2
12-128 For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E January 2001 Molded Case Circuit Breakers 12 Earth Leakage Circuit Protectors Vol. 1, Ref. No. [0594] Table 12-200. K-Frame Earth Leakage Ground Fault Breakers UL 489 and UL 1053 Note: Instruction Leaflet/FRED Number 29C118 or S.A.29A.03.S.E Table 12-201. Optional K-Frame Line and Load Terminals – Order Separately 1 Package of 3 terminals. 2 Package of 4 terminals. Table 12-202. F-Frame HMCP with Earth Leakage Ground Fault Table 12-202. F-Frame HMCP with Earth Leakage Ground Fault (Continued) Table 12-203. J and K-Frame HMCP with Earth Leakage Ground Fault Amperes 35 kA at 480V AC 65 kA at 480V AC 100 kA at 480V AC 3-Pole 4-Pole 3-Pole 4-Pole 3-Pole 4-Pole Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $ 200 225 250 300 350 400 ELKD3200 ELKD3225 ELKD3250 ELKD3300 ELKD3350 ELKD3400 4,615.00 4,615.00 4,615.00 4,615.00 4,615.00 4,615.00 ELKD4200 ELKD4225 ELKD4250 ELKD4300 ELKD4350 ELKD4400 6,150.00 6,150.00 6,150.00 6,150.00 6,150.00 6,150.00 ELHKD3200 ELHKD3225 ELHKD3250 ELHKD3300 ELHKD3350 ELHKD3400 7,190.00 7,190.00 7,190.00 7,190.00 7,190.00 7,190.00 ELHKD4200 ELHKD4225 ELHKD4250 ELHKD4300 ELHKD4350 ELHKD4400 8,330.00 8,330.00 8,330.00 8,330.00 8,330.00 8,330.00 ELKDC3200 ELKDC3225 ELKDC3250 ELKDC3300 ELKDC3350 ELKDC3400 7,330.00 7,330.00 7,330.00 7,330.00 7,330.00 7,330.00 ELKDC4200 ELKDC4225 ELKDC4250 ELKDC4300 ELKDC4350 ELKDC4400 10,290.00 10,290.00 10,290.00 10,290.00 10,290.00 10,290.00 Wire Type (Number) Range of Conductors Terminal Material Catalog Number Price U.S. $ Cu/Al Cu/Al (2) 250 kcmil (1) 500 kcmil Aluminum Aluminum 3TA401K 1 66.00 Cu/Al Cu/Al (2) 250 kcmil (1) 500 kcmil Aluminum Aluminum 4TA401K 2 76.00 Cu Cu Cu (1) 3 – 350 kcmil (1) 3 – 350 kcmil (1) 250 – 500 kcmil Copper Copper Copper T300K T300K T350K 29.50 29.50 29.50 Cu Cu Cu (1) 250 – 500 kcmil (1) 3/0 – 250 kcmil (1) 3/0 – 250 kcmil Copper Copper Copper T350K 3T400K 1 4T400K 2 29.50 76.00 76.00 Continuous Amperes 3-Pole Catalog Number Price U.S. $ 3 7 15 ELHMCP003A0C ELHMCP007C0C ELHMCP015E0C 1,225.00 1,225.00 1,225.00 25 30 50 ELHMCP025X0C ELHMCP030H1C ELHMCP050K2C 1,295.00 1,295.00 1,645.00 70 100 150 150 ELHMCP070M2C ELHMCP100R3C ELHMCP150T4C ELHMCP150U4C 1,645.00 1,645.00 2,335.00 2,335.00 3 7 15 ELHMCP003A0LC ELHMCP007C0LC ELHMCP015E0LC 1,225.00 1,225.00 1,225.00 25 30 70 ELHMCP025D0C ELHMCP030H1LC ELHMCP070J2C 1,295.00 1,295.00 1,645.00 Continuous Amperes 3-Pole Catalog Number Price U.S. $ 100 50 ELHMCP100L3C ELHMCP050G2C 1,645.00 1,645.00 70 100 ELHMCP070J2C ELHMCP100K3C 1,645.00 1,645.00 HMCPs for Application with Motor Starters Equipped with Electronic Overload Relays 3 7 15 ELHMCPS003A0C ELHMCPS007C0C ELHMCPS015E0C 1,225.00 1,225.00 1,225.00 30 50 100 ELHMCPS030H1C ELHMCPS050K2C ELHMCPS100R3C 1,295.00 1,645.00 1,645.00 150 150 ELHMCPS150T4C ELHMCPS150U4C 2,335.00 2,335.00 Continuous Amperes 3-Pole Catalog Number Price U.S. $ 250 ELHMCP250A5 ELHMCP250C5 ELHMCP250D5 ELHMCP250F5 ELHMCP250G5 ELHMCP250J5 ELHMCP250K5 ELHMCP250L5 ELHMCP250W5 3,230.00 3,230.00 3,230.00 3,230.00 3,230.00 3,230.00 3,230.00 3,230.00 3,230.00 400 ELHMCP400D5 ELHMCP400F5 ELHMCP400G5 ELHMCP400J5 ELHMCP400K5 5,250.00 5,250.00 5,250.00 5,250.00 5,250.00 Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . CB-2

12-128 Molded Case Circuit Breakers Earth Leakage …...fault relay built-in. This technique allows for protection sensitivities down to the 30 milliampere level. Leakage breakers

  • Upload
    others

  • View
    11

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 12-128 Molded Case Circuit Breakers Earth Leakage …...fault relay built-in. This technique allows for protection sensitivities down to the 30 milliampere level. Leakage breakers

12-128

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E

January 2001

Molded Case Circuit Breakers

12

Earth Leakage Circuit ProtectorsVol. 1, Ref. No. [0594]

Table 12-200. K-Frame Earth Leakage Ground Fault Breakers UL 489 and UL 1053

Note: Instruction Leaflet/FRED Number 29C118 or S.A.29A.03.S.E

Table 12-201. Optional K-Frame Line and Load Terminals – Order Separately

1 Package of 3 terminals.2 Package of 4 terminals.

Table 12-202. F-Frame HMCP with Earth Leakage Ground Fault

Table 12-202. F-Frame HMCP with Earth Leakage Ground Fault (Continued)

Table 12-203. J and K-Frame HMCP with Earth Leakage Ground Fault

Amperes 35 kA at 480V AC 65 kA at 480V AC 100 kA at 480V AC

3-Pole 4-Pole 3-Pole 4-Pole 3-Pole 4-Pole

CatalogNumber

PriceU.S. $

CatalogNumber

PriceU.S. $

CatalogNumber

PriceU.S. $

CatalogNumber

PriceU.S. $

CatalogNumber

PriceU.S. $

CatalogNumber

PriceU.S. $

200225250300350400

ELKD3200ELKD3225ELKD3250ELKD3300ELKD3350ELKD3400

4,615.004,615.004,615.004,615.004,615.004,615.00

ELKD4200ELKD4225ELKD4250ELKD4300ELKD4350ELKD4400

6,150.006,150.006,150.006,150.006,150.006,150.00

ELHKD3200ELHKD3225ELHKD3250ELHKD3300ELHKD3350ELHKD3400

7,190.007,190.007,190.007,190.007,190.007,190.00

ELHKD4200ELHKD4225ELHKD4250ELHKD4300ELHKD4350ELHKD4400

8,330.008,330.008,330.008,330.008,330.008,330.00

ELKDC3200ELKDC3225ELKDC3250ELKDC3300ELKDC3350ELKDC3400

7,330.007,330.007,330.007,330.007,330.007,330.00

ELKDC4200ELKDC4225ELKDC4250ELKDC4300ELKDC4350ELKDC4400

10,290.0010,290.0010,290.0010,290.0010,290.0010,290.00

Wire Type

(Number) Rangeof Conductors

TerminalMaterial

CatalogNumber

PriceU.S. $

Cu/AlCu/Al

(2) 250 kcmil(1) 500 kcmil

AluminumAluminum

3TA401K 1 66.00

Cu/AlCu/Al

(2) 250 kcmil(1) 500 kcmil

AluminumAluminum

4TA401K 2 76.00

CuCuCu

(1) 3 – 350 kcmil(1) 3 – 350 kcmil(1) 250 – 500 kcmil

CopperCopperCopper

T300KT300KT350K

29.5029.5029.50

CuCuCu

(1) 250 – 500 kcmil(1) 3/0 – 250 kcmil(1) 3/0 – 250 kcmil

CopperCopperCopper

T350K3T400K 1

4T400K 2

29.5076.0076.00

ContinuousAmperes

3-PoleCatalog Number

PriceU.S. $

37

15

ELHMCP003A0CELHMCP007C0CELHMCP015E0C

1,225.001,225.001,225.00

253050

ELHMCP025X0CELHMCP030H1CELHMCP050K2C

1,295.001,295.001,645.00

70100150150

ELHMCP070M2CELHMCP100R3CELHMCP150T4CELHMCP150U4C

1,645.001,645.002,335.002,335.00

37

15

ELHMCP003A0LCELHMCP007C0LCELHMCP015E0LC

1,225.001,225.001,225.00

253070

ELHMCP025D0CELHMCP030H1LCELHMCP070J2C

1,295.001,295.001,645.00

ContinuousAmperes

3-PoleCatalog Number

PriceU.S. $

10050

ELHMCP100L3CELHMCP050G2C

1,645.001,645.00

70100

ELHMCP070J2CELHMCP100K3C

1,645.001,645.00

HMCPs for Application with Motor Starters Equipped with Electronic Overload Relays

37

15

ELHMCPS003A0CELHMCPS007C0CELHMCPS015E0C

1,225.001,225.001,225.00

3050

100

ELHMCPS030H1CELHMCPS050K2CELHMCPS100R3C

1,295.001,645.001,645.00

150150

ELHMCPS150T4CELHMCPS150U4C

2,335.002,335.00

ContinuousAmperes

3-PoleCatalog Number

PriceU.S. $

250 ELHMCP250A5ELHMCP250C5ELHMCP250D5ELHMCP250F5ELHMCP250G5ELHMCP250J5ELHMCP250K5ELHMCP250L5ELHMCP250W5

3,230.003,230.003,230.003,230.003,230.003,230.003,230.003,230.003,230.00

400 ELHMCP400D5ELHMCP400F5ELHMCP400G5ELHMCP400J5ELHMCP400K5

5,250.005,250.005,250.005,250.005,250.00

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . CB-2

TAB1205.fm Page 128 Wednesday, October 25, 2000 9:29 PM

Page 2: 12-128 Molded Case Circuit Breakers Earth Leakage …...fault relay built-in. This technique allows for protection sensitivities down to the 30 milliampere level. Leakage breakers

12-126

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E

January 2001

Molded Case Circuit Breakers

12

Earth Leakage Circuit ProtectorsVol. 1, Ref. No. [0592]

ContentsDescription Page

Earth Leakage Circuit Protectors

Product Description. . . . . . . 12-126

Application Description. . . . 12-126

Options andAccessories . . . . . . . . . . . . 12-126

Technical Dataand Specifications. . . . . . . 12-127

Product Selection . . . . . . . . 12-127

Earth Leakage Circuit Breaker

Typical Earth Leakage Circuit Breaker

Product DescriptionSeries C Earth Leakage Breakers offer superior Class 1 ground fault protection and improved ground fault coordina-tion capability.

Earth leakage ground fault protection differs from other types of systems in its level of sensitivity. The sensitivity of traditional devices is limited by the cumulative error of the residual current sensors and the placement of the phase and neutral conductors inside the current sensor.

Leakage breakers are zero sequence sensing devices. They are factory sup-plied with a single sensor and ground fault relay built-in. This technique allows for protection sensitivities down to the 30 milliampere level.

Leakage breakers are provided with a full complement of easy adjustments. The ground fault pickup setting is adjustable from 0.03 to 30 amperes in eight steps, and the ground fault time delay setting is adjustable from instantaneous to 2.0 seconds in six steps. When the pickup is set to 30 mA, the time delay setting defaults internally to instantaneous only. Increased selectivity provides for improved coordination with upstream and downstream ground fault devices as well as the flexibility to adjust for transient currents.

Application DescriptionThree-Phase, Four-Wire LoadsFor three-phase applications with line-to-neutral loads, select 4-pole earth leakage breakers and wire the neutral through the fourth (right) pole.

Three-Phase, Three-Wire LoadsFor applications with only three-phase, three-wire, line-to-line connected loads, select 3-pole earth leakage breakers.

Single-Phase LoadsFor single-phase, two-wire or three-wire applications, use a 3-pole earth leakage breaker and connect all conductors through the breaker.

GeneralDo not reverse feed. Do not apply on 400 Hz systems.

Options and AccessoriesOptional Factory Installed Internal AccessoriesEarth leakage breakers use the same internal accessories as standard F-, J- and K-Frame Series C Breakers. Internal accessories fit in the right-hand pole space and are available as factory modifications only.

Bell alarm is included as standard.

Optional External AccessoriesSeries C Earth Leakage Breakers use the same external accessories as the standard F-, J- and K-Frame circuit breakers. R.H. only.

TAB1205.fm Page 126 Wednesday, October 25, 2000 9:29 PM