Electrical Systems

<Presenter>

Page 2: 10 electrical-systems

Electrical Systems

Review• Root Causes of Energy Inefficiency• Roadmap to Maximize Energy Efficiency

• Best Practices• Alternative Energy Sources• Controls

• Take Aways• Seek Professional Help.

Page 3: 10 electrical-systems

Electrical Systems

ENERGY INEFFICIENCY OF DATA CENTERS

ROOT CAUSESROOT CAUSES

Physical Infrastructure is way OVERSIZED

Power Requirements are greatly OVERSTATED

Many Legacy INEFFICIENT Equipment are Incorporated

Multi-stages of POWER CONVERSION

Why did that happen

Page 4: 10 electrical-systems

Electrical Systems

Electrical Infrastructure:

System Configuration Criteria:- Focus on Increased Reliability & Uptime to 99.999%- Fault Tolerant

Design / Sizing Concept:- Designed IT Load based on IT Nameplate plus future growth- Data Center Floor Area based on Designed IT Load / (5-100 W/SF)- UPS System Rating based on Designed IT Load + (20 – 50%)- Standby Generator Sizing based on UPS system rating x 2 ++- Lights based on (3 W / SF) x Data Center Floor Area

- Physical Rooms size(s) of UPS / Battery / Switchgear based UPS systems physical sized ++Power Protection:

- Relying on UPS Power for voltage regulation and back-up

Purchasing Process: - Lowest Bid / Cheaper Price Wins

ENERGY INEFFICIENCY OF DATA CENTERS

ROOT CAUSES ROOT CAUSES (continue)(continue)

configurationsizing

Protectionprocess

Page 5: 10 electrical-systems

Electrical Systems

ROOT CAUSESROOT CAUSES (continue)(continue)

Standby Generators- Oversizing- Redundancy Exceeds N+1

Higher power consumption of Block heaters, and water & Oil pumps Up to 5%

Transformers- Oversizing- Inefficient

Higher transformers losses up to 3%

UPS - Low Load Capacity Due To

- Oversizing- Multi-Stage Redundancy 2 (N+)

- Inefficient UPS Topology- Low Input Power Factor- High Input Current THDHigher UPS losses up to 25%

Electrical Infrastructure:

ENERGY INEFFICIENCY OF DATA CENTERS

OversizingRedundancy

Inefficientcapacity

Page 6: 10 electrical-systems

Electrical Systems

ROOT CAUSESROOT CAUSES (continue)(continue)

PDU- Excessive Use of PDUs. 4 – 6 X IT designed Load- Inefficient TransformersHigher transformers losses up to 3%

IT- Sizing of IT load is based on Nameplate ++ growth- IT Low Power Factor- IT High Current Harmonic THDHigher cables & transformers losses

Lights- Unused Floor Space- Use Of Inefficient Lights- No Lights Control Sensors

Higher power consumption up to 5%

Electrical Infrastructure:

ENERGY INEFFICIENCY OF DATA CENTERS

ExcessiveNo Sensors

losses

Page 7: 10 electrical-systems

Electrical Systems

Inverter

In Out

Bypass

Battery/ChargerRectifier

Inverter

In Out

Bypass

Battery/ChargerRectifier

Internal Drive

External Drive

I/O

Memory Controller

μ Processor

SDRAM

Graphics Controller

DC/DCAC/DC

DC/DC

AC/DC Multi outputPower Supply

Voltage Regulator Modules

5V

12V

3.3V

12V 1.5/2.5V

1.1V-1.85V

3.3V

3.3V

12V

PWM/PFCSwitcher

Unregulated DCTo Multi Output Regulated DC

Voltages

Internal Drive

External Drive

I/O

Memory Controller

μ Processor

SDRAM

Graphics Controller

DC/DCAC/DC

DC/DC

AC/DC Multi outputPower Supply

Voltage Regulator Modules

5V

12V

3.3V

12V 1.5/2.5V

1.1V-1.85V

3.3V

3.3V

12V

PWM/PFCSwitcher

Unregulated DCTo Multi Output Regulated DC

Voltages

Multi-stages of Power Conversions

Power Distribution Unit (PDU)

ServerUninterruptible Power Supply (UPS)

AC DC AC DC

ENERGY INEFFICIENCY OF DATA CENTERSROOT CAUSESROOT CAUSES (continue)(continue)

Page 8: 10 electrical-systems

Electrical Systems

LOW (Poor) DCiE FACTOR

Final Result

kW 1000 400

IT Distribution losses + Lights, Gen

ROOT CAUSESROOT CAUSES (continue)(continue)

ENERGY INEFFICIENCY OF DATA CENTERS

Excessive Energy Waste up to 40%

NEED HELP

PLEASE

Page 9: 10 electrical-systems

Electrical Systems

While Maintaining System Configuration CriteriaReliability & Uptime to 99.999%Reliability & Uptime to 99.999%

Fault Tolerant SystemFault Tolerant System

OPTIMIZE POWER CONSUMPTION X OPTIMIZE TIME USAGE

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY

Page 10: 10 electrical-systems

Electrical Systems

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY

Best Practices

Alternative Energy Source

Controls (Thermostat, Sensors, ETC)

Driving Directions

Page 11: 10 electrical-systems

Electrical Systems

Managing UPS Load Capacity: UPS Sizing and Loading Can Significantly Affect UPS efficiency:

Maximize UPS Load Capacity:< 30% for N+ X configuration< 40% for N configuration

Specify / Consider UPS system that has higher Efficiency at 10 – 40% load capacity (Most UPS units in N or N+X configuration operate at 10% to 40% load capacity)Use / Evaluate Efficient UPS Topology:

Double Conversion with FilterDelta ConversionRotaryFlywheel

Consider Modular UPS (An Option to Maximize UPS Load Capacity)

Best Practices

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY

Page 12: 10 electrical-systems

Electrical Systems

Best Practices (continue)

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY

Managing UPS Load Capacity (continue:)

Example: 10% difference in UPS efficiency per 1000 kW IT Load results in approx. 900 MWhr of Energy saving per year and approx $400K of Energy saving over 5 years.

Result >> Overall Energy Effectiveness is high.

74.0%76.0%78.0%80.0%82.0%84.0%86.0%88.0%90.0%92.0%94.0%96.0%98.0%

0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

Double Conversion UPS Delta Coversion UPS Rotary UPS Flywheel UPS

Most UPS units in N or N+X configuration operate at 10% to 40% load capacity

Page 13: 10 electrical-systems

Electrical Systems

Best Practices (continue)

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY

UPS Input SpecsSpecify / Consider UPS system with Lower Input Current THD at 10- 40% load capacity Specify / Consider UPS system with higher Power Factor at 10– 40% load capacity.

Load % P.F. THD Losses10 0.650 63.0 15.00%25 0.695 60.5 12.80%50 0.764 40.5 8.40%75 0.800 30.0 7.30%

UPS without Filter

Load % P.F. THD Losses10 0.770 25.0 15.00%25 0.820 10.0 8.00%50 0.840 6.0 6.00%75 0.900 5.0 5.60%

UPS with Filter NOTE:Input Current THD increases, and PF decreases when UPS operates at lower load capacity

Example: 10% difference in Input current THD per 1000 kW IT Load results in approx. 900 MWhr of Energy saving per year and approx $400K of Energy saving over 5 years.

Result >> Overall Energy Effectiveness is high

Page 14: 10 electrical-systems

Electrical Systems

Transformers & PDUs (with built-in Transformer):Specify / Consider Transformers with Higher Efficiency:

Transformers with 80°C temperature rise. For example:A transformer with an 80°C temperature rise uses 13- 21% less operating

energythan a 150°C rise unit.The higher-efficiency 80°C rise transformers have a first-cost premium,

but ashorter payback than the less-efficient 150°C rise transformers.

NEMA TP1 Transformers.Higher Efficient Transformers that exceed Benchmarking Efficiency:

ASHRAE 90.1, EPACT 2005, TP1Install Low voltage (LV) transformers outside the raised floor areaReduce the number of PDUs (with built-in Transformer) inside the Data Center.

Result >> Overall Energy Effectiveness is Medium / High

Best Practices (continue)

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY

Page 15: 10 electrical-systems

Electrical Systems

Energy Deficiency Typical 112.5kVA Nonlinear UL listed transformer

90%

91%

92%

93%

94%

95%

96%

97%

98%

99%

100%

1 5 9 13 17 21 25 29 33 37 41 45 49 53 57 61 65 69 73 77 81 85 89 93 97 101

% Loading

Effic

ienc

y (%

)

Typical Tx with Linear Load

Typical Tx with Nonlinear Load

Significant variation in efficiency over load range & concentration of electronic equipment

Courtesy of PowerSmithsCourtesy of PowerSmiths

Page 16: 10 electrical-systems

Electrical Systems

45kVA Efficiency Comparisons vs. Field Data & TP-1

95%

96%

97%

98%

99%

0

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

% loading

% E

fficien

cy

0

10

20

30

40

50

60

# tran

sfor

mer

s

Field Load DataPow ersmiths ESAVER-C3HTP1Pow ersmiths ESAVER-C3L

TP-1, 35%

High Performance vs. TP1 (EPACT 2005) transformer

ESAVER C3L ESAVER C3L --> Light Load optimized, > Light Load optimized, C3H C3H --> Heavy Load optimized> Heavy Load optimized

XX

Courtesy of PowerSmithsCourtesy of PowerSmiths

Page 17: 10 electrical-systems

Electrical Systems

Best Practices (continue)

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY

LightsUse energy Efficient LightsLights in raised floor area are located above the aislesMaintain regular and proper maintenance includes periodic cleaning and re-lampingReplace older coil / core Ballasts type with new efficient electronic ones.Remove the Ballast from the fixture when the lamp is removed. (some Ballast types consume power even if the lamp is removed)Switch off lights in unused / occupied areas or rooms (UPS, Battery, S/Gear, etc)

Result >> Overall Energy Effectiveness is low

Stand-By GeneratorsRight Sizing of Stand-by GeneratorMaintain N+1 RedundancyCheck with the emergency generator manufacturer on how to reduce the overall energy consumption of heater water jacket(s) (HWJ), i.e. temperature control

Result >> Overall Energy Effectiveness is low

Page 18: 10 electrical-systems

Electrical Systems

Facility-Level DC Distribution

DC Power DistributionEliminate two stages of power conversion.

Result >> Overall Energy Effectiveness is High

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY

Best Practices (continue)

Page 19: 10 electrical-systems

Electrical Systems

Rack-Level DC Distribution

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY

Best Practices (continue)

DC Power Distribution (continue)

Page 20: 10 electrical-systems

Electrical Systems

DC/ACAC/DC480 VACBulk Power

Supply

UPS PDU

AC/DC DC/DC VRM

VRM

VRM

VRM

VRM

VRM

12 V

Loadsusing

LegacyVoltages

Loadsusing

SiliconVoltages

12 V

5 V

3.3 V

1.2 V

1.8 V

0.8 VServer

PSU

AC/DC480 VACBulk Power

SupplyDC UPS

orRectifier

DC/DC VRM

VRM

VRM

VRM

VRM

VRM

12 V

Loadsusing

LegacyVoltages

Loadsusing

SiliconVoltages

12 V

5 V

3.3 V

1.2 V

1.8 V

0.8 VServer

PSU

380 VDC

2-5% measured improvement

Rotary UPS

7-7.3% measured improvement

AC System Loss Compared to DC

Best Practices (continue)

DC Power Distribution (continue)

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY

Page 21: 10 electrical-systems

Electrical Systems

Best Practices (continue)

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY

Purchasing ProcessSelection and Purchasing of Equipment should always be based not only on its initial purchase price or lowest bid but should also include its life operating energy cost, Any time there is a new Data Center Faculty is built, an existing facility is expanded, or equipment is being replaced there is a significant opportunity to save on energy costs by selecting and installing cost-effective, energy-efficient equipment.

“The least expensive equipment to buy may cost much more to operate.”

Result >> Overall Energy Effectiveness is High

Page 22: 10 electrical-systems

Electrical Systems

Best Practices (continue)

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY

Awareness & Energy ManagementRaise awareness and develop understanding among Data Center staff about the financial and environment impact of energy savings. Develop Effective energy management Program.Perform Routine Energy saving opportunities and best practices for data centersReview full system operation, and efficiency on regular basis.Perform an Infra-Red (IR) test for the main transformers and other electrical systemsImprove the load balance between the phasesChange UPS DC capacitors if older than 5 yearsMetering:

Install meters (EPMS) to measure instant DCiE values for the Data CenterInstall monitoring equipment to measure system efficiency and performance.install Meters in every RPP, PDU, STS, etcInstall Metered Power Strip in every IT Rack

Result >> Overall Energy Effectiveness is Medium

Page 23: 10 electrical-systems

Electrical Systems

Employ alternate energy source to provide power for generator engine block heaters, lights (Data Center, UPS / Switchgear rooms, etc), etc.:

SolarWindFuel Cells

Distributed Generation (DG):Diesel or Gas- Fired GeneratorsGas TurbinesMicro-TurbinesFuel CellsWindBio-Mass

Contact the Stand-by Genenerator Manufacturer on how to reduce the overall energy consumption of the block heaters per year by using temperature (thermostat) control. Employ lighting controls such as occupancy sensors for data center, emergency generator(s), UPS(s), and Battery rooms

Alternative Energy Source

Controls (Thermostat, Sensors, ETC)

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY

Page 24: 10 electrical-systems

Electrical Systems

• Distributing higher voltage (AC or DC) is more efficient• Electrical power conversions are inefficient• Highly efficient UPSs should be specified• Highly efficient Transformers should be specified• Highly efficient Lightings should be specified• Highly efficient IT equipment power supplies should be specified• Standby generation losses can be minimized• On-site generation can improve reliability and efficiency• Consider Alternative Energy Sources• Raise awareness and develop Energy management Program• Selection and Purchasing of Equipment should be based on operating energy cost.

Take Aways

Page 25: 10 electrical-systems

Electrical Systems

Professional Help

This curriculum is not intended to provide answers to all related questions.

Professionals specialized in Energy Saving should be able to assist in identifying root causes of Energy Inefficiency / Waste, and maximizing Energy Efficiency.

Page 26: 10 electrical-systems

Electrical Systems

Overall power use in data centers

Courtesy of Michael Patterson, Intel Corporation

Page 27: 10 electrical-systems

Electrical Systems

Electrical Systems Efficiency• Electrical distribution systems

• Lighting

• Standby generation

• On-site generation

Page 28: 10 electrical-systems

Electrical Systems

local distribution lines

to the building, 480 V

HVAC system

lights, office space, etc.

UPS PDU computer racks

backup diesel generators

Electricity Flows in Data CentersElectricity Flows in Data Centers

computerequipment

uninterruptible

load

UPS = Uninterruptible Power Supply

PDU = Power Distribution Unit;

Page 29: 10 electrical-systems

Electrical Systems

Electrical Distribution• Every power conversion (AC DC, DC AC, AC AC)

loses some power and creates heat• Distributing higher voltage is more efficient and saves

capital cost (wire size is smaller)• Uninterruptible power supplies (UPS’s) efficiency varies• Power supplies in IT equipment efficiency varies

Page 30: 10 electrical-systems

Electrical Systems

Data center power conversions

Inverter

In Out

Bypass

Battery/ChargerRectifier

Internal Drive

External Drive

I/O

Memory Controller

μ Processor

SDRAM

Graphics Controller

DC/DCAC/DC

DC/DC

AC/DC Multi outputPower Supply

Voltage Regulator Modules

5V

12V

3.3V

12V 1.5/2.5V

1.1V-1.85V

3.3V

3.3V

12V

PWM/PFCSwitcher

Unregulated DCTo Multi Output Regulated DC

Voltages

Power Distribution Unit (PDU)

ServerUninterruptible Power Supply (UPS)

AC DC

AC DC

Page 31: 10 electrical-systems

Electrical Systems

Electrical Power Conversions

45%

50%

55%

60%

65%

70%

75%

80%

85%

0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

% of Nameplate Power Output

% E

ffici

ency

Average of All Servers

Factory Measurements of UPS Efficiency

70%

75%

80%

85%

90%

95%

100%

0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

Percent of Rated Active Power Load

Effic

ienc

y

Flywheel UPS

Double-Conversion UPS

Delta-Conversion UPS

(tested using linear loads)Observed conversion losses suggested

other solutions

Page 32: 10 electrical-systems

Electrical Systems

LBNL DC Demonstration

DC/ACAC/DC480 VACBulk Power

Supply

UPS PDU

AC/DC DC/DC VRM

VRM

VRM

VRM

VRM

VRM

12 V

Loadsusing

LegacyVoltages

Loadsusing

SiliconVoltages

12 V

5 V

3.3 V

1.2 V

1.8 V

0.8 VServer

PSU

Today: AC DistributionToday: AC Distribution

480 VAC building

power supply

Page 33: 10 electrical-systems

Electrical Systems

LBNL DC Demonstration

AC/DC480 VACBulk Power

SupplyDC UPS

orRectifier

DC/DC VRM

VRM

VRM

VRM

VRM

VRM

12 V

Loadsusing

LegacyVoltages

Loadsusing

SiliconVoltages

12 V

5 V

3.3 V

1.2 V

1.8 V

0.8 VServer

PSU

380 VDC480 VAC Building Power

FacilityFacility--Level DC DistributionLevel DC Distribution380 VDC

Page 34: 10 electrical-systems

Electrical Systems

LBNL DC Demonstration

RackRack--Level DC DistributionLevel DC Distribution

DC/ACAC/DC480 VACBulk Power

Supply

UPS PDU

AC/DC DC/DC VRM

VRM

VRM

VRM

VRM

VRM

12 V

Loadsusing

LegacyVoltages

Loadsusing

SiliconVoltages

12 V

5 V

3.3 V

1.2 V

1.8 V

0.8 V

Server

380 VDC

Rack

PSU

480 VAC

Building Power

Page 35: 10 electrical-systems

Electrical Systems

DC Demonstration – Physical Set-up

Page 36: 10 electrical-systems

Electrical Systems

Video of DC demonstration

Page 37: 10 electrical-systems

Electrical Systems

Measured UPS performance

Page 38: 10 electrical-systems

Electrical Systems

UPS factory measurementsFactory Measurements of UPS Efficiency

70%

75%

80%

85%

90%

95%

100%

0% 20% 40% 60% 80% 100%

Percent of Rated Active Power Load

Effic

ienc

y

Flywheel UPS

Double-Conversion UPS

Line-Interactive, DeltaConversion UPS

(tested using linear loads)

Typical Operation

Page 39: 10 electrical-systems

Electrical Systems

UPS Draft Labeling StandardBased upon proposed European StandardPossible use in incentive programs

Page 40: 10 electrical-systems

Electrical Systems

Redundancy• Understand what redundancy costs – is it worth it?• Different strategies have different energy penalties (e.g.

2N vs. N+1)• Redundancy in electrical distribution always puts you

down the efficiency curve

Page 41: 10 electrical-systems

Electrical Systems

Typical operation

Measured power supply efficiency

Page 42: 10 electrical-systems

Electrical Systems

Data center lighting• Lights are on and nobody’s home• Lighting controls are well proven – why not use them?• Small benefit but easy to accomplish – also saves HVAC

energy• DC lighting would compliment DC distribution

Page 43: 10 electrical-systems

Electrical Systems

Standby generation loss• Several load sources

– Heaters– Battery chargers– Transfer switches– Fuel management systems

• Heaters (many operating hours) use more electricity than the generator will ever produce (few operating hours)

• Opportunity may be to reduce or eliminate heating, batteries, and chargers

Page 44: 10 electrical-systems

Electrical Systems

Standby generator heater

Page 45: 10 electrical-systems

Electrical Systems

On-site generation• On-site generation with utility back-up• Thermal host required for combined heat and power

– Absorption or adsorption chillers– Other campus use

• Renewable sources (future)– Fuel cells– Solar– Wind

Page 46: 10 electrical-systems

Electrical Systems

Best Electrical Practices

UPS systemsSelf-generationAC-DC distributionStandby generation

Page 47: 10 electrical-systems

Electrical Systems

Electrical take aways• Distributing higher voltage (AC or DC) is more efficient• Electrical power conversions are inefficient• Highly efficient UPS’s should be specified• Highly efficient IT equipment power supplies should be

specified• Lighting is a small but low hanging opportunity• Standby generation losses can be minimized• On-site generation can improve reliability and efficiency