1
Unit QTY Watt 1250 KVA Transformer Losses a. No-load Losses 2500 16 40 b. Load Losses 14000 8 112 100 KVA Transformer Losses a. No-load Losses 300 16 4.8 b. Load Losses 1400 8 11.2 Control room illumination No.s 6 40 24 5.76 5.76 Plant Illumination No.s 10 100 10 10 10 Control Room Exhaust Fan No.s 2 300 24 14.4 14.4 Inverter Auxiliary Power a. In operation 650 8 5.2 5.2 b. Stand-by 65 16 1.04 1.04 Water pumps for Panel Cleaning No.s 2 1500 2 6 6 210.4 Per Day 42.4 76,796 Per Year 15,476 Operating Hours No. of Units

1 MW Auxiliary Power Consumption

Embed Size (px)

DESCRIPTION

Solar power plant auxiliary consumption pattren and

Citation preview

Sheet1UnitQTYWattOperating HoursNo. of Units 1250 KVA Transformer Lossesa. No-load Losses25001640b. Load Losses140008112

100 KVA Transformer Lossesa. No-load Losses300164.8b. Load Losses1400811.2

Control room illuminationNo.s640245.765.76

Plant IlluminationNo.s10100101010

Control Room Exhaust FanNo.s23002414.414.4

Inverter Auxiliary Powera. In operation65085.25.2b. Stand-by65161.041.04

Water pumps for Panel CleaningNo.s21500266210.4Per Day42.4157500076,796Per Year15,4760.0098260317