DIMENSION RE UNEI INST L TIIFOTOVOLT ICE UTONOME
Buzau Madalina Mihaela
Dumitrascu Mirela Mihaela
5/23/2018 135608615 Dimensionarea Unei Instalatii Fotovoltaice Autonome - slidepdf....
http:///reader/full/135608615-dimensionarea-unei-instalatii-fotovoltaice-auton
Cuprins
1.Sisteme fotovoltaice(PV) autonome1.1.Structura unui sistem fotovoltaic autonom
1.1.1Estimare consumului orar
1.1.21.2 Bateriile
1.2.1 Alegerea tipului de baterie
1.2.2 Tipuri de baterii
1.2.3 Durata de viata a bateriilor
1.2.4 Dimensionarea bateriilor1.2.5 Probleme des intalnite
1.3 Regulatorul de sarcina
1.4 Dimensionarea panourilor solare
1.5 Invertorul
1.6 Dimensionarea cablurilor
1.7 Beneficiile si dezavantajele energiei solare
5/23/2018 135608615 Dimensionarea Unei Instalatii Fotovoltaice Autonome - slidepdf....
http:///reader/full/135608615-dimensionarea-unei-instalatii-fotovoltaice-auton
1.Sisteme fotovoltaice(PV) autonome
1.1.Structura unui sistem fotovoltaic autonom
Un sistem fotovoltaic autonom este constituit din urmatoarele componente
principale:
Panourile fotovoltaice
Invertorul
Regulatorul de sarcina Bateriile de stocare
Consumatorii electrici
5/23/2018 135608615 Dimensionarea Unei Instalatii Fotovoltaice Autonome - slidepdf....
http:///reader/full/135608615-dimensionarea-unei-instalatii-fotovoltaice-auton
Invertoarele utilizate in cazul sistemelor PV autonome(care au rolul de a converti
curentul continuu in curent alternativ) difera esential de invertoarele utilizate
pentru sistemele fotovoltaice conectate la retea.Exista sisteme in care curentul
continuu este utilizat direct,fara baterii;tensiunile sistemului(tensiunea la baterie)
sau tensiunea sarcinii in cazul sistemului PV fara baterie este :12 V c.c.,24 V c.c
sau 48 V c.c.
1.1.1Estimare consumului orar
5/23/2018 135608615 Dimensionarea Unei Instalatii Fotovoltaice Autonome - slidepdf....
http:///reader/full/135608615-dimensionarea-unei-instalatii-fotovoltaice-auton
1.2 Bateriile
-cele mai vulnerabile parti ale sistemului
-inmagazineaza energie-E=U*I*h
-O baterie de 12 V 100Ah inmagazineaza pana la 1200Wh.Aceasta baterie este
suficienta pentru a alimenta un bec de 100W pentru 120 de ore
1.2.1 Alegerea tipului de baterie
Se face in functie de :
5/23/2018 135608615 Dimensionarea Unei Instalatii Fotovoltaice Autonome - slidepdf....
http:///reader/full/135608615-dimensionarea-unei-instalatii-fotovoltaice-auton
-cost
-durata de viata
-gradul de dificultate al intretinerii
1.2.2 Tipuri de baterii
1.2.3 Durata de viata a bateriilor
Efectele temperaturii asupra duratei de viata a bateriilor
Desi capacitatea bateriei la temperaturi mari este mai mare,durata de viata a ei este
scurtata,la fiecare 10 Cdupa 25-ea este injumatatita.
Gradul de descarcare al bateriilor(DOD) si durata de viata
Pentru o utilizare cat mai indelungata ,nu trebuie sa le descarcam prea mult(maxim 20%).
Plumb NiCd NiMH Li-ion
Energie/greutate 30-40 40-60 30-80 160 Wh/kg
Energie/marime 60-75 50-150 140-300 270 Wh/L
Putere/greutate 180 150 250-1000 1800 W/Kg
Eficienta incarcare-
descarcare
70%-
92%
70%-
90%
66% 99.90%
Auto-descarcare 3%-20%
10% 30% 5%-10% luna
Durata de viata(nr. de
cicluri)
500-
800
2000 500-1000 ~1200 cicluri
Tensiunea/pe celula
nominala
2.105 1.2 1.2 3.6-3.7 Volti
5/23/2018 135608615 Dimensionarea Unei Instalatii Fotovoltaice Autonome - slidepdf....
http:///reader/full/135608615-dimensionarea-unei-instalatii-fotovoltaice-auton
1.2.4 Dimensionarea bateriilor
Selectarea gradului de descarcare........80%
Selectarea numarului de zile(pentru care bateria inmagazineaza
energie).........4
MarimeaBateriei=Numarul de zile x Sarcina x 100 / DOD = 4x492x100/80=2460Wh
Alegerea tensiunii bateriei............................12V
CapacitateaBateriei=MarimeaBateriei/Tensiunea bateriei=2460/12=205Ah
Selectarea tipului de baterie.....................110Ah 12V
Prin urmare avem nevoie de.2 baterii puse in paralel ([email protected])
1.2.5 Probleme des intalnite
-Stratificarea electrolitului
-Celule au sarcini diferite
-Pierderea de electrolit
5/23/2018 135608615 Dimensionarea Unei Instalatii Fotovoltaice Autonome - slidepdf....
http:///reader/full/135608615-dimensionarea-unei-instalatii-fotovoltaice-auton
1.3 Regulatorul de sarcina
Se pot distinge cateva tipuri de regulatoare de incarcare pentru sistemele PV :
Regulatoare seriale
Prin utilizarea unui astfel de regulator,conexiunea dintre un generator solar si o
unitate de stocare a energiei este intrerupta atunci cand limita de incarcare este
atinsa.Se pot folosi pentru deconectare atat relee cat si tranzistoare bipolare sau
MOFSET.Principiul de reglare seriala provine din tehnologia clasica de incarcare
si este utilizata si in dispozitivele de incarcare conectate la retea.
Atunci cand tensiunea scade sub pragul descarcarii severe,sarcina este deconectata
de la baterie pentru ca aceasta sa fie protejata.
Regulatoare unt(scurt-circuit)
Atunci cand se valorifica proprietatile specifice ale celulelor solare,se poate aplicaun principiu de reglare care sa evite dezavantajele reglarii seriale.Astfel,in circuitul
de mai jos,generatorul solar este pur si simplu scurtcircuitat printr-un comutator
electronic,atunci cand bateria este complet incarcata.Totusi,aceasta pierdere un
afecteaza balanta energetica a sistemului fotovoltaic,deoarece apare doar atunci
cand bateria este incarcata complet si energia solara nu mai este necesara oricum.
5/23/2018 135608615 Dimensionarea Unei Instalatii Fotovoltaice Autonome - slidepdf....
http:///reader/full/135608615-dimensionarea-unei-instalatii-fotovoltaice-auton
Spre deosebire de majoritatea regulatoarelor seriale,aceasta procedura functioneaza
sigur chiar si atunci cand capacitatea bateriei este complet epuizata(tensiune mai
mica de 9V),deoarece comutatorul de scurt-circuit un trebuie activat decat dupa
reincarcarea bateriei.Este necesara o dioda de blocare pentru a preveni
scurtcircuitarea bateriei.In timpul noptii aceasta va servi si impotriva descarcarii
prin generatorul solar.
Regulatoare PWM
Aceste regulatoare utilizeaza o tehnica de comutare de mare frecventa.Regulatorul
comuta rapid(deschis/inchis) dispozitivul de control.Cand bateriile sunt descarcate
atunci unitatea este complet pornita.Pe masura ce bateria se apropie de starea de
incarcare completa unitatea va incepe sa porneasca si sa opreasca dispozitivul de
control in proportie cu nivelul de incarcare necesar.Cand bateria este complet
incarcata,curentul catre baterie va fi zero.In sistemele PV,regulatorul PWM este
montat in serie cu modulele fotovoltaice.La sistemele hibride cu turbina eoliana
si/sau micro/hidro,aceasta tehnica utilizeaza o sarcina unt(de intrerupere)ce
absoarbe o mare parte din energia provenita de la generator pentru a redirectiona
eventualul exces de energie catre baterii(permanent trebuie sa existe o sarcina pegenerator,pentru a preveni supra-viteza turbinei).
5/23/2018 135608615 Dimensionarea Unei Instalatii Fotovoltaice Autonome - slidepdf....
http:///reader/full/135608615-dimensionarea-unei-instalatii-fotovoltaice-auton
Protectia la suprasarcina
Un circuit este suprasolicitat atunci cand curentul din acel circuit este mai mare
decat cel nominal(pe care-l poate suporta in conditii de siguranta).Aceasta poate
produce supra-incalzirea si poate deveni chiar un pericol de incendiu.Suprasarcinapoate fi cauzata de o defectiune(scurt-circuit) al cablajului,sau de un aparat ce
functioneaza defectuos(ex:o pompa de apa inghetata).Anumite regulatoare de
incarcare au incorporata protectia la suprasarcina,care se reseteaza de regula prin
apasarea unui buton.
Regulatoare moderne de incarcare
Ultima generatie de regulatoare solare de incarcare impune standarde noi in
tehnologia fotovoltaica.Un astfel de regulator este echipat cu un circuit integrat(ASIC) creat special pentru utilizari in tehnologia fotovoltaica.Principalele
functiuni ale acestuia sunt:compensare interna a temperaturii;algoritm de incarcare
cu auto-invatare;determinarea starii de incarcare;protectie dinamica la
suprasarcina;adaptare automata a tensiunii;diagnosticarea stariii de
functionare;indicarea starii de incarcare;protectie la supra-descarcare.Programul
sau se regleaza dupa capacitatea si vechimea bateriei.Starea de incarcare este baza
tuturor functiilor de control si reglare.Elementele de afisare dau informatii despre
starea de incarcare,avarii si despre dispozitivele de baza.
1.4 Dimensionarea panourilor solare
EnergiaZilnicaPotentiala(Wh)=H x baterie x PR x Pmaxim
Pmaxim=EnergiaZilnicaPotentiala(Wh)
HxbateriexPR
unde:
H=radiatia in kWh/zi
baterie=randamentul bateriei;de obicei 0.8
PR(performance ratio)=Randamentul total0.8
Pmaxim=puterea panoului solar atunci cand iradiatia este maxima
5/23/2018 135608615 Dimensionarea Unei Instalatii Fotovoltaice Autonome - slidepdf....
http:///reader/full/135608615-dimensionarea-unei-instalatii-fotovoltaice-auton
Date radiatie(site)
http://re.jrc.ec.europa.eu/pvgis/apps3/pvest.php#
Photovoltaic Geographical Information System
Incident global irradiation for the chosen locationLocation: 4426'39" North, 264'4" East, Elevation: 0 m a.s.l.,
Optimal inclination angle is: 35 degreesAnnual irradiation deficit due to shadowing (horizontal): 0.0 %
Month Hh Hopt H(90) Iopt T24h NDD
Jan 1330 2170 2200 64 -1.3 580Feb 2030 2930 2660 56 1.8 420
Mar 3140 3870 2940 43 6.0 331
Apr 4480 4870 2960 28 11.8 114
May 5650 5560 2790 15 17.7 16
Jun 5980 5630 2550 11 21.5 1
Jul 6090 5880 2760 12 23.5 0
Aug 5540 5860 3260 25 23.0 5
Sep 4260 5230 3730 41 17.5 80
Oct 2880 4190 3700 55 12.3 280
Nov 1500 2330 2280 61 6.3 462
Dec 1090 1790 1840 65 0.2 598
Year 3670 4200 2810 35 11.7 2887
Hh: Irradiation on horizontal plane (Wh/m2)\
Hopt: Irradiation on optimally inclined plane (Wh/m2) H(90): Irradiation on plane at angle: 90deg.
(Wh/m2) Iopt: Optimal inclination (deg.)T24h: 24 hour average of temperature (C)
NDD: Number of heating degree-days (-)
5/23/2018 135608615 Dimensionarea Unei Instalatii Fotovoltaice Autonome - slidepdf....
http:///reader/full/135608615-dimensionarea-unei-instalatii-fotovoltaice-auton
5/23/2018 135608615 Dimensionarea Unei Instalatii Fotovoltaice Autonome - slidepdf....
http:///reader/full/135608615-dimensionarea-unei-instalatii-fotovoltaice-auton
1.5 Invertorul
O componenta foarte importanta a acestor sisteme o reprezinta invertorul. Invertorul
conectarea mai multorpanouri solarein baterii, sisteme electrice si / sau alimentari cu
unei retele. Cea mai importanta sarcina a invertorului este aceea de a transforma curent
alternativ.
Majoritatea invertoarelor au un rating de eficienta in jur de 90 la suta. Noile
descoperiri in cadrul tehnologiei invertoarelor ar putea reduce costurile si ar putea
creste eficienta pana in jurul a 98 la suta. Trecand la capitolul costuri, din pacate
invertoarele nu sunt tocmai ieftine. Preturile acestora sunt stabilite in functie de
capacitate ( cata energie pot pompa ), asadar tineti minte acest lucru atunci candva decideti sa cumparati unul. Una dintre problemele invertoarele ar fi aceea ca
este posibil sa interfereze cu radiourile sau telefoanele mobile.
Printre facilitatile pe care le pot avea invertoarele se numara: protectie la scurt-
circuit pe intrare si iesire, protectie la suprasarcina si supraincalzire, protectie la
supravoltare si subvoltare, afisarea puterii consumate si a tensiunii bateriei etc.
Invertoarele au ca si caracteristica principalaputerea nominala, care reprezinta
consumul maxim admis la iesirea de 230 V. O alta caracteristica importanta a unui
invertor este forma undei de iesire. Astfel, exista invertoare cu unda sinusoidala
pura sau cu unda sinusoidala modificata. Invertoarele cu unda sinusoidala
modificata sunt mai accesibile ca pret, dar nu se preteaza la echipamente electrice
sau electronice care folosesc motoare alimentate direct la 230 V, pentru care se
utilizeaza invertoare cu unda sinusoidala pura. Modul de conectare al unui
invertor intr-un sistem solar este exemplificat prin figura urmatoare :
5/23/2018 135608615 Dimensionarea Unei Instalatii Fotovoltaice Autonome - slidepdf....
http:///reader/full/135608615-dimensionarea-unei-instalatii-fotovoltaice-auton
Probabilitatea pierderii de sarcina (Loss of load Probability LOLP)
5/23/2018 135608615 Dimensionarea Unei Instalatii Fotovoltaice Autonome - slidepdf....
http:///reader/full/135608615-dimensionarea-unei-instalatii-fotovoltaice-auton
1.6 Dimensionarea cablurilor
Aria sectiunii(mm) Curentul maxim(A) Curentul redus(A) Rezistenta m/metru
0.5 4.25 3.0 37
0.75 6.4 3.5 25
1.0 8.5 5.0 191.5 12.75 8.0 13
2.0 17.0 10.0 9
2.5 21.0 12.5 7.5
3.0 25.5 15.5 6
4.0 28.5 17.0 4.5
6.0 41.5 25.0 3
Caderea de tensiune=Rezistenta x Curent x Lungime in metri(cablu)
nu trebuie sa depaseasca 5% ,in curentul continuu
un trebuie sa depaseasca 1% ,in curentul alternativ
Exista totusi o metoda mai simpla pentru a calcula caderile de tensiune . Caderea de
tensiune (Uc) pentru o pereche de conductoare este de data de relatia:
Uc=0.04xLxI
unde: L=lungimea cablurilor in metrii
I=intensitatea curentului in amperi
A=aria sectiunii in mmIn general pentru o eficienta cat mai buna si o pierdere de energie cat mai mica
caderea de tensiune ar trebui sa fie mai mica de 5 % decat tensiunea sistemului. Sa
presupunem ca tensiunea sistemului este de 12V, lungimea cablurilor =10A iar
intensitatea curentului este de 10A.
Aria minima a sectiunii conductorului este de:
A=0.04x50mx10A = 33 mm .Acesta este un cablu costisitor!
0,6V(5%12V)
Daca acelasi cablu este dimensionat pentru o tensiune mai mare (24V) curentul esteinjumatatit pentru aceeasi putere ,caderea de tensiune permisa va fi acum de 1.2V.
A=0.04x50mx5A =8.3 mm .O patrime din cablul anterior!
1.2V
Cu cat puterea si/sau distanta ce trebuiesc transmise,se maresc ,avem nevoie de o
tensiune mai mare pentru a minimiza caderile de tensiune si marimea cablurilor.
5/23/2018 135608615 Dimensionarea Unei Instalatii Fotovoltaice Autonome - slidepdf....
http:///reader/full/135608615-dimensionarea-unei-instalatii-fotovoltaice-auton
1.7 Beneficiile si dezavantajele energiei solare
AVANTAJE
Energia solara este o resursa regenerabila in adevaratul sens al cuvantului. Nu va
disparea decat daca soarele va inceta sa arda, caz in care nu va mai exista deloc
viata pe planeta noastra.Panourile solare nu produc nicio poluare in timpul
functionarii, spre deosebire de reactoarele nucleare si instalatiile termice. In timp ce
primele cauzeaza probleme legate de evacuarea deseurilor nucleare, cele din urma
produc fum daunator si cenusa.Productia de energie solara de catre panourile solare
sau prin alte mijloace ce utilizeaza energia solara este lipsita de zgomot, spre
deosebire de alte metode.Montarea panourilor solare este facila si eficienta din
punct de vedere al costurilor. Mai mult, acestea devin utile in situatiile in care
retelele locale nu functioneaza, cum ar fi in spatiu, spre exemplu.Spre deosebire de
rezervele de ulei si carbune, energia solara este disponibila in toate zonele planetei,
nefiind concentrata intr-o singura parte. Prin urmare, recoltarea energiei solare
poate fi realizata aproape in orice loc.Unitatile generatoare de energie solare sunt
compacte si flexibile ca proiectare, ceea ce inseamna ca pot fi instalate aproape in
orice tip de spatiu, fara a va face griji ca trebuie sa construiti locatii speciale.Initial,
panourile solare costa mult, dar generarea gratuita de energie, de-a lungul anilor,
duce la un cost global extrem de eficient. In plus, panourile solare presupun mai
putina mentenanta si monitorizare.
DEZAVANTAJE
Costurile initiale pentru componente sunt ridicate. Acest lucru face ca instalarea
unui panou pentru captarea energiei solare sa coste destul de mult.Celulele solare
functioneaza doar in timpul zilei, iar eficienta lor este redusa pe parcursul zilelor
mohorate si innorate. Din acest motiv, sistemul trebuie sa fie dezvoltat si eficient,
beneficiind si de un sistem de stocare a energiei.Poluarea poate cauza efecte adverseasupra eficientei panourilor solare. Eficienta poate fi redusa, celulele solare fiind
nepotrivite pentru anumite zone.Desi aproape orice locatie primeste lumina soarelui,
nu orice locatie este fezabila pentru panourile solare.Crearea unor instalatii mari
pentru energia solara este costisitoare si dificila din punct de vedere al gasirii
locatiei.Energia solara nu este o energie concentrata precum combustibilii fosili.
5/23/2018 135608615 Dimensionarea Unei Instalatii Fotovoltaice Autonome - slidepdf....
http:///reader/full/135608615-dimensionarea-unei-instalatii-fotovoltaice-auton
Prin urmare, utilizarea ei in cazul automobilelor sau altor forme mecanizate este
dificila, daca luam in considerare rezultatul energetic.Decizia alegerii unui astfel de
sistem depinde de necesitatile si posibilitatile fiecarei persoane in parte, de locatia in
care va aflati si mai ales de banii de care dispuneti. Este o investitie folositoare, dar
si costisitoare .
5/23/2018 135608615 Dimensionarea Unei Instalatii Fotovoltaice Autonome - slidepdf....
http:///reader/full/135608615-dimensionarea-unei-instalatii-fotovoltaice-auton
Bibliografie:
Fizica si tehnologia celulelor solare si sistemelor fotovoltaice(seria monografica-
Nanotehnologiile si provocarile dezvoltarii durabile)-Laurentiu FARA (coordonator
si editor),Mihai Razvan MITROI(editor),Corneliu CINCU,Vladimir IANCU,SilvianFARA,Catalin ZAHARIA,Dumitru FINTA,Dragos COMANECI,Mihai
IANCU,Editura Academiei Oamenilor de Stiinta din Romania
Electricity from Sunlight-An Introduction to Photovoltaics-Paul A. Lynn,Editura
WILEY
Off-grid solar panels systems,short course-Centre for Alternative Technology,
Wales,UK