systems and media.
ControlFLASH Firmware Upgrade Kit Quick Start, publication 1756-QS105
Contains information on how to upgrade module firmware.
ControlLogix Controllers User Manual, publication 1756-UM001
Contains information on how to install, configure, program, and operate a ControlLogix system.
ControlLogix Chassis-Series B Installation Instructions, publication 1756-IN080
Contains information on how to install a ControlLogix chassis.
ControlLogix Power Supplies Installation Instructions, publication 1756-IN596
Contains information on how to install the 1756-PA75 and 1756-PB75 ControlLogix power supplies.
Publication 1756-IN092B-EN-P - July 2008
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
Allen-Bradley, Rockwell Automation, TechConnect, ControlLogix, RSLogix 5000, Logix5555, RSNetWorx, ControlFLASH, and RSLinx are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
United States 1.440.646.3434 Monday – Friday, 8 a.m. – 5 p.m. EST
Outside United States Please contact your local Rockwell Automation representative for any technical support issues.
United States Contact your distributor. You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
Publication 1756-IN092B-EN-P - July 2008 PN-29541Supersedes Publication - 1756-IN092A-EN-P Copyright © 2008 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
dPrint? | Content/Comp # | Split Shipment Indicator Flag | WCSS Item Number | Customer Item Number | Item Description | Producing Plant | Job Number | Replenishing Plant | Plant Code | Product Code | Packaging/Ordering UOM | Qty per Packaging/Ordering UOM | List Price Per Ea | Transfer Cost per Ea | Sell Price per Ea | Standard Cost (per Ea) | Min Order Qty (in eaches) | Multiple Order Qty (in Eaches | Chargeback Price | Item Reference #1 | Item Reference #2 | Revision Field | Max Order Qty (in eaches) | Sequentially Numbered Item? | Sequentially Numbered Item - Details | Priced for Digital or Offset | Content File Location | Item Category Form (F) Book (B) | Item Subtype | Orientation | Sides Printed | CSS/JLS Stock Componet | Paper Size Width | Paper Size Length | No of Forms to a Sheet | Page Qty | Sheets Qty | CSS/JLS Production Stock | Paper Stock Type | Paper Stock Weight | Paper Stock Color | Stack Offset | Tab Size | # of Tabs | Binder Size | Binder Color | Binder Ring Type | Binder Transparency (clearview or matt) | Thermal Tape Color | Trim Size Width | Trim Size Length | Stitching Location | Drilling Size | Drilling Location | Glue Location | # / Pad | Fold Type | Fold At | # / Poly | # / Box | Comments | Cross Reference Item Number 1 |
Publication Number | Publication Title | Packaging/Ordering Unit Of Measure | Qty per Packaging/Ordering Unit of Measure | Min Order Qty | Multiple Order Qty | Business Group | Cost Center | Revision Date | Max Order Qty | Black & Whiteor Color | Item CategoryForm (F) or Book (B) | Binding/Stitching | Orientation | Sides Printed | Printing Paper Size Width | Printing Paper Size Length | Number of Forms to a Sheet | Page Count of Publication | Number of Sheets Required to Print | CSS/JLS Production Stock | Paper Stock Type | Paper Stock Weight | Paper Stock Color | Stack Offset | Tab Size | Number of Tabs Needed | Binder Size | Binder Color | Binder Ring Type | Binder Transparency | Thermal Tape Color | Finished Trim Size Width | Finished Trim Size Length | Stitching Location | Drill Hole Size | Number and Location of Drill Holes | Glue Location | Number of Pages per Pad | Fold Type | Fold At | Number of Pieces per Poly wrap | Number of Pieces per Box | Comments | Part Number | ||||||||||||||||||
Are these items being setup on dPrint? (Yes or No). If yes, Inv Mgmt to check "Print Management" flag on item setup. | The content/Comp # will be provided by the CSC once the spec files are loaded to the DAS (the files must be named with the WCSS item #). The content/comp# must be hardcoded to the Item message Field in WCSS. Must be a 10 Digit number that starts with an 8. | Required. Setting this to yes will allow warehouse product to ship out before the JIT item is completed. Setting this to no will hold all warehoused items until the printing of this item is complete. Please indicate Y or N.** Note: Each item with a Y will always ship separately even if produced at the same time as like items. | Optional. 15 Characters Max. If the WCSS number provided already exists in the system, then Inventory Management will assign a random WCSS number. | 30 characters maximum. | Cannot use quote symbol, that is--"--. | Required. Which plant/Print Center will produce this item? | Required. To be provided from the producing plant for JIT s/u | Required: What is the plant code of the plant that has owning rights to the dPrint files? If produced at multiple plants there can be only one owning plant. | Required. What is the plant code of the facility that will produce this item? (see "Plant and Whse Codes" tab below) | Required. Enter one of the applicable product. | Method of packaging for publication shipmentClick here for explanation of each value in the pull-down | Required. This field auto-calculates (transfer cost divided by .5). Used to determine Standard Cost on WCSS (which is 50% of the list price for these product codes). | Required. Transfer Cost per ordering/packaging unit of measure. | Required. Price that will be billed to customer upon order. If Price Breaks, enter "Price Breaks" and note them on separate spreadsheet. | Required. Replacement Cost per Packaging/ordering UOM. | Click here for an explanation of this field; otherwise, type NA. | Optional. Used to assist customer with internal Chargebacks to end users. (per packaging/ordering UOM) | IMPORTANT: This information must match the DocMan record.Click here for explanation of each value in the pull-down menu. | IMPORTANT: This information must match the DocMan record. | IMPORTANT: This information must match the DocMan record.Date on the publication. | Click here for explanation of each value in the pull-down menu. | Indicate Yes or No. Enter Yes if the item is a sequentially numbered item. | Describe the details behind the sequentially numbered item, such as:- Record Sequence Shipped: whse will record the sequence numbers that shipped- Ship in Sequence Record: required to ship products in particular sequence and the whse records the numbers | Required: If PDF is to be retained in the DAS enter DAS in this field, if item is part of eCreate or Custom Docs put CUSTOM in this field. | Typically a Book.Click here for explanation of each value in the pull-down menu. | Click here for explanation of each value in the pull-down | Click here for explanation of each value in the pull-down menu. | Optional: Use when finished product stored in the warehouse is to be inserted into the construction of a JIT book. | IMPORTANT: Not Trim Size widthThis is the width of the paper on which the publication is printed. | IMPORTANT: Not Trim Size lengthThis is the length of the paper on which the publication is printed. | Click here for explanation of how to determine the information required. | Click here for explanation of how to determine the information required. | Optional: Use when product is being printed on Shell Stock. Provide warehoused WCSS Item nu,mber of product to be used in the production of JIT item. | Click here for explanation of how to determine the information required. | The pull-down menu lists the most common choices.Click here for a full list of the available choices.If you use a choice not in the pull-down list, type the value in the cell below the pull-down menu. | If item uses tabs; otherwise, NA. | If needed; otherwise type NA. | If item used in a binder; otherwise, NA. | If item used in a binder; otherwise, NA. | If item used in a binder; otherwise, NA. | If item used in a binder; otherwise, NA. | If publication is thermal tape bound; otherwise, NA. | Click here to see the available finished trim sizes.The sizes are listed - width x length. | Click here to see the available finished trim sizes.The sizes are listed - width x length. | If publication is Book [B] and stapled; otherwise, NA. | Click here for a list of possible drill locations | If publication uses padding; otherwise, NA. | If publication is a notepad or message pad; otherwise, NA. | Click here for explanation of each value in the pull-down menu. Folding of final document optional | The location(s) of the fold | Click here for explanation of each value in the pull-down menu. | Use this column to list:- Cover Stock- Text Stock- Cover Ink- Text Ink- Spine, if necessaryAlso use to indicate any other production or finishing requirements not provided in previous columnsClick here for an explanation of the available Cover Stock, Cover Ink and Text Ink values. | List only if pubication is used in manufacturing; otherwise, leave blank. | |||||||||
1756-IN092B-EN-P | ControlLogix Redundancy Module Installation Instructions | EA | 1 | 1 | Marketing Commercial | CMKMAY IA Control/Vis/Net - 19021 | 07/21/2008 | 5 | Black & White | B | SADDLE | PORTRAIT | HEAD2HEAD | RRD must provide this information | RRD must provide this information | 36 | 9 | PLAIN | 20# | White | RRD must provide this information | NA | NA | NA | NA | NA | NA | NA | 4.75 x 7 | 4.75 x 7 | SIDE | NA | NA | NA | NA | HALF | 50 | RRD must provide this information | Text Stock = 20# White Opaque BondText Ink = Black | 29541 |