DAFTAR ISIAN 3 TPG 14H PROTEKSI, SCADA & AUTOMATION : GATEWAY NO Description Requirement Proposed and Guarantee 1 Name ............................................. 2 Manufacture/Type …………../………………….. 3 Communication to SCADA / Control Center Dapat berkomunikasi dengan 2 Control Centre Serial Communication RS 232 / RS 485 data rate (bps) 300 – 19200 port 4 port (2 redundant) Ethernet 10/100BaseTX / FX data rate 10/100 port 2 port Protocol Supported IEC 60870-5-101 (wajib), IEC 60870-5-104 (option) 4 Communication to Substation Automation System (SAS) Protocol Supported IEC-61850 5 Power Supply 220 VAC ±10%, 6 Catatan :Gateway terhubung langsung ke switch LAN atau terintegrasi di station unit atau terhubung langsung ke station unit TECHNICAL PARTICULAR AND GUARANTEE Bidder : Signature : 1 - R1

05. Tpg Sogi Final 2011

Embed Size (px)

DESCRIPTION

C R Ozansoy1 Substation Automation

Citation preview

Page 1: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14H PROTEKSI, SCADA & AUTOMATION : GATEWAY

NO Description Requirement Proposed and Guarantee

1 Name .............................................

2 Manufacture/Type …………../…………………..

3 Communication to SCADA / Control Center Dapat berkomunikasi dengan 2 Control Centre

Serial Communication RS 232 / RS 485

    data rate (bps) 300 – 19200

    port 4 port (2 redundant)

Ethernet 10/100BaseTX / FX

    data rate 10/100

    port 2 port

Protocol Supported IEC 60870-5-101 (wajib), IEC 60870-5-104 (option)

4Communication to Substation Automation System

(SAS)

    Protocol Supported IEC-61850

5 Power Supply 220 VAC ±10%,

6

Catatan :Gateway terhubung langsung ke switch LAN

atau terintegrasi di station unit atau terhubung langsung

ke station unit

TECHNICAL PARTICULAR AND GUARANTEE

Bidder :

Signature : 1 - R1

Page 2: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14G PROTEKSI, SCADA & AUTOMATION : STATION UNIT

NO Description Requirement Proposed and Guarantee

1 Name .............................................

2 Manufacture/Type …………../…………………..

3 Class Industrial server

4 Hardware

Processor 4 Core, 3 Ghz

Jumlah processor terpasang 2

5 Operating System Linux / UNIX / Windows

6 RAM : 8 GB

7 Hard Disk

- Kecepatan ≥ 7200 rpm

- Kapasitas Terpasang 1000 GB

8 Optical Drive DVD ± R/RW

9 Graphic Adapter 128 MB 1 port

10 Communication Port :

         10/100 BaseTX Ethernet port 2

         Serial port 1

         USB Port 2

11 Power Supply 220 ±10%, VAC (Double)

12 Fan pendingin Redundant

13 Rackmountable Yes

14 Software

GUI Yes

TECHNICAL PARTICULAR AND GUARANTEE

Bidder :

Signature : 2 - R1

Page 3: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14G PROTEKSI, SCADA & AUTOMATION : STATION UNIT

NO Description Requirement Proposed and Guarantee

TECHNICAL PARTICULAR AND GUARANTEE

Control Sequences

Data logging 7 hari

Historical recording and archiving 93 hari

Alarm management yes

Remote Configuration yes

15 Kapasitas

Kapasitas input/output 5.000

Kapasitas komunikasi dengan IED 3 kali kapasitas IED terpasang

16 Performance

Digital input change of state 500 ms

Alarm acknoledgment 1s

Analog input change of value 1s

Control initiation 750ms

Digital input 10.000 Alarm/menit CPU peak ≤ 50%

RAM ≤ 50%

Space hardisk terpakai ≤ 50 %

Processor Start-Up

Hot Start 3s

Warm Start 5s

Cold Start 5 menit

Device/Processor Fail over (switch over) 30s

17 Protocol IEC 61850

Bidder :

Signature : 3 - R1

Page 4: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14B PROTEKSI, SCADA & AUTOMATION : WORKSTATION

NO Description Requirement Proposed and Guarantee

1 Name : .............................................

2 Manufacture/Type : …………../…………………..

3 Class : Industrial server

Hardware

Processor : 4 Core, 3 GHZ

Jumlah processor terpasang : 1

:

5 Operating System : Linux / UNIX / Windows

6 RAM : : 4 GB

Hard Disk :- Kecepatan : ≥ 7200 rpm

- Kapasitas Terpasang : 500 GB

:

8 Optical Drive : DVD ± R/RW

9 Graphic Adapter 128 MB : 2 port

Communication Port :

  10/100 BaseTX Ethernet port : 2

  Serial port : 1

  USB Port : 2

11 Power Supply : 220 ±10%, VAC (Double)

12 Fan pendingin : Redundant

13 Rackmountable : Yes

Software

GUI : Yes

Performance

Digital input 10.000 Alarm/menit : CPU peak ≤ 50%

: RAM ≤ 50%

Space hardisk terpakai : ≤ 50 %

14

15

TECHNICAL PARTICULAR AND GUARANTEE

4

7

10

Page 5: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14B PROTEKSI, SCADA & AUTOMATION : SWITCH

NO Description Requirement Proposed and Guarantee

1 Name .............................................

2 Manufacture/Type …………../…………………..

3 Technology Fully managable

4 Approval / Certificate IEC 61850 dari KEMA

5 Management Interface Web base HTML, Command Line Interface, Telnet

6 Ethernet Port

           Type port 10BaseT, 100BaseTX, 100BaseFX

           Kapasitas port per-Switch Minimal 8 port (disesuaikan)

7 Tipe port

-           Switch - IED Port fiber optik

-           Switch - Station Unit Port fiber optik atau UTP

-           Switch - Switch Port fiber optik

8 Power supply 110 VDC (-15% s.d +10%)

9 Rack mountable yes

TECHNICAL PARTICULAR AND GUARANTEE

Bidder :

Signature : 5 - R1

Page 6: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14A PROTEKSI, SCADA & AUTOMATION : BAY CONTROL UNIT

NO Description Requirement Proposed and Guarantee

1 Name .............................................

2 Manufacture/Type …………../…………………..

3 Voltage / Current

AC Voltage (secondary) Min. (100 – 120) V rms. phase-phase

Connection 3 phase, 4 wires

Min. (20 – 500) kV,

selectable VT matching

AC Current (secondary) 1 A and 5A

Connection 3 phase, 4 wire

Min. (50 – 4000) A,

selectable CT matching Taps

Frequency 50 Hz

4 AC Burden

In = 1 A 0.2 VA

In = 5 A 1.0 VA

5 DC Burden (trip condition) 50 Watt

6 Digital Input

Kapasitas 32

Rated voltage range 24 to 220 VDC

Minimum voltage threshold -20%

Maximum permitted voltage 20%

Power consumpsion < 0,2 Watt/input

Primary Nominal Voltage

Primary Nominal Current

TECHNICAL PARTICULAR AND GUARANTEE

Bidder :

Signature : 6 - R1

Page 7: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14A PROTEKSI, SCADA & AUTOMATION : BAY CONTROL UNIT

NO Description Requirement Proposed and Guarantee

TECHNICAL PARTICULAR AND GUARANTEE

7 Digital Output

Live Contact Normally Open

Kapasitas 16

Binary input / output

        Rated voltage min 125 V DC

        Contacts min 5 A continuous

min 30 A make and carry

min 30 A, 250VDC for 0.2 s

min 0.2 A, 110 VDC break

8 Analog Input (AC)

Kapasitas 7 input (3 arus, 4 tegangan)

Rated current 1 or 5 A

Rated voltage 100 / 120 V

at 1A < 0.1 VA

at 5A < 0.5 VA

Measurement range current ± 20%

Accuracy ± 0.5%

Sampling periode 100 ms

9 Analog Output (DC)

Kapasitas 2

Rated Input 4-20 mA

Power consumption

Bidder :

Signature : 7 - R1

Page 8: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14A PROTEKSI, SCADA & AUTOMATION : BAY CONTROL UNIT

NO Description Requirement Proposed and Guarantee

TECHNICAL PARTICULAR AND GUARANTEE

10 AutoRecloser single or three phase

Dead time SPAR min 0.1 – 2 sec in 0.1 sec steps

Dead time TPAR min 0.1 – 30 sec in 0.1 sec steps

Reclaim time min 5 – 100 sec in 1 sec steps

11 Synchrocheck

Voltage difference 5- 20 % of rating in 1 % steps

Phase difference 5 – 30 deg in 2.5 deg steps

Frequency slip or timer 0 – 1 sec in 0.5 sec steps

LL/DB and DL/LB Enable

12 Local Configuration

Terminal Interface RJ45/RS 485/RS 232

Database configuration Upload dan download

13 Protocol IEC61850

14 Dapat berkomunikasi dengan 3 merk IED Yes

Bidder :

Signature : 8 - R1

Page 9: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14D PROTEKSI, SCADA & AUTOMATION : DIFFERENTIAL RELAY AND RESTRICTED EARTH FAULT 150 KV

NO Description Requirement Proposed and Guarantee

1 Name Differential Relay dan Restricted Earth Fault 150 KV

2 Manufacture/Type …………../…………………..

3 Current

AC Current (Secondary) 1A and 5A

Connection (150kV, 20kV) 3 phase, 4 wires + 1 phase, 2 wire

Min. (50 – 4000) A,

Programmable CT ratio

Frequency 50 Hz

4 AC Burden

In = 1 A 0.2 VA

In = 5 A 1.0 VA

5 DC Burden (trip condition) 50 Watt

6 Binary input / output

Rated voltage ≥ 110 VDC

Trip contacts ≥ 5 A 110 VDC continuously

≥ 10 A make and carry, 1 sec

≥ 0.2 A, 110 VDC break

Auxiliary contacts ≥ 5 A 110 VDC continuously

≥ 10 A make and carry, 1 sec

≥ 0.2 A, 110 VDC break

Binary Input ≥ 8

Binary output Contact ≥ 16

Primary Nominal Current

TECHNICAL PARTICULAR AND GUARANTEE

Bidder :

Signature : 9 - R1

Page 10: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14D PROTEKSI, SCADA & AUTOMATION : DIFFERENTIAL RELAY AND RESTRICTED EARTH FAULT 150 KV

NO Description Requirement Proposed and Guarantee

TECHNICAL PARTICULAR AND GUARANTEE

7 Event records ≥ 192 event records in ring buffer FIFO

8 Internal disturbance recorder ≥ 8 analog signal

≥ 16 digital signal

Trigger analogue signal trip signal or analogue value change

Trigger event signal internal and external trigger

Recording duration each fault ≥ 8 oscillograph for each ≥ 2.0 second

Sampling rate ≥16 sample / cycle

Format file COMTRADE IEC 60255-24

9 Setting Range for Differential Min. 15 - 40 %, step 5%

10 Setting Range for REF 0.1 – 0.5 In, step 0.01

11 Accuracy at set value 7.50%

12 Operating Time

Low Set 30 ms

High Set 30 ms

13 Internal ACT Yes

14 Applicable for all vector group Yes

15 Harmonic restraint function to block inrush

currentA must

16 Minimum Feature

Watch dog Enable

Block for Relay Failure Enable

Default logic and setting Enable

LCD Display Enable

Bidder :

Signature : 10 - R1

Page 11: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14C PROTEKSI, SCADA & AUTOMATION : OVER CURRENT RELAY & GROUND FAULT RELAY 150 KV

NO Description Requirement Proposed and Guarantee

1 Name Over Current Relay & Ground Fault Relay 150 KV

2 Manufacture/Type ……………./………………

3 Models Three phase Overcurrent and Single phase Ground Fault

4 Current

AC Current (Secondary) 1 A and 5A

Connection 3 phase, 4 wires

Min. (50 – 4000) A,

Programmable CT ratio

Frequency 50 Hz

5 AC Burden

In = 1 A 0.2 VA

In = 5 A 1.0 VA

6 DC Burden (trip condition) 50 Watt

7 Binary input / output

Rated voltage ≥ 110 VDC

Trip contacts ≥ 5 A 110 VDC continuously

≥ 10 A make and carry, 1 sec

≥ 0.2 A, 110 VDC break

Auxiliary contacts ≥ 5 A 110 VDC continuously

≥ 10 A make and carry, 1 sec

≥ 0.2 A, 110 VDC break

Binary Input ≥ 8

Primary Nominal Current

TECHNICAL PARTICULAR AND GUARANTEE

Bidder :

Signature : 11 - R1

Page 12: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14C PROTEKSI, SCADA & AUTOMATION : OVER CURRENT RELAY & GROUND FAULT RELAY 150 KV

NO Description Requirement Proposed and Guarantee

TECHNICAL PARTICULAR AND GUARANTEE

Binary output Contact ≥ 12

8 Event records 192 event records in ring buffer FIFO

9 Internal disturbance recorder 8 analog signal

16 digital signal

Trigger analogue signal trip signal or analogue value change

Trigger event signal internal and external trigger

Recording duration each fault 8 oscillograph for each ≥ 2.0 second

Sampling rate 16 sample / cycle

Format file COMTRADE IEC 60255-24

10 Setting Range Over Curret & Ground Fault Two setting group

Low set

Over Current Min 0.4 – 2.0 * In (in 0.05 steps)

Earth Fault Min 0.1 – 1.0 * In (in 0.05 steps)

High set

Over Current Min 1 – 8 * Is (in 0.5 steps)

Earth Fault Min 1 – 4 * In (in 0.5 steps)

11 Characteristic Over Curret & Ground Fault Standard Inverse

Very Inverse

Extremely Inverse

Definite Time

Bidder :

Signature : 12 - R1

Page 13: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14C PROTEKSI, SCADA & AUTOMATION : OVER CURRENT RELAY & GROUND FAULT RELAY 150 KV

NO Description Requirement Proposed and Guarantee

TECHNICAL PARTICULAR AND GUARANTEE

12 Time Setting Range Over Curret & Ground Fault

Min. 0.05 – 1 with 0.05 step

for IEC standard

Min. 0.5 – 15 with step 0.5 step

for ANSI standard

Definite Independent Time Min. 0.04 – 30 s in 0.1 steps

High set delay Min. 0.04 – 500 millisecond in 0.1 steps

13Drop off to pick up ratio Over Curret & Ground

Fault 95 %

14 Setting Range Thermal Overload

Full load current trip Min. 0.3 – 1.5 In, with step 0.01

Alarm thermal overload Min. 50 – 100%, with step 1

Time constant Min. 1 – 100 minute, with step 1

15 Measurement Enable

16 Minimum Feature

Watch dog Enable

Block for Relay Failure Enable

Default logic and setting Enable

LCD Display Enable

Inverse (TMS)

Bidder :

Signature : 13 - R1

Page 14: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14C PROTEKSI, SCADA & AUTOMATION : OVER CURRENT RELAY & GROUND FAULT RELAY 20 KV

NO Description Requirement Proposed and Guarantee

1 Name Over Current Relay & Ground Fault Relay 20 KV

2 Manufacture/Type ……………./………………

3 Models Three phase Overcurrent and Single phase Ground Fault

4 Current

AC Current (Secondary) 1 A and 5A

Connection 3 phase, 4 wires

Min. (50 – 4000) A,

Programmable CT ratio

Frequency 50 Hz

5 AC Burden

In = 1 A 0.2 VA

In = 5 A 1.0 VA

6 DC Burden (trip condition) 50 Watt

7 Binary input / output

Rated voltage ≥ 110 VDC

Trip contacts ≥ 5 A 110 VDC continuously

≥ 10 A make and carry, 1 sec

≥ 0.2 A, 110 VDC break

Auxiliary contacts ≥ 5 A 110 VDC continuously

≥ 10 A make and carry, 1 sec

≥ 0.2 A, 110 VDC break

Binary Input ≥ 8

TECHNICAL PARTICULAR AND GUARANTEE

Primary Nominal Current

Page 15: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14C PROTEKSI, SCADA & AUTOMATION : OVER CURRENT RELAY & GROUND FAULT RELAY 20 KV

NO Description Requirement Proposed and Guarantee

TECHNICAL PARTICULAR AND GUARANTEE

Binary output Contact ≥ 12

8 Event records 192 event records in ring buffer FIFO

9 Internal disturbance recorder 8 analog signal

16 digital signal

Trigger analogue signal trip signal or analogue value change

Trigger event signal internal and external trigger

Recording duration each fault 8 oscillograph for each ≥ 2.0 second

Sampling rate 16 sample / cycle

Format file COMTRADE IEC 60255-24

10 Setting Range Over Curret & Ground Fault Two setting group

Low set

Over Current Min 0.4 – 2.0 * In (in 0.05 steps)

Earth Fault Min 0.1 – 1.0 * In (in 0.05 steps)

High set

Over Current Min 1 – 8 * Is (in 0.5 steps)

Earth Fault Min 1 – 4 * In (in 0.5 steps)

11 Characteristic Over Curret & Ground Fault Standard Inverse

Very Inverse

Extremely Inverse

Definite Time

Page 16: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14C PROTEKSI, SCADA & AUTOMATION : OVER CURRENT RELAY & GROUND FAULT RELAY 20 KV

NO Description Requirement Proposed and Guarantee

TECHNICAL PARTICULAR AND GUARANTEE

12 Time Setting Range Over Curret & Ground Fault

Min. 0.05 – 1 with 0.05 step

for IEC standard

Min. 0.5 – 15 with step 0.5 step

for ANSI standard

Definite Independent Time Min. 0.04 – 30 s in 0.1 steps

High set delay Min. 0.04 – 500 millisecond in 0.1 steps

13Drop off to pick up ratio Over Curret & Ground

Fault 95 %

14 Setting Range Thermal Overload

Full load current trip Min. 0.3 – 1.5 In, with step 0.01

Alarm thermal overload Min. 50 – 100%, with step 1

Time constant Min. 1 – 100 minute, with step 1

15 Measurement Enable

16 Minimum Feature

Watch dog Enable

Block for Relay Failure Enable

Default logic and setting Enable

LCD Display Enable

Inverse (TMS)

Page 17: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14E PROTEKSI, SCADA & AUTOMATION : AUTOMATIC VOLTAGE REGULATOR

NO Proposed and Guarantee

1

2

3

4

5

Setting Range Step size

      Regulated Voltage Vs 90% - 120% of Vn 0,1 %

      Deadband dVs ±0.5% to ±5.0% of Vn 0,1 %

      Resistive line drop compensation Vr 0 - 50 V 1,0 V

      Resistive line drop compensation Vxl 0 - 50V 1,0 V

      Circulating current compensation Vc 0 - 50 V 1,0 V

      Load shedding/boosting 0 - ±10% of Vs 1%

      Total taps available TapsAvail Taps Avail 1 - 40 or 1 - 30 1

- Current circuits ( In )≤ 0.2 VA (1 A)

≤ 1.0 VA (5 A)

≤ 50W

Kapasitas 8

Rated voltage range 110 VDC

Burden

- Nominal Current ( In ) 1A and 5 A

- Voltage Input ( Vn ) 100 V or 110 V

- Frequency 50 Hz ±5%

- Auxiliary DC Voltage ( Vx ) 110 V DC ( -15% ; +10% )

- Reference voltage ( Vn ) 100 V or 110 V

- Digital Input

TECHNICAL PARTICULAR AND GUARANTEE

Description Requirement

Name Automatic Voltage Regulator

Manufacture/Type …………../…………………..

Rating

Setting

Control function setting ranges

- Auxiliary volatge

Bidder :

Signature : 17 - R1

Page 18: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14E PROTEKSI, SCADA & AUTOMATION : AUTOMATIC VOLTAGE REGULATOR

NO Proposed and Guarantee

TECHNICAL PARTICULAR AND GUARANTEE

Description Requirement

      Maximum total tap position TP> 1 - 40 or 1 - 30 1

      Minimum total tap position TP< - 30 or 1 - 30 1

      Total number of tap changes TotalOps> 1 - 10000 1

      Tap Changers Operations Ops/tP> 1 - 100 1

      Time Period tP 1 - 24 hrs 1 - 24 hrs

      Intertap Delay tINTER 0 - 120 seconds 0,1 s

      Tap Change indication time tPULSE 0,5 - 5 seconds 0,5 s

      Tap Change indication time tTapChange 1 – 3 seconds 0,1 s

6

Setting Range Step size

Initial time (definite) tINIT 0 - 20 secs 0 - 20 secs

20 - 300 secs 10 secs

7

Setting Range Step size

Under voltage blocking V<< 60-130V 1,0 V

Under voltage detection V< 80-130V 1,0 V

Over voltage detection V> 105 - 160 V 1,0 V

Circulating current Ic 0.02-0.5A ( In = 1A) 0.01 A

0.1-2.5A( In = 5A) 0,05 A

t= k+[(initial time delay setting ) x ( 1/N)] *) or

Short time inverse

- Definite time delay

Time delay setting ranges

Supervision function settings

Setting

Inverse time delay

Inverse time delay

Time curve :

Bidder :

Signature : 18 - R1

Page 19: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14E PROTEKSI, SCADA & AUTOMATION : AUTOMATIC VOLTAGE REGULATOR

NO Proposed and Guarantee

TECHNICAL PARTICULAR AND GUARANTEE

Description Requirement

Load current IL> 0.05-2.0A ( In = 1A)

2.5-10A ( In = 5A) 0,05 A

Load current IL< 0 - 1A ( In = 1A)

0 - 5A ( In = 5A) 0 - 5A ( In = 5A)

Excessive circulating

current time delay tIC '0 - 180 seconds 10 secs

Power factor angle Angle 0 - 90 degrees 1 deg

8

9999 : 1 Default = 1:1

9999 : 1 Default = 1:1

9

10

11

Upload dan download

Enable

IEC 61850

RJ45/RS 485/RS 232

Protocol

Database configuration

Terminal Interface

Local Configuration

Transformers Ratios

Measurement

VT ratios

CT ratios

Bidder :

Signature : 19 - R1

Page 20: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14E PROTEKSI, SCADA & AUTOMATION : IED I/O

NO Description Requirement Proposed and Guarantee1 Name : .............................................

2 Manufacture/Type : …………../…………………..

3 Auxiliary supply

Voltage : 110 VDC (-15% s.d +10%)

Analog input

DC mA : 4 – 20 mA

RTD : PT100

5 DC Burden : 50 Watt

Digital Input

Rated voltage range : 24 to 220 VDC

Minimum voltage threshold : -20%

Maximum permitted voltage : 20%

Power consumpsion : < 0,2 Watt/input

Digital Output

Live Contact : Normally Open

Binary input / output

  Rated voltage : min 125 V DC

  Contacts : min 5 A continuous

: min 30 A make and carry

: min 30 A, 250VDC for 0.2 s

: min 0.2 A, 110 VDC break

Local Configuration

Terminal Interface : RJ45/RS 485/RS 232

Database configuration : Upload dan download

9 Protocol : IEC 61850

TECHNICAL PARTICULAR AND GUARANTEE

4

6

7

8

Page 21: 05. Tpg Sogi Final 2011

1 Jenis Meter Meter Elektronik

ANSI C12.20 dan atau IEC 62053-22 (kWh) atau yang lebih

baru

IEC 1268 (VARh) atau yang lebih baru

3 Jenis Konstruksi Switchboard (draw out)

- Optical Port

- RS232 atau RS485

- Port Ethernet (TCP/IP, Tidak menggunakan konverter)

- Modem PSTN

- Modem GSM

5 Protokol Komunikasi (tersedia) IEC 61850 dan (DLMS atau ( DNP3 dan MODBUS ))

6 Sinkronisasi dengan GPS Dapat tersinkronisasi

7 Tipe Pengawatan 3 Fasa - 4 Kawat

8 Arus Nominal Disesuaikan dengan arus sekunder CT terpasang

9 Ketahanan Arus Gangguan 1.5 x In Kontinyu, 10 x In selama 0,5 detik

10 Tegangan Nominal 57.7 - 240 V AC (auto range) Minimum pick-up voltage:

57.7V Fasa - Netral11 Aux. Power Supply 57.7 - 240 V AC (Auto Range) dan 110 - 220 V DC (Auto

Range)

12 Frekuensi 50 Hz

-kWh : 0,2 ( Mengacu pada Standard IEC62053-22 dan

atau ANSI C12.20 )

-kVARh : 2 ( Mengacu pada Standard IEC1268 atau

IEC62053-23 )14 Temperatur Operasi -40

oC sampai +75

oC

15 Jumlah Kanal Penyimpanan Load Profile 12 Channel load profile (Dapat dibagi menjadi 2 Grup)

16 Kapasitas Penyimpanan Memori Load Profile2 MB (minimum) / 12 channel 30 menit selama 120 hari

17 Interval Perekaman Daya (Dapat

Diprogram)1 Sampai 60 Menit

- Wh Kirim

- Wh Terima

- VARh Kirim

- VARh Terima

- VAh Kirim

- VAh Terima

- W Kirim

- W Terima

- VAR Kirim

- VAR Terima

- VA Kirim

- VA Terima

Besaran Energi yang diukur/direkam

19 Besaran Daya yang diukur/direkam

18

2 Standard

Terminal Komunikasi (Built in)

13 Kelas Ketelitian

4

Terminal Komunikasi (Optional)

TECHNICAL PARTICULAR AND GUARANTEE

DAFTAR ISIAN 3 TPG 14E KWH METER TRANSAKSI

NO DESCRIPTION REQUIRED PROPOSED AND GUARANTEE

Page 22: 05. Tpg Sogi Final 2011

TECHNICAL PARTICULAR AND GUARANTEE

DAFTAR ISIAN 3 TPG 14E KWH METER TRANSAKSI

NO DESCRIPTION REQUIRED PROPOSED AND GUARANTEE

20 Interval Perekaman Energi (Dapat

Diprogram) 1, 5, 10, 15, 20, 30, dan 60 Menit

- Watt Kirim

- Watt Terima

- VAR Kirim

- VAR Terima

- VA Kirim

- VA Terima

- Tegangan Tiap Fasa (Antar Fasa dan Fasa - Netral)

- Arus Tiap Fasa

- Faktor Daya

- Frekuensi

- Watt Kirim

- Watt Terima

- VAR Kirim

- VAR Terima

- VA Kirim

- VA Terima

- Tegangan Tiap Fasa (Antar Fasa dan Fasa - Netral)

- Arus Tiap Fasa

- Faktor Daya

- Frekuensi

23 Pembagian Tarif 8 Tarif (minimal)

24 End of billing / register freeze Tanggal 1 jam 10:00 setiap bulan untuk semua tarif

- Disertakan

- Berbasis Windows XP dan Windows Vista

- Dapat diinstall ke semua laptop/pc milik PLN P3B berikut

lisensinya

- Dapat Mengambil data berdasarkan waktu yang dapat

dikonfigurasi (mampu mengambil loadprofile dengan range

tanggal yang ditentukan)

- Mampu mengexport data load profile dalam format teks dan

atau spreadsheet

26 Tampilan Layar Minimum 8 digit

27 Metode Komunikasi Multi-tasking, multi-user dan Web Based

28 Pengaman Pada Hardware (lock) & Software (password level)

29 Integrasi Sistem Dapat terintegrasi dengan Sistem AMR P3B JB

22 Koinsiden Demand

25 Aplikasi Baca / Seting Meter

21 Besaran Sesaat yang diukur dan dapat

direkam

Page 23: 05. Tpg Sogi Final 2011

NO DESCRIPTION PROPOSED AND GUARANTEE

1 Name : DFR (Disturbance Fault Recorder)

2 Manufacture/Type : ……………./………………

Input :

Analog AC Input : Min. 16

Channel : (8 current, 8 voltage)

Voltage : 100/√3 volt or according to existing secondary voltage

Current : 1 A and 5 A (compatible with eksisting)

Burden : ≤ 1 VA

Error : ≤ ± 0.5 %

min. 16 channels for double busbar

min. 24 channels for one and half breaker

Wet & Dry Contact, Normally Open or Close Input, Trigger

on Active & return to normal

4 Pre-Recording Time : 0.4 Sec (Adjustable)

5 Recording Time : 10 Sec (Adjustable)

Recording

· Analog

Voltage Element : Enable

Current Element : Enable

· Digital Element : Enable

Triger

-   RMS Level Triger : V, I, P, Q, f

-   Reated of change : V, I, f

-   Sub Cycle (For Power Quality) : Yes

-   Zero and Negatife Sequence. : Yes

- Contact Input Debounce ≤ 20 msec

- Contact Rating relay ≤ 125 VDC or eksisting

9 Sampling rate : Min 128 samples per cycle (Selectable)

10 Power Quality Record:

According to IEC 61000-4-7

Ability to measure harmonic and THD current and voltage

(up to 40 thd)

·      Voltage Quality

-       Range High : 105-125% Vn Step 0.1%

6

7

8 Contact :

·      Harmonic Recording. :

TECHNICAL PARTICULAR AND GUARANTEE

DISTURBANCE FAULT RECORDER (DFR)

REQUIREMENT

3

Digital input :

Page 24: 05. Tpg Sogi Final 2011

-       Range Low : 50-95 % Vn Step 0.1 %

-       Accuracy : ≤ 0.5 % of reading

·      Current Quality

-       Range High : Min 15xIn Step 0.1%

-       Range Low : Min 0.01xIn Step 0.1 %

-       Accuracy : ≤ 0.5 % of reading

·      Sag and Swells. : Yes (IEC 61000-4-30)

·      Flicker. : Yes (IEC 61000-4-15)

·      Frequensi.

-       Range : -10%fn up to 5%fn.

-       Accuracy : ≤ 0.5 %

·      Voltage unbalance

-       Range : 1-5 %

-       Accuracy : ≤1%

·      P&Q Accuracy : ≤ 0.5 %

Memory Capacity (internal/external) ≥16 MB- With Battery Backed RAM

(Including Power Quality Data Loger). (for max.16 channels Analog, 32 events & min storage for

10 days Power Quality Data)

Hard Disk (Ekternal disk/host PC) : ≥ 80 GB

Yes

(suitable for regular paper and cartridge)

13 Resolution Power Of A/D Conversion : ≥ 16 Bit

Internal Clock

Base clock : Crystal Oscillator

Date/time (year,month,day, hour, Minute, second) : Yes

Stability up to 40° C : ≤ 0.1 sec/day

15 Starting Unit : available

16 Fault Recorder Indication : available

17 Free Contacts (for alarm/watchdog) : available

GPS, IRIG-B port (include GPS & accessory).

Accuracy ≤ 10 μs.

19 Front Panel Key Pad And Display (Meter and status

Indication)

: Host PC (internal/external)

20 Automatic & Multitasking For Recording Printing,

Transmit & Diagnostic

: Yes

21 Cross Trigger & Time Sync For More Than One Fault

Recorder

: Yes

22 Self Test Mode : Yes

23 Communication for Remote Down Load : Ethernet port, TCP/IP

Power Consumption

Standby : ≤ 150 VA

24

External Time Sync. Facilities :

12 Printer With Recording Paper :

14

18

11 :

Page 25: 05. Tpg Sogi Final 2011

Operating : ≤ 300 VA

25 Insulating Resistance At 500 V Dc : ≥ 10 MW

26 Dielectric Test For 50 Hz, 1 Min : ≥ 2000 V rms

27 Voltage Withstand Surge : According to IEC 255-5-5

28 Electro Static Discharge : According to IEC 60255-22-2

29 Vibration and Shock Test : According to IEC 60255-21-1,2

Environment

-   Operating Themperature. : 10-50°C

-   Humidity : 90%

Others :

Mounting : ≤ 19 Rack Mountable or moveable

High Class Accuracy

8 channel current probe (according number of bay and

current transformer ratio) / DFR and cable min 20 meter

Software -       Original CD software of DFR&PQ

(For Operation and Maintenance) (For Operational and Maintenance )

/Calibrating).

-       Minimum 3 years free upgrade.

-       Enable For Window XP.

-       Coexist with another software (no crash/conflict)

-       Have ability to remote download, include

automatic download, remote setting

-       Has help function.

-       Have ability to Analyze Fault.

-       Have ability to Analyze Power Quality.

Printer : Enable

With minimum requirement (Setara Lenovo Thinkpad)

·     Microsoft Windows XP (minimum)

·     Intel Core i5

·     RAM 2 GB

·     Hard Disk 500 GB

·     Camera 1.3 MP

·     DVD-CDRW Combo Drive

·     Max 14"1 WXGA

·     LAN/Modem/i.Link (IEEE1394)/SD Card slot/4 USB

2.0 port

·     Have communication card.

33 Manual Book : Original Manual Book (hard and soft copy)

34 Guarantee : Min 3 (three) years free of charge

32 Data Loader

24

30

31

Current probe and R Shunt (Direct Connection from

CT)

:

Page 26: 05. Tpg Sogi Final 2011

A Signal Digital Input (1 DFR untuk 2 Bay)

- DFR dengan Fasilitas 64 Digital Input untuk bay Line 500 kV minimal harus terdiri dari :

Main 1 Protection Operated ( Distance 1) : LP A OPRT

Main 2 Protection Operated ( Distance 2 ) : LP B OPRT

DEF 1 Operated : DEF A

DEF 2 Operated : DEF B

CB 7Ax/Bx phasa A open : 7Ax/Bx R OPEN (ex: 7A1 R OPEN)

CB 7Ax/Bx phasa B open : 7Ax/Bx S OPEN

CB 7Ax/Bx phasa C open : 7Ax/Bx T OPEN

CB 7ABx phasa A open : 7ABx R OPEN

CB 7ABx phasa B open : 7ABx S OPEN

CB 7ABx phasa C open : 7ABx T OPEN

A/R 1 In Progress : A/R 1 OPRT

A/R 2 In Progress : A/R 2 OPRT

Carrier send from Distance Main 1 : LP A SEND

Carrier send from Distance Main 2 : LP B SEND

Carrier send from DEF Main1 : DEF A SEND

Carrier send from DEF Main 2 : DEF B SEND

Carrier Receive to Distance Main 1 : LP A RCV

Carrier Receive to Distance Main 2 : LP B RCV

Carrier Receive to DEF 1 : DEF A RCV

Carrier Receive to DEF 2 : DEF B RCV

Trip phasa R : TRIP R

Trip phasa S : TRIP S

Trip phasa T : TRIP T

Send DTT : DTT SEND

Receive DTT. : DTT RCV

CCP 1 operated : CCP A OPRT

CCP 2 operated : CCP B OPRT

CBF/SZP 1 7Ax/Bx Trip : CBF/SZP A 7Ax/Bx OPRT

CBF/SZP 1 7Ax/Bx Trip : CBF/SZP A 7Ax/Bx OPRT

CBF/SZP 2 7ABx Trip : CBF/SZP B 7ABx OPRT

CBF/SZP 2 7ABx Trip : CBF/SZP B 7ABx OPRT

CB Pole Discapancy : CB DISCRAPANCY

Page 27: 05. Tpg Sogi Final 2011

-       DFR dengan Fasilitas 32 Digital Input untuk bay line 500 kV minimal harus terdiri dari:

Main 1 Protection Operated ( Distance 1) : LP A OPRT

Main 2 Protection Operated ( Distance 2 ) : LP B OPRT

CB 7Ax/Bx open : CB 7Ax/Bx OPEN

CB 7ABx open : CB 7ABx OPEN

A/R In Progress : A/R OPRT

Carrier send from Distance Main 1 : LP A SEND

Carrier send from Distance Main 2 : LP B SEND

Carrier send from DEF Main1/DEF2 : DEFA/B SEND

Carrier Receive to Distance Main 1 : LP A RCV

Carrier Receive to Distance Main 2 : LP B RCV

Carrier Receive to DEF 1/DEF2 : DEF A/B RCV

Send DTT : DTT SEND

Receive DTT : DTT RCV

CCP Operated : CCP OPRT

CBF/SZP 7Ax/7Bx Trip : CBF/SZP 7Ax/7Bx OPRT

CBF/SZP 7ABx Trip : CBF/SZP 7ABx OPRT

-       DFR dengan Fasilitas 64 Digital Input untuk bay IBT 500 kV minimal harus terdiri dari :

Main 1 Protection Operated : MAIN PROT A

Main 2 Protection Operated : MAIN PROT B

REF 500 kV Operated : REF 500 OPRT

REF 150 kV Operated : REF 150 OPRT

Back Up Protection 500 kV Operated : OC 500 OPRT

Back Up Protection 150 kV Operated : OC 150 OPRT

Over Voltage Operated : OV OPRT

Bucholz Operated : BUCHOLZ

Jansen Operated : JANSEN

Thermal Relay Operated : THERMAL

Sudden Pressure Operate : SUDDEN PRESS

PMT 7ABx Open. : 7ABx OPEN

PMT 7ABx Close. : 7ABx CLOSE

PMT 7Ax or 7Bx Open. : 7Ax or 7Bx OPEN.

PMT 7Ax or 7Bx Close. : 7Ax or 7Bx CLOSE

PMT 150 kV Open : 150 kV OPEN

Page 28: 05. Tpg Sogi Final 2011

PMT 150 kV Close : 150 kV CLOSE

CCP 1 Operated. : CCP 1 OPRT

CCP 2 Operated : CCP 2 OPRT

CBF/SZP 1 7Ax or 7Bx Trip. : CBF/SZP 1 7Ax or 7Bx OPRT.

CBF/SZP 1 7Ax or 7Bx Trip. : CBF/SZP 1 7Ax or 7Bx OPRT

CBF/SZP 2 7ABx Trip. : CBF/SZP 2 7ABx OPRT

CBF/SZP 2 7ABx Trip. : CBF/SZP 2 7ABx OPRT

Spare. :

Spare. :

Spare :

Spare. :

Spare. :

Spare. :

Spare. :

Spare :

Spare. :

-       DFR dengan Fasilitas 32 Digital Input untu bay IBT 500 kV minimal harus terdiri dari :

Main 1 Protection Operated : MAIN PROT A

Main 2 Protection Operated : MAIN PROT B

Back Up Protection 500 kV Operated : OC 500 OPRT

Back Up Protection 150 kV Operated : OC 150 OPRT

Over Voltage Operated : OV OPRT

Bucholz Operated : BUCHOLZ

Jansen Operated : JANSEN

Thermal Relay Operated : THERMAL

Sudden Pressure Operate : JANSEN

PMT 7ABx Open. : 7ABx OPEN

PMT 7Ax or 7Bx Open. : 7Ax or 7Bx OPEN.

PMT 150 kV Open : 150 kV OPEN

CCP 1 Operated. : CCP A OPRT

CCP 2 Operated : CCP B OPRT

CBF/SZP 7Ax/7Bx or B Trip. : CBF/SZP 7Ax/7Bx or B OPRT

CBF/SZP 7ABx Trip. : CBF/SZP 7ABx OPRT

Page 29: 05. Tpg Sogi Final 2011

- DFR dengan Fasilitas 64 Digital Input untuk 2 bay Line 150 kV (One & A Half Breaker) minimal harus terdiri dari :

Main 1 Protection Operated (Line

Current/Distance 1) :

LP OPRT

Back 2 Protection Operated (OCR Back Up) : OC OPRT

A/R 1 In Progress : A/R OPRT

Carrier send from Distance : LP SEND

Carrier Receive to Distance : LP RCV

Trip phasa A : TRIP R

Trip phasa B : TRIP S

Trip phasa C : TRIP T

CB 5Ax/Bx phasa A open : CB 5Ax/Bx R OPEN

CB 5Ax/B xphasa B open : CB 5Ax/Bx S OPEN

CB 5Ax/Bx phasa C open : CB 5Ax/Bx T OPEN

CB 5ABx phasa A open : CB 5ABx R OPEN

CB 5ABx phasa B open : CB 5ABx S OPEN

CB 5ABx phasa C open : CB 5ABx T OPEN

CBF/SZP 5Ax/5Bx Trip : CBF/SZP 5Ax/5Bx OPRT

CBF/SZP 5ABx Trip : CBF/SZP 5ABx OPRT

CCP 1 operated : CCP 1 OPRT

Send DTT : DTT SEND

Receive DTT. : DTT RCV.

CB Pole Discrapancy : CB DISCRAPANCY

Spare. :

Spare. :

Spare. :

Spare :

Spare. :

Spare. :

Spare. :

Spare. :

Spare :

Spare. :

Spare. :

Spare :

Page 30: 05. Tpg Sogi Final 2011

- DFR dengan Fasilitas 32 Digital Input untuk 2 bay Line 150 kV (One & A Half Breaker) minimal harus terdiri dari :

Main Protection Operated : LP OPRT

Back 2 Protection Operated (OCR Back Up) : OC OPRT

A/R 1 In Progress : A/R OPRT

Carrier send from Distance : LP SEND

Carrier Receive to Distance : LP RCV

CB 5Ax/Bx phasa A open : 5Ax/Bx R OPEN

CB 5Ax/B xphasa B open : 5Ax/Bx S OPEN

CB 5Ax/Bx phasa C open : 5Ax/Bx T OPEN

CB 5ABx phasa A open : 5ABx R OPEN

CB 5ABx phasa B open : 5ABx S OPEN

CB 5ABx phasa C open : 5ABx T OPEN

CBF/SZP 5Ax/5Bx Trip : CBF/SZP 5Ax/5Bx OPRT

CBF/SZP 5ABx Trip : CBF/SZP 5ABx OPRT

CCP operated : CCP OPRT

Send DTT : DTT SEND

Receive DTT. : DTT RCV.

- DFR dengan Fasilitas 64/32 Digital Input untuk 2 bay Line 150 kV (Double Bus) minimal harus terdiri dari :

Main Protection Operated : LP OPRT

Back 2 Protection Operated (OCR Back Up) : OC OPRT

A/R 1 In Progress : A/R OPRT

Carrier send from Distance : LP SEND

Carrier Receive to Distance : LP RCV

Trip phasa A : TRIP R

Trip phasa B : TRIP S

Trip phasa C : TRIP T

CB phasa A open : CB R OPEN

CB phasa B open : CB S OPEN

CB phasa C open : CB T OPEN

CBF/SZP Trip : CBF/SZP OPRT

Send DTT : DTT SEND

Receive DTT. : DTT RCV

Spare :

Spare. :

Page 31: 05. Tpg Sogi Final 2011

- DFR dengan Fasilitas 64 Digital Input untuk bay IBT/Trafo 150 kV (One & A Half Breaker) minimal harus terdiri dari :

Main Protection (DIFF) Operated. : MAIN PROT OPRT

Main Protection (REF HV) Operated. : REF HV OPRT

Main Protection (REF LV) Operated. : REF LV OPRT

Back Up Protection HV Operated. : OC HV OPRT

Back Up Protection LV Operated. : OC LV OPRT

Over Voltage Operated. : OV OPRT

Bucholz Operated. : BUCHOLZ

Jansen Operated. : JANSEN

Thermal Relay Operated. : THERMAL

Suddent Pressure Operated. : SUDDENT PRES

CB HV 5Ax/5Bx Open. : 5Ax/5Bx HV OPEN

CB HV 5Ax/5Bx Close. : 5Ax/5Bx HVCLOSE

CB HV 5ABx Open. : 5ABx HV OPEN

CB HV 5ABx Close. : 5ABx HV CLOSE

CB LV Open : CB LV OPEN

PMT LV Close. : PMT LV CLOSE.

CCP Operated : CCP OPRT

CBF/SZP 5Ax/5BxTrip : CBF/SZP 5Ax/5Bx OPRT

CBF/SZP 5ABxTrip : CBF/SZP 5ABx OPRT

CBF/SZP LV Trip. : CBF/SZP LV OPRT

Spare. :

Spare. :

Spare. :

Spare. :

Spare :

Spare. :

Spare. :

Spare. :

Spare. :

Spare :

Spare. :

Spare. :

Page 32: 05. Tpg Sogi Final 2011

- DFR dengan Fasilitas 32 Digital Input untuk bay IBT/Trafo 150 kV (One & A Half Breaker) minimal harus terdiri dari :

Main Protection (DIFF) Operated. : MAIN PROT OPRT

Main Protection (REF HV) Operated. : REF HV OPRT

Main Protection (REF LV) Operated. : REF LV OPRT

Back Up Protection HV Operated. : OC HV OPRT

Back Up Protection LV Operated. : OC LV OPRT

Over Voltage Operated. : OV OPRT

Bucholz Operated. : BUCHOLZ

Jansen Operated. : JANSEN

Thermal Relay Operated. : THERMAL

Suddent Pressure Operated. : SUDDENT PRES

PMT HV 5Ax/5Bx Open. : 5Ax/5Bx OPEN

PMT HV 5ABx Open. : 5ABx HV OPEN

PMT LV Open : CB LV OPEN

CCP Operated : CCP OPRT

CBF/SZP 5Ax/5BxTrip : CBF/SZP 5Ax/5Bx OPRT

CBF/SZP 5ABxTrip : CBF/SZP 5ABx OPRT

- DFR dengan Fasilitas 32 Digital Input untuk bay IBT/Trafo 150 kV (Double Bus) minimal harus terdiri dari :

Main Protection (DIFF) Operated. : MAIN PROT OPRT

Main Protection (REF HV) Operated. : REF HV OPRT

Main Protection (REF LV) Operated. : REF LV OPRT

Back Up Protection HV Operated. : OC HV OPRT

Back Up Protection LV Operated. : OC LV OPRT

Over Voltage Operated. : OV OPRT

Bucholz Operated. : BUCHOLZ

Jansen Operated. : JANSEN

Thermal Relay Operated. : THERMAL

Suddent Pressure Operated. : SUDDENT PRES

CB HV Open. : CB HV OPEN

CB HV Close : CB HV CLOSE

CB LV Open : CB LV OPEN

CB LV Close : CB LV CLOSE

CBF/SZP Trip : CBF/SZP OPRT

Spare : Spare

Page 33: 05. Tpg Sogi Final 2011

B Sensor

1. 3UV channel : 80%Vn

2. 1OV channel : 105%Vn

3. 3OC channel : 120% In CT Line or 100% In Trafo

4. 1OC channel : 0.2-0.6%In

5. Uf Channel : 49 Hz6. Of Channel : 51 Hz

C Duration

1. Pre Fault : 100 ms

2. Fault : Flexible

3. Post Fault : 100 ms

Page 34: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14E PROTEKSI, SCADA & AUTOMATION : INVERTER

NO Description Requirement Proposed and Guarantee1 Name : .............................................

2 Manufacture/Type : …………../…………………..

3 Electrical safety EN 60950, VDE 08054 Efficiency > 88% at nominal load5 Operating temperature -5 to+55 degree celcius, non condensing6 Input DC 110 (88 -132) VDC dan 220 VAC7 Output AC 220 VAC8 Failure tolerance +/-5%9 Frequency 50Hz sinewave 10 Power 2 X beban maksimum11 Power Factor 0.812 Load range 0 - 100%

TECHNICAL PARTICULAR AND GUARANTEE

Page 35: 05. Tpg Sogi Final 2011

DAFTAR ISIAN 3 TPG 14B PROTEKSI, SCADA & AUTOMATION : IED METER

NO Description Requirement Proposed and Guarantee

1 Name .............................................

2 Manufacture/Type …………../…………………..

3 Auxiliary supply

Voltage 110 VDC (-15% s.d +10%)

4 Accuracy

- Voltage 0,5 %

- Current 0,5 %

- Power factor 1%

- Total harmonic distortion (THD) ± 1 %

- kW, kVA, kVAr 0,5 %

- kWh, kVAh, kVARh Class 0,5

5 Local configuration

Terminal interface RJ 45 / RS 485 / RS 232

Database configuration Upload dan download

6 Protocol IEC 61850

TECHNICAL PARTICULAR AND GUARANTEE

Bidder :

Signature : 35 - R1