DESCRIPTION
• Aluminium alloy body with low copper contents • Shockproof and temperature-resistant borosilicate front glass cover • Anodized aluminium reflecting parabolic reflector • Hot galvanized steel clamp • Internal and external stainless steel ground screw • Wiring consisting of silicone rubber cables with glass braid insulation up to 200°C • RAL 7035 grey epoxy powder coating 62 E x d E x d CONFORMIDAD CON LA NORMATIVA STANDARD CONFORMITY TO STANDARDS TECHNICAL FEATURES
Citation preview
62
CONFORMITY TO STANDARDS
INSTALLATION AREAS
CERTIFICATION AND USE
RRLLEEEE……Series/Serie
Explosion-proof floodlights built to CENELEC standards EN 60079-1:2004, EN 60079-0: 2006, EN 64241-1: 2004, EN 64241-0: 2006 andEUROPEAN DIRECTIVE 94/9/EC: 1994.
These floodlights can be installed indoors or outdoors in potentiallyhazardous atmospheres containing explosive or combustible gasesand dusts. They are installed in the following zones: zone 1, zone 2,zone 21 and zone 22.
Execution 0722: II 2GD Ex d IIC T3/T4 Ex tD A21 IP 66
(Protection against combustible gases and dusts)
Max surface temperature: 200°C (T3)
135°C (T4)
Ambient temperature: -20°C +45°C
Ambient temperature (RLEE 107): -20°C +55°C
CE test certification of type: CESI 03 ATEX 199
CE test certification ( RLEE-107): CESI 04 ATEX 093Exec. IIB
Lampholder: EDISON 40 (E-40)Rated voltage: 230 V ac (other voltages on request)Wiring: Direct connection to the terminal box L, N,
Pe section. 4 mm2 .Power factor: 0.96
TECHNICAL FEATURES
CONFORMIDAD CON LA NORMATIVA STANDARD
LUGARES DE INSTALACIÓN
EJECUCIÓN Y CERTIFICACIÓN
CARACTERÍSTICAS TÉCNICAS
Ex d
Ex d
Los artefactos de iluminación a prueba de explosión se construyen deacuerdo a la directiva 94/9/EC y a las normas IEC/EN 60079.0; 60079.1;61241.0; 61241.1
Los artefactos de iluminación pueden ser instalados en lugares conriesgo de explosión por la presencia de gases o polvos combustibles,tanto en el interior como el exterior. Se pueden instalar en lassiguientes áreas clasificadas: Zona 1, Zona 2, Zona 21 y Zona 22
Ejecución 0722: II 2GD Ex d IIC T3/T4 Ex tD A21 IP 66
(Protección contra gases y polvos combustibles)
Máxima temperatura superficial: 200°C (T3)
135°C (T4)
Temperatura ambiente: -20°C +45°C
Temperatura ambiente (RLEE 107): -20°C +55°C
Certificado CE: CESI 03 ATEX 199
Certificado CE ( RLEE-107): CESI 04 ATEX 093Exec. IIB
Portalámparas: EDISON 40 (E-40)Tensión Nominal: 230 V ac (otros voltajes a pedido)Conexión: Conexión directa a la caja de terminales
L.N – sección 4mm, caja de terminales conectada con puentes para la entrada-salida
Factor de potencia: 0.96
• Aluminium alloy body with low copper contents
• Shockproof and temperature-resistant borosilicate front glass cover
• Anodized aluminium reflecting parabolic reflector
• Hot galvanized steel clamp• Internal and external stainless steel
ground screw • Wiring consisting of silicone rubber cables
with glass braid insulation up to 200°C• RAL 7035 grey epoxy powder coating
• Cuerpo en aleación de aluminio con bajo tenor de cobre.
• Vidrio frontal de borosilicato resistente a golpes y cambios de temperatura.
• Reflector parabólico de aluminio anodizado.
• Ménsula de fijación en acero zincado.• Tornillos a tierra interno y externo en
acero inoxidable.• Cableado de cables siliconados con
protección de fibra de vidrio hasta 260ºC.
• Protección en neopren o silicona resistente a los ácidos y a los hidrocarburos.
• Pintura en polvo horneada epoxi color gris RAL 7035..
ESPECIFICACIONES TÉCNICAS TECHNICAL SPECIFICATIONS
10-RLEE_01 EXD-5 20/09/2011 11:02 a.m. Página 62
SODIUM MERCURY MIXED LIGHT METAL HALIDE
SODIO MERCURIO LUZ MIXTA MERCURIO HALOGENADO
N5 250W F5 250W M5 300W IM5 250W
N6 400W F6 400W M6 500W IM6 400W
- F7 700W - -
SELECTION TABLE - TABLA DE SELECCIÓN
POTENCIA PORTALÁMPARA CLASE MAX TEMPERATURA TIPODE LÁMPARA DE TEMPERATURA SUPERFICIAL °C PROYECTOR
LAMP LAMPHOLDER TEMPERATURE MAX SURFACE FLOODLIGHTSPOWER CLASS TEMPERATURE °C TYPE
63
RRLLEEEE……Series/Serie
NOTESNOTAS
INCHgNaHaMix
Incandescent lampMercury vapour lampHigh pressure sodium vapour lampMetal halide lampMixed light lamp
INCHgNaHaMix
Lámpara incandescenteLámpara a vapor de mercurioLámpara a vapor de sodio de alta presiónLámpara a mercurio halogenadoLámpara de luz mixta
INC
Hg
Na
Mix
Ha
300 W
500 W
250 W
400 W
700 W
250 W
400 W
250 W
400 W
300 W
500 W
T3E40 200
RLEE-35
RLEE-55
RLEE-35
RLEE-55
RLEE-107
RLEE-35
RLEE-55
RLEE-35
RLEE-55
RLEE-35
RLEE-55
Ex
dE
x d
RLEE… series floodlights can be installed with discharge lamps using a separate enclosure for electrical parts (see page 41).
Los proyectores de la serie RLEE… pueden ser instalados con lámparas de descarga utilizando una caja separada para las partes eléctricas
ORDER CODE EXAMPLEEJEMPLO CODIGO DE PEDIDO
400W Mercury - 400W Mercurio
Floodlight size - Tamaño del proyector
Floodlight type- Tipo de proyector
RLEE - 55 6F-
10-RLEE_01 EXD-5 20/09/2011 11:02 a.m. Página 63
64
RRLLEEEE…… Series/Serie
CONSTRUCTION SPECIFICATIONS - CARACTERÍSTICAS DE CONSTRUCCIÓN
WEIGHT - PESO(Kg)
287
382
595
395
430
585
473
595
760
78
78
110
8,5
8,5
12
12,25
20,35
44,25
190
190
250
204
295
400
RLEE-35
RLEE-55
RLEE-107
DIMENSIONS - DIMENSIONI (mm)
EXTERNAL LIGHT FASTENINGEXTERNA LUZ FIJACION
A B C Ø a Ø E r Ø d
Ex d
Ex d
MODELMODELO
10-RLEE_01 EXD-5 20/09/2011 11:02 a.m. Página 64
Cable gland Prensa cable
Note: for models, codes and specifications, see cable glands/boxes catalogue.
Nota: Nota: por modelos, códigos y características vercatálogos prensa cables
65
RRLLEEEE…… Series/Serie
BOX WITH ELECTRICAL PARTS - CAJA CON PARTE ELECTRICA
RLEE-35
RLEE-55
RLEE-107
RLEE-35
RLEE-55
RLEE-107
E40
E40
E40
E40
E40
E40
E40
E40
E40
E40
E40
E40
750V 16A
For special executions
Para usos particulares
300 W
500 W
250 W
400 W
700 W
250 W
400 W
250 W
400 W
250 W
500 W
G-070
G-074
G-0112
G-162
G-160
G-308
PORT E-40
TPL4
LAMPNC300W
LAMPNC500W
LAMP-250WHQL
LAMP-400WHQL
LAMP-700WHQL
LAMPNAV250W
LAMPNAV400W
LAMP250WJM
LAMP400WJM
LAMP250WHWL
LAMP500WHWL
RLEE-35 250 W Hg GUB-02/F5
RLEE-55 400 W Hg GUB-03/F6
RLEE-107 700 W Hg EJB-3B/F7
RLEE-35 250 W Na GUB-02/N5
250 W Na GUB-03/N5
400 W Na GUB-03/N6
RLEE-35 250 W Ha GUB-02/IM5
250 W Ha GUB-03/IM5
400 W Ha GUB-03/IM6
Caja portaaparatos eléctricos
Enclosure containing electrical equipment
Sujetador frontal con vidrio
Reflector en aluminiobrillante
Porta lámparas
Bornera de conexión
Lámpara de vapor de sodioalta presión (a pedido)
Lámpara electrónica(a pedido)
Lámpara de luz mixta(a pedido)
Lámpara incandescente(a pedido)
Lámpara de mercuriohalogenado (a pedido)
Shade ring with glass
Polished aluminium reflector
Lampholder
Wiring terminal strip
Mercury vapour lamp(upon request)
Metal halide lamp(upon request)
Mixed light lamp(upon request)
Incandescent lamp(upon request)
High pressure sodium vapour lamp
(upon request)
RLEE-55
RLEE-55
ACCESSORIES AND SPARE PARTS - ACCESORIOS Y PARTES DE RECAMBIO
ILLUSTRATION SIZE SPECIFICATIONS CODEILUSTRACION TAMAÑO CARACTERÍSTICAS CÓDIGOS
DESCRIPTION DESCRIPCIÓN
Ex
dE
x d
RLEE… series floodlights can be installed with discharge lamps using a separate enclosure for electrical parts.
Los proyectores de la serie RLEE… pueden instalarse con lámparas de descarga utilizando una caja separada para las partes eléctricas.
10-RLEE_01 EXD-5 20/09/2011 11:02 a.m. Página 65
66
RRLLEEEE…… Series/Serie Ex d
Ex d
Reflector: Reflector:
Lampholders:Porta lámparas:
Reflector:Reflector:
Lampholders:Porta lámparas:
Shade ring with glass:Sujetador frontal con vidrio:
Shade ring with glass: Ghiera frontale con vetro:
Reflector:Reflector:
Lampholders:Porta lámparas:
RLEE-107 (IIB)
RLEE-55 (IIC)
RLEE-35 (IIC)
G-308
E-40
E-40
E-40
G-160
G-070
G-074
G-162
Shade ring with glass:Sujetador frontal con vidrio:
G-0112
EXPLODED VIEW OF RLEE-107 RLEE-55 RLEE-35 FLOODLIGHTS - SPARE PARTS DESCRIPTION DESPIECE ARTEFACTO PROYECTORES RLEE-107, RLEE-55, RLEE-35 - DESCRIPCIÓN DE PARTES DE REPUESTO
10-RLEE_01 EXD-5 20/09/2011 11:02 a.m. Página 66
67
RRLLEEEE…… Series/Serie
Ex
dE
x d
CODE:CÓDIGO:
RLEE-35 250W HPMV CODE:CÓDIGO:
RLEE-35 250W HPSV
CODE:CÓDIGO:
RLEE-107 1000W INC CODE:CÓDIGO: RLEE-107 500W INC
PHOTOMETRIC DIAGRAM - CURVAS FOTOMÉTRICAS
CODE:CÓDIGO:
RLEE-107 400W HPMV
= plane - plano 90270
= plane - plano C 0180
10-RLEE_01 EXD-5 20/09/2011 11:02 a.m. Página 67
68
RRLLEEEE…… Series/Serie Ex d
Ex d
CODE:CÓDIGO:
RLEE-35 250W IM CODE:CÓDIGO:
RLEE-35 300W INC
CODE:CÓDIGO:
RLEE-35 250W IM CODE:CÓDIGO: RLEE-55 500W INC
PHOTOMETRIC DIAGRAM - CURVAS FOTOMÉTRICAS
CODE:CÓDIGO:
RLEE-55 500W IM CODE:CÓDIGO:
RLEE-55 400W HPMV
10-RLEE_01 EXD-5 20/09/2011 11:02 a.m. Página 68
69
RRLLEEEE…… Series/Serie
Ex
dE
x d
CODE:CÓDIGO:
RLEE-55 400W HPSV CODE:CÓDIGO:
RLEE-55 400W IM
PHOTOMETRIC DIAGRAM - CURVAS FOTOMÉTRICAS
= plane - plano 90270
= plane - plano C 0180
10-RLEE_01 EXD-5 20/09/2011 11:02 a.m. Página 69