Upload
john-rose
View
693
Download
99
Embed Size (px)
Citation preview
1
Reinforced Concrete Design II
Lecture 13
Dr. Nader Okasha
Footing Design
2
Footing
Introduction
Footings are structural elements used to support columns and walls and transmit their
loads to the underlying soil without exceeding its safe bearing capacity below the
structure.
Column
Beam
Loads
Footing
Soil
M
P
L
B
P
L
B
3
The design of footings calls for the combined efforts of geotechnical and structural
engineers.
The geotechnical engineer, on one hand, conducts the site investigation and on the light
of his findings, recommends the most suitable type of foundation and the allowable
bearing capacity of the soil at the suggested foundation level.
The structural engineer, on the other hand, determines the concrete dimensions and
reinforcement details of the approved foundation
Footing
Introduction
4
Isolated Footings
Isolated or single footings are used to support single columns. This is one of the most
economical types of footings and is used when columns are spaced at relatively long
distances.
P
L
B C2
C1
P kN
Types of Footing
5
Types of FootingWall Footings
Wall footing are used to support structural walls that carry loads for other floors or to
support nonstructural walls.
Wall
Footing
Main reinft.
Secondary reinft
W kN/mW kN/m
6
Combined Footings
Combined footings are used when two columns are so close that single footings cannot be used. Or, when one column is located at or near a property line. In such a case, the load on the footing will be eccentric and hence this will result in uneven distribution of load to the supporting soil.
P2P1
P1 kN
P2 kN
C2
C1
C2
C1
L
B
L2L1 L2
Types of Footing
7
Combined Footings
The shape of combined footing in plan shall be such that the centroid of the foundation plan coincides with the centroid of the loads in the two columns. Combined footings are either rectangular or trapezoidal. Rectangular footings are favored due to their simplicity in terms of design and construction. However, rectangular footings are not always practicable because of the limitations that may be imposed on its longitudinalprojections beyond the two columns or the large difference that may exist between the magnitudes of the two column loads. Under these conditions, the provision of a trapezoidal footing is more economical.
Types of Footing
8
Continuous Footings
Continuous footings support a row of three or more columns
P1
P1 kN
L
B
P2 kN
P3 kN
P4 kNP2 P3 P4
Types of Footing
9
Strap (Cantilever ) footings
Strap footings consists of two separate footings, one under each column, connected together by a beam called “strap beam”. The purpose of the strap beam is to prevent overturning of the eccentrically loaded footing. It is also used when the distance between this column and the nearest internal column is long that a combined footing will be too narrow.
P2P1
P1 kN
C2
C1
C2
C1
B1
P2 kN
B2
L1 L2
Strap Beam
prop
erty
line
Types of Footing
10
Mat (Raft) Footings
Mat Footings consists of one footing usually placed under the entire building area. They
are used when soil bearing capacity is low, column loads are heavy and differential
settlement for single footings are very large or must be reduced.
L
B
Types of Footing
11
Pile caps
Pile caps are thick slabs used to tie a group of piles together to support and transmit
column loads to the piles.
P
L
B
Types of Footing
12
Distribution of Soil Pressure
The distribution of soil pressure under a footing is a function of the type of soil, the
relative rigidity of the soil and the footing, and the depth of foundation at level of
contact between footing and soil
For design purposes, it is common to assume the soil pressures are linearly distributed.
The pressure distribution will be uniform if the centroid of the footing coincides with
the resultant of the applied loads
P
L
P
L
P
L
Footing on sand Footing on clay Equivalent uniform distribution
Centroidal axis
13
Footing
Pressure Distribution Below Footings
The maximum intensity of loading at the base of a foundation which causes shear
failure of soil is called ultimate bearing capacity of soil, denoted by qu.
The allowable bearing capacity of soil is obtained by dividing the ultimate bearing
capacity of soil by a factor of safety on the order of 2.50 to 3.0.
The allowable soil pressure for soil may be either gross or net pressure permitted on the
soil directly under the base of the footing.
The gross pressure represents the total stress
in the soil created by all the loads above the
base of the footing.
a net soil pressure is used instead of the gross pressure value
P
Dfh
14
Footing
Concentrically loaded Footings
If the resultant of the loads acting at the base of the footing coincides with the centroid
of the footing area, the footing is concentrically loaded and a uniform distribution of
soil pressure is assumed in design, as shown in the figure
Centroidal axis
P
L
P/A
B
L
15
Footing
Eccentrically Loaded Footings
Footings are often designed for both axial load and moment. Moment may be caused by
lateral forces due to wind or earthquake, and by lateral soil pressures.
Footing is eccentrically loaded if the supported column is not concentric with the
footing area or if the column transmits at its juncture with the footing not only a vertical
load but also a bending moment.
Centroidal axis
P
L
P/A
Pey/I
y
eM
P
L
P/A
My/I
y
Centroidal axis
16
Footing
17
Eccentrically Loaded Footings
Footing
18
Eccentrically Loaded Footings
Footing
3
19
Eccentrically Loaded Footings
Footing
In this case, compressive stresses develop over the entire base of thefooting
20
Eccentrically Loaded Footings
Footing
Large eccentricities cause tensile stresses on part of the base area of thefooting. With the dimensions of the footing established and the eccentricity ofthe vertical load known, the distance between the resultant of the appliedload P and the outside edge a can be established. The length of base on which the triangular distribution of soil pressure acts is equal to 3a, where a = L / 2 − e. Equating the resultant of the soil pressure to the applied forces gives
Eccentrically Loaded FootingDesign
21
22
Eccentrically Loaded Footings
Design Procedure
1.0 1.0
Check service stresses to ensure pressure is all compressive under the footing
If tension stresses develop, resize the footing
23
Eccentrically Loaded Footings
Design Procedure
The critical section for punching shear is located at distance d / 2 from column faces and usually takes the shape of the column.
Calculate Vu using the volume under the trapezoidal shaped stress distribution.
1.2 1.6
= 0.75
24
Eccentrically Loaded Footings
Design Procedure
The critical section for punching shear is located at distance d /2 from column faces and usually takes the shape of the column.
25
Eccentrically Loaded Footings
Design Procedure
= 1.0 for normal weight concrete
26
Eccentrically Loaded Footings
Design Procedure
27
Eccentrically Loaded Footings
Design Procedure
Calculate Mu using the volume under the trapezoidal shaped stress distribution.
28
Eccentrically Loaded Footings
Design Procedure
According to ACI Code 15.4.3, for square footings, the reinforcement is identical in both directions. For rectangular footings, the reinforcement in the long direction is uniformly distributed while the reinforcement in the short direction is concentrated in a band centered on centerline of column and with a width equals to the short dimension of the footing.
29
Eccentrically Loaded Footings
Example 1
30
Eccentrically Loaded Footings
Example 1
In order to have uniform soil pressure under the footing, the footing is to be positioned in such a way to balance the given moment through shifting thecentroid of the footing 0.25 m away from the centroid of the column
Continue the design as a concentrically loaded footing supporting only the axial loads transmitted by the column
31
Eccentrically Loaded Footings
Example 2
32
Eccentrically Loaded Footings
Example 2
33
Eccentrically Loaded Footings
Example 2
Pu = 1.2PD + 1.6PL = 69 tons
34
Eccentrically Loaded Footings
Example 2
Should use as 0.75
35
Eccentrically Loaded Footings
Example 2
Should use as 0.75
36
Eccentrically Loaded Footings
Example 2
Should use as 0.75
Eccentrically Loaded Footings
Example 2
5
2
5
2
0.85 2 101 1
0.85
0.85 250 2 10 0.871 1 0.00003
4200 0.85 0.9 250 400 (40.9)
c u
y c w
f M
f f b d
38
Eccentrically Loaded Footings
Example 2
Combined FootingDesign
39
40
Combined Footings
Design Procedure
41
Combined Footings
Design Procedure
42
Combined Footings
ExampleDesign an appropriate footing/footings to support two columns A and B spaced at distance 2.1 m center-to-center. Column A is 20 cm × 30 cm and carries a dead load of 20 tons and a live load of 10 tons. Column B is 20 cm × 40 cm in cross section but carries a dead load of 30 tons and a live load of 15 tons. Width of footing is not to exceed 1.0 m, and there is no property line restriction.
43
Combined Footings
Example
44
Combined Footings
Example
2.1 m
Pa Pb
x1
R
x2l1 l2
45
Combined Footings
Example
Should use DL
46
Combined Footings
Example
47
48
Combined Footings
Example
49
Combined Footings
Example
50
Combined Footings
Example
51
Combined Footings
Example
52
Combined Footings
Example