Upload
herbert-edwards
View
217
Download
1
Embed Size (px)
Citation preview
1© 2013 Eaton. All Rights Reserved.
UL/ANSI/NEMALow Voltage Circuit Breakers
2© 2013 Eaton. All Rights Reserved.
Product
Standards and
Certification
InstallationCodes
Safe Products and Safe
Installations
Inspection and
Enforcement
(verification)
“System” Consideration
3© 2013 Eaton. All Rights Reserved.
UL Standards for LV components
• UL 98: Enclosed and Deadfront Switches
• UL 508: Industrial Control Equipment
• UL 489: Molded Case Circuit Breakers
• UL 1066: LV Power Circuit Breakers
4© 2013 Eaton. All Rights Reserved.
UL Standards for LV Assemblies• UL 67: Panelboards
• UL 891: Switchboards
• UL 1558: LV Switchgear
• UL 845: Motor Control Centers
• UL 857: Busway
• UL 508A: Industrial Control Panels
5© 2013 Eaton. All Rights Reserved.
IEC Standards for LV Components
• IEC 60947: LV Switchgear and Controlgear
• Part 1: General rules
• Part 2: Circuit breakers• Part 3: Switches, disconnectors…
• Part 4 series: Contactors and motor-starters
• Part 5 series: Control circuit devices and switching elements
• Part …
• Part …
6© 2013 Eaton. All Rights Reserved.
IEC Standards for LV Assemblies
• IEC 61439: LV Switchgear and Controlgear Assemblies
• Part 1: General rules
• Part 2: Power Switchgear
• Part 3: Distribution boards operated by ordinary persons
• Part 4: Construction sites
• Part 5: Distribution in public networks
• Part 6: Busbar Trunking Systems (Busways)
• Part 7: Marinas, camping sites, market squares, EV charging
7© 2013 Eaton. All Rights Reserved.
National Electrical Code, NEC • NFPA 70, contains “installation” rules
- Cable connections = AWG sizes- Wire bending spaces- Enclosure type designations- Grounding- Working spaces- Creepage/Clearance distances- Temperature rises- Mentions “Listed” products
o References “product” Standards (Annex A)
8© 2013 Eaton. All Rights Reserved.
UL conformity assessment
• UL Listing provides- Independent confirmation of original
design- On-going factory inspections- Periodic follow-up testing
9© 2013 Eaton. All Rights Reserved.
Support the installed “system”
IEC Components
IEC Assemblies
UL Components
UL Assemblies
SAFE
10© 2013 Eaton. All Rights Reserved.
Do not “intermix”
IEC Components
IEC Assemblies
UL Components
UL Assemblies
UNSAFE
11© 2013 Eaton. All Rights Reserved.
System Considerations - Summary
Support your installed electrical infrastructure Concerns extend beyond individual components Need alignment with Installation requirements Certification confirms initial & continued
compliance Do not intermix IEC and UL products, it will
compromise safety!
12© 2013 Eaton. All Rights Reserved.
UL 1066, Low-Voltage AC and DC Power Circuit Breakers Used in Enclosures
Background/Evolution: LV Power Breakers
13© 2013 Eaton. All Rights Reserved.
Low Voltage Circuit Breaker Standards
IEC & UL
IEC 60947-2Low Voltage Switchgearand Controlgear-Part 2
Circuit Breakers
IEC 60898Circuit-breakers for
overcurrent protection for household and similar installations
UL 489UL Standard for
Molded-Case Circuit Breakers
UL 1066UL Standard for
Low Voltage AC and DCPower Circuit Breakers
used in Enclosures
MouldedCase
CircuitBreakers
Air(Power)Circuit
Breakers
14© 2013 Eaton. All Rights Reserved.
Key differences Power Circuit Breakers have compared to Molded Case Circuit Breakers
Electronic Trip Only Used Primarily in Draw-out Switchboards Serviceable and Maintainable Typically used upstream from Molded Case
Circuit Breakers Provide a Higher Level of Selective Coordination Stored Energy Mechanism
15© 2013 Eaton. All Rights Reserved.
Many Standards differences between IEC 60947-2 and UL 1066, including
• Testing Approach- For example, Short Circuit Interrupting Capability
• Performance Requirements- For example:
- Temperature Rise- Overload
• Follow Up Test Requirements- For example, periodic UL 1066 Follow Up
Testing
16© 2013 Eaton. All Rights Reserved.
Power Circuit Breakers: Short Circuit Capability
UL requires defined/vigorous short circuit verifications and single pole interruption.
IEC 60947-2 UL 1066
• Significant clause is 4.4: Utilization Categories
• Category B “Determine rated short time withstand current”
• Annex H Single Pole Interrupting – Optional
• Ics: Rated Breaking Capacity (Seq. II)
• Icu: Rated Ultimate Capability (Seq. III)
References ANSI/NEMA C37.50 for:• Short-Time Current Duty Cycle
• Carry fault current for two 0.5 second periods
• Short-Circuit Current Duty Cycle• Single Pole Test at 87% of
Interrupting Capacity (ANSI C37.50 Table 4)
• Short Circuit Current Tests required in each Test Sequence (C37.50 Table 1)
17© 2013 Eaton. All Rights Reserved.
IEC UL
Philosophy different for temperature tests
Maximum Allowable Temperature Rise
80°C Enclosure not required, sample previously tested in Seq. I and Seq. II
55˚C Tested in the Enclosure, tested on a new sample (C37.50 Table 1 Sequence V)
Maximum allowable Temperature Rise At the Circuit Breaker Contacts
No value specified but no damage to adjacent parts (Table 7 Note a)
85°C
Power Circuit Breakers: Temperature
18© 2013 Eaton. All Rights Reserved.
IEC UL
UL always requires overload, alsoRequires short circuit test after overload
Overload test requirements
Required for 630A and less, optional above 630A (8.3.3.4 and Test Sequence I)
Required for ALL circuit breakers (ANSI C37.50 Table 1, Seq. 1)
Tests after Overload
Short Circuit Test not required and not part of test sequence Short Circuit Test required
Power Circuit Breakers: Overload Capability
19© 2013 Eaton. All Rights Reserved.
Power Circuit Breakers:Conformance Testing/Conformity Assessment
IEC UL
• Conformance to IEC Standard (CE Mark) typically justified solely by manufacturer’s self declaration
• UL Third-Party Witness of Conformance Testing
• UL Factory Surveillance• UL “procedures” document the
construction/components for on-going compliance
• UL periodic Follow-up Testing based on production volume or number of years (ANSI C37.50 Table 7)
Third-party certification assures independent verification & ongoing conformance
20© 2013 Eaton. All Rights Reserved.
Emerging technology: Addressing Arc Flash Hazards
• Data is available to apply UL low voltage circuit breakers to limit arc flash energy
21© 2013 Eaton. All Rights Reserved.
Circuit breakers were originally intended to protect the installed conductors:
– Protect & prevent possible damage for operating beyond their capability.
– Cut-off current below the cable damage curves.
Traditional Circuit Protection
22© 2013 Eaton. All Rights Reserved.
Arc Flash Hazards
Pressure Waves
Copper Vapor:Solid to VaporExpands by67,000 times
Molten Metal
Intense Light
Hot Air-Rapid Expansion
35,000 °F
Shrapnel
Sound Waves
Pressure Waves
Copper Vapor:Solid to VaporExpands by67,000 times
Copper Vapor:Solid to VaporExpands by67,000 times
Molten Metal
Intense Light
Hot Air-Rapid Expansion
35,000 °F
Shrapnel
Sound Waves
23© 2013 Eaton. All Rights Reserved.
IEEE 1584, Guide for Performing Arc-Flash Hazard Calculations
– Calculate Incident energy• Use fault current level and interruption time of the
overcurrent device.
– Circuit breaker calculation methods do not account for their current limiting aspects!
– Published Papers referencing circuit breaker arc flash applications are:
• “Molded-Case Circuit Breakers reduce Arc-Flash Hazard Impact” NEMA (available for free download from the NEMA Website)
• “Understanding IEEE 1584 Arc-Flash Calculations”, K. J. Lippert, D. M. Colaberardino, and C. W. Kimblin, IEEE IAS Magazine, May/June 2005.
• Applying Low Voltage Circuit Breakers to Limit Arc-Flash Energy”, G. Gregory and K. J. Lippert, IEEE PCIC, September 2006
24© 2013 Eaton. All Rights Reserved.
Comparison of MCCB arc test results Incident Energy
at Bolted Fault Current (kA)
Min Mid Max 250 A MCCB with Thermal - Magnetic Trip Unit Bolted fault current Inc. Energy via IEEE 1584 Table E.1 Generic (Cal/cm
2)
Inc. Energy via IEEE 1584 & Trip Curve (Cal/cm2)
Measured Incident Energy (Cal/cm2)
3.7 kA N/A
1
27.6 0.11
35 kA 1.7 0.9 0.15
100 kA 4.7 1.8 0.13
400 A MCCB with Thermal - Magnetic Trip Unit Bolted fault current Inc. Energy via IEEE 1584 Table E.1 Generic (Cal/cm
2)
Inc. Energy via IEEE 1584 & Trip Curve (Cal/cm2)
Measured Incident Energy (Cal/cm2)
6 kA N/A
1
72 0.12
35 kA 1.7 0.7 0.2
100 kA 4.7 1.4 0.20
600 A MCCB with Thermal - Magnetic Trip Unit Bolted fault current Inc. Energy via IEEE 1584 Table E.1 Generic (Cal/cm
2)
Inc. Energy via IEEE 1584 & Trip Curve (Cal/cm2)
Measured Incident Energy (Cal/cm2)
9 kA N/A
1
46 1.22
35 kA 2.3 1.1 0.78
100 kA 5.7 1.8 0.36
800 A MCCB with Thermal - Magnetic Trip Unit Bolted fault current Inc. Energy via IEEE 1584 Table E.1 Generic (Cal/cm
2)
Inc. Energy via IEEE 1584 & Trip Curve (Cal/cm2)
Measured Incident Energy (Cal/cm2)
12 kA N/A
1
61.4 0.86
35 kA 2.3 1.7 1.14
65 kA 3.9 2.8 1.05
1200 A MCCB with Electronic Trip Unit Bolted fault current Inc. Energy via IEEE 1584 Table E.1 Generic (Cal/cm
2)
Inc. Energy via IEEE 1584 & Trip Curve (Cal/cm2)
Measured Incident Energy (Cal/cm2)
20 kA N/A
1
218 1.86
35 kA 3.5 3.5 1.20
100 kA 9.4 5.8 1.64
2500 A MCCB with Electronic Trip Unit Bolted fault current Inc. Energy via IEEE 1584 Table E.1 Generic (Cal/cm
2)
Inc. Energy via IEEE 1584 & Trip Curve (Cal/cm2)
Measured Incident Energy (Cal/cm2)
35 kA N/A
1
110 3.96
65 kA 7.7 5.4 3.48
100 kA 11.5 6.5 2.12
1.
N/A represents “Not Applicable” because the parameters are outside the range of the
IEEE 1584 Table E.1 generic equation.
25© 2013 Eaton. All Rights Reserved.
Conclusions from Molded Case Circuit Breaker arc flash testing
• In the instantaneous region, tested incident energies are significantly lower than calculated values due to:
• Actual arcing time• Current reduction by the circuit breaker
(particularly for current limiting circuit breakers)
26© 2013 Eaton. All Rights Reserved.
Zone Selective Interlocking (ZSI)
• Many modern circuit breakers have electronic trip units which make them more “intelligent”
• Electronic trips with ZSI allows breakers in the same zone to communicate with each other
• ZSI bypasses the preset short delay time (and ground fault delay time when available) on the upstream circuit breaker closest to the fault, which then trips with no intentional delay
27© 2013 Eaton. All Rights Reserved.
Zone A
Feeder 1
Circuit Breaker
Circuit Breaker
Circuit Breaker
Circuit Breaker
Feeder 2 Feeder 3
Main 1
All is OK here, so I’m quiet.
All is OK here, so I’m quiet.
I sense trouble!
Circuit Breaker
Circuit Breaker
Zone Selective Interlocking (ZSI)
All is OK here, so I’m quiet.
When a fault occurs at point X...
X
28© 2013 Eaton. All Rights Reserved.
Zone A
Feeder 1
Circuit Breaker
Circuit Breaker
Circuit Breaker
Circuit Breaker
Feeder 2 Feeder 3
Main 1
Circuit Breaker
Circuit Breaker
Zone Selective Interlocking (ZSI)
X
Without ZSI, I’d normally wait for my Short Delay time, and then open!
But with ZSI… since none of my downstream buddies are telling me that they sense trouble, I know not to wait at all, and open as quickly as I can!
29© 2013 Eaton. All Rights Reserved.
Zone A
Feeder 1
Circuit Breaker
Circuit Breaker
Circuit Breaker
Circuit Breaker
Feeder 2 Feeder 3
Main 1
Circuit Breaker
Circuit Breaker
Zone Selective Interlocking (ZSI)However, when a fault occurs at point XX...
XX
I sense trouble!
I sense trouble too! Hey upstream buddy, hang in there, I’ve got it!All is OK here, so
I’m quiet.
All is OK here, so I’m quiet.
Coordination Is Maintained!
30© 2013 Eaton. All Rights Reserved.
ZSI Arc Flash Example
With ZSI = 0.08 S:7.0* Cal/cm2
FR Shirt & Pants + Cotton underwear
Cat. 2 PPE
Without ZSI = 0.5 S:43.7* Cal/cm2
Greater than Cat. 4 PPE!
FIND ALTERNATIVES!
Short Delay=0.5S
ShortDelay=0.3S
Feeder 1
Circuit Breaker
Circuit Breaker
Circuit Breaker
Circuit Breaker
ShortDelay=0.3S
ShortDelay=0.3S
Feeder 2 Feeder 3
Main 1
X35kA fault current
* Using IEEE 1584: 480V-35kA, MCC, 18” from Arc
31© 2013 Eaton. All Rights Reserved.
Arc-reducing maintenance switching• Manually or Automatically enables an
instantaneous pickup• Trip Times May Vary Between Manufacturers
– Some may be same as Instantaneous– Some my be faster than Instantaneous
• Reduces arc energy to downstream equipment/personnel
• Limits energy available during maintenance
EXAMPLE:
•Normal settings calculates to 10.7 cal (Cat. 3)
•With Arcflash Reduction Maintenance Switch 2.2 cal (Cat. 1)
32© 2013 Eaton. All Rights Reserved.
Arc flash mitigation system
• When activated, this technology continuously monitors current and voltage to identify an arc flash.
• When an arc flash occurs, the arc is automatically dealt with, without changes to the circuit breaker.
• Sometimes referred to as “crowbar systems”
33© 2013 Eaton. All Rights Reserved.
Summary of UL circuit breaker applicationsto reduce arc flash energy
• Use Arc flash energy values published by the circuit breaker manufacturer
• Zone Selective Interlocking
• Arc Reduction Maintenance Switch
• Arc Flash Mitigation Systems
34© 2013 Eaton. All Rights Reserved.
UL 489B, Outline of Investigation for Molded-Case Circuit Breakers …for Use with Photovoltaic (PV) Systems
Emerging technology: PV Circuit Breakers
35© 2013 Eaton. All Rights Reserved.
• UL 489B:- First published July, 2010 - Several manufacturers have UL Listed
products
• IEC 60947-2- No published requirements yet for PV
breakers- CD circulated 2014-02-28
UL 489B and IEC
36© 2013 Eaton. All Rights Reserved.
UL 489B PV Circuit Breaker Requirements
• 1500 V dc capability
• Rated/marked for 50 C
• Vigorous dc current tests
• Evaluated for reverse direction current
37© 2013 Eaton. All Rights Reserved.
www.eaton.com