01L 17.02.10 AS BUILT JGL SAK GKri B 27.01.10 Issued for Acceptance JGL SAK GKri A 03.12.09 Issued for Acceptance FrLe KjAB GKri Rev./ status
Date Reason for issue Author Contr. Disc Approved
Contractor Approved
Hydro Approved
Access Keywords Replace Replaced by Issued by Package no.
U Unclassified
H Internal (Unit)
F Confidential
SF Strictly confidential
Retention
EEx p Manual
50217
Responsible Purchase order no. Frode Lervik PO 5451115
Area System Supplier ref. C14 23 1235.000-Z-003
Tag. no
0 To be destroyed after handling 3 Retention 3 months 2 Retention 2 years 5 Retention > 5 years P Retention project period P02 Retention project period plus 2
years P05 Retention project period plus 5
years P10 Retention project period plus 10
years E Return to basic organisation I Until reissued
Supplier
EE-23-0001
Document title
Client
TECHICAL MANUAL FOR EEx p SYSTEM
HYDRO V&M
Cover Pages
27
Attachment
ACCEPTANCE CODES: ID. NO.
1: Accepted 2: Accepted with
comments incorporated Document no.
3: Not accepted. Revise and resubmit
Project and installation
Orginator Discip.+Doc. type
Package no. Sequence no. Rev./ Status
4: For information only 17-1B AOP E04 50217 0001 01L
An der Hartbrücke 8 D-64625 Bensheim Tel.: 06251/63736 FAX: 06251/63729
sheet no. of sheets
STANDARD 1 25 title
TECHNICAL DOCUMENTATION EEx p SYSTEM F-361.C4
date of change revision originator format file
03.04.2006 Rev. 3.1 A4 F-361c4se.doc
rev. originator: release: 3.0
originate (date / sign) checked: (date / sign) release: (date / sign)
15.07.2003
07.04.2006 / QBS
Bachmann
EEEExx pp ssyysstteemm ffoorr mmoottoorr ooppeerraattiioonn iinn EExx--aarreeaass
Technical documentation
Description EEx-p System F-361.C4 2
Änd./
Mod.
15.07.2003 page 2 of 25
Description of EEx p system F-361.C4 The EEx p pressurization system F-361.C4 serves to create and maintain an overpressure in an EEx p motor enclosure to prevent the ingress of the ambient(potentially explosive) atmosphere, according to EN 60079-2 / EN 50016. In addition a compensation for leakage losses is realized in a unique redundancy combination with a mechanical and an electronic controlled proportional valve. Motors with kind of Ex-protection EEx p can operate in combination with the EEx p system F-361.F4 in Ex areas 1 and 2 (according to DIN EN 60079-14). Combined with an enclosure which is suitable for use with overpressure the Ex protection class EEx p IIC T4 according to EN 60079-2 / EN50016 can be obtained. Standard ambient temperature for operation is -20 °C up to +55°C. Other temperature ranges are available on request.
Before commissioning please take note of the following points: 1. Clean the connected air pipe or tubing system of the installation plant to ensure
that the supplied air tube is free of dirt or small parts which will cause a malfunction of the purging system, if no air filter is used.
2. The internal volume of the motor enclosure must be purged with non-explosive compressed air, to reduce a possible explosive gas concentration to safety limits.
3. After purging the motor enclosure, an overpressure must be maintained inside the motor to prevent ambient air, which can contain explosive gas.
The overpressure inside the motor enclosure is continuously monitored.
If the pressure drops under the reference value an alarm signal is given and the motor has to be switched off automatically. The EEx p System F-361.C4 comprises the following components:
• control cabinet ST-200F/ST-200FM
consists of: main air valve for pressure supply, purge valve, proportional valve for operating pressure (leakage compensation), adjustment valves for purge- and leakage volume, measure points (to acquire leakage volume and the pressure inside the motor enclosure), indicator for purge pressure, EEx d junction box F900.041, EEx d box F-900.001, main switch, control unit F-351 (connected with terminals in junction box) for the signals "ready to start“, “motor not purged“, purging in progress", "purge sequence finished" and „motor shutdown“.
The control cabinet ST-200C/200CM monitors the air flow of the outlet valve and the pressure inside the motor enclosure. Simultaneous the control automatic works in accordance with EN 60079-2 / EN 50016 and ATEX 94/9. This monitoring system is a highly secure and redundancy controlling unit certified according to EN954-1 (security class Cat. 3).
Description EEx-p System F-361.C4 3
Änd./
Mod.
15.07.2003 page 3 of 25
• Outlet valve VA-100-3H
The outlet facility consists of a heavy duty case with built in pneumatic controlled valve and integrated spark arrestor and particle barrier. The outlet valve opens during the purging sequence to ensure the purging of the motor enclosure according to EN60079-2/EN50016 .The outlet valve itself can be mounted in any position. The valve closes completely if the purging sequence is finished.
• Test certificate The motor system is provided with a test certificate as shown in the annexure of this documentation.
Mounting example
1: control cabinet ST-200C/CM 2: outlet valve VA-100-3H 3: measure point motor inside pressure 4: pilot line to outlet valve 5 and 6: measure points air volume 7: measure line motor inside pressure 8: compressed air connector for supply 9: compressed air connector to motor 10: motor enclosure
EEx p Motor
2
10
1
89
657
P A B
3
4
Description EEx-p System F-361.C4 4
Änd./
Mod.
15.07.2003 page 4 of 25
Dimensions of ST-200C
600
370
cable plate
grill panel
p min A Bp
50
100170
3060
0
800
640
earthing point M8
90
85130+5-5
85
pressure air outlet to motor
pressure air inlet
If not written down the tolerance is ± 2 mm. Dimensions of ST-200CM
If not written down the tolerance is ± 2 mm.
600
370
p minBAp
50
100170
30
600
800
640
90
85 130+5-5
85
pressure air inletpressure air outlet to motor
cable plateearthing point M8
grill panel
Description EEx-p System F-361.C4 5
Änd./
Mod.
15.07.2003 page 5 of 25
Outlet valve VA-100-3H
450
4 x Ø 18 mmhole arrangement according to DIN 2527NW 100 PN 16
100.
0200.
0
50.0
PA B
300.0
300.
0
67.5°
Ø180.0
450.0
If not written down the tolerance is ± 2 mm. P&I diagram
control unit F-351
P
Minswitch
P
Maxswitch
P
Purgeswitch
adjustment valve"Leakage volume"
main valve pressure regulator
purge valve adjustment valve"Purge volume"
motor enclosure
outlet valve
control valve
measuring pointdifferential pressure
Description EEx-p System F-361.C4 6
Änd./
Mod.
15.07.2003 page 6 of 25
Internal view control cabinet ST-200C / ST-200CM
13
67
5
98
10
06
11
12
2
4
3
1
17
2
1
3
4
5
14
15
16
18
212019
13
10
9
11
120 6
PE 11L1 N 322 64 5 PE7
51 3 7 9 11
PE
-X2
62 4 8 10
5
62 4
1 3
8 10
7 9
12
PE12
11
17
14
15
16
2 4
5
3
1
18
19
-X1
F1K2 K3
8
76
5
51 3 7 9 11
PE
-X2
62 4 8 10
5
62 4
1 3
8 10
7 9
12
PE12
11
PE743 6511 22PE NL1
2
4
3
1
2021
-X1
F1K2 K3
1: control unit F-351 12: adjustment valve “leakage comp.” 2: control cabinet 13: pressure gauge 3: EEx d enclosure F-900.001 14: proportional valve 4: EEx d enclosure F-900.041 15: purge valve 5: name plate 16: adjustment valve „purge volume“ 6: cable plate 17: test conn. “pilot pressure outlet valve” 7: test conn. „diff. pressure“ 18: main switch 8: air outlet to motor 19: conn. “pilot pressure outlet valve” 9: main air valve 20: conn. “diff.pressure” 10: grill panel 21: conn. “motor inside pressure” 11: pressure reducer
Description EEx-p System F-361.C4 7
Änd./
Mod.
15.07.2003 page 7 of 25
Technical data
1: Control unit F-351 Ex-protection class: II 2 G EEx e m ia [p] IIC T4 Protection class: IP 65 Temperature range: -30°C ... +60°C
Certified by: TÜV02 ATEX 1801 Security class: AK4, acc. to EN 954-1, cat. 3 Min flow volume: 0,1 – 99 Nl/s (setting: 10 Nl/s) Pressure switch „Min“: 0,8 – 25 mbar (setting 0,8 mbar) Pressure switch „Max“: 10 - 25 mbar (setting 15,0 mbar)
2: Control cabinet Type: ST-200C/CM Material: sheet steel, 2 mm
Colour: RAL 7032 Protection class: IP 23 (IP 55 on request) (Other materials or colours on request !) 3: Control- and junction box F-900.001 Ex-protection class: II 2 GD EEx d IIC T6 Protection class: IP 66 Temperature range: -20°C ... +55°C
Certified by: CESI 01 ATEX 036 Bore holes: ½“ NPT
EEx d cable glands Type: FL 1 Diameter: I1B (ELB), I1B for client Ex-protection class: EEx d IIC Protection class: IP 66 Temperature range: -20°C ... +80°C
Certified by: CESI 00 ATEX 052 4: Control- and junction box F-900.041 Ex-protection class: II 2 GD EEx d IIC T6 Protection class: IP 66 Temperature range: -20°C ... +55°C
Certified by: CESI 01 ATEX 036 Bore holes: ½“ NPT
EEx d cable glands Type: FL 1 Diameter: F1B (ELB), I1B for client Ex-protection class: EEx d IIC Protection class: IP 66 Temperature range: -20°C ... +80°C
Certified by: CESI 00 ATEX 052 5: name plate Identification of the system
Description EEx-p System F-361.C4 8
Änd./
Mod.
15.07.2003 page 8 of 25
6: Cable plate W x H x D: 160 x 120 x 10 mm Cut out in cabinet: 80 x 60 mm 7: Test connector
Differential pressure (Dim. for air volume) Connector: quick disconnect coupling DN 5 8: Air connector to motor: Rp 1“, inside screwed flanges on inquiry 9: main air valve: Rp1 ½”, inside screwed flanges on inquiry 10: Grill panel for air compensation 11: Pressure regulator Inlet pressure: max. 25 bar Outlet pressure: 0 – 6 bar 12: Adjustment valve „Leakage volume“ Adjustment range with prop.valve : max. 90 Nm³/h, at 3 bar pre- pressure 13: Pressure gauge Indication range: 0 – 6 bar 14: Control valve „Operating pressure“ Proportional valve (coil type 72): Tamb up to + 40 °C Proportional valve (coil type 73): Tamb up to + 55 °C Ex-protection class: II 2 G EEx m II T4
Certified by: PTB 00 ATEX 2202 X Operating range: variable Nm³/h
15: Purge valve Ex-protection class: II 2 G EEx em II T4 Temperature range: -30°C ... +60°C
Certified by: PTB No. 00 ATEX 2129 X Operating range: max. 450 Nm³/h 16: Adjustment valve
Purge volume Adjustment range if pre-pressure 3 bar: 0 – 450 Nm³/h
17: Test connector Pilot pressure outlet valve
Connector: quick disconnect coupling DN 5 Pilot pressure: ca. 1 bar
Description EEx-p System F-361.C4 9
Änd./
Mod.
15.07.2003 page 9 of 25
18: Main switch Ex-protection class: II 2 G EEx ed IIC T6 Protection class: max. IP66 Certified by: PTB 01 ATEX 1105
Temperature range: -20°C ... +50°C 19: Connector
Pilot line outlet valve Connection: male adapter union , tube 10 mm
20: Connector Differential pressure
Connection: male adapter union , tube 10 mm
21: Connector Motor inside pressure
Connection: male adapter union , tube 10 mm
Electrical data Power supply Purge Operate 230 VAC 150 mA 125 mA 115 VAC 300 mA 230 mA 24 VDC 1200 mA 750 mA
Temperature range F-361.C4 Tamb: -20°C ... +40°C, optional: -20°C ... +55°C, -40°C … +40°C, -40°C … +55°C For an operation below temperatures of – 20°C down to -40°C an Ex-heater (400 W) is additional mounted in the enclosure. Using the EEx p system with temperatures higher than + 40°C the proportional valve (Pos. 14) has to be interchanged with a proportional valve suitable for +60°C. The main switch (Pos. 18) has to be changed while the temperature is higher than + 50 °C. Weight Control cabinet ST-200C/CM: 88 kg Outlet valve VA-100-3H: 27 kg Minimum requirements for air pressure recommended pressure air volume: 450 m3/h / 3 bar particle size: 100 µm max water content: 90 % rel. humidity max medium temp. range: -10 °C … + 40 °C The maximum air flow can reach ca. 450 m³/h and produces during the purging sequence in the motor enclosure an overpressure of ca. 5 mbar. If the air quality is not guaranteed, special filters can be delivered on inquiry.
Description EEx-p System F-361.C4 10
Änd./
Mod.
15.07.2003 page 10 of 25
Basic functional description F-351 For a detailed description see manual F-350. Clear text LC display with choice of language. 3 lines with 12 characters each.
K1 Out PE
MENUE
ValvePE
OK / INFO button Switches the display over between measuring data and info menu. Confirms selected parameters or values.
Wheel Shuttle
Rotary switch, screwdriver-activated. Switches over between different parametrizing menus, submenus or selectable data.
CLEAR TEXT
DISPLAY–3X12
CHARACTERS
Description EEx-p System F-361.C4 11
Änd./
Mod.
15.07.2003 page 11 of 25
Menue
Lang
uage
?
Ent
erpu
rge
time
?
Sw
itchp
o int
min
pre
ssur
e
?
Sw
itchp
oint
o ver
pres
sure
?
Switc
hpoi
ntp u
rge
star
t
?
OK
OK
OK
OK
OK
E
nter
purg
e tim
e 0
0:1 0
min
Sw
itchp
oint
p urg
e st
art
xx.x
x m
b ar
0.0
5/ s
tep
1 m
bar/
s
tep
OK
1 m
bar/
s
tep
0.0
5/ s
tep
1 m
bar/
s
tep
0.0
5/ s
tep
OK
Par
amet
er ra
nge:
0
,8 -
25 m
bar
pres
et p
aram
eter
: 0,8
C
onfir
mm
in p
ress
ure
xx.
xx m
b ar
OK
OK
OK
C
onfir
mov
erpr
essu
re x
x.xx
mba
r
OK
pres
et p
aram
eter
: 25,
0
Par
amet
er ra
nge:
0
,8 -
25 m
bar
C
onfir
msw
p.pu
rgin
gxx
.xx
mba
r
OK
pres
et p
aram
eter
: 0,5
OK
Par
amet
er ra
nge:
0
,8 -
25 m
bar
upd
ate d
flow
(yy.
yy m
bar)
stor
ed a
s
purg
e st
art p
aram
eter
(x
x.xx
mba
r) s
et p
oint
= fe
e dba
ck v
alue
C
onfir
mS
wp.
pur
g ing
yy.
y y m
bar
OK
Dis
play
cont
ras t
####
____
OK
pres
et p
aram
eter
: 5
Par
amet
er ra
nge:
1
- 8
OK
OK
OK
Func
tion
of re
lay
K1 X
XXXX
Inpu
t dat
a- I
sola
tion
Pre
ssur
ere
gula
t ion
XX
XXX
OK
Par
amet
er ra
nge:
00:1
0 ...
99:
50 m
in
OK
pre s
et p
aram
eter
00:
10 m
in
OK
Con
firm
purg
e tim
e x
x.xx
mi n
Eng
l ish
Fran
cais
OK
OK
OK
Dis
play
cont
rast
?
Func
tion
of r
elay
K1
?
Pre
ssur
e re
gula
tion
?
- Sys
tem
Fau
lt- F
ault
1 m
in- F
ault
flash
- Pre
-al.
MIN
- Pre
-al.
MAX
- Pur
ging
- Byp
ass
pres
et p
aram
eter
: Pur
ging
OK
- Tw
o-po
sitio
n- p
ulse
d- p
ropo
rtion
al
pres
et p
aram
e ter
: pul
sed
Inpu
t dat
a
Sw
itchp
oint
min
pre
ssur
e x
x.xx
mba
r
Sw
itchp
oint
o ver
pres
sure
xx.
xx m
bar
Swp
purg
ing
xx.
xx m
bar
yy.
yy m
b ar
OK
Func
tion
bypa
ss
?
En
ter
Pas
swor
d
5112
OK
F
unct
ion
B
ypas
s<O
N>
/ OFF
OK
OK
F
unct
ion
B
ypas
s O
N /
<OFF
>
Qui
tB y
pass
men
ue
YE
S / N
O
OK
OK
(set
poi
nt)
(feed
back
val
ue)
pres
s fo
r 3 s
ec
12
34
56
78
9
Men
u is
act
ivat
ed, w
hen
Whe
el S
h uttl
e is
t urn
edA
ll m
enu s
are
clo
sed,
if n
o in
puts
are
mad
e fo
r mor
e th
an 1
0 s e
cond
s !
Sta
ndby
/op
erat
e m
odus
durin
g pu
rgin
g se
quen
ce a
ndp
>
switc
hpoi
nt p
(in c
ompi
latio
n)
MEN
U
Ger
man
Qui
tB y
pass
men
ue
YE
S / N
O
OK
Bac
k to
fact
ory
setti
ngs
(pre
sets
) :
- sw
itch
off p
ower
sup
ply
- ke e
p
pr
esse
dO
K
- sw
itch
on p
ower
sup
ply
- wai
t fo r
mes
sage
"LO
AD
ING
mot
or-p
urge
set
tings
"
- tur
n
to
6 o
'clo
ck
encl
osu r
em
in
++
OK
OK
+
Description EEx-p System F-361.C4 12
Änd./
Mod.
15.07.2003 page 12 of 25
Structure and Function
In conjunction with an enclosure (motor enclosure, junction box), the EEx-p system F-361.C4 provides a pressurized motor that is in compliance with EN 60079-2 / EN 50016. For this purpose, it has all the facilities and sensors needed to monitor the necessary purging phase and then to monitor and maintain an overpressure within the EEx-p enclosure (motor cabinet).
1 Structure
The controlling system consists mainly of two components which must be installed separately:
• controlling cabinet ST-200C/CM, with built-in piping ,valves, electronic and • the outlet valve VA-100-3H.
The controller F-351 itself monitors and regulates the overpressure in the enclosure, while the digital/proportional valves doses the air quantity needed to achieve the pressurized apparatus.
2 General Functional Description
After a functional test and start-up, the controller F-351 in the control cabinet ST-200C/CM monitors the flowrate of the compressed air or inert gas during the initial purging process, and then monitors and regulates the internal pressure of the EEx-p enclosure with regard to the surrounding atmosphere during normal operation.
Display In three lines of 12 characters each, the digital display shows the enclosure’s internal pressure during normal operation, and the remaining purging time in minutes and seconds during the initial purging process. During normal operation, you can call up further information by pressing the button "OK / Info". Faults which are detected during the self-check are shown here with a number. OK-button The button on the left side (“OK / INFO”) is used in normal operation to call up the stored parameters “Enclosure Pressure”, “Purging Time”, “Function of Relay 3”, “Function of Relay 4”, “Switchpoint of Purge Start”, “Switchpoint of Minimum Pressure”, “Switchpoint of Overpressure” and “Regulation”. During the parametrization, this button is used to select and confirm the various parameters.
Description EEx-p System F-361.C4 13
Änd./
Mod.
15.07.2003 page 13 of 25
Rotary switch The right field (“Menu”) permits access to the Wheel Shuttle® with a tool (e.g. a screwdriver) for parametrizing the controller. With this Wheel Shuttle, you can start the parametrization and set the individual parameter values.
Screw terminal In the lower part of the cover (see page 1), the terminal assignment of the Controller is shown. Terminals 1 to 3 are inputs; they provide electrical power to the Controller. Terminals 4 to 19 are outputs, over which the monitoring unit drives its peripherals, e.g. the digital/proportional controller.
Immediately after the compressed air supply is opened and the main voltage is applied, the internal self-check of the controller begins automatically. Any fault occurring during the self-check sequence is indicated by An explanation of the fault numbers (XX) is given in the manual, section 3.5 “Faults and Troubleshooting”, Table 1: Faults detected during the self-check. If the self-check is carried out successfully, the initial purging of the enclosure commences, ending when at least five times the enclosure volume has been circulated. The purging process is indicated by the message in the display. All the time, the remaining purging time is counted down to 00 min and 00 seconds. After the end of the purging sequence, the Non-Ex units in the enclosure are switched on. The overpressure in the enclosure then constantly monitored for adherence to the setpoint value (factory setting: 2.0 mbar) and also for transgressing of the Min value (factory setting: 0.9 mbar) and exceeding of the Max value (factory setting: 20.0 mbar). Normal operation is indicated by the message in the display.
FAULT XX
REMAINING PURGE TIME: XX MIN XX SEC
ENCLOSURE PRESSURE: XX..XX MBAR
Description EEx-p System F-361.C4 14
Änd./
Mod.
15.07.2003 page 14 of 25
3 Behaviour of the controller during normal operation In normal operation, the controller F-351 in the control cabinet ST-200C/CM monitors and regulates the internal pressure of the EEx-p enclosure to the setpoint value in relation to the surrounding atmosphere. The limit values set in the factory are: MIN: 0.8 mbar and MAX: 15.0 mbar. At an increased level of internal enclosure pressure (over the limit value for Max) with regard to the surrounding atmosphere, the mechanical valve VA-100-3H opens automatically. This allows the excessive internal pressure to drop. The valve closes again when the internal enclosure pressure has again attained normal values (under the limit value for Max). Function procedure of the EEx p system After connecting the pressure supply and turn on the main switch (Pos.18) the purge valve (Pos.15), the proportional valve (Pos.14) and the outlet valve VA-100-3H are open. Through the adjustment valve (Pos.12) and in addition through the proportional valve and the parallel mounted manual valve (Pos. 9) the pressure air reaches the motor enclosure and flees through the outlet valve VA-100-3H. If the purge flow of the motor enclosure exceeds the adjusted minimum flow value, the purging sequence starts. The remaining purge time is displayed. If the air flow through the motor during the purging sequence drops below the pressetted value for minimum flow, the purging sequence stops. The required purging time depends on the setting of the purge volume (normally 10 times the free volume of the motor cabinet) and the presetted inlet pressure at the pressure regulator (7). After the purging sequence is finished: The power supply of the purge valve (Pos.15) is cut off with the relay K3 in the EEx d box. Thereby the outlet valve VA-100-3H and the purge valve closes. The pressure air now flows only through the manual valve "leakage losses" and the proportional valve in the motor enclosure. The required overpressure in the motor enclosure is now maintained by the proportional valve and the manual valve. Likewise due to compensation of leakage losses. At the terminals –X2 9 and 10 in the EEx d box the signal "ready to start" is given. The overpressure in the motor enclosure is monitored by the pressure switches "Min" and "Max" of the control unit. If the overpressure drops below the presetted value "Min", or exceeds the overpressure value "Max", then K2 and K3 in the EEx d box are switching and a signal is given to cut off the motor power. To prevent a false alarm, as a result of pressure oscillations through the motor housing during the purging sequence, terminals 9 and 10 have a drop-out time delay of approx. 5 sec.
Description EEx-p System F-361.C4 15
Änd./
Mod.
15.07.2003 page 15 of 25
EEx d junction and control box F-900.041 In the EEx d junction box are all needed functions for the potential free signals and terminals for power supply mounted. The power supply has to be connected
in this box. The EEx d box consists of: 2 x PE terminals type USLKG 5 11 x terminals type UK5N 2 x relays with 4 switchover contacts (K2, K3) 1 x fuse holder 7 x bore holes ½“ NPT 5 x EEx d cable glands type FL1 F1B (used by ELB) 1 x EEx d cable gland type FL1 I1B (used by ELB) 1 x EEx d cable gland type FL1 I1B (cable ø = 10,5 – 12 mm) for power supply (customer) Cable glands for other diameters or armoured cables on request. Terminal block
-X1
NPE L1 11 22
F1
53
64
5
6
3
47 PEPE
-X1
4 6
3 5
PE L1 N 1 1 2 24
3
6
5
F1
PE7 PE
Description EEx-p System F-361.C4 16
Änd./
Mod.
15.07.2003 page 16 of 25
EEx d junction and control box F-900.001 In this EEx d junction box all potential free signals can be picked off.
Terminal 1 and 2: Motor shutdown Terminal 3 and 4: Purging in progress Terminal 5 and 6: Motor not purged Terminal 7 and 8: Purging sequence finished Terminal 9 and 10: Ready to start Terminal 11 and 12: Spare (wiring to F-900.041 terminals 5 and 6)
The EEx d box consists of: 2 x PE terminals type USLKG 6 6 x terminals type UKK 5 1 x bore hole ½“ NPT 1 x Bore hole ¾“ NPT 1 x EEx d cable gland type FL1 I1B (used by ELB) 1 x EEx d cable glands type FL1 I1B (cable ø = 10,5 – 12 mm)
for signal cables Cable glands for other diameters or armoured cables on request. Terminal block
9531
10642
642 10
531 9
PE PE
7
7
8
8
11
12
12
11
-X2
531 97 11
PE
-X2
62 4 8 10
62 4 8 10
12
12
51 3 7 9 11
PE
Description EEx-p System F-361.C4 17
Änd./
Mod.
15.07.2003 page 17 of 25
Wiring plan
Potential free contacts
control
1 2 3 4 5 6 7 8 9 10
K2 K3
LPE Npower supply
control valveleakage compensation
drive
A1
A2
A2
A1
13
14
23
24
K3
12
11
22
21
K3
purge valve
main switch
F-351
L N PE 1 2
power supply
(3) (4)
(1) (2)
PE PE
EEx d enclosure F-900.041
purging in progress
EEx prelease
K1 N L
3 4
purging in progress
F1
7
-X1
22
21
14 34
11
34
31
31
1 2 3 4 5 6 7 8 11 12PE PE
EEx d enclosure F-900.041
EEx d enclosure F-900.001
purging inprogress
motor not purged
purge sequence finished
ready tostart
(1) (2) (4)(3) (5) (6) (7) (8) (10)(9)
spare
9 10
65
(11) (12)
3 4
44
41
44
K2
41
motorshutdown
-X2
K3
Description EEx-p System F-361.C4 18
Änd./
Mod.
15.07.2003 page 18 of 25
Name plate
.L.B. EX-GERÄTE
TÜV 02 ATEX 1801 Operating voltage:
Motor Manufacturer:
Project name:
Serial no.:
VAC/48-62 Hz VDC
Order no.:
Project no.:
Date of pass:
EEx-p System Type F-361.C4
For the identification of the system a stainless steel plate is fixed at the enclosure of the control cabinet.
Description EEx-p System F-361.C4 19
Änd./
Mod.
15.07.2003 page 19 of 25
Checklist and test certificate
Test certificate and checklist for motor systems
customer:
address:
motor system: F-361.C4
power supply: ___ V ____ Hz date of pass: __.__.____ serial number: ___ order number: __________
checked by E.L.B. date:
name:
Description EEx-p System F-361.C4 20
Änd./
Mod.
15.07.2003 page 20 of 25
Appendix A Timing diagram purging sequence
T1: Switching on power supply and opening air pressure supply the control unit begins with a self test and the purging sequence of the EEx p motor enclosure starts. With an air flow which is higher than the adjusted value “min air flow” and the air flow is adequate the adjusted purge volume (min. 10-fold inner free motor volume), the motor enclosure is purged.
T2: The purging sequence is finished. The adjusted motor enclosure overpressure is controlled by the leakage compensation (see chapter 5 of main manual). The Non- Ex units can be powered.
T3: Normal operation starts.
Timing diagram operating modus
T1: The purging sequence is finished. The adjusted motor enclosure overpressure is controlled by the leakage compensation (see chapter 5 of main manual). The Non- Ex units can be powered.
T2: Normal operation starts. The internal enclosure overpressure is regulated to the setpoint value.
T3: The internal enclosure pressure rises.
T4: The increased overpressure is controlled down with the proportional valve.
T5: Normal operation begins.
Description EEx-p System F-361.C4 21
Änd./
Mod.
15.07.2003 page 21 of 25
Timing diagram errors during purging sequence
T1: Switching on power supply and opening air pressure supply the control unit begins with a self test and the purging
sequence of the EEx p motor enclosure starts. With an air flow which is higher than the adjusted value “min air flow” and the air flow is adequate the adjusted purge volume (min. 10-fold inner free motor volume), the motor enclosure is purged.
T2: During the purging sequence the internal overpressure increases to an excessively high value. The purge operation is aborted.
T3: During the purging sequence the minimum air volume flow falls. The purging sequence is resetted.
Timing diagram errors during the operating modus
T1: The purging sequence is finished. The adjusted motor enclosure overpressure is controlled by the leakage
compensation (see chapter 5 of main manual). The Non- Ex units can be powered.
T2: Normal operation starts. The internal enclosure overpressure is regulated to the setpoint value.
T3: The internal enclosure pressure drops. If the pressure value falls below the switchpoint „Minimum pressure“ in relation to the external pressure, the Non- Ex units are switched off.
T4: Renewed purge.
T5: Normal operation begins.
T6: The internal enclosure pressure rises. The increased internal enclosure pressure cannot controlled down.
T7: If the internal pressure value exceeds the switchpoint „Overpressure“, the Non- Ex units are switched off. The purge valve is powered, so the outlet valve opens. The increased overpresse sinks to operation values.
T8: After the pressure decrease, normal operation begins without purging.
Description EEx-p System F-361.C4 22
Änd./
Mod.
15.07.2003 page 22 of 25
Leakage compensation diagram To determine the approx. leakage of your purged motor enclosure during operation please count the turnarounds of the adjustment valve „leakage comp.“ (Pos.12) and use this diagram.
Leakagecompensation F-361.C4
05
1015202530354045505560657075808590
0,00 0,25 0,50 0,75 1,00 1,25 1,50 1,75 2,00 2,25 2,50 2,75 3,00 3,25
Turns for adjustment valve"leakage comp." (Pos.12)
Leak
age
in N
m3 /h
bei 3 Bar Max.leakage compensation with proportional valvel
Description EEx-p System F-361.C4 23
Änd./
Mod.
15.07.2003 page 23 of 25
F-369PE
2 4 6
1 3 5PE
Option: Evaluation of additional signals If wanted, the evaluation of more potential free signals is possible. Therefore the module F-369 will be mounted. This module is directly controlled via EEx i circuits of the control unit F-351.P. Each relay (K2, K3 and K4) is free programmable in his function. The module F-369 itself is mounted in an EE x d enclosure type F-900.031F369. An exchange of the F-900.031F369 against the F-900.001 in already operating systems is only possible, if the control unit is also changed. EEx d control box F-900.031F369 In this EEx d junction box all potential free signals can be picked off. Layout of the cable glands can be different from sketch.
Terminal 1 and 2: Motor stop Terminal 3 and 4: Purging in progress Terminal 5 and 6: Operate F-369 1/2 (K2): free programmable F-369 5/6 (K3): free programmable F-369 9/10 (K4): free programmable
Power supply has to be connected to F-369 terminals 14 (PE)/15 (L1)/16 (N). The intrinsic safe circuit cable is direct wired to the socket at the left side of the control unit F-351.P. The EEx d box consists of: 2 x PE terminals type USLKG 5 3 x terminals type UKK 5 1 x opto-relay module F-369 5 x bore hole ½“ NPT 1 x EEx d cable gland type FL1 G1B (used by ELB) 1 x EEx d cable gland type FL 01 F1B for EEx i wiring (used by ELB) 1 x EEx d cable glands type FL1 I1B (cable ø = 10,5 – 12 mm) for signal cable (client)
Description EEx-p System F-361.C4 24
Änd./
Mod.
15.07.2003 page 24 of 25
Programming the additional potential free contacts K2, K3, K4 All contacts can be programmed as NC or NO. The function of each relay is programmable as listed:
isolation contact switches simultaneous with contacts at terminals (6) and (7) of F-351
system fault contact switches in case of a fault malfunction 1 minute contact switches 1 min after fault
malfunction flashing contact switches 1 min after fault and switches over in a cycle of 1 sec
pre-alarm “Min” when the internal enclosure pressure drops under the adjusted value of “Min”, range 0,8 – 15 mbar
pre-alarm “Max” switches when the internal enclosure pressure rises above the adjusted value of “Max”, range 0,8 – 24 mbar
purge contact switches during purging sequence bypass contact switches, if bypass key-switch is active
fault/bypass fault: contact switches in case of a fault bypass: contact switches over in cyle of 1 sec
Extended wiring plan
drive
power supply
13
(1)
14
mainswitch (3)
-X1 L
PEpower supply
F-351.P
L N
21 3
K1
4
controlN
5 6
L
7
purge valve
23
(2)
24
(4)
purging inprogress
3
N PE 1 2 PE
A1
A2
K24
K3A2
A1 11 21
K3K3
12 22
PE
leakage valve
108 9
7
F1
EEx d enclosure F-900.041
F-900.031
EEx i socket
intrinsic safecircuit
purging inprogress
Description EEx-p System F-361.C4 25
Änd./
Mod.
15.07.2003 page 25 of 25
Potential free contacts
K3
K2
EEx d enclosure F-900.041
41
44
41
3
44
4
EEx d enclosure F-900.031
-X2 PE 1 2 3 4
purging inprogress
K3
34
31
31
34
K2
5 6
operate
PE
motor stop
F-36
9/K2
F-36
9/K3
F -36
9/K4
free programmable contacts
L N PE
F-369
intrinsic safe circuit from F-351.P
wiring to F-900.041terminal 1 and 2
contact 1 contact 2 contact 3
The electronic is designed to work according to the “closed-circuit principle”
EC Declaration of Conformity E.L.B. Ex-Geräte
We hereby confirm the conformity of the equipment listed below with the directives of the Council of the European Community. The safety and installation instructions of the product documentation must be observed.
Model: EEx px Purge System F-35... and F-361.A4/.B4/.C4/.F4, consist of: -EEx px Controller F-351 -EEx m digital / proportional valves F-220.2/.2B/.3/.4
-EEx d box (es) -EEx m main switch -EEx d cable glands -EEx e cable glands
Directive: EMC Directive 98/336/EC)*
European standards: EN 50081-1, 3/93*) EN 50081-2, 3/93*) EN 50082-1, 2/96*) EN 50082-2, 2/96*)
Directive: Low Voltage Directive 73/23/EC*)
European standard: EN 61010-1 :3/94
Directive: ATEX 94/9/EC European Standards: EN 60079-0 :2006 EN 60079-2 :2004 EN 60954-1 :1996 EN 60079-7 :2003 EN 60079-11:2007 EN 60079-18:2004
A quality management system according to DIN EN ISO 9001 (reg.-no. 8000307346) and ATEX 94/9 is established since 1998 and will be periodly supervised from a notified body (TÜV CE0032/ 0044).
Managing Director E.L.B. Ex-Geräte Bachmann GmbH&Co KG, Postadress: An der Hartbrücke 8, 64625 Bensheim, Germany Phone: +49 6251 637 36, Fax: +49 6251 637 29 E-Mail: [email protected], [email protected] Commercial Register of Bensheim, HRB No. 21728, Managing Director: S. Bachmann Trademark™ and registered trademarks ®
High-Flow Technology™ - trademark of the E.L.B. company. Permits low enclosure pressures even for high air flowrates
Wheel-Shuttle® - Patented and registered trademark of the University of Dresden and the E.L.B. company. Operating and parametrization for the EEx-p controller F-351 with simple, intuitive operator guidance.