Technical Data
Switched Mode Power Supply SpecificationsBulletin Numbers 1606-XL, -XLE, -XLP, -XLS
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Topic Page
Quick Selection Table 2
1606-XLS Power Supplies Specifications and Approximate Dimensions 3
1606-XLE Power Supplies 5
1606-XLP Power Supplies 7
1606-XL Power Supplies 9
Specialty Modules 12
Accessory Approximate Dimensions 14
Application Information 16
Resource Description
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, http://www.ab.com Provides declarations of conformity, certificates, and other certification details.
2 Rockwell Automation Publication -1606-TD002B-EN-P
1606 Switched Mode Power Supplies Specifications
Quick GuideBulletin 1606 Power Supply Quick Guide
15...40 W 50 W 60 W 72...80 W 90...100 W 120 W 180 W 240 W 480 W 720 W 960 W
5...5.5V XLP15AXLP25A
10...12V XLP30B
12...15V 1-Ph XLP15B XLP50B XLP60BQXLP60BQT XLP90B XL180B
12...15 V 3-Ph XLE96B
(+/-)12 and 15V XLP36C
24...28V 1-PhXLP15EXLP30E
XLP30EQ
XLP50EXLP50EZ
XL60DXLP60EQ
XLP60EQT
XLS80EXLE80EXLP72E
XLP95EXLP100E
XLS120EXLS120EAXLE120E
XLE120ECXLE120EEXLE120EN
XLS240EXLS240ECXLE240E
XLE240EPXLE240EEXLE240EN
XLS480EXLS480EAXLS480ECXLS480EE
XLS960EE
24...28V 2-Ph/3-Ph
XLP90E-2XLP100E-2 XLE120E-2
XL240E-3CXLE240E-3
XLS480E-3XLS480E-3C XL720E-3
XLE960DX-3N
XLS960E-3
36...43V XLS480G-3
48...56V 1-Ph XLP50F XLP100F XLE240F XLS480F XLS960FE
48...56V 3-Ph XLE240F-3 XLS480F-3
XLE960MX-3N
XLS960F-3
24V Redundant XL60DR XL120DR XL240DR
DeviceNet XLEDNET3 XLSDNET4 XLSDNET8
Example: For a 24...28 Volt, 3-Phase, 120 Watt power supply, the Cat. No. would be 1606-XL120E-3.
Special Applications
Bulletin Number NEC Class 2 ABS/GL MarineHazardeous LocationRating, Class 1 Div 2 ODVA Requirements Conformal Coating ATEX
1606-XLE XLE80E All XLE PowerSuppliesAll XLE Power
Supplies XLEDNET3 XLE120EC
1606-XLP
XLP15AXLP15BXLP15EXLP25AXLP30BXLP30EXLP36CXLP50BXLP50E
XLP50EZXLP50FXLP72EXLP90B
XLP90E-2XLP95E
XLP15AXLP15BXLP15EXLP25AXLP30EXLP36CXLP50E
XLP50EZXLP72EXLP90BXLP100EXLP100FXLPRED
XLP15AXLP15BXLP15EXLP25AXLP30BXLP30EXLP50BXLP50E
XLP50EZXLP72EXLP90BXLP95E
XLP100EXLPRED
1606-XLS XLSDNET4 ALL XLS PowerSuppliesAll XLS Power
SuppliesXLSDNET4XLSDNET8
XLS240ECXLS480E-C
XLS480E-3C
XLS120EAXLS240EAXLS480EA
Cat. No. 1606-XLS240K does not have Hazardeous Location Rating.
3Rockwell Automation Publication -1606-TD002B-EN-P
1606 Switched Mode Power Supplies Specifications
Bulletin 1606-XLS
1606-XLS80E1606-XLS120E
1606-XLS120EA& 1606-XLS180B
1606-XLS240E 1606-XLS240EA&1606-XLS240EC
Output Volts/Watts 2428V/80 W 2428V/120 W 12...15V/180 W 2428V/240 W
Input Voltage (47...63 Hz) 100240V AC,110...150V DC 100240V AC, 110...300V DC 100240V AC, 110...150V DC 100240V AC, 110...150V DC
Operational Range 85276V AC, 88188V DC 85264V AC, 88360V DC 85264V AC, 88188V DC 85276V AC, 88188V DC
Hold-up Time 27174 ms 3359 ms 32 ms 27 ms
Rated Input Current 1.4 A (100V AC), 0.82 A (240V AC)1.4 A (100V AC), 0.65 A (240V AC)
1.65 A (120V AC), 0.93 A (230V AC)
2.8 A (100V AC), 1.2 A (240V AC)
Efficiency typ. 90.0% typ. 92.7% typ. 91.5% typ. 91.8%
Output Voltage 2428V 2428V 12...15V 2428V
Rated Output Current 3.4 A (@ 24V)3.0 A (@ 28V)5 A (@ 24V)
4.5 A (@ 28V) 15 A10 A (@ 24V)9 A (@ 28V)
ReservePower (typ. 4 s) 5.4 A (@ 24V)5.0 A (@ 28V)7.5 A (@ 24V)6.7 A (@ 28V) 22.5 (@12V)
15 A (@ 24V)13.5 A (@ 28V)
Ripple/Noise 577 000 hours >581 000 hoursDimensions (W x H x D) 32 x 124 x 102 mm 40 x 124 x 117 mm 60 x 124 x 117 mm 60 x 124 x 117 mm
Weight 420 g 620 g 900 g 900 g
Certifications/Standards
1, 2, 3, 5, 6, 7, 9 1, 2, 3, 5, 6, 7, 8, 9
Special Features Active PFC; Class 1 Div. 2; Semi F47, 9) ABS/GL/RINA (Marine)
1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards =EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1, 8) ATEX, 9) GL/ABS
MTBF determined by Siemens norm SN 29500 at full load current and 40 C, 8) ATEX& Indicates ATEX rating Indicates conformal coating
1606-XLS480E1606-XLS480EA&1606-XLS480EC
1606-XLS480E-31606-XLS480E-3C 1606-XLS480F 1606-XLS480F-3 1606-XLS480G 1606-XLS480G-3
Output Volts/Watts 2428V/480 W 2428V/480 W 48...56V/480 W 48...56V/480 W 36...42V/480 W 36...42V/480 W
Input Voltage (47...63 Hz) 100240V AC/110...150V DC
380480V AC,600V DC
100240V AC,110...300V DC
380480V AC,600V DC
100240V AC,110...300V DC
380480V AC,600V DC
Operational Range 85276V AC,88188V DC323552V AC,450780V DC
85276V AC,88375V DC
323552V AC,450780V DC
85276V AC,88375V DC
323552V AC,450780V DC
Hold-up Time 3251 ms 19 ms 32...51 ms 22 ms 32...51 ms 22 ms
Rated Input Current 4.6 A (100V AC), 2.5 A (240V AC)0.9 A (380V AC), 0.65 A (480V AC)
4.6 A (100V AC), 2.5 A (240V AC)
0.79 A (380V AC), 0.65 A (480V AC)
4.6 A (100V AC), 2.5 A (240V AC)
0.79 A (380V AC), 0.65 A (480V AC)
Efficiency typ. 92.4% typ. 94.8% typ. 92.4% typ. 95.4 % typ. 92.4% typ. 94.8%
Output Voltage 2428V 2428V 2428V 48...55V 36...42V 36...42V
Rated Output Current 20 A (@ 24V)17 A (@ 28V)20 A (@ 24V)
17.5 A (@ 28V)20 A (@ 24V)17 A (@ 28V) 10 A (@ 48V) 13 A (@ 36V) 13.3 A (@ 36V)
ReservePower (typ. 4 s) 30 A (@ 24V)26 A (@ 28V)30 A (@ 24V)26 A (@ 28V) 30 A (@ 24V) 15 A (@ 48V) 20 A (@ 42V) 20 A (@ 42V)
Ripple/Noise 690 000 hours > 407 000 hours > 690 000 hoursDimensions (W x H x D) 84 x 124 x 127 mm 65 x 124 x 127 mm 84 x 124 x 127 mm 65 x 124 x 127 mm 82 x 124 x127 mm 65 x 124 x127 mm
Weight 1200 g 870 g 1200 g 870 g 1200 g 870 g
Certifications/Standards
1, 2, 3, 5, 6, 7, 8, 9 1, 2, 3, 5, 6, 7, 9
Special Features ABS/GL/RINA (Marine)
1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards =EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1, 8) ATEX, 9) ABS/GL/RINA (Marine)
MTBF determined by Siemens norm SN 29500 at full load current and 40 C& Indicates ATEX rating Indicates conformal coating
4 Rockwell Automation Publication -1606-TD002B-EN-P
1606 Switched Mode Power Supplies Specifications
Bulletin 1606-XLS
1606-XLS960EE 1606-XLS960E-3 1606-XLS960F-3
Output Volts/Watts 2428V/960 W 2428V/960 W 2428V/960 W
Input Voltage (47...63 Hz) 200...240V AC 380...480 V AC 200...240V AC
Operational Range 170...264V AC 380....480V AC 170...264V AC
Hold-up Time 32 ms 20 ms 20 ms
Rated Input Current 4.6 A 1.65 A 1.65 A
Efficiency typ. 94.6% typ. 95.2% typ. 95.4%
Output Voltage 24...28V 24...28V 48...54V
Rated Output Current 40 A (@ 24V)34 A (@ 28V)40 A (@ 24V)
34.3 A (@ 28V)20 A (@ 48V)
17.8 A (@ 54V)
ReservePower (typ. 4 s) 60 A (@ 24V)51 A (@ 28V)60 A (@ 24V)51 A (@ 28V)
30 A (@ 48V)26.7 A (@ 54V)
Ripple/Noise
5Rockwell Automation Publication -1606-TD002B-EN-P
1606 Switched Mode Power Supplies Specifications
Bulletin 1606-XLE
1606-XLE80E
1606-XLE120E
1606-XLE120EC
1606-XLE120EE
1606-XLE120EN
1606-XLE240E
1606-XLE240EE
1606-XLE240EN
1606-XLE240EP
1606-XLE240F
Output Volts/Watts
24V...28V/80 W
24V...28V/120 W
24V...28V/120 W
24V...28V/120 W
24V...28V/240 W
24V...28V/240 W
24V...28V/240 W
24V...28V/240 W
48V...52V/240 W
Input Voltage (47...63 Hz)
100...120/200...240V
AC,110...150V
DC
100...120/200...240V
AC
200...240VAC
100...120VAC
100...120/200...240V
AC
200...240VAC
100...120VAC 100...120/200...240V AC
Operational Range
90...132/180...264V
AC,88...188V DC
90...132V AC 180...264VAC 90...132V AC90...132/
180...264VAC
180...264VAC 90...132V AC 90...132/180...264V AC
Hold-up Time
>60 ms(120V)
>244 ms(240V)
>80 ms(120V)
>78 ms(240V)
>80 ms(120V)
>78 ms(240V)
>46 ms(120V)
>42 ms(240V)
>45 ms(240V)
>46 ms(120V)
>46ms(120V)>42ms(240V)
>46ms(120V)>42ms(240V)
Rated Input Current
1.24 A (100VAC)
0.68 A (240VAC)
2.6 A (100VAC)
1.3 A (240VAC)
2.6 A 1.4 A
5 A (100V AC)
2.5 A (240V AC)
2.7 A 5 A
6 Rockwell Automation Publication -1606-TD002B-EN-P
1606 Switched Mode Power Supplies Specifications
Bulletin 1606-XLE
1606-XLE96B-2 1606-XLE120E-2 1606-XLE240E-3 1606-XLE240F-3 1606-XLE960DX-3N 1606-XLE960MX-3N
Output Volts/Watts
12V...15V/ 96 W
24V...28V/120 W
24V...28V/240 W
48V...52V/240 W
24V...28V/960 W
48V...52V/960 W
Input Voltage (47...63 Hz)[V AC] 380...480 380...480 380...480 380...480 480 480
Operational Range[V AC] 380...480 380...480 380...480 380...480 408...552 408...552
Hold-up Time 33 ms (400)58 ms (480)27 ms (400)48 ms (480)
34 ms (400)54 ms (480)
34 ms (400)54 ms (480)
3 ms (19V) 3 ms (41V)
Rated Input Current
Efficiency 87 90 92 92 95 96
Output Voltage 12...15 24...28 24...28 48...56 24 48
Rated Output Current 8 (12)6.4 (15)5 (24)
4.3 (28)10 (24)8.6 (28)
5 (48)4.3 (56) 40 20
Ripple/Noise 60 C with derating
Non-OperatingTemperature Range -40...+85 C
MTBF >700 000 hoursDimensions (W x H x D) 40 x 124 x 117 mm 96 x 124 x 157 mm
Weight 500 g 750 g 1400 g
Certifications/Standards
1, 2, 3, 4, 5, 6, 7, 9
Special Features NEC Class 2
1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards =EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1, 9) ABS/GL/RINA (Marine)
MTBF determined by Siemens norm SN 29500 at full load current and 40 C. Indicates conformal coating.
7Rockwell Automation Publication -1606-TD002B-EN-P
1606 Switched Mode Power Supplies Specifications
1606-XLP30B 1606-XLP30E 1606-XLP30EQ 1606-XLP36C 1606-XLP50B
Output Volts/Watts 10...12V/30 W 24...28V/30 W 24...28V/30 W 12V/15V/36 W 12...15V/50 W
Input Voltage (47...63 Hz) 100...240V AC wide range; 85...375V DC
Operational Range 85...264V AC
Hold-up Time >170 ms (230V AC)>18 ms (100V AC)>190 ms (230V AC)>19 ms (100V AC)
>141 ms (230V AC)>31 ms (100V AC)
>180 ms (230V AC)>18 ms (100V AC)
>170 ms (230V AC)>17 ms (100V AC)
Rated Input Current 196 ms (230V AC)>47 ms (100V AC)
>170 ms (230V AC)>19 ms (100V AC)
Rated Input Current 80%
Output Voltage 5...5.5V5.1V preset 12...15V 24...28V5...5.5V
5.1V preset
Rated Output Current 3 A 1.0...1.3 A 0.54...0.63 A 5 A (at 5.1V),4.5 A (at 5.5V)
Ripple/Noise
8 Rockwell Automation Publication -1606-TD002B-EN-P
1606 Switched Mode Power Supplies Specifications
Bulletin 1606-XLP
1606-XLP50E 1606-XLP50EZ 1606-XLP50F 1606-XLP60EQ 1606-XLP60EQT
Output Volts/Watts 24...28V/50 W 48...56V/50 W 24...28V/60 W
Input Voltage (47...63 Hz) 100...240V AC wide range; 85...375V DC
Operational Range 85...264V AC
Hold-up Time >171 ms (230V AC)>17 ms (100V AC)>170 ms (230V AC)>17 ms (100V AC)
>107 ms (230V AC)>24 ms (120V AC)
Rated Input Current 25 ms (120V AC)>113 ms (230V AC)>25 ms (120V AC)
>40 ms (230V AC)>25 ms (100V AC)
>40 ms (230V AC)>20 ms (196V AC,
100V AC)
>52 ms (400V)>93 ms (480V)
Rated Input Current
9Rockwell Automation Publication -1606-TD002B-EN-P
1606 Switched Mode Power Supplies Specifications
Bulletin 1606-XLP
1606-XLP95E 1606-XLP100E 1606-XLP100F 1606-XLP100E-2
Output Volts/Watts 24...28V/95 W 24...28V/100 W 48...56V/100 W 24...28V/100 W
Input Voltage (47...63 Hz) 100...120/220...240V AC auto select; 220...375V DC 2, 380...480V AC
Operational Range 85...132/184...264V AC 323..552V AC
Hold-up Time >40 ms (230V AC)>20 ms (100V AC)>48 ms (400V)>85 ms (480V)
Rated Input Current
10 Rockwell Automation Publication -1606-TD002B-EN-P
1606 Switched Mode Power Supplies Specifications
1606-XL Single Phase Specifications
1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards =EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
Low inrush current MTBF determined by Siemens norm SN 29500 at full load current and 40 C
1606-XL60D 1606-XL180B 1606-XL480EP1606-
XL480EPT 1606-XL480GP 1606-XL480F
Output Volts/Watts 24V/60 W 12...15V/180 W 24...28V/480 W 36...43V/480 W 48...56V/480 W
Input Voltage (47...63 Hz)100...120/200...240V AC
manual select;160...375V DC
100...120/220...240V AC240...375V DC 100...120/200...240V AC
Operational Range 85...132/176...264V AC 85...132/176...264V AC 85...132/184...264V AC
Hold-up Time >20 ms (196V AC)>81 ms (230V AC)>84 ms (120V AC)>45 ms (100V AC)
30 ms (120/230V AC) >27 ms (230V AC) 30 ms (230V AC)
Rated Input Current
11Rockwell Automation Publication -1606-TD002B-EN-P
1606 Switched Mode Power Supplies Specifications
1606-XL120E-31606-XL240E-3 and1606-XL240E-3C 1606-XL480F-3H 1606-XL720E-3 1606-XL960E-3 1606-XL960E-3S
Output Volts/Watts 24...28V/120 W 24...28V/240 W 48...56V/480 W 24...28V/720 W 24...28V/960 W
Input Voltage (47...63 Hz)3, 400...500V AC
wide range; 450...820V DC
3, 400...500V ACwide range;
450...820V DC
3, 400V AC; 450...700V DC
3, 400...500V AC widerange;
450...820V DC3, 400...500V AC wide range
Operational Range 340...576V AC 340...479V AC 340...576V AC
Hold-up Time >16 ms (3 400V AC)>10 ms (2 400V AC)>24 ms (3 400V AC)>20 ms (2 400V AC) >11 ms >10 ms (3 400V AC) >15 ms (3 400V AC)
Rated Input Current 3 x 0.5 A 3 x 0.8/0.7 A @400/500V 3 x 1.5 A 3 x 2.0 A 3 x 3.0 A
Efficiency typ. 89% typ. 92% typ. 92% typ. 92.5% typ. 92.5%
Output Voltage 24...28V24.5V preset24...28V
24.5V preset48...56V
48.1V preset24...28V front panel
potentiometer24...28V
front panel potentiometer
Rated Output Current 5 A (@ 24V),4.3 A (@ 28V)10 A (@ 24V)8.6 A (@ 28V)
10 A (@ 48V),9 A (@ 56V)
30 A (@ 24V),26 A (@ 28V)
40 A (@ 24V),35 A (@ 28V)
Power Boost 6 A 12 A (up to 288 W) 12.5 A 33 A 45 A
Ripple/Noise
12 Rockwell Automation Publication -1606-TD002B-EN-P
1606 Switched Mode Power Supplies Specifications
"DC Ok" OutputFunction: Indicating whether the unit is operating properly. Output can directly energize a relay or a control light.Signaling: Output signal is at a "high" level (24V, current source) in normal operation (no overload, overheating, short circuit). When the output signal switches to "low" level (no power atoutput), Vout remains for 5 ms (nominal) at nominal load.Connection (signal common): Connection is made with respect to the "Signal GND" terminal (signal output).Important: Do not connect to the power output (terminals + and -).
Permissible load: resistance - min. 300 , e.g. 24V relay, control lights (LEDs need no series resistance), Evaluation logic.For 5V signal: In order to receive a 5V signal: switch a 5V Zener diode (0.5 W) and 1 k resistance in parallel between this output and the "Signal GND" terminal.
"Thermal Alarm" OutputFunction: Output gives warning shortly before and while overtemperature state occurs. Output can directly control a relay or a control light.Signaling: Output signal is at a "high" level (24V, current source) in normal operation (no overtemperature). At overtemperature, the output switches to "low". Only when the temperature inthe unit increases further will the unit reduce its output current (power output).Connection and permissible load: same as for "DC ok" output.
"Current Monitor" OutputFunction: Measuring the output current (power output). Output signal is proportional to the output current of the unit.Connection: Made with respect to the "Signal GND" terminal (signal output).Important: Do not connect to the power output (terminals + and -).Signaling:Voltage measuring: Voltage at signal output is 1V per 10 A output current (Ri(voltmeter) > 100 k ohm )Current measurement: Current at signal output is 1 mA per 10 A output current (Ri(ammeter) < 100 W)
"Current Balance" In-/OutputFunction: Using these terminals, parallel operating units ensure an equal load sharing (active balancing). Balancing also works reliably with decoupling diodes at the power output(redundancy).
Connection: Connect together "Current Balance" outputs of all units involved.Important: Signal common here is the - terminal of the power output, not the "Signal GND". Do not connect the "Signal GND" terminals to each other!
"Signal GND" TerminalFunction: Grounding terminal for all signal terminals (not for "Current Balance").Connection instructions: Do not connect this terminal with terminals + or - of the unit (not even over a load: risk of overload). Do not connect this terminal with terminals of other units (noteven with the "Signal GND" terminal of another unit).Permissible load: Maximum current load: 0.3 A. Terminal is fused internally with a self-healing fuse (polyswitch).
Shu
t Dow
nD
C ok
Ther
mal
Ala
rmCu
rrent
Mon
itor
Curre
nt B
alan
ceSi
gnal
-GND
1 k
1 k
5V/0.5 W
DC OkThermal A larm
Signal -GND
5V signal
Bulletin 1606 Special Modules
1606-XLDC40A 1606-XLDC92D 1606-XLSDNET4 1606-XLSDNET8 1606-XLEDNET3
Output Volts/Watts 24V/40 W 24V/92 W 24V/91 W 24V/192 W 24V...28V/80 W
Input Voltage (47...63 Hz) 18...36V DC 24V DC 100240V AC;110...300V DCAC 100240V DC
110...300V100...120V AC/200...240
V AC
Operational Range 16...40V DC 14...32.4V DC 85264V AC88360V DC85276 V AC88375 V DC
90...132V AC/180...264VAC
Hold-up Time 18...36V DC 18...36V DC 43 ms (120V AC)77 ms (240V AC)38 ms (120V AC)41 ms (240V AC)
>60 ms (120V)>244 ms (240V)
Rated Input Current 60 C withderating
Non-OperatingTemperature Range -25...+85 C -40...+85 C -40...+85 C
-25...+70 C>60 C with derating -40...+85 C
MTBF > 510 000 hours - >581 000 hours >831 000 hours >700 000 hoursDimensions (W x H x D) 49 x 124 x 102 mm 32 x 124 x 102 mm 40 x 124 x 117 mm 60 x 124 x 117 mm 32 x 124 x 102 mm
Weight 470 g 410 g 620 g 900 g 430 g
Certifications/Standards
1, 2, 3, 5, 6, 7 1, 2, 3, 5, 6, 7 1, 2, 3, 5, 6, 7 1, 2, 3, 4, 5, 6, 7
Special Features
NEC Class 2 powersupply; Active PFC;
ODVA Approved; Class1 Div. 2; Semi F47
Active PFC; ODVAApproved; Class 1 Div.
2; Semi F47
NEC Class 2 powersupply; ODVA Approved;Class 1 Div. 2; Semi F47
1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards =EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
MTBF determined by Siemens norm SN 29500 at full load current and 40 C
13Rockwell Automation Publication -1606-TD002B-EN-P
1606 Switched Mode Power Supplies Specifications
Bulletin 1606 Redundant Power Supplies
N+1 Redundancy N+1 Redundancy N+1 Redundancy
1606-XL60DR 1606-XL120DR 1606-XL240DR
Output Volts/Watts 24V/60 W 24V/120 W 24V/240 W
Input Voltage (47...63 Hz) 100...120V/200...240V AC manual select; 160...375V DC100...120/200...240V AC manual select;
210...375V DCAC 100...120/200...240V manual select;
DC 240...375V
Operational Range 85...132/176...264V AC 85...132/176...264 V AC
Hold-up Time >20 ms (AC 196V) >37 ms (AC 196V) >25 ms (AC 196V)
Rated Input Current
14 Rockwell Automation Publication -1606-TD002B-EN-P
1606 Switched Mode Power Supplies Specifications
Bulletin 1606-XLS UPS
UPS UPS UPS UPS
1606-XLS240-UPS 1606-XLS240-UPSC 1606-XLS240-UPSD 1606-XLS240-UPSE
Output Volts/Watts 22.5V...30V/240 W 22.25V/240 W 22.25V and12V/240 W
Input Voltage (47...63 Hz) 24V DC (22.5...30V DC) 24V DC (22.5...30V DC) 24V DC (22.5...30V DC)
Rated Input CurrentVoltagestand-by mode/chargingmode
typ. 0.12 A/max. 1.3 A
typ. 0.12 A/max. 1.3 A
typ. 0.12 A/max. 1.3 A
Operational Range 22.5...30V DC 22.5...30V DC 22.5...30V DC 22.5...30V DC
Hold-up Time battery dependent
Output Voltage 22.4V 22.25V 22.25V 22.25V
Rated Output Current 10 A 10 A 10 A 10 A
Power Boost 15 A 15 A 15 A 15 A
Operating TemperatureRange (Tamb)
-25...+60 C -25...+40 C
Non-OperatingTemperature Range -40...+85 C -20...+50 C
MTBF 886 000 hours 886 000 hours 788 000 hours 886 000 hoursDimensions (W x H x D) 49 x 124 x 117 123 x 124 x 119 49 x 124 x 117 49 x 124 x 117
Weight 530 g 2850 g 650 g 545 g
Certifications/Standards
1, 2, 3, 5, 6
Special Features Inhibit replacement battery buffering
1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards =EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
MTBF determined by Siemens norm SN 29500 at full load current and 40 C
Bulletin 1606-XLSBUFFER
Buffer Module Buffer Module
1606-XLSBUFFER 24 1606-XLSBUFFER 48
Output Volts 22.5V DC 45V DC
Input Current 80 mA typ.600 mA max.40 mA typ.
500 mA max.
Hold-up Time 200 ms @ 20 A 100 ms @ 20 A
Output Voltage Vin -1V: 22.5V fixed Vin -2V: 45V fixed
Rated Output Current 20 A 20 A
Operating TemperatureRange (Tamb)
-25...+70 C
Non-OperatingTemperature Range -40...+85 C
Dimensions (W x H x D) 64 x 124 x 102 mm 64 x 124 x 102 mm
Weight 740 g 740 g
Certifications/Standards
1, 2, 3, 5, 6
Special Features Selectable buffered voltage;
1) = CE, 2) = UL 508 (cULus LISTED), 3) = UL 1950 (cURus), 4) = CSA C22.2, No. 60950, 5) Safety standards = IEC/EN 60950, EN 50178, 6) EMC standards =EN 55011 (Class B), EN 55022 (Class B), EN 61000-6-2, 7) EMC standards = EN 61000-3-2 (A14), EN 50081-1
Low inrush current
15Rockwell Automation Publication -1606-TD002B-EN-P
1606 Switched Mode Power Supplies Specifications
Approximate Dimensions - AccessoriesApproximate dimensions are shown in millimeters (in.) unless otherwise indicated. Dimensions are not to be used for manufacturing purposes.
Cat. No. 1606-XLB, Back of Panel Mounting Bracket For use with Bulletin 1606-XLE and -XLS Power Supplies below 20 A.
mm A B C 1606-XLS80E 32 4.8 22.5 1606-XLS120E 40 5.3 29.5 1606-XLS240E 60 5.8 48.5 1606-XLS480E-3 65 6.3 40
N L PE
+ + - -
CBA
133
143
5.1
INPUT
OUTPUT
1606-XLSRED 32 4.8 22.5
133
48.6
3.15
143
5
8
7.5
Cat. No. 1606-XLC, Back of Panel Mounting Bracket For use with Bulletin 1606-XLE and -XLS Power Supplies 20 A and above.
16 Rockwell Automation Publication -1606-TD002B-EN-P
1606 Switched Mode Power Supplies Specifications
Application Information1606-XL Redundancy CapabilitiesThe 1606-XL family has two cost effective methods for providing redundancy to applications that are critical and can not risk failure.
1606-XL60DR, XL120DR and XL240DR Redundant Power Supplies
XL60DR orXL120DR
XL60DR orXL120DR
GND +24V
The 1606-XL60DR, XL120DR and XL240DR are enhanced versions of the standard power supplies. Each device has internal diodes which provide isolation against DC bus problems corrupting working supplies. Provides "DC OK" output relay to allow remote monitoring of DC power status. Utilizes pluggable terminals for easy installation.
1606-XLRED20-30 and 1606-XLRED40 Redundancy Modules
XL480 or XL720
XL480 or XL720
GND +24V GND +24V
Extensive Diagnostic & Monitoring FunctionsProtective Features: Wrong battery voltage (24V instead of 12V) Deep discharge (battery) protection Wrong battery polarity Wrong polarity on input terminals Too high ambient temperature Over-voltage protection
(malfunctioning of the internal regulation loops) Output overload or output short-circuit
17Rockwell Automation Publication -1606-TD002B-EN-P
1606 Switched Mode Power Supplies Specifications
A B C
D
E
A - Status LED (green): Ready: Battery is charged > 85%, no wiring failure is recognized, input voltage is sufficient and inhibit signal is not active. Charging: Battery is charging and battery capacity is below 85%. Buffering: Unit is in buffer mode.
B - Diagnosis LED (yellow): Overload: Output has switched off, due to long overload in buffer mode or due to high temperatures. Replace battery: Indicates a battery which failed the battery quality test (SCH test). Battery should be replaced soon. Buffer time expired: Output has switched off due to settings of buffer time. The signal will be stored and displayed for 15 minutes. Inhibit active: Indicates that buffering is disabled due to an active inhibit signal.
C - Check wiring LED (red): Check wiring between DC UPS and battery, as well as the battery itself. Also indicates when input voltage is not in range.
D - Adjustor: Buffer time limiter: User accessible switch which limits the maximum buffer time in a buffer event, to save battery capacity. End-of-charge voltage: User accessible potentiometer which sets the end-of-charge voltage. Adjust the potentiometer according to the
expected battery temperature.
E - Signal contacts: Ready (contact 1-2):
Contact is closed when battery is charged more than 85%, no wiring failure is recognized, input voltage is sufficient, and inhibit signal is notactive.
Buffering (contact 3-4):
Contact is closed when unit is buffering.
Replace battery (contact 5-6):
Contact is closed when input voltage is sufficient and battery quality test (SCH test) indicates a negative result, three times in a row.
Inhibit input (contact 7&8):
The inhibit input disables buffering. In normal mode, a static signal is required. In buffer mode, a pulse with a minimum length of 250 ms isrequired to stop buffering. The inhibit is stored and can be reset by cycling the input voltage.
Allen-Bradley, Rockwell Software, Rockwell Automation, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1606-TD002B-EN-P - September 2014 Copyright 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Rockwell Otomasyon Ticaret A.., Kar Plaza Merkezi E Blok Kat:6 34752 erenky, stanbul, Tel: +90 (216) 5698400