5
RELIANCE JAMNAGAR 3 PROGRAM Spent Caustic Oxidation Package Scrubber Tower Appendix 4 to Report No. SL/GEC /14/006 Seismic Load calculation

1.1 CMTR-07 Seismic Load Calculation-C

Embed Size (px)

DESCRIPTION

earth

Citation preview

Page 1: 1.1 CMTR-07 Seismic Load Calculation-C

RELIANCE JAMNAGAR 3 PROGRAM

Spent Caustic Oxidation Package Scrubber Tower

Appendix 4

to

Report No.

SL/GEC /14/006

Seismic Load calculation

Page 2: 1.1 CMTR-07 Seismic Load Calculation-C

Appendix 2 RELIANCE JAMNAGAR 3 PROGRAM

Doc No.SL/GEC /14/004 Page No.1 of 1

Calculation of Seismic Load As per IS 1893 :Part-I for SCO Scrubber Equipment:

As per Design Basis for Seismic Analysis and Design 100800-1ENGG-DBD-CS-002 Rev.1 Cl.5.5.4.2

Seismic Force, =

Where

= 0.32

= 0 m

= 0.2 m

= 2.5

= 2.5

= 1.5

= 70 kN

= 0.5 x 0.32(1 +0) x 2.5 x 1.5 x (28)

= 16.8 kN

= 7 kN

Height of the equipment, H = 10.0 m

= 1.69 kN/m

Seismic Force on structure @ EL 0000:

Influence height of the equipment = 2.64 m

= 4.46 kN

Seismic Force on structure @ EL 5750:

Influence height of the equipment = 4.01 m

= 6.77 kN

Seismic Force on structure @ EL 8500:

Influence height of the equipment = 3.3 m

= 5.57 kN

Zone Factor, Z As per 100800-1ENGG-DBD-CS-002 Rev.1 Cl.5.5.4.2

Height of the attachment of component from GL, x

Height of supporting Structure, h

Component amplification factor , ap As per 100800-1ENGG-DBD-CS-002 Rev.1 Cl.5.5.4.2 - Annexure-A & BComponent response Modification factor, Rp

Component Importance factor, Ip

Self Weight of the component, Wp

Seismic Force, Fp

Seismic force shall > 10% of self weight of the component

Seismic Force, Fp

Seismic Force, Fp

Seismic Force, Fp

Seismic Force, Fp

Page 3: 1.1 CMTR-07 Seismic Load Calculation-C

Seismic analysis is carried out based on Equivalent lateral force system as per ASCE 7-05 code.

Earthquake Loads are considered as per the code ASCE 7-05 and IBC 2009.

The parameters for the site is as per the Spec: P7512-BD-2000-C-0001 Rev B2 & P7512-TS-2000-C-0003 Rev B3

Spectral acceleration for short periods SS = 0.32

Spectral acceleration for a 1-second period S1 = 0.1

Site class = D

Long period transition period TL = 8

Design spectral response acceleration for short period SDS = 0.33

Design spectral response acceleration for a 1-second period SD1 = 0.154

Occupancy category or Risk factor III

Importance factor I or Ie = 1.25

Response modification co-efficient R = 3.25

Co-efficient Ct = 0.0724

x = 0.8

Height of Building = 5.63 m

The Seismic Analysis carried out Equivalent Lateral Force method.

Fundamental Period of Structure

T = 0.288 sec

Seismic Response Co-efficient

= 0.118

Seismic Base Shear V =

Vertical Base Shear =

= 0.495 IBC 2009 Cl.1613.5.4SMs = Max Considered earthquake spectral response accelerations for short period

IBC 2009 Cl.1613.5.4SM1 = Max Considered earthquake spectral response = 0.231 accelerations for 1 second period

Site coefficient

= 1.55 IBC 2009 Cl.1613.5.3

= 2.31 IBC 2009 Cl.1613.5.3

P7512-TS-2000-C-0003 Rev B3 Table-1

P7512-TS-2000-C-0003 Rev B3 Cl. 6.5.1

P7512-TS-2000-C-0003 Rev B3 Table-2

ASCE 7 -05 Table 12.2-1, B.4

ASCE 7 -05 Table 12.8.2

hn

ASCE 7-05 Eq-12.8-7

ASCE 7-05 Eq-12.8-2

Cs

Cs X WASCE 7-05Eq-12.8-1

Ev 0.2SDSDASCE 7-05Eq-12.4-4

SMs3

2

SDs

SM13

2

SD1

Fa

SMs

Ss

Fv

SM1

S1