Upload
smalltownschools
View
217
Download
0
Embed Size (px)
Citation preview
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
1/164
Loudoun
ounty Virginia
Department of
Transportation &
Capital
Infrastructure
Lovettsville
Community Center
Mechanical Systems
Narrative & Analysis
V.3
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
2/164
LOVETTSVILLECOMMUNITY
CENTERRENOVATION
LOUDONCOUNTY,VIRGINIA
MECHANICALNARRATIVE
&
ECONOMICANALYSIS
APRIL 11,2014
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
3/164
LOVETTSVILLE COMMUNITYCENTER LCCHVACVIRGINIA PRELIMINARYDESIGNNARRATIVE
TABLE OF CONTENTS
1. EXECUTIVE SUMMARY............................................................................................................... 1
PAGE
2.
MECHANICAL SYSTEM OPTIONS ............................................................................................ 4
2.1 Option 1aPackaged Roof top unit (DX cooling & Propane gas heating), Fan poweredVariable volume boxes with Hot water heating.
2.2
Option 2a Geothermal system, Roof top unit (heat pump), WSHP with DOAS (DedicatedOutdoor Air System).
Appendices
Appendix A
Title Page
System Checksums
Design Cooling Load Summary
System Component Selection SummaryDesign Airflow Quantities
Design Cooling Capacities
Design Heating Capacities
Engineering Checks
System Load Profiles
Building Cooling & Heating Demand
Building Temperature Profile
Building Humidity Profile
Geothermal Plant Peak Load Summary
Geothermal Plant Cumulative Load Summary
Appendix B
Economic Parameters
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
4/164
LOVETTSVILLE COMMUNITY CENTER LCCHVAC
VIRGINIA PRELIMINARY DESIGN NARRATIVE
1.
EXECUTIVE SUMMARY
The engineering team of Setty & Associates International analyzed five (5) different options todetermine which HVAC system was the most economical and feasible type of system to be used forthis project. The five (5) options are deemed appropriate for this project and were analyzed are asfollows:
Option 1Packaged Roof top unit (DX cooling& electric pre-heating), Fan poweredVariable volume boxes with electric heating.
Option 1aPackaged Roof top unit (DX cooling & Propane gas heating), Fan powered
Variable volume boxes with Hot water heating.
Option 2Geothermal system, Roof top unit (heat pump) & Fan powered Variable volumeboxes with electric heating
Option 2a Geothermal system, Roof top unit (heat pump), WSHP with DOAS (DedicatedOutdoor Air System).
Option 3 VRF with DOAS (Dedicated Outdoor Air System), Roof top unit (DX cooling &electric pre-heating).
On March 28, 2014 the options above were reviewed with the County Design/Construction and DGSStaff to determine which HVAC system should be implemented for the LCC project. Options 1 and2 were not accepted due to utilizing total electric as a fuel source. Option 3 (VRF) was not deemedacceptable due to unfavorable past experience by the DGS staff. Two(2) options were accepted,which are option 1a and 2a. Option 1a utilizing DX cooling and propane gas for roof top unitheating and gas fired hot water boiler for the fan powered VAV box reheat. this option is consideredto be the most viable option by the DGS staff as it relates to maintenance and occupant comfort.Option 2a utilizing the constant ground temperature to store and supply heat to the building. This isthe preferred option by county engineer since this option is save more energy. Radiant heating wereadded into the discussion during the meeting. Floor radiant heating will be provided for four (4)classrooms, one (1) day care and one (1) adult room. Each room will be provided with its owncontrol
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
5/164
LOVETTSVILLE COMMUNITY CENTER LCCHVAC
VIRGINIA PRELIMINARY DESIGN NARRATIVE
Table 2 - Life Cycle Cost Analysis Summary (Without Maintenance Cost)
Option # First CostAnnualUtility
Cost
SimplePay Back
(years)
Life CycleCost
Analysis
Option 1a - Packaged Roof top unit (DXcooling & Propane gas heating), Fanpowered Variable volume boxes with Hotwater heating.
$503,624 $20,701 N/A $581,396.22
Option 2a - Geothermal system, Roof top
unit (heat pump), WSHP with DOAS(Dedicated Outdoor Air System). $683,921 $18,074 68.6 $577,654.40
The cost estimate above is not for budgeting purposes but only for comparison between systems(refer to Appendix E for cost breakdown). The costs were based on RS Means cost estimate. All ofthe advantages and disadvantages of the various systems are presented in section 2 - mechanicalsystem options. The final approved option could be impacted by the final architectural scheme.
The building HVAC load for new building will be calculated based on ASHRAE recommendationsand good engineering practices. The HVAC system will be designed to follow the followingguidelines:
Table 3 - Design Parameters
Item#
Category Design Parameters Parameter Notes
1Winter Temperature
Summer Temperature
68.5oF to 75.5oF
74
o
F to 80
o EPA 2000 & ASHRAE 55-04
F2 Humidity
30% to 60% RelativeHumidity
EPA 2000 & ASHRAE 55-04
3Outdoor AirV til ti
10 CFM per Person + 0.12/ft2 of Area
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
6/164
LOVETTSVILLE COMMUNITY CENTER LCCHVAC
VIRGINIA PRELIMINARY DESIGN NARRATIVE
Four possible locations for the geothermal well field (refer to page 12 for locations) were also
reviewed during the meeting. The location considered were:
1.
Area of existing playground, North-East of new building.
2.
Area to the west of new building entrance.
3.
Area for future unpaved parking, North-West of new building.
4.
Area of Existing building/new parking.
Location 3 was deemed to be the most appropriate location by Loudon County staff. This location isthe most remote and had least impact of existing site conditions. The main distribution piping to thevault will be oversized to maintain acceptable pump head loss and operating cost. If this location isaccepted, the proposed mechanical room location will be relocated to the west end of the newbuilding in the final architectural DD scheme. The location of mechanical room that house thepump(s) for the geothermal / condenser water loop in the building will be determine after location ofgeothermal field is accepted.
2.
MECHANICAL SYSTEM OPTIONS
The two (2) options are deemed appropriate for this project and were analyzed are as follows:
Option 1aPackaged Roof top unit (DX cooling & Propane gas heating), Fan poweredVariable volume boxes with Hot water heating.
Option 2a Geothermal system, Roof top unit (heat pump), WSHP with DOAS (DedicatedOutdoor Air System).
Option 1a Option 2a
EFFICIENCY AND OPERATIONS SAVINGS AVERAGE HIGH
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
7/164
LOVETTSVILLE COMMUNITY CENTER LCCHVAC
VIRGINIA PRELIMINARY DESIGN NARRATIVE
2.1
Option-1: Packaged Roof top unit (DX cooling & Propane gas heating), Fan powered Variable
volume boxes with Hot water heating
In this scheme of system four (4) packaged, Roof Top Units (RTU-1 & RTU-2 for the gymnasium,RTU-3 for the lobby/admin and RTU-4 for the classroom wing), shall be installed on the buildingroof to provide cooling, heating and appropriate ventilation air to the spaces per IMC. Supply andreturn air shall be ducted vertically down with horizontal ductwork distribution above ceiling. TheRTUS and associated components shall be sized to accommodate the cooling, heating andventilation air requirements of all the spaces served at maximum occupancy. The RTUS shall beequipped with MERV 14 filters, DX cooling coil, gas heating coil, high efficiency
compressor/condensing sections and variable frequency drive fan/motor assemblies to modulateairflow as necessary to maintain space temperature set-points.
The term packaged refers to the HVAC unit which is incorporated into the RTU such thatconditioning (cooling& heating) of air can be done depending on the seasonal change andrequirement. Refrigerant DX coil & gas heating coil are located inside the RTU for cooling & pre-heating operation within the unit.
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
8/164
LOVETTSVILLE COMMUNITY CENTER LCCHVAC
VIRGINIA PRELIMINARY DESIGN NARRATIVE
Boilers shall be sized based on natural gas input and provide hot water to the building distributionsystems. The hot water will generally circulate in the range of 180F and a maximum Delta T on thereturn water temperature of 20 to 40F will be the design goal. Two condensing boilers wereconsidered for this school. Each of these boilers will be sized to accommodate 80% of the peakheating load.
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
9/164
LOVETTSVILLE COMMUNITY CENTER LCCHVAC
VIRGINIA PRELIMINARY DESIGN NARRATIVE
System Advantages
Good Individual zone control.
Packaged unit utilizes refrigerant R410A which is ozone depletion free& provideLEED benefits.
Low first cost.
Low classroom noise.
System Disadvantages
Most of the units are located on the roof which will impact the roof structurally.
Risk of entire building or large areas of the building being without heating andcooling when equipment fails.
Higher energy operating costs.
Mechanical room is needed to house boiler(s) and hot water pump(s).
2.2
Option 2A: Geothermal system, Roof top unit (heat pump), WSHP with DOAS (Dedicated
Outdoor Air System)
In this scheme of system two (2) packaged, Roof Top Units (RTU-1 & RTU-2 for the gymnasium,shall be installed on the building roof to provide cooling, heating and appropriate ventilation air tothe spaces per IMC. Supply and return air shall be ducted vertically down with horizontal ductworkdistribution above ceiling. The RTUS and associated components shall be sized to accommodate thecooling, heating and ventilation air requirements of all the spaces served at maximum occupancy.The RTUS shall be equipped with MERV 14 filters, heat-pump cooling coil with reversible valvefor heating option, and variable frequency drive fan/motor assemblies to modulate airflow as
necessary to maintain space temperature set-points.
The term heat pump refers to the HVAC unit which is incorporated into the RTU such thatconditioning (cooling& heating) of air can be done depending on the seasonal change and
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
10/164
LOVETTSVILLE COMMUNITY CENTER LCCHVAC
VIRGINIA PRELIMINARY DESIGN NARRATIVE
Water Source Heat Pump (WSHP):
Heat pumps units are good incremental units for use in classroom spaces provided; the OutsideAir requirement per International code is met by a dedicated OA system (DOAS). The highlatent loads presented by the required ventilation exceed the capacity of the heat pump unit coils.Circulated water is used as the heat sink to eliminate the need for individual condensing units aswould be required for air-cooled heat pumps. This arrangement allows for the heat source/sink tobe located in a remote location to minimize damage. The main water pipes can be run to eachheat pump present in the served space ceiling or a closet present inside the space. There areseveral manufacturers of this type of Heat pump. A typical image of this kind of unit is as shown
below.
Figure 5: Water Source Heat Pump (Indoor)
Unit heater shall be provided at the entrance areas and restrooms shall be exhausted as per IMCrequirement.
Geothermal field will require approximately 30 bore wells with a depth of 300 to 450 ft each.Vertical geothermal well layout will be used in this project as this type of installation takes lessground area when compared to horizontal type. Geo-thermal vault will be provided and installed nearthe selected field area to provide necessary condenser water for the roof top units. Below is the
d l i f h l fi ld
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
11/164
LOVETTSVILLE COMMUNITY CENTER LCCHVAC
VIRGINIA PRELIMINARY DESIGN NARRATIVE
Dedicated Outside Air System (DOAS):
A dedicated outdoor air system (DOAS) is a type ofHVAC system that consists of two parallelsystems: a dedicated outdoor air ventilation system that handleslatent loads and a parallel system tohandlesensible loads.
Depending on the environment and the parallel system involved, the outdoor air system will handlesome of the sensible load in addition to the latent load and the parallel system will handle the rest ofthe sensible load. The main point of a DOAS system is to provide dedicated ventilation rather thanventilation as part of conditioned air. For a typical DOAS ventilation system, the outside air system
can accommodate around 0-30% of the space sensible load and thus provides enough ventilation asper international mechanical code. In order to create a comfortable indoor environment, the balanceof the space sensible loads is be accommodated by other optional equipment choices as fan coil unitsin this case. Also, a DOAS system comes with an energy wheel to make this unit more energyefficient. A typical DOAS unit is show in the image below.
System Advantages
Simultaneous heating and cooling is possible allowing credit for load movement within the
facility.
Low operating cost.
Decentralized approach allows one unit to be serviced without affecting any other zone.
Individual zone control.
Ventilation through DOAS is controlled by carbon dioxide sensor so it helps to monitor the
outside air quantity.
System Disadvantages
Highest Initial cost for installing because many types of equipment involved in this type of
system
http://en.wikipedia.org/wiki/HVAChttp://en.wikipedia.org/wiki/Latent_heathttp://en.wikipedia.org/wiki/Sensible_heathttp://en.wikipedia.org/wiki/Sensible_heathttp://en.wikipedia.org/wiki/Latent_heathttp://en.wikipedia.org/wiki/HVAC8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
12/164
LOVETTSVILLE COMMUNITY CENTER LCCHVAC
VIRGINIA PRELIMINARY DESIGN NARRATIVE
Figure 6 shows a simple flow diagram of a ground source system. In the figure it can be seen that
water from the well field is circulated to the vault(s) and then to a series of water-to-water heatpumps. There are many configurations that water-to-water heat pumps can have to effectively heatand condition a building. In this example, the building load demands heating and coolingsimultaneously; therefore, three heat pumps are shown in heating operation and three in cooling. Theheat pumps through condensation or evaporation provide the hot or cold water to the building. Atthis point, the system operates in a similar fashion to a traditional boiler and chiller system.
Figure 6: Simple Flow Diagram of a Ground Source System
In a closed loop geothermal application, vertical wells spaced 15 to 20 feet apart are bored in the
ground on average 150 to 500 feet deep. Each well consists of a double loop of pipe with a U-bendat the bottom. The remaining open area of the drilled borehole is backfilled or grouted to encase theU-bend assembly. A typical ground loop installation can be seen in Figures 7.
VaultGeothermal
WellField
Cold Water
Hot Water
WWHP
WWHP
WWHP
WWHP
WWHP
WWHP
HP Conditioned
Air
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
13/164
LOVETTSVILLE COMMUNITY CENTER LCCHVAC
VIRGINIA PRELIMINARY DESIGN NARRATIVE
Each vertical pipe is connected to a horizontal underground pipe that carries fluid in a closed system
to and from a well field header system that has multiple valved circuits that are brought into a vaultwhere they are connected to a manifold. The use of a vault proves to be advantageous by creatingredundancy in the system. If a problem occurs in one of the boreholes, that row can be isolatedthrough valves. This allows maintenance to take place without shutting down the entire system. Atypical vault installation can be seen in Figures 8 and 9.
Figure 8: Typical Ground Loop Vault
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
14/164
LOVETTSVILLE COMMUNITY CENTER LCCHVAC
VIRGINIA PRELIMINARY DESIGN NARRATIVE
A typical manifold, as seen in Figure 10, includes butterfly isolation valves, combination
balancing/isolation valves and pressure/temperature ports for each circuit. With this design setup,circuit isolation, pressure testing and flow balancing can be easily performed.
Figure 10: Typical Ground Loop Manifold Piping Installation Details
Using geothermal heating and cooling is a very efficient alternative to using traditional boiler and chillercombinations. Minimal maintenance is required for a typical ground source system as well as a reducedd d h i l i M i i ll i l d i i d l k
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
15/164
LOVETTSVILLECOMMUNITYCENTER LCCHVAC
VIRGINIA PRELIMINARYDESIGNNARRATIVE
Proposed Geothermal field location
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
16/164
LOVETTSVILLE COMMUNITY CENTER LCCHVAC
VIRGINIA PRELIMINARY DESIGN NARRATIVE
APPENDIX A
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
17/164
SETTY
LOUDON COUNTY, VA
LOVETTSVILLE COMMUNITY CENTER
SETTY
Comments
Company
Program user
Building owner
Location
LOVETTSVILLE COMMUNITY CENTER
Washington, D.C.Location
Latitude
Longitude
38.0 deg
77.05
deg
14
29.9
t
in. Hg
Time Zone
Elevation
Barometric pressure
Air density
Air specific heat
Density-specific heat product
Latent heat factor
Enthalpy factor
lb/cu ft0.0760
0.2444
1.1147
4,906.9
4.5604
Btu/lbF
Btu/hcfmF
Btumin/hcu ft
lbmin/hrcu ft
Summer design dry bulb
Summer design wet bulb
Winter design dry bulb
Summer clearness number
Winter clearness number
Summer ground reflectance
Winter ground reflectance
95
78
10
F
F
F
0.85
0.85
0.20
0.20
TETD-TA1
UATD
Design simulation period
Cooling load methodology
Heating load methodology
January - December
By Setty
W:\2014\SAP14728.01\SAP14728.01M\LOADS\LATEST\LCC
.TRC
Dataset name
05:01 PM on 04/10/2014Calculation time
TRACE 700 version
400Carbon Dioxide Level ppm
6.3
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
18/164
System ChecksumsBy Setty
Single ZoneRTU-1
HEATING COIL PEAKCLG SPACE PEAKCOOLING COIL PEAK TEMPERATURES
Heating DesignMo/Hr:Sum ofMo/Hr:7 / 17Mo/Hr:Peaked at Time: Cooling Heat ing
SADBOADB: 10OADB:93 / 77 / 114OADB/WB/HR:Outside Air: 57.0 95.0
Ra Plenum 76.3 68.8
ReturnPercentCoil PeakSpace PeakSpace PercentPercentNetPlenumSpace 76.8 68.8
Ret/OASens. + Lat. Of TotalTot SensSpace SensOf TotalSensibleOf TotalTotalSens. + Lat 54.777.7 0.00.2Fn MtrTDBtu/h (%)Btu/hBtu/h(%)Btu/h(%)Btu/hBtu/h0.00.4Fn BldTDEnvelope Loads0.01.1Fn Frict0Skylite Solar 0.000000000
0Skylite Cond 0.000000000
0Roof Cond 2.67-6,30400035,1825,182
0.0044,424Glass Solar 004345,7072844,4240
8,259Glass/Door Cond -27,477 11.66-27,47777,63858,2590AIRFLOWS
HeatingCooling4,694Wall Cond 3.11-7,332-6,04455,00845,686993
0Partition/Door 0.00000000
0Floor 0.0000000
Sec Fan0.000Infiltration 000000
0 0MinStop/Rh
17.4457,377Sub Total ==> -41,112-33,5205558,3544063,5516,174
5,251Return 5,251
Internal Loads
1,2601,260Exhaust
8,601Lights 0.000088,601710,7512,150
0 0Rm Exh
49,500People 0.0003233,75031
00Auxiliary
3,840Misc 0.000043,84023,8400
61,940Sub Total ==> 0.00004446,1904064,0912,150
904Ceiling Load 0.000-824181300-904
0Ventilation Load 35.75-84,2740001423,2160
Sup. Fan Heat 69,335
ENGINEERING CKS
HeatingCooling
Ret. Fan Heat 23,1123,112 % OA 24.024.0
Duct Heat Pkup 000 2.332.33cfm/ft
0Ov/Undr Sizing
47.50-111,985-111,985
0000
391.90cfm/ton
Exhaust Heat
-0.691,624
-2-2,527
167.94ft/ton
-104.7871.46Btu/hrft
150No. People120,221Grand Total ==> 100.00-235,747-146,329100.00105,357100.00160,7768,005
AREAS HEATING COIL SELECTIONCOOLING COIL SELECTIONTotal Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Coil Airflow Ent LvgCapacity
ton MBh MBh cfm F F gr/lb F F gr/lb ft (%) FFcfmMBh
Floor 2,250 Main Htg -235.8 5,251 54.7 95.013.4 160.8 129.8 5,251 77.7 64.2 68.4 55.4 54.1 60.3Main Clg
Part 0 Aux Htg 0.0 0.00.000.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Aux Clg
ExFlr 0
-4.0Preheat 54.7 55.45,2510.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Opt Vent
Roof 2,250 0 0
Wall 2,712 814 30Humidif 0.0 0 0.0 0.013.4 160.8Total
Opt Vent 0.0 0.00.00
-235.8Total
Envelope LoadsSkylite Solar
Skylite Cond
Roof Cond
Glass Solar
Glass/Door Cond
Wall Cond
Partition/Door
Floor
Infiltration
Sub Total ==>
LightsPeople
Misc
Sub Total ==>
Ceiling Load
Ventilation Load
Additional Reheat
OA Preheat Diff.
Ov/Undr Sizing
Exhaust Heat
RA Preheat Diff.
Grand Total ==>
Internal Loads
0
0
0
0.00
0.00
0.00
-2,527
Supply Air Leakage
Peaks
Dehumid. Ov Sizing 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0Leakage Ups
Leakage Dwn
00Infil
AHU Vent
Nom Vent
Main FanTerminal
Adjacent Floor
Diffuser
Supply Air Leakage
Underflr Sup Ht Pkup Underflr Sup Ht Pkup
Adjacent Floor0 0 0 0
0 0
0 0 0
0
0
0 0 0 0
0 0.00
0 0.00
5,251
5,2515,251
0
1,260
1,260
0
0
5,251
5,2515,251
0
1,260
1,260
0
0
0 49,500 0
Int Door 0
Ext Door 0 0 0
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 1 System Checksums Report Page 1 of 7LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
19/164
System ChecksumsBy Setty
Single ZoneRTU-2
HEATING COIL PEAKCLG SPACE PEAKCOOLING COIL PEAK TEMPERATURES
Heating DesignMo/Hr:Sum ofMo/Hr:7 / 18Mo/Hr:Peaked at Time: Cooling Heat ing
SADBOADB: 10OADB:92 / 76 / 112OADB/WB/HR:Outside Air: 57.0 95.0
Ra Plenum 76.3 68.6
ReturnPercentCoil PeakSpace PeakSpace PercentPercentNetPlenumSpace 76.9 68.6
Ret/OASens. + Lat. Of TotalTot SensSpace SensOf TotalSensibleOf TotalTotalSens. + Lat 49.578.0 0.00.2Fn MtrTDBtu/h (%)Btu/hBtu/h(%)Btu/h(%)Btu/hBtu/h0.00.4Fn BldTDEnvelope Loads0.01.1Fn Frict0Skylite Solar 0.000000000
0Skylite Cond 0.000000000
0Roof Cond 3.21-6,28000033,9813,981
0.0023,644Glass Solar 003224,9811923,6440
3,199Glass/Door Cond -11,793 6.02-11,79342,88233,1990AIRFLOWS
HeatingCooling2,443Wall Cond 1.91-3,748-3,12332,47022,930486
0Partition/Door 0.00000000
0Floor 0.0000000
Sec Fan0.000Infiltration 000000
0 0MinStop/Rh
11.1429,286Sub Total ==> -21,821-14,9163930,3332733,7544,467
3,860Return 3,860
Internal Loads
1,2601,260Exhaust
8,601Lights 0.0000118,601910,7512,150
0 0Rm Exh
49,500People 0.0004433,75040
00Auxiliary
3,840Misc 0.000053,84033,8400
61,940Sub Total ==> 0.00006046,1905164,0912,150
941Ceiling Load 0.000-981192700-941
0Ventilation Load 43.03-84,2740001620,5180
Sup. Fan Heat 56,862
ENGINEERING CKS
HeatingCooling
Ret. Fan Heat 22,2872,287 % OA 32.632.6
Duct Heat Pkup 000 1.721.72cfm/ft
0Ov/Undr Sizing
46.81-91,673-91,673
0000
370.82cfm/ton
Exhaust Heat
-0.991,934
-2-2,600
216.15ft/ton
-87.0455.52Btu/hrft
150No. People92,167Grand Total ==> 100.00-195,834-107,570100.0077,451100.00124,9125,365
AREAS HEATING COIL SELECTIONCOOLING COIL SELECTIONTotal Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Coil Airflow Ent LvgCapacity
ton MBh MBh cfm F F gr/lb F F gr/lb ft (%) FFcfmMBh
Floor 2,250 Main Htg -195.8 3,860 49.5 95.010.4 124.9 96.0 3,860 78.0 64.5 69.4 55.4 53.8 59.2Main Clg
Part 0 Aux Htg 0.0 0.00.000.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Aux Clg
ExFlr 0
-25.5Preheat 49.5 55.43,8600.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Opt Vent
Roof 2,250 0 0
Wall 1,320 349 26Humidif 0.0 0 0.0 0.010.4 124.9Total
Opt Vent 0.0 0.00.00
-195.8Total
Envelope LoadsSkylite Solar
Skylite Cond
Roof Cond
Glass Solar
Glass/Door Cond
Wall Cond
Partition/Door
Floor
Infiltration
Sub Total ==>
LightsPeople
Misc
Sub Total ==>
Ceiling Load
Ventilation Load
Additional Reheat
OA Preheat Diff.
Ov/Undr Sizing
Exhaust Heat
RA Preheat Diff.
Grand Total ==>
Internal Loads
0
0
0
0.00
0.00
0.00
-2,600
Supply Air Leakage
Peaks
Dehumid. Ov Sizing 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0Leakage Ups
Leakage Dwn
00Infil
AHU Vent
Nom Vent
Main FanTerminal
Adjacent Floor
Diffuser
Supply Air Leakage
Underflr Sup Ht Pkup Underflr Sup Ht Pkup
Adjacent Floor0 0 0 0
0 0
0 0 0
0
0
0 0 0 0
0 0.00
0 0.00
3,860
3,8603,860
0
1,260
1,260
0
0
3,860
3,8603,860
0
1,260
1,260
0
0
0 49,500 0
Int Door 0
Ext Door 0 0 0
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 1 System Checksums Report Page 2 of 7LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
20/164
System ChecksumsBy Setty
Parallel Fan-Powered VAV, Htg Coil on Plenum InletRTU-3
HEATING COIL PEAKCLG SPACE PEAKCOOLING COIL PEAK TEMPERATURES
Heating DesignMo/Hr:7 / 17Mo/Hr:7 / 17Mo/Hr:Peaked at Time: Cooling Heat ing
SADBOADB: 10OADB:93 / 77 / 114OADB/WB/HR:Outside Air: 57.0 78.7
Ra Plenum 77.1 67.7
ReturnPercentCoil PeakSpace PeakSpace PercentPercentNetPlenumSpace 77.1 67.7
Ret/OASens. + Lat.
Of TotalTot SensSpace SensOf TotalSensibleOf TotalTotalSens. + Lat
15.778.5 0.00.2Fn MtrTDBtu/h (%)Btu/hBtu/h(%)Btu/h(%)Btu/hBtu/h0.10.4Fn BldTDEnvelope Loads0.21.3Fn Frict0Skylite Solar 0.000000000
0Skylite Cond 0.000000000
0Roof Cond 7.69-11,18200069,0519,051
0.0031,201Glass Solar 003431,2012031,2010
8,448Glass/Door Cond -28,193 19.40-28,19398,44858,4480AIRFLOWS
HeatingCooling3,757Wall Cond 5.15-7,479-5,75243,75734,8681,111
0Partition/Door 0.00000000
0Floor 0.0000000
Sec Fan0.000Infiltration 000000
1,623 1,623MinStop/Rh
32.2443,406Sub Total ==> -46,853-33,9444743,4063453,56910,162
4,598Return 1,623
Internal Loads
1,4621,507Exhaust
13,849Lights 0.00001513,8491117,3113,462
0 0Rm Exh
47,700People 0.0002926,50031
00Auxiliary
5,756Misc 0.000065,75645,7560
67,305Sub Total ==> 0.00005046,1054570,7673,462
2,741Ceiling Load 0.000-3,01932,74100-2,741
0Ventilation Load 67.28-97,7780001725,8210
Sup. Fan Heat 69,536
ENGINEERING CKS
HeatingCooling
Ret. Fan Heat 000 % OA 38.532.8
Duct Heat Pkup 000 0.531.13cfm/ft
0Ov/Undr Sizing
0.0000
0000
353.38cfm/ton
Exhaust Heat
-2.623,812
-2-3,567
313.06ft/ton
-34.8538.33Btu/hrft
106No. People113,452Grand Total ==> 100.00-145,320-36,963100.0092,252100.00156,1267,318
AREAS HEATING COIL SELECTIONCOOLING COIL SELECTIONTotal Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Coil Airflow Ent LvgCapacity
ton MBh MBh cfm F F gr/lb F F gr/lb ft (%) FFcfmMBh
Floor 4,073 Main Htg -66.1 2,170 67.7 95.013.0 156.1 119.7 4,598 78.5 64.7 69.6 55.1 53.5 58.4Main Clg
Part 0 Aux Htg 0.0 0.00.000.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Aux Clg
ExFlr 0
-75.8Preheat 10.0 55.11,5070.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Opt Vent
Roof 4,073 0 0
Wall 2,783 835 30Humidif 0.0 0 0.0 0.013.0 156.1Total
Opt Vent 0.0 0.00.00
-142.0Total
Envelope LoadsSkylite Solar
Skylite Cond
Roof Cond
Glass Solar
Glass/Door Cond
Wall Cond
Partition/Door
Floor
Infiltration
Sub Total ==>
LightsPeople
Misc
Sub Total ==>
Ceiling Load
Ventilation Load
Additional Reheat
OA Preheat Diff.
Ov/Undr Sizing
Exhaust Heat
RA Preheat Diff.
Grand Total ==>
Internal Loads
0
-2,257
-2,244
1.55
1.54
0.00
-3,567
Supply Air Leakage
93
Dehumid. Ov Sizing 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0Leakage Ups
Leakage Dwn
00Infil
AHU Vent
Nom Vent
Main FanTerminal
Adjacent Floor
Diffuser
Supply Air Leakage
Underflr Sup Ht Pkup Underflr Sup Ht Pkup
Adjacent Floor0 0 0 0
0 0
0 0 0
0
0
0 0 0 0
0 0.00
0 0.00
4,598
4,5984,598
0
1,507
1,507
0
0
3,793
3,7931,623
2,170
1,462
1,462
0
0
0 47,700 0
Int Door 0
Ext Door 0 0 0
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 1 System Checksums Report Page 3 of 7LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
21/164
System ChecksumsBy Setty
Parallel Fan-Powered VAV, Htg Coil on Plenum InletRTU-4
HEATING COIL PEAKCLG SPACE PEAKCOOLING COIL PEAK TEMPERATURES
Heating DesignMo/Hr:9 / 11Mo/Hr:7 / 11Mo/Hr:Peaked at Time: Cooling Heat ing
SADBOADB: 10OADB:89 / 76 / 118OADB/WB/HR:Outside Air: 57.0 78.9
Ra Plenum 76.4 68.0
ReturnPercentCoil PeakSpace PeakSpace PercentPercentNetPlenumSpace 76.6 68.6
Ret/OASens. + Lat.
Of TotalTot SensSpace SensOf TotalSensibleOf TotalTotalSens. + Lat
42.078.6 0.00.1Fn MtrTDBtu/h (%)Btu/hBtu/h(%)Btu/h(%)Btu/hBtu/h0.10.3Fn BldTDEnvelope Loads0.20.9Fn Frict0Skylite Solar 0.000000000
0Skylite Cond 0.000000000
1,841Roof Cond 8.42-5,287-2,60021,13043,7381,898
0.0028,524Glass Solar 005935,7252928,5240
2,931Glass/Door Cond -15,186 24.17-15,186172832,9310AIRFLOWS
HeatingCooling2,639Wall Cond 7.18-4,511-3,94142,18133,188549
0Partition/Door 0.00000000
0Floor 0.0000000
Sec Fan0.000Infiltration 000000
950 950MinStop/Rh
39.7735,934Sub Total ==> -24,984-21,7276539,7643938,3802,446
3,039Return 950
Internal Loads
432475Exhaust
6,132Lights 0.0000106,13287,6651,533
0 0Rm Exh
15,600People 0.000148,57516
00Auxiliary
6,212Misc 0.0000106,21266,2120
27,943Sub Total ==> 0.00003420,9183029,4761,533
433Ceiling Load 0.000-633028700-433
0Ventilation Load 46.03-28,9160002726,0870
Sup. Fan Heat 44,230
ENGINEERING CKS
HeatingCooling
Ret. Fan Heat 000 % OA 19.215.6
Duct Heat Pkup 000 0.691.61cfm/ft
0Ov/Undr Sizing
0.0000
0000
374.68cfm/ton
Exhaust Heat
-1.28806
-1-857
232.31ft/ton
-33.0051.65Btu/hrft
34No. People64,311Grand Total ==> 100.00-62,823-22,360100.0060,970100.0097,3172,690
AREAS HEATING COIL SELECTIONCOOLING COIL SELECTIONTotal Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Coil Airflow Ent LvgCapacity
ton MBh MBh cfm F F gr/lb F F gr/lb ft (%) FFcfmMBh
Floor 1,884 Main Htg -38.0 1,296 68.7 95.08.1 97.3 71.4 2,855 78.6 65.0 70.6 55.7 53.7 58.6Main Clg
Part 0 Aux Htg 0.0 0.00.000.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Aux Clg
ExFlr 0
-24.2Preheat 10.0 55.74750.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Opt Vent
Roof 1,884 0 0
Wall 1,619 450 28Humidif 0.0 0 0.0 0.08.1 97.3Total
Opt Vent 0.0 0.00.00
-62.2Total
Envelope LoadsSkylite Solar
Skylite Cond
Roof Cond
Glass Solar
Glass/Door Cond
Wall Cond
Partition/Door
Floor
Infiltration
Sub Total ==>
LightsPeople
Misc
Sub Total ==>
Ceiling Load
Ventilation Load
Additional Reheat
OA Preheat Diff.
Ov/Undr Sizing
Exhaust Heat
RA Preheat Diff.
Grand Total ==>
Internal Loads
0
-2,162
-7,566
3.44
12.04
0.00
-857
Supply Air Leakage
80
Dehumid. Ov Sizing 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0Leakage Ups
Leakage Dwn
00Infil
AHU Vent
Nom Vent
Main FanTerminal
Adjacent Floor
Diffuser
Supply Air Leakage
Underflr Sup Ht Pkup Underflr Sup Ht Pkup
Adjacent Floor0 0 0 0
0 0
0 0 0
0
0
0 0 0 0
0 0.00
0 0.00
3,039
3,0393,039
0
475
475
0
0
2,246
2,246950
1,296
432
432
0
0
0 15,600 0
Int Door 0
Ext Door 0 0 0
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 1 System Checksums Report Page 4 of 7LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
22/164
System ChecksumsBy Setty
Water Source Heat PumpRTU-1
HEATING COIL PEAKCLG SPACE PEAKCOOLING COIL PEAK TEMPERATURES
Heating DesignMo/Hr:Sum ofMo/Hr:7 / 17Mo/Hr:Peaked at Time: Cooling Heat ing
SADBOADB: 10OADB:93 / 77 / 114OADB/WB/HR:Outside Air: 57.0 95.0
Ra Plenum 76.3 68.8
ReturnPercentCoil PeakSpace PeakSpace PercentPercentNetPlenumSpace 76.3 68.8
Ret/OASens. + Lat.
Of TotalTot SensSpace SensOf TotalSensibleOf TotalTotalSens. + Lat 54.677.4
0.00.2Fn MtrTDBtu/h (%)Btu/hBtu/h(%)Btu/h(%)Btu/hBtu/h0.00.4Fn BldTDEnvelope Loads0.01.1Fn Frict0Skylite Solar 0.000000000
0Skylite Cond 0.000000000
0Roof Cond 2.69-6,30300035,1815,181
0.0044,371Glass Solar 004445,6552944,3710
7,524Glass/Door Cond -24,926 10.62-24,92676,95857,5240AIRFLOWS
HeatingCooling4,694Wall Cond 3.12-7,332-6,04455,00845,686992
0Partition/Door 0.00000000
0Floor 0.0000000
Sec Fan0.000Infiltration 000000
0 0MinStop/Rh
16.4356,588Sub Total ==> -38,561-30,9695557,6214162,7616,173
5,214Return 5,214
Internal Loads
1,2601,260Exhaust
8,601Lights 0.000088,601710,7512,150
0 0Rm Exh
49,500People 0.0003233,75032
00Auxiliary
3,840Misc 0.000043,84023,8400
61,940Sub Total ==> 0.00004446,1904164,0912,150
909Ceiling Load 0.000-829181800-909
0Ventilation Load 35.90-84,2740001320,4370
Sup. Fan Heat 69,270
ENGINEERING CKS
HeatingCooling
Ret. Fan Heat 000 % OA 24.224.2
Duct Heat Pkup 000 2.322.32cfm/ft
0Ov/Undr Sizing
48.36-113,520-113,520
0000
404.31cfm/ton
Exhaust Heat
-0.701,634
-1-1,792
174.46ft/ton
-104.3268.79Btu/hrft
150No. People119,438Grand Total ==> 100.00-234,721-145,319100.00104,630100.00154,7675,623
AREAS HEATING COIL SELECTIONCOOLING COIL SELECTIONTotal Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Coil Airflow Ent LvgCapacity
ton MBh MBh cfm F F gr/lb F F gr/lb ft (%) FFcfmMBh
Floor 2,250 Main Htg -234.7 5,214 54.6 95.012.9 154.8 126.6 5,214 78.9 64.6 68.4 57.0 54.9 61.0Main Clg
Part 0 Aux Htg 0.0 0.00.000.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Aux Clg
ExFlr 0
-4.6Preheat 54.6 55.45,2140.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Opt Vent
Roof 2,250 0 0
Wall 2,712 814 30Humidif 0.0 0 0.0 0.012.9 154.8Total
Opt Vent 0.0 0.00.00
-234.7Total
Envelope LoadsSkylite Solar
Skylite Cond
Roof Cond
Glass Solar
Glass/Door Cond
Wall Cond
Partition/Door
Floor
Infiltration
Sub Total ==>
LightsPeople
Misc
Sub Total ==>
Ceiling Load
Ventilation Load
Additional Reheat
OA Preheat Diff.
Ov/Undr Sizing
Exhaust Heat
RA Preheat Diff.
Grand Total ==>
Internal Loads
0
0
0
0.00
0.00
0.00
-1,792
Supply Air Leakage
Peaks
Dehumid. Ov Sizing 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0Leakage Ups
Leakage Dwn
00Infil
AHU Vent
Nom Vent
Main FanTerminal
Adjacent Floor
Diffuser
Supply Air Leakage
Underflr Sup Ht Pkup Underflr Sup Ht Pkup
Adjacent Floor0 0 0 0
0 0
0 0 0
0
0
0 0 0 0
0 0.00
0 0.00
5,214
5,2145,214
0
1,260
1,260
0
0
5,214
5,2145,214
0
1,260
1,260
0
0
0 49,500 0
Int Door 0
Ext Door 0 0 0
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 2 System Checksums Report Page 5 of 7LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
23/164
System ChecksumsBy Setty
Water Source Heat PumpRTU-2
HEATING COIL PEAKCLG SPACE PEAKCOOLING COIL PEAK TEMPERATURES
Heating DesignMo/Hr:Sum ofMo/Hr:7 / 18Mo/Hr:Peaked at Time: Cooling Heat ing
SADBOADB: 10OADB:92 / 76 / 112OADB/WB/HR:Outside Air: 57.0 95.0
Ra Plenum 76.3 68.6
ReturnPercentCoil PeakSpace PeakSpace PercentPercentNetPlenumSpace 76.3 68.6
Ret/OASens. + Lat.Of TotalTot SensSpace SensOf TotalSensibleOf TotalTotal
Sens. + Lat 49.477.6
0.00.2Fn MtrTDBtu/h (%)Btu/hBtu/h(%)Btu/h(%)Btu/hBtu/h0.00.4Fn BldTDEnvelope Loads0.01.1Fn Frict0Skylite Solar 0.000000000
0Skylite Cond 0.000000000
0Roof Cond 3.21-6,28000033,9813,981
0.0023,618Glass Solar 003224,9542023,6180
2,915Glass/Door Cond -10,698 5.47-10,69832,62522,9150AIRFLOWS
HeatingCooling2,443Wall Cond 1.92-3,748-3,12332,47022,930486
0Partition/Door 0.00000000
0Floor 0.0000000
Sec Fan0.000Infiltration 000000
0 0MinStop/Rh
10.6028,976Sub Total ==> -20,726-13,8213930,0502833,4434,467
3,846Return 3,846
Internal Loads
1,2601,260Exhaust
8,601Lights 0.0000118,601910,7512,150
0 0Rm Exh
49,500People 0.0004433,75041
00Auxiliary
3,840Misc 0.000053,84033,8400
61,940Sub Total ==> 0.00006046,1905364,0912,150
943Ceiling Load 0.000-984193000-943
0Ventilation Load 43.12-84,2740001517,6790
Sup. Fan Heat 66,837
ENGINEERING CKS
HeatingCooling
Ret. Fan Heat 000 % OA 32.832.8
Duct Heat Pkup 000 1.711.71cfm/ft
0Ov/Undr Sizing
47.27-92,375-92,375
0000
383.98cfm/ton
Exhaust Heat
-0.991,939
-2-1,859
224.64ft/ton
-86.8653.42Btu/hrft
150No. People91,860Grand Total ==> 100.00-195,435-107,181100.0077,170100.00120,1913,815
AREAS HEATING COIL SELECTIONCOOLING COIL SELECTIONTotal Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Coil Airflow Ent LvgCapacity
ton MBh MBh cfm F F gr/lb F F gr/lb ft (%) FFcfmMBh
Floor 2,250 Main Htg -195.4 3,846 49.4 95.010.0 120.2 94.2 3,846 79.2 64.9 69.4 57.0 54.7 60.3Main Clg
Part 0 Aux Htg 0.0 0.00.000.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Aux Clg
ExFlr 0
-25.7Preheat 49.4 55.43,8460.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Opt Vent
Roof 2,250 0 0
Wall 1,320 349 26Humidif 0.0 0 0.0 0.010.0 120.2Total
Opt Vent 0.0 0.00.00
-195.4Total
Envelope LoadsSkylite Solar
Skylite Cond
Roof Cond
Glass Solar
Glass/Door Cond
Wall Cond
Partition/Door
Floor
Infiltration
Sub Total ==>
LightsPeople
Misc
Sub Total ==>
Ceiling Load
Ventilation Load
Additional Reheat
OA Preheat Diff.
Ov/Undr Sizing
Exhaust Heat
RA Preheat Diff.
Grand Total ==>
Internal Loads
0
0
0
0.00
0.00
0.00
-1,859
Supply Air Leakage
Peaks
Dehumid. Ov Sizing 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0Leakage Ups
Leakage Dwn
00Infil
AHU Vent
Nom Vent
Main FanTerminal
Adjacent Floor
Diffuser
Supply Air Leakage
Underflr Sup Ht Pkup Underflr Sup Ht Pkup
Adjacent Floor0 0 0 0
0 0
0 0 0
0
0
0 0 0 0
0 0.00
0 0.00
3,846
3,8463,846
0
1,260
1,260
0
0
3,846
3,8463,846
0
1,260
1,260
0
0
0 49,500 0
Int Door 0
Ext Door 0 0 0
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 2 System Checksums Report Page 6 of 7LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
24/164
System ChecksumsBy Setty
Water Source Heat PumpWSHP - 1
HEATING COIL PEAKCLG SPACE PEAKCOOLING COIL PEAK TEMPERATURES
Heating DesignMo/Hr:Sum ofMo/Hr:7 / 11Mo/Hr:Peaked at Time: Cooling Heat ing
SADBOADB: 10OADB:89 / 76 / 118OADB/WB/HR:Outside Air: 57.0 95.0
Ra Plenum 76.3 68.5
ReturnPercentCoil PeakSpace PeakSpace PercentPercentNetPlenumSpace 76.2 68.7
Ret/OASens. + Lat.Of TotalTot SensSpace SensOf TotalSensibleOf TotalTotal
Sens. + Lat 68.776.2
0.00.0Fn MtrTDBtu/h (%)Btu/hBtu/h(%)Btu/h(%)Btu/hBtu/h0.00.1Fn BldTDEnvelope Loads0.00.2Fn Frict0Skylite Solar 0.000000000
0Skylite Cond 0.000000000
2,310Roof Cond 7.10-16,663-2,60012,310511,6409,330
0.0072,424Glass Solar 004876,8273472,4240
7,281Glass/Door Cond -35,579 15.17-35,57946,16937,2810AIRFLOWS
HeatingCooling5,740Wall Cond 4.61-10,816-8,61945,86337,2271,487
0Partition/Door 0.00000000
0Floor 0.0000000
Sec Fan0.000Infiltration 000000
0 0MinStop/Rh
26.8887,755Sub Total ==> -63,059-46,7985791,1694698,57110,816
10,012Return 10,012
Internal Loads
1,9821,982Exhaust
19,981Lights 0.00001219,9811224,9764,995
0 0Rm Exh
63,300People 0.0002235,07530
00Auxiliary
11,968Misc 0.0000711,968611,9680
95,248Sub Total ==> 0.00004267,02347100,2444,995
2,058Ceiling Load 0.000-2,35611,84100-2,058
13,427Ventilation Load 56.50-132,535-132,53500613,4270
Sup. Fan Heat 12,379
ENGINEERING CKS
HeatingCooling
Ret. Fan Heat 000 % OA 24.724.7
Duct Heat Pkup 000 1.351.35cfm/ft
1,099Ov/Undr Sizing
17.95-42,106-42,106
11,09911,099
423.50cfm/ton
Exhaust Heat
-1.333,123
-1-2,755
314.15ft/ton
-39.5238.20Btu/hrft
140No. People199,587Grand Total ==> 100.00-234,576-223,795100.00161,132100.00212,96610,999
AREAS HEATING COIL SELECTIONCOOLING COIL SELECTIONTotal Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Coil Airflow Ent LvgCapacity
ton MBh MBh cfm F F gr/lb F F gr/lb ft (%) FFcfmMBh
Floor 5,957 Main Htg -235.4 8,030 68.7 95.017.8 213.0 171.3 8,030 76.5 63.1 65.0 57.0 54.2 58.1Main Clg
Part 0 Aux Htg 0.0 0.00.000.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Aux Clg
ExFlr 0
0.0Preheat 0.0 0.001.2 14.6 14.5 1,982 81.6 67.8 80.2 75.0 65.7 80.2Opt Vent
Roof 5,957 0 0
Wall 3,982 1,176 30Humidif 0.0 0 0.0 0.019.0 227.6Total
Opt Vent 0.0 0.00.00
-235.4Total
Envelope LoadsSkylite Solar
Skylite Cond
Roof Cond
Glass Solar
Glass/Door Cond
Wall Cond
Partition/Door
Floor
Infiltration
Sub Total ==>
LightsPeople
Misc
Sub Total ==>
Ceiling Load
Ventilation Load
Additional Reheat
OA Preheat Diff.
Ov/Undr Sizing
Exhaust Heat
RA Preheat Diff.
Grand Total ==>
Internal Loads
0
0
0
0.00
0.00
0.00
-2,755
Supply Air Leakage
Peaks
Dehumid. Ov Sizing 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0Leakage Ups
Leakage Dwn
00Infil
AHU Vent
Nom Vent
Main FanTerminal
Adjacent Floor
Diffuser
Supply Air Leakage
Underflr Sup Ht Pkup Underflr Sup Ht Pkup
Adjacent Floor0 0 0 0
0 0
0 0 0
0
0
0 0 0 0
0 0.00
0 0.00
8,030
8,0308,030
0
1,982
1,982
0
0
8,030
8,0308,030
0
1,982
1,982
0
0
0 63,300 0
Int Door 0
Ext Door 0 0 0
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 2 System Checksums Report Page 7 of 7LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
25/164
Design Cooling Load Summary
By Setty
LOVETTSVILLE COMMUNITY CENTER
LOUDON COUNTY, VA
Solar Gain
Glass TransmissionWall Transmission
Roof Transmission
Floor Transmission
Partition Transmission
Net Ceiling Load
Lighting
People
Misc. Equipment Loads
Cooling Infiltration
Sub-Total ==>
Ventilation Load
Supply Fan Load
Return Fan Load
Net Duct Heat Pickup
Wall Load to Plenum
Roof Load to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to Plenum
Glass Solar to Plenum
Over/Under Sizing
Total Cooling Loads
44,424
8,2594,694
0
0
0
0
8,601
33,750 15,750
3,840 0
0 0
8,001 15,215
9,335
3,112
0
993
5,182
2,150
0 0
0
0
0
0 0
0
Reheat at Design
44,424
8,2594,694
0
0
0
0
8,601
9,335
3,112
993
5,182
2,150
0
0
0
23,216
49,500
3,840
0
0
0
103,567 15,750 119,317
129,811 30,965 160,776
27.6%
5.1%2.9%
0.0%
0.0%
0.0%
0.0%
5.3%
30.8%
2.4%
0.0%
74.2%
14.4%
5.8%
1.9%
0.0%
0.6%
3.2%
1.3%
0.0%
0.0%
0.0%
0.0%
0.0%
100.0 %
Load Component Sensible Latent TotalBtu/h Btu/h Btu/h
Percent
of Total
Coil Selection Parameters
Coil Entering Air (DB / WB)
Coil Entering Humidity RatioCoil Leaving Air (DB / WB)
Coil Leaving Humidity Ratio
Coil Sensible Load
Coil Total Load
Cooling Supply Air Temperature
Total Cooling Airflow
Resulting Room Relative Humidity
General Engineering Checks
Total Cooling Load
Area / Load
Total Floor AreaCooling Airflow
Airflow / Load
Percent Outdoor Air
Cooling Load Methodology
77.7 / 64.2
55.4 / 54.168.37
60.26
129.81
160.78
57.00
5,250.74
47.75
13.4
167.94
2,2502.33
391.90
24.0
TETD-TA1
cfm/ft
ton
ft/ton
ft
cfm/ton
%
F
gr/lbF
gr/lb
MBh
MBh
cfm
F
%
COOLING COIL SELECTIONCOOLING COIL LOAD INFORMATION
Zone - Zone - 001
System - RTU-1
Coil Location - Zone
Ambient DB/WB/HR: 93 / 77 / 114
Coil Peak Calculation Time: July, hour 17
-2,527 0 -2,527 -1.6%Exhaust Heat
Adj Floor Transmission 0 0.00
Adj Floor to Plenum 0 0
Underfloor Sup Heat Pickup
Supply Air Leakage
0 0
0 0
0.0%
0.0%
0
0.0%
0.0%
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 1 Design Cooling Load Report Page 1 of 19LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
26/164
Design Cooling Load Summary
By Setty
LOVETTSVILLE COMMUNITY CENTER
LOUDON COUNTY, VA
Solar Gain
Glass TransmissionWall Transmission
Roof Transmission
Floor Transmission
Partition Transmission
Net Ceiling Load
Lighting
People
Misc. E ui ment Loads
Cooling Infiltration
Sub-Total ==>
Ventilation Load
Supply Fan Load
Return Fan LoadNet Duct Heat Pickup
Wall Load to Plenum
Roof Load to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to Plenum
Glass Solar to Plenum
Over/Under Sizing
Total Cooling Loads
23,644
3,1992,443
0
0
0
0
8,601
33,750 15,750
3,840 0
0 0
7,397 13,121
6,862
2,2870
486
3,981
2,150
0 0
0
0
0
0 0
0
Reheat at Design
23,644
3,1992,443
0
0
0
0
8,601
6,862
2,287
486
3,981
2,150
0
0
0
20,518
49,500
3,840
0
0
0
75,477 15,750 91,227
96,041 28,871 124,912
18.9%
2.6%2.0%
0.0%
0.0%
0.0%
0.0%
6.9%
39.6%
3.1%
0.0%
73.0%
16.4%
5.5%
1.8%0.0%0.4%
3.2%
1.7%
0.0%0.0%
0.0%
0.0%
0.0%
100.0 %
Load Component Sensible Latent Total
Btu/h Btu/h Btu/hPercent
of Total
Coil Selection Parameters
Coil Entering Air (DB / WB)
Coil Entering Humidity RatioCoil Leaving Air (DB / WB)
Coil Leaving Humidity Ratio
Coil Sensible Load
Coil Total Load
Cooling Supply Air Temperature
Total Cooling Airflow
Resulting Room Relative Humidity
General Engineering Checks
Total Cooling Load
Area / Load
Total Floor Area
Cooling AirflowAirflow / Load
Percent Outdoor Air
Cooling Load Methodology
78.0 / 64.5
55.4 / 53.869.42
59.21
96.04
124.91
57.00
3,859.95
49.11
10.4
216.15
2,250
1.72370.82
32.6
TETD-TA1
cfm/ft
ton
ft/ton
ft
cfm/ton
%
F
gr/lbF
gr/lb
MBh
MBh
cfm
F
%
COOLING COIL SELECTIONCOOLING COIL LOAD INFORMATION
Zone - Zone - 002
System - RTU-2
Coil Location - Zone
Ambient DB/WB/HR: 92 / 76 / 112
Coil Peak Calculation Time: July, hour 18
-2,600 0 -2,600 -2.1%Exhaust Heat
Adj Floor Transmission 0 0.00
Adj Floor to Plenum 0 0
Underfloor Sup Heat Pickup
Supply Air Leakage
0 0
0 0
0.0%
0.0%
0
0.0%
0.0%
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 1 Design Cooling Load Report Page 2 of 19LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
27/164
Design Cooling Load Summary
By Setty
LOVETTSVILLE COMMUNITY CENTER
LOUDON COUNTY, VA
Solar Gain
Glass TransmissionWall Transmission
Roof Transmission
Floor Transmission
Partition Transmission
Net Ceiling Load
Lighting
People
Misc. E ui ment Loads
Cooling Infiltration
Sub-Total ==>
Ventilation Load
Supply Fan Load
Return Fan LoadNet Duct Heat Pickup
Wall Load to Plenum
Roof Load to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to Plenum
Glass Solar to Plenum
Over/Under Sizing
Total Cooling Loads
31,201
8,4483,757
0
0
0
0
13,849
26,500 21,200
5,756 0
0 0
10,631 15,190
9,536
00
1,111
9,051
3,462
0 0
0
0
0
0 0
0
Reheat at Design
31,201
8,4483,757
0
0
0
0
13,849
9,536
0
1,111
9,051
3,462
0
0
0
25,821
47,700
5,756
0
0
0
89,511 21,200 110,711
119,736 36,390 156,126
20.0%
5.4%2.4%
0.0%
0.0%
0.0%
0.0%
8.9%
30.6%
3.7%
0.0%
70.9%
16.5%
6.1%
0.0%0.0%0.7%
5.8%
2.2%
0.0%0.0%
0.0%
0.0%
0.0%
100.0 %
Load Component Sensible Latent Total
Btu/h Btu/h Btu/hPercent
of Total
Coil Selection Parameters
Coil Entering Air (DB / WB)
Coil Entering Humidity RatioCoil Leaving Air (DB / WB)
Coil Leaving Humidity Ratio
Coil Sensible Load
Coil Total Load
Cooling Supply Air Temperature
Total Cooling Airflow
Resulting Room Relative Humidity
General Engineering Checks
Total Cooling Load
Area / Load
Total Floor Area
Cooling AirflowAirflow / Load
Percent Outdoor Air
Cooling Load Methodology
78.5 / 64.7
55.1 / 53.569.62
58.43
119.74
156.13
57.00
4,597.60
49.91
13.0
313.06
4,073
1.13353.38
32.8
TETD-TA1
cfm/ft
ton
ft/ton
ft
cfm/ton
%
F
gr/lbF
gr/lb
MBh
MBh
cfm
F
%
COOLING COIL SELECTIONCOOLING COIL LOAD INFORMATION
Type - Parallel Fan-Powered VAV, Htg Coil on Plenum Inlet
System - RTU-3
Coil Location - System
Ambient DB/WB/HR: 93 / 77 / 114
Coil Peak Calculation Time: July, hour 17
-3,567 0 -3,567 -2.3%Exhaust Heat
Adj Floor Transmission 0 0.00
Adj Floor to Plenum 0 0
Underfloor Sup Heat Pickup
Supply Air Leakage
0 0
0 0
0.0%
0.0%
0
0.0%
0.0%
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 1 Design Cooling Load Report Page 3 of 19LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
28/164
Design Cooling Load Summary
By Setty
LOVETTSVILLE COMMUNITY CENTER
LOUDON COUNTY, VA
Solar Gain
Glass TransmissionWall Transmission
Roof Transmission
Floor Transmission
Partition Transmission
Net Ceiling Load
Lighting
People
Misc. E ui ment Loads
Cooling Infiltration
Sub-Total ==>
Ventilation Load
Supply Fan Load
Return Fan LoadNet Duct Heat Pickup
Wall Load to Plenum
Roof Load to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to Plenum
Glass Solar to Plenum
Over/Under Sizing
Total Cooling Loads
28,524
2,9312,639
1,841
0
0
0
6,132
8,575 7,025
6,212 0
0 0
7,193 18,894
4,230
00
549
1,898
1,533
0 0
0
0
0
0 0
0
Reheat at Design
28,524
2,9312,639
1,841
0
0
0
6,132
4,230
0
549
1,898
1,533
0
0
0
26,087
15,600
6,212
0
0
0
56,852 7,025 63,877
71,398 25,919 97,317
29.3%
3.0%2.7%
1.9%
0.0%
0.0%
0.0%
6.3%
16.0%
6.4%
0.0%
65.6%
26.8%
4.3%
0.0%0.0%0.6%
1.9%
1.6%
0.0%0.0%
0.0%
0.0%
0.0%
100.0 %
Load Component Sensible Latent Total
Btu/h Btu/h Btu/hPercent
of Total
Coil Selection Parameters
Coil Entering Air (DB / WB)
Coil Entering Humidity RatioCoil Leaving Air (DB / WB)
Coil Leaving Humidity Ratio
Coil Sensible Load
Coil Total Load
Cooling Supply Air Temperature
Total Cooling Airflow
Resulting Room Relative Humidity
General Engineering Checks
Total Cooling Load
Area / Load
Total Floor Area
Cooling AirflowAirflow / Load
Percent Outdoor Air
Cooling Load Methodology
78.6 / 65.0
55.7 / 53.770.58
58.55
71.40
97.32
57.00
2,854.97
47.11
8.1
232.31
1,884
1.61374.68
15.6
TETD-TA1
cfm/ft
ton
ft/ton
ft
cfm/ton
%
F
gr/lbF
gr/lb
MBh
MBh
cfm
F
%
COOLING COIL SELECTIONCOOLING COIL LOAD INFORMATION
Type - Parallel Fan-Powered VAV, Htg Coil on Plenum Inlet
System - RTU-4
Coil Location - System
Ambient DB/WB/HR: 89 / 76 / 118
Coil Peak Calculation Time: July, hour 11
-857 0 -857 -0.9%Exhaust Heat
Adj Floor Transmission 0 0.00
Adj Floor to Plenum 0 0
Underfloor Sup Heat Pickup
Supply Air Leakage
0 0
0 0
0.0%
0.0%
0
0.0%
0.0%
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 1 Design Cooling Load Report Page 4 of 19LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
29/164
Design Cooling Load Summary
By Setty
LOVETTSVILLE COMMUNITY CENTER
LOUDON COUNTY, VA
Solar Gain
Glass TransmissionWall Transmission
Roof Transmission
Floor Transmission
Partition Transmission
Net Ceiling Load
Lighting
People
Misc. Equipment Loads
Cooling Infiltration
Sub-Total ==>
Ventilation Load
Supply Fan Load
Return Fan Load
Net Duct Heat Pickup
Wall Load to Plenum
Roof Load to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to Plenum
Glass Solar to Plenum
Over/Under Sizing
Total Cooling Loads
44,371
7,5244,694
0
0
0
0
8,601
33,750 15,750
3,840 0
0 0
8,009 12,428
9,270
0
0
992
5,181
2,150
0 0
0
0
0
0 0
0
Reheat at Design
44,371
7,5244,694
0
0
0
0
8,601
9,270
0
992
5,181
2,150
0
0
0
20,437
49,500
3,840
0
0
0
102,778 15,750 118,528
126,589 28,178 154,767
28.7%
4.9%3.0%
0.0%
0.0%
0.0%
0.0%
5.6%
32.0%
2.5%
0.0%
76.6%
13.2%
6.0%
0.0%
0.0%
0.6%
3.3%
1.4%
0.0%
0.0%
0.0%
0.0%
0.0%
100.0 %
Load Component Sensible Latent TotalBtu/h Btu/h Btu/h
Percent
of Total
Coil Selection Parameters
Coil Entering Air (DB / WB)
Coil Entering Humidity RatioCoil Leaving Air (DB / WB)
Coil Leaving Humidity Ratio
Coil Sensible Load
Coil Total Load
Cooling Supply Air Temperature
Total Cooling Airflow
Resulting Room Relative Humidity
General Engineering Checks
Total Cooling Load
Area / Load
Total Floor Area
Cooling Airflow
Airflow / Load
Percent Outdoor Air
Cooling Load Methodology
78.9 / 64.6
57.0 / 54.968.39
61.00
126.59
154.77
57.00
5,214.48
50.14
12.9
174.46
2,250
2.32
404.31
24.2
TETD-TA1
cfm/ft
ton
ft/ton
ft
cfm/ton
%
F
gr/lbF
gr/lb
MBh
MBh
cfm
F
%
COOLING COIL SELECTIONCOOLING COIL LOAD INFORMATION
Room - Gym-1
Zone - Zone - 001
System - RTU-1
Coil Location - Room
Ambient DB/WB/HR: 93 / 77 / 114
Coil Peak Calculation Time: July, hour 17
-1,792 0 -1,792 -1.2%Exhaust Heat
Adj Floor Transmission 0 0.00
Adj Floor to Plenum 0 0
Underfloor Sup Heat Pickup
Supply Air Leakage
0 0
0 0
0.0%
0.0%
0
0.0%
0.0%
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 2 Design Cooling Load Report Page 5 of 19LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
30/164
Design Cooling Load Summary
By Setty
LOVETTSVILLE COMMUNITY CENTER
LOUDON COUNTY, VA
Solar Gain
Glass TransmissionWall Transmission
Roof Transmission
Floor Transmission
Partition Transmission
Net Ceiling Load
Lighting
People
Misc. E ui ment Loads
Cooling Infiltration
Sub-Total ==>
Ventilation Load
Supply Fan Load
Return Fan LoadNet Duct Heat Pickup
Wall Load to Plenum
Roof Load to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to Plenum
Glass Solar to Plenum
Over/Under Sizing
Total Cooling Loads
23,618
2,9152,443
0
0
0
0
8,601
33,750 15,750
3,840 0
0 0
7,401 10,278
6,837
00
486
3,981
2,150
0 0
0
0
0
0 0
0
Reheat at Design
23,618
2,9152,443
0
0
0
0
8,601
6,837
0
486
3,981
2,150
0
0
0
17,679
49,500
3,840
0
0
0
75,166 15,750 90,916
94,163 26,028 120,191
19.7%
2.4%2.0%
0.0%
0.0%
0.0%
0.0%
7.2%
41.2%
3.2%
0.0%
75.6%
14.7%
5.7%
0.0%0.0%0.4%
3.3%
1.8%
0.0%0.0%
0.0%
0.0%
0.0%
100.0 %
Load Component Sensible Latent Total
Btu/h Btu/h Btu/hPercent
of Total
Coil Selection Parameters
Coil Entering Air (DB / WB)
Coil Entering Humidity RatioCoil Leaving Air (DB / WB)
Coil Leaving Humidity Ratio
Coil Sensible Load
Coil Total Load
Cooling Supply Air Temperature
Total Cooling Airflow
Resulting Room Relative Humidity
General Engineering Checks
Total Cooling Load
Area / Load
Total Floor Area
Cooling AirflowAirflow / Load
Percent Outdoor Air
Cooling Load Methodology
79.2 / 64.9
57.0 / 54.769.43
60.25
94.16
120.19
57.00
3,845.97
51.55
10.0
224.64
2,250
1.71383.98
32.8
TETD-TA1
cfm/ft
ton
ft/ton
ft
cfm/ton
%
F
gr/lbF
gr/lb
MBh
MBh
cfm
F
%
COOLING COIL SELECTIONCOOLING COIL LOAD INFORMATION
Room - Gym-2
Zone - Zone - 002
System - RTU-2
Coil Location - Room
Ambient DB/WB/HR: 92 / 76 / 112
Coil Peak Calculation Time: July, hour 18
-1,859 0 -1,859 -1.5%Exhaust Heat
Adj Floor Transmission 0 0.00
Adj Floor to Plenum 0 0
Underfloor Sup Heat Pickup
Supply Air Leakage
0 0
0 0
0.0%
0.0%
0
0.0%
0.0%
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 2 Design Cooling Load Report Page 6 of 19LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
31/164
Design Cooling Load Summary
By Setty
LOVETTSVILLE COMMUNITY CENTER
LOUDON COUNTY, VA
Solar Gain
Glass TransmissionWall Transmission
Roof Transmission
Floor Transmission
Partition Transmission
Net Ceiling Load
Lighting
People
Misc. E ui ment Loads
Cooling Infiltration
Sub-Total ==>
Ventilation Load
Supply Fan Load
Return Fan LoadNet Duct Heat Pickup
Wall Load to Plenum
Roof Load to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to Plenum
Glass Solar to Plenum
Over/Under Sizing
Total Cooling Loads
7,166
1,748868
0
0
0
0
2,683
5,500 4,400
1,198 0
0 0
0 1,935
301
00
262
1,329
671
0 0
0
738
0
0 0
0
Reheat at Design
7,166
1,748868
0
0
0
0
2,683
301
0
262
1,329
671
0
0
738
1,935
9,900
1,198
0
0
0
19,163 4,400 23,563
22,024 6,335 28,359
25.3%
6.2%3.1%
0.0%
0.0%
0.0%
0.0%
9.5%
34.9%
4.2%
0.0%
83.1%
6.8%
1.1%
0.0%0.0%0.9%
4.7%
2.4%
0.0%0.0%
0.0%
2.6%
0.0%
100.0 %
Load Component Sensible Latent Total
Btu/h Btu/h Btu/hPercent
of Total
Coil Selection Parameters
Coil Entering Air (DB / WB)
Coil Entering Humidity RatioCoil Leaving Air (DB / WB)
Coil Leaving Humidity Ratio
Coil Sensible Load
Coil Total Load
Cooling Supply Air Temperature
Total Cooling Airflow
Resulting Room Relative Humidity
General Engineering Checks
Total Cooling Load
Area / Load
Total Floor Area
Cooling AirflowAirflow / Load
Percent Outdoor Air
Cooling Load Methodology
76.6 / 63.1
57.0 / 53.764.95
56.33
22.02
28.36
57.00
1,017.18
53.49
2.6
275.05
702
1.45398.54
29.9
TETD-TA1
cfm/ft
ton
ft/ton
ft
cfm/ton
%
F
gr/lbF
gr/lb
MBh
MBh
cfm
F
%
COOLING COIL SELECTIONCOOLING COIL LOAD INFORMATION
Room - Pre-School Room #1
Zone - Zone - 003
System - WSHP - 1
Coil Location - Room
Ambient DB/WB/HR: 92 / 76 / 112
Coil Peak Calculation Time: July, hour 18
-440 0 -440 -1.6%Exhaust Heat
Adj Floor Transmission 0 0.00
Adj Floor to Plenum 0 0
Underfloor Sup Heat Pickup
Supply Air Leakage
0 0
0 0
0.0%
0.0%
0
0.0%
0.0%
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 2 Design Cooling Load Report Page 7 of 19LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
32/164
Design Cooling Load Summary
By Setty
LOVETTSVILLE COMMUNITY CENTER
LOUDON COUNTY, VA
Solar Gain
Glass TransmissionWall Transmission
Roof Transmission
Floor Transmission
Partition Transmission
Net Ceiling Load
Lighting
People
Misc. E ui ment Loads
Cooling Infiltration
Sub-Total ==>
Ventilation Load
Supply Fan Load
Return Fan LoadNet Duct Heat Pickup
Wall Load to Plenum
Roof Load to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to Plenum
Glass Solar to Plenum
Over/Under Sizing
Total Cooling Loads
12,319
1,8901,152
0
0
0
0
2,683
5,500 4,400
1,198 0
0 0
0 2,149
374
00
349
1,609
671
0 0
0
1
0
0 0
0
Reheat at Design
12,319
1,8901,152
0
0
0
0
2,683
374
0
349
1,609
671
0
0
1
2,149
9,900
1,198
0
0
0
24,743 4,400 29,143
27,241 6,549 33,790
36.5%
5.6%3.4%
0.0%
0.0%
0.0%
0.0%
7.9%
29.3%
3.5%
0.0%
86.2%
6.4%
1.1%
0.0%0.0%1.0%
4.8%
2.0%
0.0%0.0%
0.0%
0.0%
0.0%
100.0 %
Load Component Sensible Latent Total
Btu/h Btu/h Btu/hPercent
of Total
Coil Selection Parameters
Coil Entering Air (DB / WB)
Coil Entering Humidity RatioCoil Leaving Air (DB / WB)
Coil Leaving Humidity Ratio
Coil Sensible Load
Coil Total Load
Cooling Supply Air Temperature
Total Cooling Airflow
Resulting Room Relative Humidity
General Engineering Checks
Total Cooling Load
Area / Load
Total Floor Area
Cooling AirflowAirflow / Load
Percent Outdoor Air
Cooling Load Methodology
76.8 / 63.2
57.0 / 54.264.95
58.16
27.24
33.79
57.00
1,260.53
53.17
3.0
233.63
702
1.80419.51
24.1
TETD-TA1
cfm/ft
ton
ft/ton
ft
cfm/ton
%
F
gr/lbF
gr/lb
MBh
MBh
cfm
F
%
COOLING COIL SELECTIONCOOLING COIL LOAD INFORMATION
Room - Pre-School Room #2
Zone - Zone - 004
System - WSHP - 1
Coil Location - Room
Ambient DB/WB/HR: 93 / 77 / 114
Coil Peak Calculation Time: July, hour 17
-507 0 -507 -1.5%Exhaust Heat
Adj Floor Transmission 0 0.00
Adj Floor to Plenum 0 0
Underfloor Sup Heat Pickup
Supply Air Leakage
0 0
0 0
0.0%
0.0%
0
0.0%
0.0%
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 2 Design Cooling Load Report Page 8 of 19LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
33/164
Design Cooling Load Summary
By Setty
LOVETTSVILLE COMMUNITY CENTER
LOUDON COUNTY, VA
Solar Gain
Glass TransmissionWall Transmission
Roof Transmission
Floor Transmission
Partition Transmission
Net Ceiling Load
Lighting
People
Misc. E ui ment Loads
Cooling Infiltration
Sub-Total ==>
Ventilation Load
Supply Fan Load
Return Fan LoadNet Duct Heat Pickup
Wall Load to Plenum
Roof Load to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to Plenum
Glass Solar to Plenum
Over/Under Sizing
Total Cooling Loads
6,262
356361
0
0
0
0
2,416
5,000 4,000
1,079 0
0 0
0 1,539
237
00
110
646
604
0 0
0
354
0
0 0
0
Reheat at Design
6,262
356361
0
0
0
0
2,416
237
0
110
646
604
0
0
354
1,539
9,000
1,079
0
0
0
15,473 4,000 19,473
17,167 5,539 22,706
27.6%
1.6%1.6%
0.0%
0.0%
0.0%
0.0%
10.6%
39.6%
4.7%
0.0%
85.8%
6.8%
1.0%
0.0%0.0%0.5%
2.8%
2.7%
0.0%0.0%
0.0%
1.6%
0.0%
100.0 %
Load Component Sensible Latent Total
Btu/h Btu/h Btu/hPercent
of Total
Coil Selection Parameters
Coil Entering Air (DB / WB)
Coil Entering Humidity RatioCoil Leaving Air (DB / WB)
Coil Leaving Humidity Ratio
Coil Sensible Load
Coil Total Load
Cooling Supply Air Temperature
Total Cooling Airflow
Resulting Room Relative Humidity
General Engineering Checks
Total Cooling Load
Area / Load
Total Floor Area
Cooling AirflowAirflow / Load
Percent Outdoor Air
Cooling Load Methodology
76.1 / 62.9
57.0 / 53.464.95
54.94
17.17
22.71
57.00
800.82
54.29
2.1
306.28
632
1.27388.09
34.4
TETD-TA1
cfm/ft
ton
ft/ton
ft
cfm/ton
%
F
gr/lbF
gr/lb
MBh
MBh
cfm
F
%
COOLING COIL SELECTIONCOOLING COIL LOAD INFORMATION
Room - Pre-School Room #3
Zone - Zone - 005
System - WSHP - 1
Coil Location - Room
Ambient DB/WB/HR: 83 / 74 / 112
Coil Peak Calculation Time: July, hour 9
-258 0 -258 -1.1%Exhaust Heat
Adj Floor Transmission 0 0.00
Adj Floor to Plenum 0 0
Underfloor Sup Heat Pickup
Supply Air Leakage
0 0
0 0
0.0%
0.0%
0
0.0%
0.0%
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 2 Design Cooling Load Report Page 9 of 19LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
34/164
Design Cooling Load Summary
By Setty
LOVETTSVILLE COMMUNITY CENTER
LOUDON COUNTY, VA
Solar Gain
Glass Transmission
Wall Transmission
Roof Transmission
Floor Transmission
Partition Transmission
Net Ceiling Load
Lighting
People
Misc. E ui ment Loads
Cooling Infiltration
Sub-Total ==>
Ventilation Load
Supply Fan Load
Return Fan LoadNet Duct Heat Pickup
Wall Load to Plenum
Roof Load to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to Plenum
Glass Solar to Plenum
Over/Under Sizing
Total Cooling Loads
7,616
770
602
0
0
0
0
2,416
5,000 4,000
1,079 0
0 0
0 1,605
276
00
183
1,416
604
0 0
0
1
0
0 0
0
Reheat at Design
7,616
770
602
0
0
0
0
2,416
276
0
183
1,416
604
0
0
1
1,605
9,000
1,079
0
0
0
17,483 4,000 21,483
19,505 5,605 25,109
30.3%
3.1%
2.4%
0.0%
0.0%
0.0%
0.0%
9.6%
35.8%
4.3%
0.0%
85.6%
6.4%
1.1%
0.0%0.0%0.7%
5.6%
2.4%
0.0%0.0%
0.0%
0.0%
0.0%
100.0 %
Load Component Sensible Latent Total
Btu/h Btu/h Btu/hPercent
of Total
Coil Selection Parameters
Coil Entering Air (DB / WB)
Coil Entering Humidity Ratio
Coil Leaving Air (DB / WB)
Coil Leaving Humidity Ratio
Coil Sensible Load
Coil Total Load
Cooling Supply Air Temperature
Total Cooling Airflow
Resulting Room Relative Humidity
General Engineering Checks
Total Cooling Load
Area / Load
Total Floor Area
Cooling AirflowAirflow / Load
Percent Outdoor Air
Cooling Load Methodology
76.8 / 63.2
57.0 / 54.1
64.95
57.88
19.50
25.11
57.00
930.16
52.68
2.3
279.18
632
1.47410.89
29.7
TETD-TA1
cfm/ft
ton
ft/ton
ft
cfm/ton
%
F
gr/lb
F
gr/lb
MBh
MBh
cfm
F
%
COOLING COIL SELECTIONCOOLING COIL LOAD INFORMATION
Room - Pre-School Room #4
Zone - Zone - 006
System - WSHP - 1
Coil Location - Room
Ambient DB/WB/HR: 91 / 75 / 106
Coil Peak Calculation Time: August, hour 16
-458 0 -458 -1.8%Exhaust Heat
Adj Floor Transmission 0 0.00
Adj Floor to Plenum 0 0
Underfloor Sup Heat Pickup
Supply Air Leakage
0 0
0 0
0.0%
0.0%
0
0.0%
0.0%
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 2 Design Cooling Load Report Page 10 of 19LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
35/164
Design Cooling Load Summary
By Setty
LOVETTSVILLE COMMUNITY CENTER
LOUDON COUNTY, VA
Solar Gain
Glass Transmission
Wall Transmission
Roof Transmission
Floor Transmission
Partition Transmission
Net Ceiling Load
Lighting
People
Misc. E ui ment Loads
Cooling Infiltration
Sub-Total ==>
Ventilation Load
Supply Fan Load
Return Fan LoadNet Duct Heat Pickup
Wall Load to Plenum
Roof Load to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to Plenum
Glass Solar to Plenum
Over/Under Sizing
Total Cooling Loads
1,871
281
155
0
0
0
0
956
0 0
0 0
0 0
0 596
57
00
47
1,546
239
0 0
0
1
0
0 0
0
Reheat at Design
1,871
281
155
0
0
0
0
956
57
0
47
1,546
239
0
0
1
596
0
0
0
0
0
3,262 0 3,262
5,083 596 5,679
32.9%
5.0%
2.7%
0.0%
0.0%
0.0%
0.0%
16.8%
0.0%
0.0%
0.0%
57.4%
10.5%
1.0%
0.0%0.0%0.8%
27.2%
4.2%
0.0%0.0%
0.0%
0.0%
0.0%
100.0 %
Load Component Sensible Latent Total
Btu/h Btu/h Btu/hPercent
of Total
Coil Selection Parameters
Coil Entering Air (DB / WB)
Coil Entering Humidity Ratio
Coil Leaving Air (DB / WB)
Coil Leaving Humidity Ratio
Coil Sensible Load
Coil Total Load
Cooling Supply Air Temperature
Total Cooling Airflow
Resulting Room Relative Humidity
General Engineering Checks
Total Cooling Load
Area / Load
Total Floor Area
Cooling AirflowAirflow / Load
Percent Outdoor Air
Cooling Load Methodology
76.8 / 63.2
57.0 / 53.2
64.95
54.24
5.08
5.68
57.00
192.02
45.44
0.5
1,401.84
700
0.27384.55
21.9
TETD-TA1
cfm/ft
ton
ft/ton
ft
cfm/ton
%
F
gr/lb
F
gr/lb
MBh
MBh
cfm
F
%
COOLING COIL SELECTIONCOOLING COIL LOAD INFORMATION
Room - Corridor
Zone - Zone - 007
System - WSHP - 1
Coil Location - Room
Ambient DB/WB/HR: 93 / 77 / 114
Coil Peak Calculation Time: July, hour 17
-70 0 -70 -1.2%Exhaust Heat
Adj Floor Transmission 0 0.00
Adj Floor to Plenum 0 0
Underfloor Sup Heat Pickup
Supply Air Leakage
0 0
0 0
0.0%
0.0%
0
0.0%
0.0%
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 2 Design Cooling Load Report Page 11 of 19LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
36/164
Design Cooling Load Summary
By Setty
LOVETTSVILLE COMMUNITY CENTER
LOUDON COUNTY, VA
Solar Gain
Glass Transmission
Wall Transmission
Roof Transmission
Floor Transmission
Partition Transmission
Net Ceiling Load
Lighting
People
Misc. E ui ment Loads
Cooling Infiltration
Sub-Total ==>
Ventilation Load
Supply Fan Load
Return Fan LoadNet Duct Heat Pickup
Wall Load to Plenum
Roof Load to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to Plenum
Glass Solar to Plenum
Over/Under Sizing
Total Cooling Loads
12,603
939
844
0
0
0
0
2,695
5,500 4,400
1,203 0
0 0
0 1,971
355
00
256
968
674
0 0
0
1
0
0 0
0
Reheat at Design
12,603
939
844
0
0
0
0
2,695
355
0
256
968
674
0
0
1
1,971
9,900
1,203
0
0
0
23,784 4,400 28,184
25,666 6,371 32,037
39.3%
2.9%
2.6%
0.0%
0.0%
0.0%
0.0%
8.4%
30.9%
3.8%
0.0%
88.0%
6.2%
1.1%
0.0%0.0%0.8%
3.0%
2.1%
0.0%0.0%
0.0%
0.0%
0.0%
100.0 %
Load Component Sensible Latent Total
Btu/h Btu/h Btu/hPercent
of Total
Coil Selection Parameters
Coil Entering Air (DB / WB)
Coil Entering Humidity Ratio
Coil Leaving Air (DB / WB)
Coil Leaving Humidity Ratio
Coil Sensible Load
Coil Total Load
Cooling Supply Air Temperature
Total Cooling Airflow
Resulting Room Relative Humidity
General Engineering Checks
Total Cooling Load
Area / Load
Total Floor Area
Cooling AirflowAirflow / Load
Percent Outdoor Air
Cooling Load Methodology
76.4 / 63.0
57.0 / 54.0
64.95
57.61
25.67
32.04
57.00
1,197.59
53.76
2.9
246.59
705
1.70418.89
25.4
TETD-TA1
cfm/ft
ton
ft/ton
ft
cfm/ton
%
F
gr/lb
F
gr/lb
MBh
MBh
cfm
F
%
COOLING COIL SELECTIONCOOLING COIL LOAD INFORMATION
Room - Childcare#5
Zone - Zone - 008
System - WSHP - 1
Coil Location - Room
Ambient DB/WB/HR: 86 / 75 / 114
Coil Peak Calculation Time: July, hour 10
-372 0 -372 -1.2%Exhaust Heat
Adj Floor Transmission 0 0.00
Adj Floor to Plenum 0 0
Underfloor Sup Heat Pickup
Supply Air Leakage
0 0
0 0
0.0%
0.0%
0
0.0%
0.0%
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 2 Design Cooling Load Report Page 12 of 19LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
37/164
Design Cooling Load Summary
By Setty
LOVETTSVILLE COMMUNITY CENTER
LOUDON COUNTY, VA
Solar Gain
Glass Transmission
Wall Transmission
Roof Transmission
Floor Transmission
Partition Transmission
Net Ceiling Load
Lighting
People
Misc. E ui ment Loads
Cooling Infiltration
Sub-Total ==>
Ventilation Load
Supply Fan Load
Return Fan LoadNet Duct Heat Pickup
Wall Load to Plenum
Roof Load to Plenum
Lighting Load to Plenum
Misc. Equip. Load to Plenum
Glass Transmission to Plenum
Glass Solar to Plenum
Over/Under Sizing
Total Cooling Loads
5,656
532
447
0
0
0
0
1,831
6,000 4,800
817 0
0 0
0 1,896
252
00
136
953
458
0 0
0
1
0
0 0
0
Reheat at Design
5,656
532
447
0
0
0
0
1,831
252
0
136
953
458
0
0
1
1,896
10,800
817
0
0
0
15,283 4,800 20,083
16,643 6,696 23,339
24.2%
2.3%
1.9%
0.0%
0.0%
0.0%
0.0%
7.8%
46.3%
3.5%
0.0%
86.1%
8.1%
1.1%
0.0%0.0%0.6%
4.1%
2.0%
0.0%0.0%
0.0%
0.0%
0.0%
100.0 %
Load Component Sensible Latent Total
Btu/h Btu/h Btu/hPercent
of Total
Coil Selection Parameters
Coil Entering Air (DB / WB)
Coil Entering Humidity Ratio
Coil Leaving Air (DB / WB)
Coil Leaving Humidity Ratio
Coil Sensible Load
Coil Total Load
Cooling Supply Air Temperature
Total Cooling Airflow
Resulting Room Relative Humidity
General Engineering Checks
Total Cooling Load
Area / Load
Total Floor Area
Cooling AirflowAirflow / Load
Percent Outdoor Air
Cooling Load Methodology
76.6 / 63.1
57.0 / 53.9
64.95
56.92
16.64
23.34
57.00
848.87
54.75
2.1
224.92
479
1.77398.60
35.0
TETD-TA1
cfm/ft
ton
ft/ton
ft
cfm/ton
%
F
gr/lb
F
gr/lb
MBh
MBh
cfm
F
%
COOLING COIL SELECTIONCOOLING COIL LOAD INFORMATION
Room - Adultroom#6
Zone - Zone - 009
System - WSHP - 1
Coil Location - Room
Ambient DB/WB/HR: 89 / 76 / 118
Coil Peak Calculation Time: July, hour 11
-439 0 -439 -1.9%Exhaust Heat
Adj Floor Transmission 0 0.00
Adj Floor to Plenum 0 0
Underfloor Sup Heat Pickup
Supply Air Leakage
0 0
0 0
0.0%
0.0%
0
0.0%
0.0%
TRACE 700 v6.3 calculated at 05:01 PM on 04/10/2014Project Name: LOVETTSVILLE COMMUNITY CENTER
Dataset Name: Alternative - 2 Design Cooling Load Report Page 13 of 19LCC.TRC
8/21/2019 140415 LCC Revised Mechanical Systems Analysis Report
38/164
Design Cooling Load Summary
By Setty
LOVETTSVILLE COMMUNITY CENTER
LOUDON COUNTY, VA
Solar Gain
Glass Transmission
Wall Transmission
Roof Transmission
Floor Transm