04524745

Embed Size (px)

Citation preview

  • 7/29/2019 04524745

    1/5

    1

    Estimating General Pollution Waveforms in

    Non-Monitored Electrical System Buses

    Jacques Szczupak,Fellow, IEEE1

    Abstract-- This work studies the estimation of injected currentsin internal system buses. It generalizes previous studies on

    harmonic pollution estimation, such as to allow estimating

    general injected current waveforms. The electrical network is

    first modeled in order to derive necessary and sufficient

    conditions to permit single frequency component estimation. This

    result is shown to be sufficient when applicable to the desired

    spectrum region. Digital signal processing techniques are used as

    a basis to return from frequency-domain back into time-domain,

    recovering the unknown waveform. An illustrative case supports

    the theory, indicating excellent match between injected and

    recovered currents. Computational load is discussed and possible

    reduction procedures are suggested.

    Index Terms Quality, Signal Processing, Estimation,

    Harmonics, Injections

    I. INTRODUCTION

    RESERVING energy quality is an important factor in

    order to keep electrical utility customers satisfied.

    However, to maintain minimum standards of quality is not

    only expensive, but frequently also technically difficult to

    achieve. Electrical pollution may have unknown time varying

    sources, from load polluting customers to malfunctioning

    equipments. Correctly monitoring quality is essential to limit

    its effects by some type of control procedure; technically and,

    sometimes, commercially acting on the pollution source.

    It is common sense in the electrical sector to face the large

    variety of electrical disturbances by assuming itsdecomposition in a collection of qualified signal distortions

    such as harmonics, sags, swells, flickers etc. This tactic makes

    it easier to understand and study causes and consequences of

    the sets of signal perturbations. For instances, specific studies

    and estimating techniques exist and are being developed for

    each of the phenomena.

    Estimating the pollution source is not a simple problem.

    System dimension/complexity and the large variety of

    possible pollution distortions make it a difficult task. It is

    common practice to reduce problem complexity by studying

    pollution estimation and source location, restricted to the

    existence of just one of the previously mentioned phenomena.

    Practical observations, however, indicate a commonsituation; the pollution involves more than one of the

    previously mentioned types of perturbations. Not only this,

    but sometimes the phenomena somehow interact, as for

    instance is the case of larger sags associated with larger

    harmonic energies.

    J. Szczupak is with the Catholic University of Rio de Janeiro (PUC-RJ) and

    Engenho Pesquisa, Desenvolvimento e Consultoria Ltda., Rio de Janeiro,

    Brasil ([email protected])

    As a result, the energy quality estimation problem may getinvolved, even for the case of directly monitored electrical

    signals.

    Economical reasons limit the number of signal-monitored

    buses, requiring pollution estimation for non-monitored buses.

    This has been successfully done, for instances, in the

    harmonic pollution case.

    II. NETWORKMODEL

    The power network is usually composed by linear and

    nonlinear subsystems, making it difficult to find a general and

    adequate model for representation. The network nonlinear

    subsystems include operating equipments, such as saturated

    power transformers, but may also result from nonlinear loads,

    partly responsible for the network loss of quality. As a result,

    the selected network model must deal with unknown, possibly

    time-variant, types of non-linear behavior.

    The selected model assumes the non-linear network to be

    monitored by L access ports, delimiting its external frontiers.

    In addition, extra monitoring ports are created by the

    extraction of non-linear sub-systems from the network. This

    extraction procedure may be understood as pulling the non-

    linear device out of the network without destroying its

    electrical connections. As such, new access ports are created,

    L+1, , L+K, corresponding to the non-linear sub-system

    ports, as indicated in Figure 1.

    Figure 1 Transformer Equivalent Circuit

    P

  • 7/29/2019 04524745

    2/5

    2

    The resulting network is still non-linear, since there might

    be unknown internal non-linear loads. These internal loads are

    modeled by proper injection of currents to the internal buses.

    Figure 2 represents the final linear network model, after

    extraction of the non-linear loads. The total number of ports is

    now N, consisting of L external, K non-linear sub-systems

    extraction related and (N-L-K) representing the non-linear

    loads internal buses injections.

    Fig. 2 Linear N-Port Network

    In practice the model requires monitoring all first (L+K)

    ports, such as the port vectors

    [ ]t

    1 2 K= V V ... V1V (1)

    and

    [ ]t

    1 1 2 K = I I ... II (2)

    are supposed to be known.

    All monitored port voltages and currents are supposed

    acquired with sampling frequency fT, covering from dc to the

    Nyquist frequency fT/2 [1]. The data acquisitions are supposed

    to be satellite synchronized.

    The unknown port variables are described by the port vectors

    [ ]t

    2 K+1 K+2 N= V V ... VV (3)

    and

    [ ]t

    2 K+1 K+2 N= I I ... II . (4)

    The port admittance matrix [2] description was chosen for

    the linear network , with no loss of generality. The resulting

    N-port description is

    1 11 12

    2 21 22

    1

    2

    =

    Y YY Y

    I V

    I V, (5)

    where the index 1 identifies monitored variables and index 2

    stands for unknown.

    III. NETWORKESTIMATION MODEL

    If exists, it is possible to determine from (5)-1

    12Y

    -1

    12 (= 2 1 11Y Y )1V I V (6)

    and substituting its value on eq. (5) it follows

    21 22 2Y Y= +2 1I V V . (7)

    The existence of this type of matrix description and of

    depends on the network topology and parameters and on

    the relative port locations. Any choice for the Monitoring portlocations satisfying these conditions may be used.

    -1

    12Y

    It should be noticed that the network modeling is all

    frequency domain based. This naturally leads to the harmonic

    case estimation procedure, since it consists of applying the

    derived equations for the fundamental and for each of the

    harmonic frequencies [3-8]. In the case of general waveforms

    this is no longer the situation, since the frequency spectrum is

    no more discrete, but continuous. This more general injection

    pollution problem is discussed next.

    IV. GENERALWAVEFORMCURRENT INJECTION

    Although general waveforms require a continuous

    frequency spectrum description, it is possible to very closelyapproximate this spectrum by sampling it at a sufficiently

    dense discrete number of points. This can be done by

    uniformly sampling the voltages and currents on the jw-axis

    (of the Laplace plane), satisfying the Nyquist frequency [1].

    Therefore, eqs. (6) and (7) are successfully applied so as to

    uniformly sample the values of the pair of vectors (V2, I2) . At

    the end of this sampling evaluations, each of the elements of

    V2 and I2 may now form a complex vector ordering its

    frequency sampled values.

    Clearly, it is not necessary to evaluate for positive and

    negative frequencies, since one may use the symmetry and

    antisymmetry properties for the corresponding spectrum realand imaginary parts. However, the final vectors must contain

    all those values.

    Applying the IFFT (Inverse Fast Fourier Transform)

    operator to each of the frequency domain described vectors

    results the equivalent time-domain pair of vectors (v2, i2)

  • 7/29/2019 04524745

    3/5

    3

    The proper choice of sampling frequency is strongly

    dependent of the analysis objectives. In the case of harmonics

    this is quite obvious, choosing a sampling frequency of at

    least twice the highest harmonic frequency. For general

    waveforms, the usual constraint is related to spikes or any

    other fast varying situation to be registered. The faster the

    transient, the higher the sampling frequency.

    Window length is a second parameter to be considered. If a

    continuous recovery is necessary, subsequent windows shouldhave their results concatenated by known procedures [1].

    Larger window length imply heavier computation and delay in

    applying the IFFT. The designer will have to balance between

    larger window length with less concatenation to next window

    effort or smaller windows (faster IFFT) with a larger number

    of concatenation to next window operations. The decision

    depends on the application.

    V. ILLUSTRATIVECASE

    The chosen illustrative case is based on the meshed six

    buses system shown in Figure 3, slightly modified from the

    original WSCC (Western System Coordinating Council)

    unifilar diagram [10].

    1,026 3,7

    j0,0586j0,0625

    0,0085 j0,072 0,0119 j0,1008

    0,032

    j0,161

    0,01j0,088

    0,017

    j0,092

    0,039

    j0,17

    1

    2 8

    5 6

    4

    7

    9

    10

    11

    12

    13

    14

    15

    j0,0576

    -j4,399

    -j5,9878

    -j5,5844-j3,5274

    -j3,878-j4,151

    0,913

    j0,311

    j0,2707 j0,3287

    0,6831,02SWING

    3

    1,016 0,7 1,032 2,0

    0,996 -4,0 1,013 -3,7

    1,026 -2,2

    I1

    I3I2

    Fig. 3 Case Sudy Network

    Computer synthesized current waveforms, besides the

    usual 60 Hz currents indicated in the figure, were injected into

    the buses. These currents are composed not only by

    fundamental and harmonic components, but they also include

    non-harmonic modulating sinusoids as well as exponentially

    decreasing magnitude spikes of random nature.

    The set of bus injected current spectrum magnitude is

    shown in Figure 4. The legend identifies the corresponding

    bus numbering. As it is possible to observe, it was supposed

    buses 1, 2 and 3 are the external connections, while buses 5, 6

    and 8 are those were non-linear loads could be connected. The

    synthesized waveforms occupy practically all the frequency

    spectrum.

    Fig. 4 Magnitude of the Bus Injected Currents

    The unknown vectors, (V2, I2), are estimated from the pair

    of known vectors (V1, I1), following eqs. (6) and (7),

    sweeping the frequency axis, up to the Nyquist frequency. In

    the sequence, the estimated frequency-domain pair of vectors,

    (V2, I2), is IFFT mapped back into time-domain (v2, i2). The

    result offers an almost perfect match between original and

    reconstructed waveforms.

    This is illustrated in Figure 5 displaying bus 8 original and

    estimated currents. It is possible from this figure to observe

    the complexity of the recovered waveform.

    Fig. 5 Injected Current in Bus 8

    Figure 6 represents the detail of bus 8 current also

    exhibiting almost perfect match between original and

    recovered waveforms.

  • 7/29/2019 04524745

    4/5

    4

    Fig. 6 Injected Current in Bus 8 Detail

    Figure 7 displays details of the bus 6 injected currents,

    while figures 8 and 9 shows bus 5 currents, the whole windowand a detail, respectively. Purposely the waveforms are

    severely distorted with respect to the desired sinusoidal

    waveform. This was done in order to emphasize the methods

    possibilities.

    All the figures indicate a very close match between original

    and recovered currents. It is possible to detect, mostly in the

    details, almost unnoticeable mismatches.

    Real life data will not fit as nicely as those, computer

    synthesized, used in the illustrative case. There will exist

    sampling time uncertainties as well as quantization effects,

    from A/D conversion to arithmetic word length nonlinear

    effects, altering the exact results. The author is now pursuing

    this line of research.

    Fig. 7 Injected Current in Bus 6 Detail

    Fig. 8 Injected Current in Bus 5

    Fig. 9 Injected Current in Bus 5 - Detail

    VI. COMPUTATIONALCOMPLEXITY

    Although simple, the method involves a tremendous

    computational load. This load is strongly dependent on the

    size of the network under analysis and on the number of times

    one should obtain , one for each sampled frequency.-1

    12Y

    It is possible to reduce this computational load by

    restricting the sampling rate, but this is not always possible, as

    previously discussed. A second approach is to obtain at a

    reduced number of points, generating the remaining samples

    by interpolation procedures. Multirate digital signal methods

    are available for this purpose [1].

    -1

    12Y

    This last approach was used in the illustrative case

    resulting a reduction of at least an order of magnitude in the

    computational load. This result is not always possible to

    generalize.

  • 7/29/2019 04524745

    5/5

    5

    It is strongly connected to the network under examination

    and a good hint on the result might come from the

    interpretation of in eq. (6). It acts as the impedance

    matrix mapping port 1 currents into voltages in port 2. For

    instance for the chosen ports, in the used network, this almost

    reduces in low frequencies to series RL sub networks. As a

    result the impedance elements in have almost constant

    real part, while the imaginary part varies linearly withfrequency. A simple linear interpolation procedure would

    work as well as the more sophisticated used. This simple case

    will probably be found repeatedly due to the very nature of

    power networks.

    -1

    12Y

    -1

    12Y

    VII. CONCLUSIONS

    A new method is presented in order to estimate general

    pollution injection in the electric energy network. The

    approach is general, not being restricted to radial topology

    power networks.

    The original network is modified by the introduction of

    extra monitoring ports, simplifying the network description

    and allowing establishing a one to one relation betweenunknown injections and monitoring port measurements. A

    mathematical description of the transformed network, leads to

    a close form solution to the problem.

    It is shown, for the general type of waveform injection case

    that one may sequentially operate in frequency and time

    domains alternating from one to the other. The approach leads

    to very accurate signal reconstructions, as illustrated with a

    meshed type of network. The injected pollution was not

    limited to harmonics, but included modulating signals and

    random generated spikes. A digital signal multirate approach

    is suggested in order to reduce computational complexity in

    large networks. The idea being to evaluate a reduced number

    of inverse matrices and digitally interpolate the missingvalues.

    VIII. REFERENCES

    [1] S.K.MITRA, Digital Signal Processing A Computer-Based Approach,

    McGraw-Hill, 1998

    [2] N. BALABANIAN and T. A. BICKART, Network Theory, John Wiley

    and Sons, 1969.

    [3] A. C. PARSONS, W. M. GRADY, E. J. POWERS and J. C. SOWARD,

    "A Direction Finder for Power Quality Disturbances Based upon

    Disturbance Power and Energy", Proceedings of the 8th International

    Conference on Harmonics and Quality of Power, pp. 693 to 699, Greece,

    October 1998.

    [4] A. TESHOME, "Harmonic source and type identification in a radial

    distribution system," in Proc. 1991 IEEE Industry Applications Society

    Annual Meeting, pp. 1605-1609.

    [5] H. MA and A. A. GIRGIS, "Identification and tracking of harmonic

    sources in a power system using a kalman filter," IEEE Transactions on

    Power Delivery, vol. 11, no. 3, pp. 1659-1665, July 1996.

    [6] V. L. PHAM, K. P. WONG, N. R. WATSON, and J. ARRILLAGA, "A

    method of utilizing non-source measurements for harmonic state

    estimation," ELSEVIER Electric Power Systems Research, vol. 56, pp.

    231-241, May 2000.

    [7] J. ARRILLAGA, M. H. J. BOLLEN, and N. R. WATSON, "Power

    quality following deregulation," (invited paper) Proceedings of the

    IEEE, vol. 88, no. 2, pp. 246-261, Feb. 2000.

    [8] J. SZCZUPAK and G.P.B.CASTRO,Estimao e Localizao de

    Fontes Poluidoras de Harmnicos, XVII SNPTEE, Brazil, 2003.

    [9] J. SZCZUPAK, R. A. F. CHACON, P. A. M-S. DAVID, "Real TimePrecise Harmonic Estimation", Proceedings of the 13th Power System

    Computation Conference, PSCC, vol.: II, pp. 1063 to 1069, Throndheim,

    Norway, 1999.

    [10] M. A. PAI e P. W. SAUER, Power System Dynamics and Stability,

    Prentice Hall, 1998.

    [11] S. HAYKIN, Adaptive Filter Theory, Prentice Hall, Upper Side River,

    NJ, third edition, 1996.

    IX. BIOGRAPHY

    Jacques Szczupak (Fellow, IEEE) is an Electrical Engineer, graduated in

    1964 (UFRJ), M.Sc. in 1967 (UFRJ) and Ph.D. in 1975 (University of

    California). He was a professor in COPPE/UFRJ, leader of the Signal

    Processing group (CEPEL) and is now a full professor at PUC-RIO. He is the

    technical director of Engenho. Dr. Szczupak participated in different

    committees and working groups, was editor of many technical magazines,

    founded the IEEE Circuits and Systems Rio de Janeiro Chapter and was

    Circuits and Systems Region IX President. His areas of interest include

    Instrumentation, Signal Processing, Energy, Quality and Simulation.