8/11/2019 10. VA1 LICI 00EG I M4D DAS 0010 Temperature Transmitter
1/17
DOCUMENT SUBMISSION STATUS: AP
A 10/11/10 ISSUED FOR APPROVAL
REV DATE DESCRIPTION DRWN CHKD APPN
OWNER OWNERS CONSULTANT
EPC CONTRACTOR EPC CONTRACTORS CONSULTANT
PROJECT TITLE
VUNG ANG 1 THERMAL POWER PLANT 2 x 600MW
HEAVY FUEL OIL SYSTEM
CONTRACT No. 180810/LILAMA-LISEMCO
DRAWING TITLE
TEMPERATURE TRANSMITTER
SUB-CONTRACTORFUNCTION NAME SIGN DATE
DRWN TUAN
CHKD HOAN
APPD WILLIAM LIU
DOCUMENT No. VA1-LICI-00EG-I-M4D-DAS-0010 SCALE
NONE
REV.
A
VIETNAM OIL AND GAS GROUP (PVN) POYRY ENERGY LTD
VIETNAM MACHINERY INSTALLATION
CORPPORATION (LILAMA)
FICHTNER GMBH &CO.KG
8/11/2019 10. VA1 LICI 00EG I M4D DAS 0010 Temperature Transmitter
2/17
1 6
2 7 Document no
3 8 Latest revision A Date 10/11/'10
4 9 Issue status Approval Page
5 10
1 TT-00EGA10CT002 32 TT-00EGA10CT003 4
3 TT-00EGB10CT011 5
4 TT-00EGB10CT012 6
5 TT-00EGB10CT021 7
6 TT-00EGB10CT022 8
7 TT-00EGB10CT031 9
8 TT-00EGB10CT032 10
9 TT-10EGC15CT003 11
10 TT-10EGC15CT011 12
11 TT-20EGC25CT003 13
12 TT-20EGC25CT010 14
13 TT-00EGD10CT012 15
14 TT-00PCD10CT013 1615 TT-00PCD15CT014 17
2
SPECIFICATION IDENTIFICATIONS
TRANSMITTER OR SWITCH VA1-LICI-00EG-I-M4D-DAS-0010
Tag No. Page
RESPONSIBLE ORGANIZATION RTD/THERMOCOUPLE TEMPERATURE
Remark
INDEX
Item
Device Specification
Tag No. Page Remark Item
8/11/2019 10. VA1 LICI 00EG I M4D DAS 0010 Temperature Transmitter
3/17
1 6
2 7 Document no
3 8 Latest revision A Date 10/11/'10
4 9 Issue status Approval Page
5 10 Instrument TT-00EGA10CT002
11 TRANSMITTER OR SWITCH 56 PERFORMANCE CHARACTERISTICS
12 Housing type REMOTE MOUNT TRANSMITTER 57 Accuracy rating 0.1% OF SCALE
13 Input sensor type RTD PT100 58 Measurement LRL 60 C URL 65 C
14 Output signal type 4 ~ 20 mA 59 Min ambient working temp Max
15 Min measurement span 0 C Max 100 C 60 Contacts ac rating --- At Max ---16 Temp coef/Tolerance cl --- 61 Contacts dc rating --- At Max ---
17 Isolation type INPUT-OUTPUT ISOLATION 62
18 Enclosure type no/class IP66 63
19 Adjustment type MFR. STD 64 ACCESSORIES
20 Characteristic curve LINEAR TO MEASUREMENT 65 Remote indicator style
21 Digital communication std --- 66 Indicator enclosure
22 Signal power source 24VDC - LOOP POWERED 67 Air set filter style
23 Measurement type SINGLE INPUT 68 Air set gauges
24 Configuration-no of wires 3 WIRES 69
25 Contacts arrangement --- Quantity 70
26 Failsafe style FAIL SAFE 71 SPECIAL REQUIREMENTS
27 Transient protection --- 72 Custom tag TT-00EGA10CT002
28 Integral indicator style 4 DIGIT LCD 73 Reference specification29 Signal termination type MFR. STD 74 Compliance standard
30 Cert/Approval type 75 Calibration Report
31 Mounting type 2" PIPE W/BRACKET SS 76 Software configuration
32 Failure/Diagnostic action DOWN SCALE 77
33 Dead band type MFR. STD 78
34 Switch time delay --- 79 PHYSICAL DATA
35 Temp compensation type --- 80 Estimated weight
RTD/THERMOCOUPLE TEMPERATURE
VA1-LICI-00EG-I-M4D-DAS-0010
RESPONSIBLE ORGANIZATION
3
SPECIFICATION IDENTIFICATIONS
TRANSMITTER OR SWITCH
Device Specification
36 Enclosure material CAST ALUMINUM 81 Overall height
37 Mounting kit material S.S. 82 Removal clearance
38 83 Signal conn nominal Style
39 84 Mfr reference dwg
40 85
41 86
42 87
43 88
44 89
45 90
46 91
47 92
48 93
49 94
50 95
51 96
52 97
53 98
54 99
55 100100 CALIBRATIONS AND TEST INPUT OR SETPOINT OUTPUT OR SCALE
101 TAG NO/FUNCTIONAL IDENT MEAS/SIGNAL/TEST LRV URV LRV URV
102 TT-00EGA10CT002 Temp- Analog output 0 C 100 C 4 mA 20 mA
103
104
105
106
107
108 COMPONENT TYPE MANUFACTURER MODEL NUMBER
109
110
111
112113
COMPONENT IDENTIFICATIONS
REMARKSBY CHECKED APPROVEDREVISION DESCRIPTION
A
REV DATE
ISSUED FOR APPROVAL TUAN HOAN10/11/'10 WILLIAM LIU
8/11/2019 10. VA1 LICI 00EG I M4D DAS 0010 Temperature Transmitter
4/17
1 6
2 7 Document no
3 8 Latest revision A Date 10/11/'10
4 9 Issue status Approval Page
5 10 Instrument TT-00EGA10CT003
11 TRANSMITTER OR SWITCH 56 PERFORMANCE CHARACTERISTICS
12 Housing type REMOTE MOUNT TRANSMITTER 57 Accuracy rating 0.1% OF SCALE
13 Input sensor type RTD PT100 58 Measurement LRL 60 C URL 65 C
14 Output signal type 4 ~ 20 mA 59 Min ambient working temp Max
15 Min measurement span 0 C Max 100 C 60 Contacts ac rating --- At Max ---16 Temp coef/Tolerance cl --- 61 Contacts dc rating --- At Max ---
17 Isolation type INPUT-OUTPUT ISOLATION 62
18 Enclosure type no/class IP66 63
19 Adjustment type MFR. STD 64 ACCESSORIES
20 Characteristic curve LINEAR TO MEASUREMENT 65 Remote indicator style
21 Digital communication std --- 66 Indicator enclosure
22 Signal power source 24VDC - LOOP POWERED 67 Air set filter style
23 Measurement type SINGLE INPUT 68 Air set gauges
24 Configuration-no of wires 3 WIRES 69
25 Contacts arrangement --- Quantity 70
26 Failsafe style FAIL SAFE 71 SPECIAL REQUIREMENTS
27 Transient protection --- 72 Custom tag TT-00EGA10CT003
28 Integral indicator style 4 DIGIT LCD 73 Reference specification29 Signal termination type MFR. STD 74 Compliance standard
30 Cert/Approval type 75 Calibration Report
31 Mounting type 2" PIPE W/BRACKET SS 76 Software configuration
32 Failure/Diagnostic action DOWN SCALE 77
33 Dead band type MFR. STD 78
34 Switch time delay --- 79 PHYSICAL DATA
35 Temp compensation type --- 80 Estimated weight
4
RESPONSIBLE ORGANIZATION RTD/THERMOCOUPLE TEMPERATURE SPECIFICATION IDENTIFICATIONS
TRANSMITTER OR SWITCH VA1-LICI-00EG-I-M4D-DAS-0010
Device Specification
36 Enclosure material CAST ALUMINUM 81 Overall height
37 Mounting kit material S.S. 82 Removal clearance
38 83 Signal conn nominal Style
39 84 Mfr reference dwg
40 85
41 86
42 87
43 88
44 89
45 90
46 91
47 92
48 93
49 94
50 95
51 96
52 97
53 98
54 99
55 100100 CALIBRATIONS AND TEST INPUT OR SETPOINT OUTPUT OR SCALE
101 TAG NO/FUNCTIONAL IDENT MEAS/SIGNAL/TEST LRV URV LRV URV
102 TT-00EGA10CT003 Temp- Analog output 0 C 100 C 4 mA 20 mA
103
104
105
106
107
108 COMPONENT TYPE MANUFACTURER MODEL NUMBER
109
110
111
112113
COMPONENT IDENTIFICATIONS
A 10/11/'10 ISSUED FOR APPROVAL TUAN HOAN WILLIAM LIU
REMARKSREV DATE REVISION DESCRIPTION BY CHECKED APPROVED
8/11/2019 10. VA1 LICI 00EG I M4D DAS 0010 Temperature Transmitter
5/17
1 6
2 7 Document no
3 8 Latest revision A Date 10/11/'10
4 9 Issue status Approval Page
5 10 Instrument TT-00EGB10CT011
11 TRANSMITTER OR SWITCH 56 PERFORMANCE CHARACTERISTICS
12 Housing type REMOTE MOUNT TRANSMITTER 57 Accuracy rating 0.1% OF SCALE
13 Input sensor type RTD PT100 58 Measurement LRL 60 C URL 65 C
14 Output signal type 4 ~ 20 mA 59 Min ambient working temp Max
15 Min measurement span 0 C Max 100 C 60 Contacts ac rating --- At Max ---16 Temp coef/Tolerance cl --- 61 Contacts dc rating --- At Max ---
17 Isolation type INPUT-OUTPUT ISOLATION 62
18 Enclosure type no/class IP66 63
19 Adjustment type MFR. STD 64 ACCESSORIES
20 Characteristic curve LINEAR TO MEASUREMENT 65 Remote indicator style
21 Digital communication std --- 66 Indicator enclosure
22 Signal power source 24VDC - LOOP POWERED 67 Air set filter style
23 Measurement type SINGLE INPUT 68 Air set gauges
24 Configuration-no of wires 3 WIRES 69
25 Contacts arrangement --- Quantity 70
26 Failsafe style FAIL SAFE 71 SPECIAL REQUIREMENTS
27 Transient protection --- 72 Custom tag TT-00EGB10CT011
28 Integral indicator style 4 DIGIT LCD 73 Reference specification29 Signal termination type MFR. STD 74 Compliance standard
30 Cert/Approval type 75 Calibration Report
31 Mounting type 2" PIPE W/BRACKET SS 76 Software configuration
32 Failure/Diagnostic action DOWN SCALE 77
33 Dead band type MFR. STD 78
34 Switch time delay --- 79 PHYSICAL DATA
35 Temp compensation type --- 80 Estimated weight
5
RESPONSIBLE ORGANIZATION RTD/THERMOCOUPLE TEMPERATURE SPECIFICATION IDENTIFICATIONS
TRANSMITTER OR SWITCH VA1-LICI-00EG-I-M4D-DAS-0010
Device Specification
36 Enclosure material CAST ALUMINUM 81 Overall height
37 Mounting kit material S.S. 82 Removal clearance
38 83 Signal conn nominal Style
39 84 Mfr reference dwg
40 85
41 86
42 87
43 88
44 89
45 90
46 91
47 92
48 93
49 94
50 95
51 96
52 97
53 98
54 99
55 100100 CALIBRATIONS AND TEST INPUT OR SETPOINT OUTPUT OR SCALE
101 TAG NO/FUNCTIONAL IDENT MEAS/SIGNAL/TEST LRV URV LRV URV
102 TT-00EGB10CT011 Temp- Analog output 0 C 100 C 4 mA 20 mA
103
104
105
106
107
108 COMPONENT TYPE MANUFACTURER MODEL NUMBER
109
110
111
112113
COMPONENT IDENTIFICATIONS
A 10/11/'10 ISSUED FOR APPROVAL TUAN HOAN WILLIAM LIU
REMARKSREV DATE REVISION DESCRIPTION BY CHECKED APPROVED
8/11/2019 10. VA1 LICI 00EG I M4D DAS 0010 Temperature Transmitter
6/17
1 6
2 7 Document no
3 8 Latest revision A Date 10/11/'10
4 9 Issue status Approval Page
5 10 Instrument TT-00EGB10CT012
11 TRANSMITTER OR SWITCH 56 PERFORMANCE CHARACTERISTICS
12 Housing type REMOTE MOUNT TRANSMITTER 57 Accuracy rating 0.1% OF SCALE
13 Input sensor type RTD PT100 58 Measurement LRL 60 C URL 65 C
14 Output signal type 4 ~ 20 mA 59 Min ambient working temp Max
15 Min measurement span 0 C Max 100 C 60 Contacts ac rating --- At Max ---16 Temp coef/Tolerance cl --- 61 Contacts dc rating --- At Max ---
17 Isolation type INPUT-OUTPUT ISOLATION 62
18 Enclosure type no/class IP66 63
19 Adjustment type MFR. STD 64 ACCESSORIES
20 Characteristic curve LINEAR TO MEASUREMENT 65 Remote indicator style
21 Digital communication std --- 66 Indicator enclosure
22 Signal power source 24VDC - LOOP POWERED 67 Air set filter style
23 Measurement type SINGLE INPUT 68 Air set gauges
24 Configuration-no of wires 3 WIRES 69
25 Contacts arrangement --- Quantity 70
26 Failsafe style FAIL SAFE 71 SPECIAL REQUIREMENTS
27 Transient protection --- 72 Custom tag TT-00EGB10CT012
28 Integral indicator style 4 DIGIT LCD 73 Reference specification29 Signal termination type MFR. STD 74 Compliance standard
30 Cert/Approval type 75 Calibration Report
31 Mounting type 2" PIPE W/BRACKET SS 76 Software configuration
32 Failure/Diagnostic action DOWN SCALE 77
33 Dead band type MFR. STD 78
34 Switch time delay --- 79 PHYSICAL DATA
35 Temp compensation type --- 80 Estimated weight
6
RESPONSIBLE ORGANIZATION RTD/THERMOCOUPLE TEMPERATURE SPECIFICATION IDENTIFICATIONS
TRANSMITTER OR SWITCH VA1-LICI-00EG-I-M4D-DAS-0010
Device Specification
36 Enclosure material CAST ALUMINUM 81 Overall height
37 Mounting kit material S.S. 82 Removal clearance
38 83 Signal conn nominal Style
39 84 Mfr reference dwg
40 85
41 86
42 87
43 88
44 89
45 90
46 91
47 92
48 93
49 94
50 95
51 96
52 97
53 98
54 99
55 100100 CALIBRATIONS AND TEST INPUT OR SETPOINT OUTPUT OR SCALE
101 TAG NO/FUNCTIONAL IDENT MEAS/SIGNAL/TEST LRV URV LRV URV
102 TT-00EGB10CT012 Temp- Analog output 0 C 100 C 4 mA 20 mA
103
104
105
106
107
108 COMPONENT TYPE MANUFACTURER MODEL NUMBER
109
110
111
112113
COMPONENT IDENTIFICATIONS
A 10/11/'10 ISSUED FOR APPROVAL TUAN HOAN WILLIAM LIU
REMARKSREV DATE REVISION DESCRIPTION BY CHECKED APPROVED
8/11/2019 10. VA1 LICI 00EG I M4D DAS 0010 Temperature Transmitter
7/17
1 6
2 7 Document no
3 8 Latest revision A Date 10/11/'10
4 9 Issue status Approval Page
5 10 Instrument TT-00EGB10CT021
11 TRANSMITTER OR SWITCH 56 PERFORMANCE CHARACTERISTICS
12 Housing type REMOTE MOUNT TRANSMITTER 57 Accuracy rating 0.1% OF SCALE
13 Input sensor type RTD PT100 58 Measurement LRL 60 C URL 65 C
14 Output signal type 4 ~ 20 mA 59 Min ambient working temp Max
15 Min measurement span 0 C Max 100 C 60 Contacts ac rating --- At Max ---16 Temp coef/Tolerance cl --- 61 Contacts dc rating --- At Max ---
17 Isolation type INPUT-OUTPUT ISOLATION 62
18 Enclosure type no/class IP66 63
19 Adjustment type MFR. STD 64 ACCESSORIES
20 Characteristic curve LINEAR TO MEASUREMENT 65 Remote indicator style
21 Digital communication std --- 66 Indicator enclosure
22 Signal power source 24VDC - LOOP POWERED 67 Air set filter style
23 Measurement type SINGLE INPUT 68 Air set gauges
24 Configuration-no of wires 3 WIRES 69
25 Contacts arrangement --- Quantity 70
26 Failsafe style FAIL SAFE 71 SPECIAL REQUIREMENTS
27 Transient protection --- 72 Custom tag TT-00EGB10CT021
28 Integral indicator style 4 DIGIT LCD 73 Reference specification29 Signal termination type MFR. STD 74 Compliance standard
30 Cert/Approval type 75 Calibration Report
31 Mounting type 2" PIPE W/BRACKET SS 76 Software configuration
32 Failure/Diagnostic action DOWN SCALE 77
33 Dead band type MFR. STD 78
34 Switch time delay --- 79 PHYSICAL DATA
35 Temp compensation type --- 80 Estimated weight
7
RESPONSIBLE ORGANIZATION RTD/THERMOCOUPLE TEMPERATURE SPECIFICATION IDENTIFICATIONS
TRANSMITTER OR SWITCH VA1-LICI-00EG-I-M4D-DAS-0010
Device Specification
36 Enclosure material CAST ALUMINUM 81 Overall height
37 Mounting kit material S.S. 82 Removal clearance
38 83 Signal conn nominal Style
39 84 Mfr reference dwg
40 85
41 86
42 87
43 88
44 89
45 90
46 91
47 92
48 93
49 94
50 95
51 96
52 97
53 98
54 99
55 100100 CALIBRATIONS AND TEST INPUT OR SETPOINT OUTPUT OR SCALE
101 TAG NO/FUNCTIONAL IDENT MEAS/SIGNAL/TEST LRV URV LRV URV
102 TT-00EGB10CT021 Temp- Analog output 0 C 100 C 4 mA 20 mA
103
104
105
106
107
108 COMPONENT TYPE MANUFACTURER MODEL NUMBER
109
110
111
112113
COMPONENT IDENTIFICATIONS
A 10/11/'10 ISSUED FOR APPROVAL TUAN HOAN WILLIAM LIU
REMARKSREV DATE REVISION DESCRIPTION BY CHECKED APPROVED
8/11/2019 10. VA1 LICI 00EG I M4D DAS 0010 Temperature Transmitter
8/17
1 6
2 7 Document no
3 8 Latest revision A Date 10/11/'10
4 9 Issue status Approval Page
5 10 Instrument TT-00EGB10CT022
11 TRANSMITTER OR SWITCH 56 PERFORMANCE CHARACTERISTICS
12 Housing type REMOTE MOUNT TRANSMITTER 57 Accuracy rating 0.1% OF SCALE
13 Input sensor type RTD PT100 58 Measurement LRL 60 C URL 65 C
14 Output signal type 4 ~ 20 mA 59 Min ambient working temp Max
15 Min measurement span 0 C Max 100 C 60 Contacts ac rating --- At Max ---16 Temp coef/Tolerance cl --- 61 Contacts dc rating --- At Max ---
17 Isolation type INPUT-OUTPUT ISOLATION 62
18 Enclosure type no/class IP66 63
19 Adjustment type MFR. STD 64 ACCESSORIES
20 Characteristic curve LINEAR TO MEASUREMENT 65 Remote indicator style
21 Digital communication std --- 66 Indicator enclosure
22 Signal power source 24VDC - LOOP POWERED 67 Air set filter style
23 Measurement type SINGLE INPUT 68 Air set gauges
24 Configuration-no of wires 3 WIRES 69
25 Contacts arrangement --- Quantity 70
26 Failsafe style FAIL SAFE 71 SPECIAL REQUIREMENTS
27 Transient protection --- 72 Custom tag TT-00EGB10CT022
28 Integral indicator style 4 DIGIT LCD 73 Reference specification29 Signal termination type MFR. STD 74 Compliance standard
30 Cert/Approval type 75 Calibration Report
31 Mounting type 2" PIPE W/BRACKET SS 76 Software configuration
32 Failure/Diagnostic action DOWN SCALE 77
33 Dead band type MFR. STD 78
34 Switch time delay --- 79 PHYSICAL DATA
35 Temp compensation type --- 80 Estimated weight
8
RESPONSIBLE ORGANIZATION RTD/THERMOCOUPLE TEMPERATURE SPECIFICATION IDENTIFICATIONS
TRANSMITTER OR SWITCH VA1-LICI-00EG-I-M4D-DAS-0010
Device Specification
36 Enclosure material CAST ALUMINUM 81 Overall height
37 Mounting kit material S.S. 82 Removal clearance
38 83 Signal conn nominal Style
39 84 Mfr reference dwg
40 85
41 86
42 87
43 88
44 89
45 90
46 91
47 92
48 93
49 94
50 95
51 96
52 97
53 98
54 99
55 100100 CALIBRATIONS AND TEST INPUT OR SETPOINT OUTPUT OR SCALE
101 TAG NO/FUNCTIONAL IDENT MEAS/SIGNAL/TEST LRV URV LRV URV
102 TT-00EGB10CT022 Temp- Analog output 0 C 100 C 4 mA 20 mA
103
104
105
106
107
108 COMPONENT TYPE MANUFACTURER MODEL NUMBER
109
110
111
112113
COMPONENT IDENTIFICATIONS
A 10/11/'10 ISSUED FOR APPROVAL TUAN HOAN WILLIAM LIU
REMARKSREV DATE REVISION DESCRIPTION BY CHECKED APPROVED
8/11/2019 10. VA1 LICI 00EG I M4D DAS 0010 Temperature Transmitter
9/17
8/11/2019 10. VA1 LICI 00EG I M4D DAS 0010 Temperature Transmitter
10/17
1 6
2 7 Document no
3 8 Latest revision A Date 10/11/'10
4 9 Issue status Approval Page
5 10 Instrument TT-00EGB10CT032
11 TRANSMITTER OR SWITCH 56 PERFORMANCE CHARACTERISTICS
12 Housing type REMOTE MOUNT TRANSMITTER 57 Accuracy rating 0.1% OF SCALE
13 Input sensor type RTD PT100 58 Measurement LRL 60 C URL 65 C
14 Output signal type 4 ~ 20 mA 59 Min ambient working temp Max
15 Min measurement span 0 C Max 100 C 60 Contacts ac rating --- At Max ---16 Temp coef/Tolerance cl --- 61 Contacts dc rating --- At Max ---
17 Isolation type INPUT-OUTPUT ISOLATION 62
18 Enclosure type no/class IP66 63
19 Adjustment type MFR. STD 64 ACCESSORIES
20 Characteristic curve LINEAR TO MEASUREMENT 65 Remote indicator style
21 Digital communication std --- 66 Indicator enclosure
22 Signal power source 24VDC - LOOP POWERED 67 Air set filter style
23 Measurement type SINGLE INPUT 68 Air set gauges
24 Configuration-no of wires 3 WIRES 69
25 Contacts arrangement --- Quantity 70
26 Failsafe style FAIL SAFE 71 SPECIAL REQUIREMENTS
27 Transient protection --- 72 Custom tag TT-00EGB10CT032
28 Integral indicator style 4 DIGIT LCD 73 Reference specification29 Signal termination type MFR. STD 74 Compliance standard
30 Cert/Approval type 75 Calibration Report
31 Mounting type 2" PIPE W/BRACKET SS 76 Software configuration
32 Failure/Diagnostic action DOWN SCALE 77
33 Dead band type MFR. STD 78
34 Switch time delay --- 79 PHYSICAL DATA
35 Temp compensation type --- 80 Estimated weight
10
RESPONSIBLE ORGANIZATION RTD/THERMOCOUPLE TEMPERATURE SPECIFICATION IDENTIFICATIONS
TRANSMITTER OR SWITCH VA1-LICI-00EG-I-M4D-DAS-0010
Device Specification
36 Enclosure material CAST ALUMINUM 81 Overall height
37 Mounting kit material S.S. 82 Removal clearance
38 83 Signal conn nominal Style
39 84 Mfr reference dwg
40 85
41 86
42 87
43 88
44 89
45 90
46 91
47 92
48 93
49 94
50 95
51 96
52 97
53 98
54 99
55 100100 CALIBRATIONS AND TEST INPUT OR SETPOINT OUTPUT OR SCALE
101 TAG NO/FUNCTIONAL IDENT MEAS/SIGNAL/TEST LRV URV LRV URV
102 TT-00EGB10CT032 Temp- Analog output 0 C 100 C 4 mA 20 mA
103
104
105
106
107
108 COMPONENT TYPE MANUFACTURER MODEL NUMBER
109
110
111
112113
COMPONENT IDENTIFICATIONS
A 10/11/'10 ISSUED FOR APPROVAL TUAN HOAN WILLIAM LIU
REMARKSREV DATE REVISION DESCRIPTION BY CHECKED APPROVED
8/11/2019 10. VA1 LICI 00EG I M4D DAS 0010 Temperature Transmitter
11/17
1 6
2 7 Document no
3 8 Latest revision A Date 10/11/'10
4 9 Issue status Approval Page
5 10 Instrument TT-10EGC15CT003
11 TRANSMITTER OR SWITCH 56 PERFORMANCE CHARACTERISTICS
12 Housing type REMOTE MOUNT TRANSMITTER 57 Accuracy rating 0.1% OF SCALE
13 Input sensor type RTD PT100 58 Measurement LRL 130 C URL 150 C
14 Output signal type 4 ~ 20 mA 59 Min ambient working temp Max
15 Min measurement span 0 C Max 200 C 60 Contacts ac rating --- At Max ---16 Temp coef/Tolerance cl --- 61 Contacts dc rating --- At Max ---
17 Isolation type INPUT-OUTPUT ISOLATION 62
18 Enclosure type no/class IP66 63
19 Adjustment type MFR. STD 64 ACCESSORIES
20 Characteristic curve LINEAR TO MEASUREMENT 65 Remote indicator style
21 Digital communication std --- 66 Indicator enclosure
22 Signal power source 24VDC - LOOP POWERED 67 Air set filter style
23 Measurement type SINGLE INPUT 68 Air set gauges
24 Configuration-no of wires 3 WIRES 69
25 Contacts arrangement --- Quantity 70
26 Failsafe style FAIL SAFE 71 SPECIAL REQUIREMENTS
27 Transient protection --- 72 Custom tag TT-10EGC15CT003
28 Integral indicator style 4 DIGIT LCD 73 Reference specification29 Signal termination type MFR. STD 74 Compliance standard
30 Cert/Approval type 75 Calibration Report
31 Mounting type 2" PIPE W/BRACKET SS 76 Software configuration
32 Failure/Diagnostic action DOWN SCALE 77
33 Dead band type MFR. STD 78
34 Switch time delay --- 79 PHYSICAL DATA
35 Temp compensation type --- 80 Estimated weight
11
RESPONSIBLE ORGANIZATION RTD/THERMOCOUPLE TEMPERATURE SPECIFICATION IDENTIFICATIONS
TRANSMITTER OR SWITCH VA1-LICI-00EG-I-M4D-DAS-0010
Device Specification
36 Enclosure material CAST ALUMINUM 81 Overall height
37 Mounting kit material S.S. 82 Removal clearance
38 83 Signal conn nominal Style
39 84 Mfr reference dwg
40 85
41 86
42 87
43 88
44 89
45 90
46 91
47 92
48 93
49 94
50 95
51 96
52 97
53 98
54 99
55 100100 CALIBRATIONS AND TEST INPUT OR SETPOINT OUTPUT OR SCALE
101 TAG NO/FUNCTIONAL IDENT MEAS/SIGNAL/TEST LRV URV LRV URV
102 TT-10EGC15CT003 Temp- Analog output 0 C 200 C 4 mA 20 mA
103
104
105
106
107
108 COMPONENT TYPE MANUFACTURER MODEL NUMBER
109
110
111
112113
COMPONENT IDENTIFICATIONS
A 10/11/'10 ISSUED FOR APPROVAL TUAN HOAN WILLIAM LIU
REMARKSREV DATE REVISION DESCRIPTION BY CHECKED APPROVED
8/11/2019 10. VA1 LICI 00EG I M4D DAS 0010 Temperature Transmitter
12/17
8/11/2019 10. VA1 LICI 00EG I M4D DAS 0010 Temperature Transmitter
13/17
1 6
2 7 Document no
3 8 Latest revision A Date 10/11/'10
4 9 Issue status Approval Page
5 10 Instrument TT-20EGC25CT003
11 TRANSMITTER OR SWITCH 56 PERFORMANCE CHARACTERISTICS
12 Housing type REMOTE MOUNT TRANSMITTER 57 Accuracy rating 0.1% OF SCALE
13 Input sensor type RTD PT100 58 Measurement LRL 130 C URL 150 C
14 Output signal type 4 ~ 20 mA 59 Min ambient working temp Max
15 Min measurement span 0 C Max 200 C 60 Contacts ac rating --- At Max ---16 Temp coef/Tolerance cl --- 61 Contacts dc rating --- At Max ---
17 Isolation type INPUT-OUTPUT ISOLATION 62
18 Enclosure type no/class IP66 63
19 Adjustment type MFR. STD 64 ACCESSORIES
20 Characteristic curve LINEAR TO MEASUREMENT 65 Remote indicator style
21 Digital communication std --- 66 Indicator enclosure
22 Signal power source 24VDC - LOOP POWERED 67 Air set filter style
23 Measurement type SINGLE INPUT 68 Air set gauges
24 Configuration-no of wires 3 WIRES 69
25 Contacts arrangement --- Quantity 70
26 Failsafe style FAIL SAFE 71 SPECIAL REQUIREMENTS
27 Transient protection --- 72 Custom tag TT-20EGC25CT003
28 Integral indicator style 4 DIGIT LCD 73 Reference specification29 Signal termination type MFR. STD 74 Compliance standard
30 Cert/Approval type 75 Calibration Report
31 Mounting type 2" PIPE W/BRACKET SS 76 Software configuration
32 Failure/Diagnostic action DOWN SCALE 77
33 Dead band type MFR. STD 78
34 Switch time delay --- 79 PHYSICAL DATA
35 Temp compensation type --- 80 Estimated weight
13
RESPONSIBLE ORGANIZATION RTD/THERMOCOUPLE TEMPERATURE SPECIFICATION IDENTIFICATIONS
TRANSMITTER OR SWITCH VA1-LICI-00EG-I-M4D-DAS-0010
Device Specification
36 Enclosure material CAST ALUMINUM 81 Overall height
37 Mounting kit material S.S. 82 Removal clearance
38 83 Signal conn nominal Style
39 84 Mfr reference dwg
40 85
41 86
42 87
43 88
44 89
45 90
46 91
47 92
48 93
49 94
50 95
51 96
52 97
53 98
54 99
55 100100 CALIBRATIONS AND TEST INPUT OR SETPOINT OUTPUT OR SCALE
101 TAG NO/FUNCTIONAL IDENT MEAS/SIGNAL/TEST LRV URV LRV URV
102 TT-20EGC25CT003 Temp- Analog output 0 C 200 C 4 mA 20 mA
103
104
105
106
107
108 COMPONENT TYPE MANUFACTURER MODEL NUMBER
109
110
111
112113
COMPONENT IDENTIFICATIONS
A 10/11/'10 ISSUED FOR APPROVAL TUAN HOAN WILLIAM LIU
REMARKSREV DATE REVISION DESCRIPTION BY CHECKED APPROVED
8/11/2019 10. VA1 LICI 00EG I M4D DAS 0010 Temperature Transmitter
14/17
1 6
2 7 Document no
3 8 Latest revision A Date 10/11/'10
4 9 Issue status Approval Page
5 10 Instrument TT-20EGC25CT010
11 TRANSMITTER OR SWITCH 56 PERFORMANCE CHARACTERISTICS
12 Housing type REMOTE MOUNT TRANSMITTER 57 Accuracy rating 0.1% OF SCALE
13 Input sensor type RTD PT100 58 Measurement LRL 130 C URL 150 C
14 Output signal type 4 ~ 20 mA 59 Min ambient working temp Max
15 Min measurement span 0 C Max 200 C 60 Contacts ac rating --- At Max ---16 Temp coef/Tolerance cl --- 61 Contacts dc rating --- At Max ---
17 Isolation type INPUT-OUTPUT ISOLATION 62
18 Enclosure type no/class IP66 63
19 Adjustment type MFR. STD 64 ACCESSORIES
20 Characteristic curve LINEAR TO MEASUREMENT 65 Remote indicator style
21 Digital communication std --- 66 Indicator enclosure
22 Signal power source 24VDC - LOOP POWERED 67 Air set filter style
23 Measurement type SINGLE INPUT 68 Air set gauges
24 Configuration-no of wires 3 WIRES 69
25 Contacts arrangement --- Quantity 70
26 Failsafe style FAIL SAFE 71 SPECIAL REQUIREMENTS
27 Transient protection --- 72 Custom tag TT-20EGC25CT010
28 Integral indicator style 4 DIGIT LCD 73 Reference specification29 Signal termination type MFR. STD 74 Compliance standard
30 Cert/Approval type 75 Calibration Report
31 Mounting type 2" PIPE W/BRACKET SS 76 Software configuration
32 Failure/Diagnostic action DOWN SCALE 77
33 Dead band type MFR. STD 78
34 Switch time delay --- 79 PHYSICAL DATA
35 Temp compensation type --- 80 Estimated weight
14
RESPONSIBLE ORGANIZATION RTD/THERMOCOUPLE TEMPERATURE SPECIFICATION IDENTIFICATIONS
TRANSMITTER OR SWITCH VA1-LICI-00EG-I-M4D-DAS-0010
Device Specification
36 Enclosure material CAST ALUMINUM 81 Overall height
37 Mounting kit material S.S. 82 Removal clearance
38 83 Signal conn nominal Style
39 84 Mfr reference dwg
40 85
41 86
42 87
43 88
44 89
45 90
46 91
47 92
48 93
49 94
50 95
51 96
52 97
53 98
54 99
55 100100 CALIBRATIONS AND TEST INPUT OR SETPOINT OUTPUT OR SCALE
101 TAG NO/FUNCTIONAL IDENT MEAS/SIGNAL/TEST LRV URV LRV URV
102 TT-20EGC25CT010 Temp- Analog output 0 C 200 C 4 mA 20 mA
103
104
105
106
107
108 COMPONENT TYPE MANUFACTURER MODEL NUMBER
109
110
111
112113
COMPONENT IDENTIFICATIONS
A 10/11/'10 ISSUED FOR APPROVAL TUAN HOAN WILLIAM LIU
REMARKSREV DATE REVISION DESCRIPTION BY CHECKED APPROVED
8/11/2019 10. VA1 LICI 00EG I M4D DAS 0010 Temperature Transmitter
15/17
1 6
2 7 Document no
3 8 Latest revision A Date 10/11/'10
4 9 Issue status Approval Page
5 10 Instrument TT-00EGD10CT012
11 TRANSMITTER OR SWITCH 56 PERFORMANCE CHARACTERISTICS
12 Housing type REMOTE MOUNT TRANSMITTER 57 Accuracy rating 0.1% OF SCALE
13 Input sensor type RTD PT100 58 Measurement LRL 60 C URL 65 C
14 Output signal type 4 ~ 20 mA 59 Min ambient working temp Max
15 Min measurement span 0 C Max 100 C 60 Contacts ac rating --- At Max ---16 Temp coef/Tolerance cl --- 61 Contacts dc rating --- At Max ---
17 Isolation type INPUT-OUTPUT ISOLATION 62
18 Enclosure type no/class IP66 63
19 Adjustment type MFR. STD 64 ACCESSORIES
20 Characteristic curve LINEAR TO MEASUREMENT 65 Remote indicator style
21 Digital communication std --- 66 Indicator enclosure
22 Signal power source 24VDC - LOOP POWERED 67 Air set filter style
23 Measurement type SINGLE INPUT 68 Air set gauges
24 Configuration-no of wires 3 WIRES 69
25 Contacts arrangement --- Quantity 70
26 Failsafe style FAIL SAFE 71 SPECIAL REQUIREMENTS
27 Transient protection --- 72 Custom tag TT-00EGD10CT012
28 Integral indicator style 4 DIGIT LCD 73 Reference specification29 Signal termination type MFR. STD 74 Compliance standard
30 Cert/Approval type 75 Calibration Report
31 Mounting type 2" PIPE W/BRACKET SS 76 Software configuration
32 Failure/Diagnostic action DOWN SCALE 77
33 Dead band type MFR. STD 78
34 Switch time delay --- 79 PHYSICAL DATA
35 Temp compensation type --- 80 Estimated weight
15
RESPONSIBLE ORGANIZATION RTD/THERMOCOUPLE TEMPERATURE SPECIFICATION IDENTIFICATIONS
TRANSMITTER OR SWITCH VA1-LICI-00EG-I-M4D-DAS-0010
Device Specification
36 Enclosure material CAST ALUMINUM 81 Overall height
37 Mounting kit material S.S. 82 Removal clearance
38 83 Signal conn nominal Style
39 84 Mfr reference dwg
40 85
41 86
42 87
43 88
44 89
45 90
46 91
47 92
48 93
49 94
50 95
51 96
52 97
53 98
54 99
55 100100 CALIBRATIONS AND TEST INPUT OR SETPOINT OUTPUT OR SCALE
101 TAG NO/FUNCTIONAL IDENT MEAS/SIGNAL/TEST LRV URV LRV URV
102 TT-00EGD10CT012 Temp- Analog output 0 C 100 C 4 mA 20 mA
103
104
105
106
107
108 COMPONENT TYPE MANUFACTURER MODEL NUMBER
109
110
111
112113
COMPONENT IDENTIFICATIONS
A 10/11/'10 ISSUED FOR APPROVAL TUAN HOAN WILLIAM LIU
REMARKSREV DATE REVISION DESCRIPTION BY CHECKED APPROVED
8/11/2019 10. VA1 LICI 00EG I M4D DAS 0010 Temperature Transmitter
16/17
1 6
2 7 Document no
3 8 Latest revision A Date 10/11/'10
4 9 Issue status Approval Page
5 10 Instrument TT-00PCD10CT013
11 TRANSMITTER OR SWITCH 56 PERFORMANCE CHARACTERISTICS
12 Housing type REMOTE MOUNT TRANSMITTER 57 Accuracy rating 0.1% OF SCALE
13 Input sensor type RTD PT100 58 Measurement LRL 47 C URL 60 C
14 Output signal type 4 ~ 20 mA 59 Min ambient working temp Max
15 Min measurement span 0 C Max 100 C 60 Contacts ac rating --- At Max ---16 Temp coef/Tolerance cl --- 61 Contacts dc rating --- At Max ---
17 Isolation type INPUT-OUTPUT ISOLATION 62
18 Enclosure type no/class IP66 63
19 Adjustment type MFR. STD 64 ACCESSORIES
20 Characteristic curve LINEAR TO MEASUREMENT 65 Remote indicator style
21 Digital communication std --- 66 Indicator enclosure
22 Signal power source 24VDC - LOOP POWERED 67 Air set filter style
23 Measurement type SINGLE INPUT 68 Air set gauges
24 Configuration-no of wires 3 WIRES 69
25 Contacts arrangement --- Quantity 70
26 Failsafe style FAIL SAFE 71 SPECIAL REQUIREMENTS
27 Transient protection --- 72 Custom tag TT-00PCD10CT013
28 Integral indicator style 4 DIGIT LCD 73 Reference specification29 Signal termination type MFR. STD 74 Compliance standard
30 Cert/Approval type 75 Calibration Report
31 Mounting type 2" PIPE W/BRACKET SS 76 Software configuration
32 Failure/Diagnostic action DOWN SCALE 77
33 Dead band type MFR. STD 78
34 Switch time delay --- 79 PHYSICAL DATA
35 Temp compensation type --- 80 Estimated weight
16
RESPONSIBLE ORGANIZATION RTD/THERMOCOUPLE TEMPERATURE SPECIFICATION IDENTIFICATIONS
TRANSMITTER OR SWITCH VA1-LICI-00EG-I-M4D-DAS-0010
Device Specification
36 Enclosure material CAST ALUMINUM 81 Overall height
37 Mounting kit material S.S. 82 Removal clearance
38 83 Signal conn nominal Style
39 84 Mfr reference dwg
40 85
41 86
42 87
43 88
44 89
45 90
46 91
47 92
48 93
49 94
50 95
51 96
52 97
53 98
54 99
55 100100 CALIBRATIONS AND TEST INPUT OR SETPOINT OUTPUT OR SCALE
101 TAG NO/FUNCTIONAL IDENT MEAS/SIGNAL/TEST LRV URV LRV URV
102 TT-00PCD10CT013 Temp- Analog output 0 C 100 C 4 mA 20 mA
103
104
105
106
107
108 COMPONENT TYPE MANUFACTURER MODEL NUMBER
109
110
111
112113
COMPONENT IDENTIFICATIONS
A 10/11/'10 ISSUED FOR APPROVAL TUAN HOAN WILLIAM LIU
REMARKSREV DATE REVISION DESCRIPTION BY CHECKED APPROVED
8/11/2019 10. VA1 LICI 00EG I M4D DAS 0010 Temperature Transmitter
17/17
1 6
2 7 Document no
3 8 Latest revision A Date 10/11/'10
4 9 Issue status Approval Page
5 10 Instrument TT-00PCD15CT014
11 TRANSMITTER OR SWITCH 56 PERFORMANCE CHARACTERISTICS
12 Housing type REMOTE MOUNT TRANSMITTER 57 Accuracy rating 0.1% OF SCALE
13 Input sensor type RTD PT100 58 Measurement LRL 37 C URL 60 C
14 Output signal type 4 ~ 20 mA 59 Min ambient working temp Max
15 Min measurement span 0 C Max 100 C 60 Contacts ac rating --- At Max ---16 Temp coef/Tolerance cl --- 61 Contacts dc rating --- At Max ---
17 Isolation type INPUT-OUTPUT ISOLATION 62
18 Enclosure type no/class IP66 63
19 Adjustment type MFR. STD 64 ACCESSORIES
20 Characteristic curve LINEAR TO MEASUREMENT 65 Remote indicator style
21 Digital communication std --- 66 Indicator enclosure
22 Signal power source 24VDC - LOOP POWERED 67 Air set filter style
23 Measurement type SINGLE INPUT 68 Air set gauges
24 Configuration-no of wires 3 WIRES 69
25 Contacts arrangement --- Quantity 70
26 Failsafe style FAIL SAFE 71 SPECIAL REQUIREMENTS
27 Transient protection --- 72 Custom tag TT-00PCD15CT014
28 Integral indicator style 4 DIGIT LCD 73 Reference specification29 Signal termination type MFR. STD 74 Compliance standard
30 Cert/Approval type 75 Calibration Report
31 Mounting type 2" PIPE W/BRACKET SS 76 Software configuration
32 Failure/Diagnostic action DOWN SCALE 77
33 Dead band type MFR. STD 78
34 Switch time delay --- 79 PHYSICAL DATA
35 Temp compensation type --- 80 Estimated weight
17
RESPONSIBLE ORGANIZATION RTD/THERMOCOUPLE TEMPERATURE SPECIFICATION IDENTIFICATIONS
TRANSMITTER OR SWITCH VA1-LICI-00EG-I-M4D-DAS-0010
Device Specification
36 Enclosure material CAST ALUMINUM 81 Overall height
37 Mounting kit material S.S. 82 Removal clearance
38 83 Signal conn nominal Style
39 84 Mfr reference dwg
40 85
41 86
42 87
43 88
44 89
45 90
46 91
47 92
48 93
49 94
50 95
51 96
52 97
53 98
54 99
55 100100 CALIBRATIONS AND TEST INPUT OR SETPOINT OUTPUT OR SCALE
101 TAG NO/FUNCTIONAL IDENT MEAS/SIGNAL/TEST LRV URV LRV URV
102 TT-00PCD15CT014 Temp- Analog output 0 C 100 C 4 mA 20 mA
103
104
105
106
107
108 COMPONENT TYPE MANUFACTURER MODEL NUMBER
109
110
111
112113
COMPONENT IDENTIFICATIONS
A 10/11/'10 ISSUED FOR APPROVAL TUAN HOAN WILLIAM LIU
REMARKSREV DATE REVISION DESCRIPTION BY CHECKED APPROVED