OXYGEN OXYGEN VACUUM VACUUM OXYGEN MEDICAL AIR MEDICAL AIR CENTER EMBED 4" 5/8" DOWEL 12" ON 3/4" 45° CHAMFERED EDGE FLOOR SLAB T.O.S. PLAN DIMENSION AS REQ'D FOR EQUIPMENT (COORDINATE W/APPROVED SHOP DRAWINGS) 6X6-W1.4XW1.4 W.W.F. COUNTERTOP 6" 1/2" DCW WALL BOX FLOOR SLAB NO WEIGHT PERMITTED SUPPORTS. ABSOLUTELY PIPE JACKET & INSULATION PIPE WITH INDEPENDENT PIPE TO BEAR ON SLEEVE. FLOOR SLAB BACKER ROD OR MINERAL WOOL DAMMING MATERIAL PIPE SLEEVE FIRE BARRIER CAULK. THICKNESS BASED ON MANUFACTURER'S RECOMMENDATIONS AND PRODUCT LISTING. FIRE RATED "LINKSEAL" BRAND MECHANICAL SEAL MODEL FS/FD FIRE BARRIER CAULK. THICKNESS BASED ON MANUFACTURER'S RECOMMENDATIONS AND PRODUCT LISTING. INSULATION PIPE JACKET & PIPE SLEEVE WITH WATER STOP BACKER ROD OR MINERAL WOOL DAMMING MATERIAL WALL/FLOOR PENETRATION W/CAST IN PLACE SLEEVE WALL/FLOOR PENETRATION THROUGH CORE DRILLED HOLE MIN. 2" MIN. 2" SUPPLY STOP (TYP) COPPER TUBING ADAPTER (TYP) INSULATE (INSIDE WALL) DOMESTIC HOT WATER SUPPLY (130°F) FLEX CONNECTOR BRAIDED-STAINLESS STEEL 3/8"C X 1/2" FIP -16" FAUCET SUPPLY (TYP.) NOTE: 1. 4" OR 8" CENTER TO CENTER ILLUSTRATION SHOWN. SINGLE HOLE FAUCET SUPPLIES SIMILAR FOR SINKS. FRONT VIEW SIDE VIEW PIPING TO PRESSURE TRANSDUCER IN ALARM PANEL ALARM MONITORING PANEL, AP (COORDINATE LOCATION WITH HOSPICE STAFF) OXYGEN VACUUM FINISHED FLOOR CRASH RAIL 3" MIN. 3" MIN. WALL FRAMING CEILING MEDICAL GAS VALVE CABINET VC VERIFY HEIGHT W/ ARCHITECT USE SIDE SOURCE SIDE 5" TYP. 48" UNLESS NOTED OTHERWISE (SLIDE) TYP. 5" TYP. 5" 20" GO1 GO3 5" INSULATE INSIDE WALL TO ELBOW/LAST FITTING (TYP.) 4-SIDES 1 / 2 " ANGLE VALVE W/ 3 / 8 " COMPRESSION FITTING, 3 / 8 " CONTINUOUS PRESSURE TYPE DOUBLE CHECK VALVE (FDA APPROVED) 60" OF 3 / 8 " CLEAR (NSF APPROVED) TUBING, AND UNION. MAKE FINAL CONNECTION. J DETAIL TYPICAL PIPE TRAPEZE HANGER N.T.S. 12 GAUGE STEEL (ASTM A570) 2 7 __ 16 " HEIGHT x 1 5 / 8 " WIDTH POWER-STRUT PS-150 CHANNEL, TOLCO OR APPROVED EQUAL, CONTINUOUS SLOT W/ INTURNED LIPS, INTERMITTENT SLOTTED BOTTOM, AND GALVANIZED AFTER FABRICATION PER ASTM A123. TO STRUCTURE 2" WIDE x 1 / 4 " THICK STEEL BAR LENGTH AS REQ'D. (BEND TO SUIT) (EVERY THIRD SUPPORT) 2.5 PCF RIGID INSULATION SATISFIES 25/50 FLAME-SMOKE RATING PER ASTM E-84 (TYP.) G90 180° CARBON STEEL FLARED EDGE SADDLE, RIBBED TO PREVENT SADDLE MOVMENT INSIDE HANGER. 3 / 4 " 3 / 4 " NPT PRESSURE RELIEF VALVE SET AT 75 PSIG THRU EXTERIOR WALL 10'-0" ABOVE GRADE TURN DOWN ELBOW W/STAINLESS STEEL SCREEN TO SYSTEM ¾" 1" NPT EMERGENCY OXYGEN SUPPLY CONNECTION FINISHED FLOOR 36" RECESSED, WEATHERTIGHT BOX W/PADLOCK 5" TYP. 48" UNLESS NOTED OTHERWISE 20" GO2 5" TYP. 48" UNLESS NOTED OTHERWISE PAD HEIGHT VARIES (REFER TO DETAILS) INSULATE (INSIDE WALL) DOMESTIC COLD WATER SUPPLY 120V SINGLE POINT POWER SUPPLY TO ASSEMBLY BY E.C. RECIRCULATION PUMP POWER SWITCH MIXING VALVE (CAST BRONZE BODY) W/ INTEGRAL CHECKS & SCREEN (ASSE 1070) SET @ 110°F ADJUSTABLE S S PUMP SEQUENCING OPERATION BY BMS 1" 1" RCP1 RCP2 NOTE: ONE PUMP OPERATES CONTINUOUSLY. ALTERNATE PUMP OPERATION WEEKLY. INTER LOCK PUMP OPERATION w/ SOLENOID VALVE. 1" 1" DHWR(130°F) MED AIR M CEILING 2" DCW (INSIDE PIPE CHASE) SHUT OFF VALVE ACCESS PANEL PROVIDE ½" STUB OUT W/ SHUT OFF VALVE AND PNEUMATIC FITTING FOR BLOW DOWN (WINTERIZATION) DCW DCW TO IRRIGATION SYSTEM TO POND FINISHED GRADE PIPE SLEEVE L P6-2 FINISHED FLOOR 2" BFP2 2" DEDUCT WATER METER DCW DCW REMOTE READER CHECK VALVE (SLIDE) FOR LOCATIONS AIR COMPRESSOR (OIL-LESS RECIPROCATING) FINISHED FLOOR 3" HIGH CONCRETE HOUSEKEEPING PAD (REFER TO DETAIL F) ½" DRAIN CONN. 2" DISCHARGE FLANGE 2½" 2" 3" HIGH CONCRETE HOUSEKEEPING PAD (REFER TO DETAIL F) 1¼" FNPT INLET CONNECTION FINISHED FLOOR 2" ¾" FNPT SYSTEM DISCHARGE CONNECTION 2" TERMINATE ½" FNPT CONDENSATE DRAIN ABOVE / NEAR FLOOR DRAIN 1" REFER TO SPECIFICATION SECTION 22 63 00 FOR FURTHER REQUIREMENTS TERMINATE CONDENSATE ABOVE FLOOR DRAIN TERMINATE 2" VACUUM EXHAUST / DISCHARGE PIPING 48" ABOVE ROOF w/ TURNDOWN OUTSIDE AIR INTAKE (TURNED DOWN AND SCREENED OR FILTERED) CO 2" INLET FLANGE (BACK SIDE) FLEX CONNECTOR TERMINATE TANK DRAIN ABOVE FLOOR DRAIN FILTER (TYP.) GFWH1 (130º F DOMESTIC HOT WATER) ET1 2½" SW FROM DCW SOURCE DHW (130º F) TO DISTRIBUTION SYSTEM DCW DHW (130º F) G (2 PSIG) 1½" FROM GAS MAIN 1¼" 3/4" NPT DRAIN CONN. 1½" CONN. 2 6 3 1 3 GPR1 REDUCER 1½" CONN. FINISHED FLOOR 5 DOMESTIC HOT WATER GENERATION SYSTEM DETAIL CODED NOTES 1. DOWN - FIRED POWERED BURNER. 2. CSA CERTIFIED AND ASME RATED T & P RELIEF VALVE. 3. CONNECT TO FACTORY PROVIDED DIRECT VENTING CONNECTION AT THIS LOCATION. 4. 3" HIGH CONCRETE HOUSEKEEPING PAD W/ 3/4" CHAMFERED EDGES. 5. TERMINATE DRAIN 6" ABOVE FINISH FLOOR. 6. MAKE FINAL CONNECTION TO GAS SUPPLY TRAIN. 2½" 2½" DCW GFWH2 (130º F DOMESTIC HOT WATER) STORAGE 100 GALLON STORAGE 100 GALLON 6 1 3 GPR2 FULL SIZE DIRT LEG 3/4" NPT DRAIN CONN. 1½" CONN. 2 5 3 1½" 1¼" THERMOMETER (TYP.) 2½" 2½" 2½" C P6.1 D C P6.1 D 1¼" 4 G P6.1 G VACUUM RELIEF VALVE (BOTTOM FED WATER HEATER) 4" VACUUM RELIEF VALVE (BOTTOM FED WATER HEATER) CONCENTRIC VENT KIT TERMINATION (TYP.) ROOF 4" 4" 4" 4" SW 1½" CONN. FULL SIZE DIRT LEG REDUCER 3" HIGH CONCRETE HOUSEKEEPING PAD (TYP.) REFER TO DETAIL F. M DETAIL ICE MAKER CONNECTION N.T.S. F DETAIL MAINTENANCE/HOUSEKEEPING PAD N.T.S. K DETAIL TYPICAL PIPE HANGER N.T.S. L DETAIL FLOOR/WALL PENETRATION N.T.S. A DETAIL DOMESTIC HOT WATER GENERATION SYSTEM N.T.S. H DETAIL ASSE 1070 CONNECTION (TYPICAL UNDER SINK/LAVATORY WATER SUPPLY PIPING) N.T.S. D DETAIL MEDICAL GAS VALVE CABINET /ALARM MONITORING PANEL N.T.S. E TYPICAL DETAIL MEDICAL GAS OUTLETS REFER TO P3 SERIES (PLUMBING) AND ARCHITECTURAL PLANS N.T.S. REFER TO SPEC. SECTION 22 63 00 FOR FURTHER REQUIREMENTS FOR FURTHER REQUIREMENTS N DETAIL WATER SERVICES FOR IRRIGATION AND POND N.T.S. C DETAIL MEDICAL VACUUM PUMP, MVS1 N.T.S. REFER TO SPEC. SECTION 22 62 00 FOR FURTHER REQUIREMENTS B DETAIL MEDICAL AIR SYSTEM, MAS1 N.T.S. G DETAIL EMERGENCY OXYGEN SUPPLY CONNECTION REFER TO SPEC. SECTION 22 63 00 N.T.S. PIPE CLAMP UNISTRUT CHANNEL HANGER ROD PIPE INSULATION PROVIDE A SECTION OF HIGH COMPRESSION STRENGTH INSULATION AT EACH HANGER POINT. INSULATION MAY BE HALF ROUND OR FULL ROUND & EXTEND 2" BEYOND GALVANIZED SHIELD EACH WAY. GALVANIZED%%032CARBON STEEL%%032SHIELD PIPE INSULATION PRECOMPRESSED FIBERGLASS BLOCK BLOCK FIBERGLASS PRECOMPRESSED SUPPORT FROM STRUCTURE LOOSE FIT 3/8"∅ U-BOLT (TYPICAL) 1/2"∅ HANGER ROD NOTE: EACH CHANNEL TO BE INDEPENDENTLY SUPPORTED FOR MULTITIER ARRANGEMENT. PRECOMPRESSED FIBERGLASS BLOCK (TYPICAL) PIPE (TYPICAL) U-BOLT (TYPICAL) FROM MEDICAL GAS (OXYGEN) MANIFOLD 1" DHWR (130°F) ¾" PROJECT NUMBER: CHECKED BY: DESIGNED BY: 1650 WATERMARK DRIVE COLUMBUS, OHIO 43215 SUITE 200 DRAWN BY: 1 2 3 4 5 A B C D MKC JOB #: SUBMITTED: DEVELOPER / OFFEROR THIS DRAWING SHALL NOT BE REPRODUCED, PUBLISHED, STORED IN AN ELECTRONIC RETRIEVAL SYSTEM, OR USED IN ANY WAY WITHOUT WRITTEN PERMISSION OF THE ARCHITECT. COPYRIGHT C 2015 MKC ASSOCIATES, INC 6 E 55 Monument Circle, Suite 450 Indianapolis, Indiana 46204 GENERAL CONTRACTOR Phone: 317-573-4600 www.ambrosegp.com 9550 W. Higgins Road, Suite 200 Rosemont, Illinois 60018 Phone: 847-292-4300 Fax: 847-292-4312 www.mcshaneconstruction.com ENGINEERING Structural, Mechanical, Electrical, Plumbing, Fire Protection 1650 Watermark Drive, Suite 200 Columbus, Ohio 43215 Phone: 614-487-1650 Fax: 614-487-8981 www.korda.com LANDSCAPE & SITE DESIGN 330 West Spring Street, Suite 350 Columbus, Ohio 43215 Phone: 614-486-3343 Fax: 614-486-3344 www.edgela.com CIVIL ENGINEERING SFO: VA-101-12-I-0063 MISHAWAKA, INDIANA VA ST. JOSEPH COUNTY CBOC PHYSICAL SECURITY / FORCE PROTECTION 2015-0211 100% CONSTRUCTION DOCUMENTS C:\Local Revit\Revit 2016\16-50211 VA South Bend PLUMBING(yu chen).rvt 9/9/2016 10:00:13 AM JUNE 1, 2016 PLUMBING DETAILS P6-2 15-089 Steve Glinsky Bill Rezabek W. P. Stafa 1 07-15-2016 Addendum 1 2 08-03-2016 Bulletin 1, Rev 2 3 09-09-2016 RFP 3, Steam VE 1 2 3

16-50211 VA South Bend PLUMBING(yu chen) - MKC RFP3 Steam VE/P6-2 - PLUM… · and galvanized after fabrication per astm a123. to structure ... (slide) for locations air compressor

Embed Size (px)

Citation preview

OXYGEN

OXYGEN

VACUUM

VACUUM

OXYGEN

MEDICAL AIR

MEDICAL AIR

CENTER EMBED 4"

5/8" DOWEL 12" ON

3/4" 45° CHAMFERED EDGE

FLOOR SLAB

T.O.S.

PLAN DIMENSION AS REQ'D

FOR EQUIPMENT (COORDINATE

W/APPROVED SHOP DRAWINGS)

6X6-W1.4XW1.4 W.W.F.

COUNTERTOP

6"

1/2" DCW

WALL BOX

FLOOR SLAB

NO WEIGHT PERMITTED

SUPPORTS. ABSOLUTELY

PIPE JACKET &

INSULATION

PIPE WITH INDEPENDENT

PIPE

TO BEAR ON SLEEVE.

FLOOR SLAB

BACKER ROD OR MINERAL

WOOL DAMMING MATERIAL

PIPE SLEEVE

FIRE BARRIER CAULK.THICKNESS BASED ONMANUFACTURER'SRECOMMENDATIONS ANDPRODUCT LISTING.

FIRE RATED "LINKSEAL"BRAND MECHANICALSEAL MODEL FS/FD

FIRE BARRIER CAULK.THICKNESS BASED ONMANUFACTURER'SRECOMMENDATIONS ANDPRODUCT LISTING.

INSULATION

PIPE JACKET &

PIPE SLEEVE WITHWATER STOP

BACKER ROD ORMINERAL WOOLDAMMING MATERIAL

WALL/FLOOR PENETRATION W/CAST IN PLACE SLEEVE WALL/FLOOR PENETRATION THROUGH CORE DRILLED HOLE

MIN. 2"

MIN. 2"

SUPPLY STOP (TYP)COPPER TUBING

ADAPTER (TYP)

INSULATE(INSIDE WALL)DOMESTIC HOTWATER SUPPLY(130°F)

FLEX CONNECTORBRAIDED-STAINLESS STEEL3/8"C X 1/2" FIP -16" FAUCETSUPPLY (TYP.)

NOTE:

1. 4" OR 8" CENTER TO CENTER ILLUSTRATION

SHOWN. SINGLE HOLE FAUCET SUPPLIES

SIMILAR FOR SINKS.

FRONT VIEW SIDE VIEW

PIPING TO PRESSURE TRANSDUCERIN ALARM PANEL

ALARM MONITORING PANEL, AP

(COORDINATE LOCATION

WITH HOSPICE STAFF)

OXYGEN

VACUUM

FINISHED FLOOR

CRASH RAIL

3"

MIN

.3

" M

IN.

WALL FRAMING

CEILING

MEDICAL GAS

VALVE CABINET

VC

VERIFY HEIGHTW/ ARCHITECT

USE SIDESOURCE SIDE

5"

TY

P.

48"

UN

LE

SS

NO

TE

D O

TH

ER

WIS

E

(SLIDE)

TYP.

5"

TYP.

5"

20"

GO1

GO3

5"

INS

ULA

TE

IN

SID

E

WA

LL T

O E

LB

OW

/LA

ST

FIT

TIN

G (

TY

P.)

4-SIDES

1/2" ANGLE VALVE W/ 3/8" COMPRESSION

FITTING, 3/8" CONTINUOUS PRESSURE TYPE

DOUBLE CHECK VALVE (FDA APPROVED)

60" OF 3/8" CLEAR (NSF APPROVED) TUBING,

AND UNION. MAKE FINAL CONNECTION.

JDETAILTYPICAL PIPE TRAPEZE HANGER N.T.S.

12 GAUGE STEEL (ASTM A570) 2 7__16

" HEIGHT x

15/8" WIDTH POWER-STRUT PS-150 CHANNEL, TOLCO

OR APPROVED EQUAL, CONTINUOUS SLOT W/

INTURNED LIPS, INTERMITTENT SLOTTED BOTTOM,

AND GALVANIZED AFTER FABRICATION PER ASTM

A123.

TO STRUCTURE

2" WIDE x 1/4" THICK STEEL BAR

LENGTH AS REQ'D. (BEND TO SUIT)

(EVERY THIRD SUPPORT)

2.5 PCF RIGID INSULATIONSATISFIES 25/50 FLAME-SMOKERATING PER ASTM E-84 (TYP.)

G90 180° CARBON STEELFLARED EDGE SADDLE, RIBBEDTO PREVENT SADDLE MOVMENTINSIDE HANGER.

3/4"

3/4" NPT

PRESSURE RELIEF VALVE

SET AT 75 PSIG

THRU EXTERIOR WALL10'-0" ABOVE GRADETURN DOWN ELBOWW/STAINLESS STEELSCREEN

TO SYSTEM

¾"

1" NPTEMERGENCY OXYGENSUPPLY CONNECTION

FINISHED FLOOR

36"

RECESSED, WEATHERTIGHTBOX W/PADLOCK

5"

TY

P.

48"

UN

LE

SS

NO

TE

D O

TH

ER

WIS

E

20"

GO2

5"

TY

P.

48"

UN

LE

SS

NO

TE

D O

TH

ER

WIS

E

PAD HEIGHTVARIES (REFERTO DETAILS)

INSULATE (INSIDEWALL) DOMESTICCOLD WATER SUPPLY

120V SINGLE POINTPOWER SUPPLY TOASSEMBLY BY E.C.

RECIRCULATION PUMPPOWER SWITCH

MIXING VALVE (CASTBRONZE BODY) W/INTEGRAL CHECKS& SCREEN (ASSE1070) SET @110°F ADJUSTABLE

S

S

PUMP SEQUENCINGOPERATION BY BMS

1"

1"

RCP1

RCP2

NOTE: ONE PUMP OPERATESCONTINUOUSLY. ALTERNATEPUMP OPERATION WEEKLY.INTER LOCK PUMP OPERATIONw/ SOLENOID VALVE.

1" 1"

DHWR(130°F)

MED AIR

M

CEILING2" DCW(INSIDE PIPE CHASE)

SHUT OFFVALVE

ACCESS PANEL

PROVIDE ½" STUB OUT W/ SHUT OFFVALVE AND PNEUMATIC FITTINGFOR BLOW DOWN (WINTERIZATION)

DC

W

DC

W

TO IRRIGATIONSYSTEM

TO POND

FINISHEDGRADE

PIPE SLEEVEL

P6-2 FINISHED FLOOR

2"BFP2

2" DEDUCTWATER METER

DCW

DCW

REMOTEREADER

CHECK VALVE

(SLIDE)

FOR LOCATIONS

AIR COMPRESSOR(OIL-LESSRECIPROCATING)

FINISHED FLOOR

3" HIGH CONCRETEHOUSEKEEPING PAD(REFER TO DETAIL F)

½" DRAIN CONN.

2"DISCHARGEFLANGE

2½"

2"

3" HIGH CONCRETEHOUSEKEEPING PAD(REFER TO DETAIL F)

1¼" FNPT INLETCONNECTION

FINISHED FLOOR

2"

¾" FNPT SYSTEMDISCHARGECONNECTION

2"

TERMINATE ½" FNPTCONDENSATE DRAINABOVE / NEARFLOOR DRAIN

1"

REFER TO SPECIFICATION SECTION 22 63 00FOR FURTHER REQUIREMENTS

TERMINATECONDENSATEABOVEFLOOR DRAIN

TERMINATE 2" VACUUMEXHAUST / DISCHARGE PIPING48" ABOVE ROOF w/ TURNDOWNOUTSIDE AIR INTAKE

(TURNED DOWN ANDSCREENED ORFILTERED)

CO

2" INLETFLANGE (BACKSIDE)

FLEX CONNECTOR

TERMINATETANK DRAINABOVEFLOOR DRAIN

FILTER (TYP.)

GFWH1

(130º F DOMESTICHOT WATER)

ET1

2½" SW FROMDCW SOURCE

DHW (130º F)TO DISTRIBUTIONSYSTEM

DC

W

DHW (130º F)

G (2 PSIG)1½" FROMGAS MAIN

1¼"

3/4" NPTDRAIN CONN.

1½"CONN.

2

6

3

1 3

GPR1REDUCER

1½"CONN.

FINISHED FLOOR5

DOMESTIC HOT WATER GENERATION SYSTEM DETAIL CODED NOTES

1. DOWN - FIRED POWERED BURNER.

2. CSA CERTIFIED AND ASME RATED T & P RELIEF VALVE.

3. CONNECT TO FACTORY PROVIDED DIRECT VENTING CONNECTION AT

THIS LOCATION.

4. 3" HIGH CONCRETE HOUSEKEEPING PAD W/ 3/4" CHAMFERED EDGES.

5. TERMINATE DRAIN 6" ABOVE FINISH FLOOR.

6. MAKE FINAL CONNECTION TO GAS SUPPLY TRAIN.

2½"

2½"

DC

W

GFWH2

(130º F DOMESTICHOT WATER)

STORAGE100 GALLON

STORAGE100 GALLON

6

1 3

GPR2

FULL SIZEDIRT LEG

3/4" NPTDRAIN CONN.

1½"CONN.

2

5

3

1½"1¼"

THERMOMETER(TYP.)

2½"

2½"

2½"

C

P6.1D

C

P6.1D

1¼"

4G

P6.1G

VACUUM RELIEF VALVE(BOTTOM FED WATER HEATER)

4"

VACUUM RELIEF VALVE(BOTTOM FED WATER HEATER)

CONCENTRIC VENTKIT TERMINATION(TYP.)

ROOF

4"

4"

4"4"

SW

1½"CONN.

FULL SIZEDIRT LEG

REDUCER

3" HIGH CONCRETEHOUSEKEEPING PAD (TYP.)REFER TO DETAIL F.

MDETAILICE MAKER CONNECTION N.T.S.

FDETAILMAINTENANCE/HOUSEKEEPING PAD N.T.S.

KDETAILTYPICAL PIPE HANGER N.T.S.

LDETAILFLOOR/WALL PENETRATION N.T.S.

ADETAILDOMESTIC HOT WATER GENERATION SYSTEM N.T.S.

HDETAILASSE 1070 CONNECTION (TYPICAL UNDER

SINK/LAVATORY WATER SUPPLY PIPING)

N.T.S.

DDETAILMEDICAL GAS VALVE CABINET

/ALARM MONITORING PANEL

N.T.S. ETYPICAL DETAILMEDICAL GAS OUTLETS

REFER TO P3 SERIES (PLUMBING) AND ARCHITECTURAL PLANS

N.T.S.

REFER TO SPEC. SECTION 22 63 00FOR FURTHER REQUIREMENTS FOR FURTHER REQUIREMENTS

NDETAILWATER SERVICES FOR IRRIGATION AND POND N.T.S.

CDETAILMEDICAL VACUUM PUMP, MVS1 N.T.S.REFER TO SPEC. SECTION 22 62 00FOR FURTHER REQUIREMENTS

BDETAILMEDICAL AIR SYSTEM, MAS1 N.T.S.

GDETAILEMERGENCY OXYGEN SUPPLY CONNECTION

REFER TO SPEC. SECTION 22 63 00

N.T.S.

PIPE

CLAMP

UNISTRUT

CHANNEL

HANGER

ROD

PIPE

INSULATION

PROVIDE A SECTION OF HIGH

COMPRESSION STRENGTH

INSULATION AT EACH HANGER

POINT. INSULATION MAY BE

HALF ROUND OR FULL ROUND

& EXTEND 2" BEYOND

GALVANIZED SHIELD EACH WAY.

GALVANIZED%%032CARBON

STEEL%%032SHIELD

PIPE

INSULATION

PRECOMPRESSED

FIBERGLASS

BLOCK

BLOCK

FIBERGLASS

PRECOMPRESSED

SUPPORT FROM STRUCTURE

LOOSE FIT 3/8"∅

U-BOLT

(TYPICAL)1/2"∅ HANGER ROD

NOTE:

EACH CHANNEL TO

BE INDEPENDENTLY

SUPPORTED FOR

MULTITIER

ARRANGEMENT.

PRECOMPRESSED

FIBERGLASS

BLOCK (TYPICAL)

PIPE (TYPICAL)U-BOLT (TYPICAL)

FROM MEDICALGAS (OXYGEN)MANIFOLD

1" DHWR(130°F)

¾"

PROJECT NUMBER:

CHECKED BY:

DESIGNED BY:

1650 WATERMARK DRIVE

COLUMBUS, OHIO 43215SUITE 200

DRAWN BY:

1 2 3 4 5

A

B

C

D

MKC JOB #:

SUBMITTED:

DEVELOPER / OFFEROR

THIS DRAWING SHALL NOT BE REPRODUCED, PUBLISHED, STORED IN AN ELECTRONIC RETRIEVAL SYSTEM, OR USED IN ANY WAY WITHOUT WRITTEN PERMISSION OF THE ARCHITECT. COPYRIGHT C 2015 MKC ASSOCIATES, INC

6

E

55 Monument Circle, Suite 450Indianapolis, Indiana 46204

GENERAL CONTRACTOR

Phone: 317-573-4600www.ambrosegp.com

9550 W. Higgins Road, Suite 200Rosemont, Illinois 60018

Phone: 847-292-4300Fax: 847-292-4312www.mcshaneconstruction.com

ENGINEERINGStructural, Mechanical, Electrical, Plumbing,Fire Protection

1650 Watermark Drive, Suite 200Columbus, Ohio 43215

Phone: 614-487-1650Fax: 614-487-8981www.korda.com

LANDSCAPE & SITE DESIGN

330 West Spring Street, Suite 350Columbus, Ohio 43215

Phone: 614-486-3343Fax: 614-486-3344www.edgela.com

CIVIL ENGINEERING

SFO: VA-101-12-I-0063

MISHAWAKA, INDIANA

VA ST. JOSEPHCOUNTY CBOC

PHYSICAL SECURITY / FORCE PROTECTION

2015-0211

100% CONSTRUCTION DOCUMENTS

C:\

Local R

evit\R

evit 2

016\1

6-5

0211 V

A S

outh

Bend P

LU

MB

ING

(yu c

hen).

rvt

9/9

/2016 1

0:0

0:1

3 A

M

JUNE 1, 2016

PLUMBING DETAILS

P6-2

15-089

Steve Glinsky

Bill Rezabek

W. P. Stafa

1 07-15-2016 Addendum 1

2 08-03-2016 Bulletin 1, Rev 2

3 09-09-2016 RFP 3, Steam VE

1

2

3