Upload
generalclimatic
View
7
Download
1
Embed Size (px)
Citation preview
Setting of the rated current (Ib)
Set the nominal current (In):
Of each machines in cable:– In Lathe = 3 kW -> In = 6 A
– In Milling machine = 11 kW -> In = 20 A
Of a several machines in Canalis:– In = 3 x 11 + 3 x 3 = 42 kW -> In = 80 A
Take into account the Simultaneity factor (Ks)
Canalis: In = 80 x 0.7 = 56 A
N b o f K s
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 12
Rq: for a machine which works continuously / for lighting K=1.
Take into account the expansion factor: generally, in the case of an industrial installations, it needs at least a factor of 1.2 (= leave a margin of 20%)
Canalis: In = 56 x 1.2 = 68 APower sum
N b o fm a c h in e s
K s
2 e t 3 0 ,94 e t 5 0 ,86 à 9 0 ,71 0 à 3 9 0 ,6
4 0 a n d m o r e 0 ,5
Choice of the electrical distribution architecture
Choice of materials according to external influences
Power sum
Sizing of wires
Chronology of a design
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 13
OverloadsPermissive current
Conductors are always sized from the value of the permissive current
It corresponds to the maximal current which can go through the conductor
Beyond this value, the insulation qualities are jeopardised
premature ageing
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 14
A cable which is submitted to a 10%overload current will have a reduced lifetime up to 50%
Sizing
OverloadsPermissive current
The permissive current of a cable is:
Iz = (K x Ib) / (f1 x f2 x f3 x f4 x f5 x n x fs)
The nominal rated current is:
Inc = (K x Ib) / (f1 x f3)
– With:
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 15
– In: Nominal current of the circuit
– K: Type of protection (fuse / circuit breaker)
– f1: Ambient temperature
– f2: Number of conductors loaded in a circuit
– f3: Reference method and fixing mode
– n: Number of parallel cables
– fs: Symmetrical factor
– f4: Number of layers
– f5: Several circuit grouping (joined cables)Sizing
Constant
parameters
whenever
Factors
depending on the evolutions
Iz = (K x In) / (f1 x f2 x f3 x f4 x f5 x fs x n)
Protection by circuit breaker K = 1
Ambient temperature = 30°C f1 = 1
Neutral not loaded f2 = 1
T
R R
Example 1: 5 machines - P = 9 kW/ machine(Cos ϕ = 0.87 / Ib = 15 A)
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 16
Cable with 3 conductors (Méthode E) + cable fixed on cable tray on a horizontal
way (Mode 13) f3 = 1
1 layer f4 = 1
5 non joined circuits f5 = 0,1
No parallel cables n et fs = 1
Iz = (1 x 15) / (1x1x1x1x1x1x1) = 15 A
R R R
S theoric = 1.08 mm² S chosen = 1.5 mm²
Example 2: 9 machines - P = 9 kW / machine(Cos ϕ = 0.87 then Ib = 15 A)
Iz = (K x In) / (f1 x f2 x f3 x f4 x f5 x fs x n)
Protection by circuit breaker K = 1
Ambient temperature de 30°C f1 = 1
Neutral not loaded f2 = 1
Cable with 3 conductors (Méthode E) + cable fixed on cable tray on a horizontalway (Mode 13) f3 = 1R R R
TD
R R R RR
R
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 17
way (Mode 13) f3 = 1
1 layer f4 = 1
9 non joined circuits f5 = 0.72
No parallel cables n et fs = 1
Iz = (1 x 15) / (1x1x1x0,8x0,72x1x1) = 21 A
S theoric = 1.83 mm² S chosen = 2.5 mm²
R R R R
4 machines more:
9 joined circuits f5 = 0.72
Sz1 = 2.5 mm²
Setting up 5 machines in t0:
5 non joined circuits f5 = 1
Sz0 = 1.5 mm²
Evolution from 5 to 9 machines
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 18
Results:
the 5 circuits installed in t0 are overloaded :
no conformity to installation standards
Consequences :
the circuits installed in t0 have to be replaced by 2.5 mm²
material and labour extra-costs and a long production stopping, ….
if the installation remains the same, the cable lifetime will considerably
be reduced Fire risks ….
Overloads Application: Canalis 3 lathes + 3 milling machines
Inc = (K x Ib) / (f1 x f3)
Choice of the range of Canalis:
Ib = 68 A
IP < 55
KN is chosen
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 19
KN is chosen
Choice of the rating of the Canalis:
Protection by circuit breaker K = 1
Ambient temperature = 30°C f1 = 1
Edgewise mounting = Standard f3 = 1
Inc = (1 x 68) / (1 x 1) = 68 A
KN 100 A is chosenSizing
Overloads Application: cable supplying Canalis
Iz = (K x In) / (f1 x f2 x f3 x f4 x f5 x fs x n)
Protection by circuit breaker K = 1
Ambient temperature = 30°C f1 = 1
Neutral not loaded f2 = 1
Cable with 3 conductors (Method E) + cable fixed on cable tray
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 20
Cable with 3 conductors (Method E) + cable fixed on cable tray
on a horizontal way (Mode 13) f3 = 1
1 layer f4 = 1
2 joined circuits f5 = 1
No parallel cables n et fs = 1
Iz = (1 x 100) / (1 x 1 x 1 x 1 x 1 x 1 x 1) = 100 A
S chosen = 16 mm²
Sizing
Ligthing Otheruse
Installation power directly supplied by alow voltage public distribution network
3% 5%
Voltage drops
The voltage drop between the origin and any point of use mustn’t
exceed the values below:
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 21
Sizing
Setting of the voltage drop
In cable (it needs a calculation):
u = b (ρL/S x Ib x cos ϕ)
– u: voltage drop in V
– b: 1 in single phase and 2 in 3 phases
– ρ: resistivity of phase conductor in ?.mm²/m
– L: length of the cable
– S: section of the phase conductor in mm²
– Ib: rated current in A
– cos ϕ: power factor (use 0.8 when there is no indication)
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 22
Sizing
In Canalis (catalogue data):
u = Val catalogue * Ib * L / 100
Example : Page "CharactéristicsKN from 40 until 100 A"
KN 40 A KN 63 A KN 100 A
With Cos ϕ = 0,8 V/100m/A 0.389 0.163 0.075
With Cos ϕ = 0,9 V/100m/A 0.433 0.180 0.080
With Cos ϕ = 1 V/100m/A 0.473 0.191 0.080
Checking of the voltage dropApplication: cable of the lathe
u = b (ρL/S x Ib x cos ϕ)
3 phases machines b = 2
Copper cable ρcopper = 22.5 x 10-3 Ω.mm²/m
– Rq: ρaluminium = 36 x 10-3 Ω.mm²/m
LLathe (The worst case) = 40 m
Section of a phase conductor 1.5 mm²
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 23
Sizing
Rated current 8 A
cos ϕ = 0.8 (No specification)
u = 2 (22.5 x 10-3 x 40 / 1.5 x 8 x 0.8) = 7.68 V
∆U = u x 100 / U
u = 7.68 V
U = 400 V
∆∆∆∆U = 0.768 x 100 / 400 = 1.92 %
Checking of the voltage dropApplication: Canalis
Supplying cable of the busway:
u = 2 (22.5 x 10-3 x 18 / 16 x 100 x 0.8) = 4.05 V
Canalis:
Canalis KN 100 A, Cos ϕ = 0.8 Val cat 0.075 V / 100 m/A
Ib = 100 A (the worst case - it’s not the actual rated current)
L = 20 m
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 24
L = 20 m
u = 0.075 x 100 x 20 /100 = 1.5 V
Supplying cable of the lathe:
u = 2 (22.5 x 10-3 x 6 /1.5 x 8 x 0.8) = 1.15 V
∆Ucable + canalis = u x 100 / U
u = 4.05 + 1.5 + 1.15 = 6.7 V
U = 400 V
∆∆∆∆U = 6.7 x 100 / 400 = 1.68 %
Sizing
Short circuits currents (Isc)
Generally, Canalis is over sized and can support the short circuits.
Particular cases (building > 5000 m²):
Transformers in parallel
Canalis of low power near a transformer of high power
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 25
Sizing
Power distribution
60 m
45 m
L: Lathe 4 kW
M: Milling machine 4 kW
B: Buffing wheel 0,75 kW
C: Circular saw 4 kW
DT: Drilling/Tapper machine 2.2 kW
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 27
45 m
Exercise
D: Drilling machine 1.5 kW
DT: Drilling/Tapper machine 2.2 kW
DM: Drilling/milling machine 3 kW
RD: Radial drilling machine 7.5 kW
V: Vice filer 2.2 kW
Fluo Tubes 2 x 58 W
45 m
60 m
Ligthing distribution
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 28
Structure: 1 beam every 2.50 m
Exercise
Power - Choice of the materials
Calculation of the current needed by each machine:
I = P / √3 x U x cosϕ– L: Lathe = 4 kW I = 7.2 A
– M: Milling machine = 4 kW I = 7.2 A
– B: Buffing wheel = 0.75 kW 1.4
– C: Circular saw= 4 kW I = 7.2 A
– DT: Drilling / Tapper machine = 2,2 kW I = 4 A
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 30
– DT: Drilling / Tapper machine = 2,2 kW I = 4 A
– DM: Drilling / Milling machine = 3 kW I = 5.4 A
– RD: Radial drilling machine = 7.5 kW I = 13.5 A
– V: Vice filer = 2.2 kW I = 4 A
– D: Drilling machine = 1.5 kW I = 2.7 A
Exercise
L1 L2 L3 L4
L0
20 m
Power - Tracking of the runsSolution 1
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 31
L5 L6 L7 L8
L0
25 m
Exercise
Power - Power sumSolution 1
IL1 = (3 IEL + 3 IF) x Ks x 1.2 = (3x4 + 3x7.2)x0.7x1.2 = 28 A
IL2 = IL1 = 28 A
IL3 = (3 IT + 3 IF) x Ks x 1.2 = (3x7.2 + 3x7.2)x0.7x1.2 = 36 A
IL4 = IL3 = 36 A
IL5 = (6 IF + 2 IM) x Ks x 1.2 = (6x7.2 + 2x1.4)x0.7x1.2 = 39 A
IL6 = IL5 = 39 A
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 32
L6 L5
IL7 = (3 IP + 3 IF) x Ks x 1.2 = (3x2.7 + 3x7.2)x0.7x1.2 = 25 A
IL8 = (2 Itr + IPT + IPF + IPR) x Ks x 1.2 = (2x7.2 + 4 + 5.4 + 13.5)x0.8x1.2 = 36 A
IL0 = (IL1 + IL2 + IL3 + IL4 + IL5 + IL6 + IL7 + IL8 )x Ks x 1.2 =
(2x28 + 2x36 + 2x39 + 25 + 36 )x0.7x1.2 = 225 A
Exercise
Power - Choice of the buswaysSolution 1
Workshop: IPbusway > 20
Inc = (K x Ib) / (f1 x f3)
Protection of runs by circuit breaker K = 1
Ambient temperature = 30°C f1 = 1
Edgewise mounting = standard f3 = 1
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 33
Exercise
Edgewise mounting = standard f3 = 1
Inc L1/L2 = 28 A KNA 40 A
Inc L3/L4 = 36 A KNA 40 A
Inc L5/L6 = 39 A KNA 40 A
Inc L7 = 25 A KNA 40 A
Inc L8 = 36 A KNA 40 A
Inc L0 = 225 A KSA 250 A
Power - Choice of Canalis elements (1/2) Solution 1
Runs L1 to L8:
Canalis KNA 40 A, 3L+N+PE - length 20 m:– 1 End feed box 63 A
– 7 straight elements 40 A - 3m - 1 tap-off outlet / m
– 8 universal brackets
Connectors KNA 3L+N+PE,for fuses:
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 34
Exercise
Connectors KNA 3L+N+PE,for fuses:– Runs L1/L2: 6 connectors 25 A
– Runs L3/L4: 6 connectors 25 A
– Runs L5/L6: 8 connectors 25 A
– Run L7: 6 connectors 25 A
– Run L8: 5 connectors 25 A
Power - Choice of Canalis Elements (2/2) Solution 1
Run L0 :
Canalis KSA 250 A, 3L+N+PE - length 55 m:– 1 end feed box 250 A + 1 end cover
– 11 straight elements 250 A - 5m - 2 tap-off outlets / m
– 20 universal brackets
Connectors KSA 3L+N+PE, for circuit-breakers:
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 35
Exercise
Connectors KSA 3L+N+PE, for circuit-breakers:
– 8 connectors 50 A
L0
Power - Tracking of the runs Solution 2
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 36
L1 L2 L3 L4
45 m
Exercise
Power - Power sumSolution 2
IL1 = (3 IEL + 9 IF + 2 IM)x Ks x 1.2 = (3x4 + 9x7.2 + 2x1.4)x0.6x1,2 = 57 A
IL2 = IL1 = 57 A
IL3 = (3 IT + 6 IF + 3 IP) x Ks x 1.2 = (3x7.2 + 6x7.2 + 3x2.7)x0.6x1.2 = 52 A
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 37
Exercise
IL4 = (3 IF + 3 IT + 2 Itr + IPT + IPF + IPR)x Ks x 1.2 =
(3x7.2 + 6x7.2 + 2x7.2 + 4 + 5.4 + 13.5)x0.6x1.2 = 74 A
IL0 = (IL1 + IL2 + IL3 + IL4 )x Ks x 1.2 = (57x2 + 52 + 74)x0.8 x1,2 = 230 A
Power - Choice of the buswaysSolution 2
Work-shop: IPbusway > 20
Inc = (K x Ib) / (f1 x f3)
Protection of runs by circuit-breaker K = 1
Ambient temperature = 30°C f1 = 1
Edgewise mounting = Standard f3 = 1
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 38
Edgewise mounting = Standard f3 = 1
Inc L1 = 57 A KNA 63 A
Inc L1/L2 = 57 A KNA 63 A
Inc L3 = 52 A KNA 63 A
Inc L4 = 74 A KNA 100 A
Inc L0 = 230 A KSA 250 A
Exercise
Power - Choice of Canalis elements (1/2) Solution 2
Runs L1, L2 and L3:
Canalis KNA 63 A, 3L+N+PE - Length 41 m:– 1 end feed box 63 A
– 13 straight elements 63 A - 3 m - 1 tap-off outlet / m
– 14 universal brackets
Connectors KNA 3L+N+PE, for fuses:– Run L1: 14 connectors 25 A
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 39
– Run L1: 14 connectors 25 A
– Run L2: 14 connectors 25 A
– Run L3: 12 connectors 25 A
Run L4:
Canalis KNA 100 A, 3L+N+PE length 41 m:– 1 end feed box 100 A
– 13 straight elements 100 A de 3 m - 1 tap-off outlet / m
– 14 universal outlets
Connectors KNA 3L+N+PE, for fuses:– Run L1: 11 connectors 25 A
Exercise
Power - Choice of Canalis elements (2/2) Solution 2
Run L0:
Canalis KSA 250 A, 3L+N+PE length 55 m:– 1 end feed box 250 A
– 11 straight elements 250 A - 5m - 2 tap-off outlets / m
– 20 universal brackets
Connectors KSA 3L+N+PE, for circuit-breakers:
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 40
Connectors KSA 3L+N+PE, for circuit-breakers:– 4 connectors 100 A
Exercise
Lighting - Tracking of the runsSolution 1
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 42
Exercise
Lighting - Power sumSolution 1
Iluminaire = (Pluminaire+Pballast) / (U0xcos ϕ) = (2*58+5)/(230*0.86)
Iluminaire = 0.65
Iéclairage = 12 ILuminaire x Ks x 1.2 = (12x0.65)x1x1.2 = 9,36 A
I = 14 I x Ks x 1.2= (14x9,36)x1x1.2 = 157 A
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 43
Ifeeder = 14 Iéclairage x Ks x 1.2= (14x9,36)x1x1.2 = 157 A
Exercise
Lighting - Choice of the buswaysSolution 1
Work-shop: IPbusways > 20
Inc = (K x Ib) / (f1 x f3)
Protection of runs by circuit-breakers K = 1
Ambient temperature = 30°C f1 = 1
Edgewise mounting = standard f3 = 1
Schneider Electric / E&S – Bernard Genoulaz – 14/12/2005 - FR 44
Edgewise mounting = standard f3 = 1
Inc Llighting = 9,36 A KBA 25 A - 1L+N+PE
Inc Lfeeder = 157 A KSA 160 A
Exercise