Upload
eligius-martinez
View
214
Download
0
Embed Size (px)
Citation preview
7/29/2019 04524745
1/5
1
Estimating General Pollution Waveforms in
Non-Monitored Electrical System Buses
Jacques Szczupak,Fellow, IEEE1
Abstract-- This work studies the estimation of injected currentsin internal system buses. It generalizes previous studies on
harmonic pollution estimation, such as to allow estimating
general injected current waveforms. The electrical network is
first modeled in order to derive necessary and sufficient
conditions to permit single frequency component estimation. This
result is shown to be sufficient when applicable to the desired
spectrum region. Digital signal processing techniques are used as
a basis to return from frequency-domain back into time-domain,
recovering the unknown waveform. An illustrative case supports
the theory, indicating excellent match between injected and
recovered currents. Computational load is discussed and possible
reduction procedures are suggested.
Index Terms Quality, Signal Processing, Estimation,
Harmonics, Injections
I. INTRODUCTION
RESERVING energy quality is an important factor in
order to keep electrical utility customers satisfied.
However, to maintain minimum standards of quality is not
only expensive, but frequently also technically difficult to
achieve. Electrical pollution may have unknown time varying
sources, from load polluting customers to malfunctioning
equipments. Correctly monitoring quality is essential to limit
its effects by some type of control procedure; technically and,
sometimes, commercially acting on the pollution source.
It is common sense in the electrical sector to face the large
variety of electrical disturbances by assuming itsdecomposition in a collection of qualified signal distortions
such as harmonics, sags, swells, flickers etc. This tactic makes
it easier to understand and study causes and consequences of
the sets of signal perturbations. For instances, specific studies
and estimating techniques exist and are being developed for
each of the phenomena.
Estimating the pollution source is not a simple problem.
System dimension/complexity and the large variety of
possible pollution distortions make it a difficult task. It is
common practice to reduce problem complexity by studying
pollution estimation and source location, restricted to the
existence of just one of the previously mentioned phenomena.
Practical observations, however, indicate a commonsituation; the pollution involves more than one of the
previously mentioned types of perturbations. Not only this,
but sometimes the phenomena somehow interact, as for
instance is the case of larger sags associated with larger
harmonic energies.
J. Szczupak is with the Catholic University of Rio de Janeiro (PUC-RJ) and
Engenho Pesquisa, Desenvolvimento e Consultoria Ltda., Rio de Janeiro,
Brasil ([email protected])
As a result, the energy quality estimation problem may getinvolved, even for the case of directly monitored electrical
signals.
Economical reasons limit the number of signal-monitored
buses, requiring pollution estimation for non-monitored buses.
This has been successfully done, for instances, in the
harmonic pollution case.
II. NETWORKMODEL
The power network is usually composed by linear and
nonlinear subsystems, making it difficult to find a general and
adequate model for representation. The network nonlinear
subsystems include operating equipments, such as saturated
power transformers, but may also result from nonlinear loads,
partly responsible for the network loss of quality. As a result,
the selected network model must deal with unknown, possibly
time-variant, types of non-linear behavior.
The selected model assumes the non-linear network to be
monitored by L access ports, delimiting its external frontiers.
In addition, extra monitoring ports are created by the
extraction of non-linear sub-systems from the network. This
extraction procedure may be understood as pulling the non-
linear device out of the network without destroying its
electrical connections. As such, new access ports are created,
L+1, , L+K, corresponding to the non-linear sub-system
ports, as indicated in Figure 1.
Figure 1 Transformer Equivalent Circuit
P
7/29/2019 04524745
2/5
2
The resulting network is still non-linear, since there might
be unknown internal non-linear loads. These internal loads are
modeled by proper injection of currents to the internal buses.
Figure 2 represents the final linear network model, after
extraction of the non-linear loads. The total number of ports is
now N, consisting of L external, K non-linear sub-systems
extraction related and (N-L-K) representing the non-linear
loads internal buses injections.
Fig. 2 Linear N-Port Network
In practice the model requires monitoring all first (L+K)
ports, such as the port vectors
[ ]t
1 2 K= V V ... V1V (1)
and
[ ]t
1 1 2 K = I I ... II (2)
are supposed to be known.
All monitored port voltages and currents are supposed
acquired with sampling frequency fT, covering from dc to the
Nyquist frequency fT/2 [1]. The data acquisitions are supposed
to be satellite synchronized.
The unknown port variables are described by the port vectors
[ ]t
2 K+1 K+2 N= V V ... VV (3)
and
[ ]t
2 K+1 K+2 N= I I ... II . (4)
The port admittance matrix [2] description was chosen for
the linear network , with no loss of generality. The resulting
N-port description is
1 11 12
2 21 22
1
2
=
Y YY Y
I V
I V, (5)
where the index 1 identifies monitored variables and index 2
stands for unknown.
III. NETWORKESTIMATION MODEL
If exists, it is possible to determine from (5)-1
12Y
-1
12 (= 2 1 11Y Y )1V I V (6)
and substituting its value on eq. (5) it follows
21 22 2Y Y= +2 1I V V . (7)
The existence of this type of matrix description and of
depends on the network topology and parameters and on
the relative port locations. Any choice for the Monitoring portlocations satisfying these conditions may be used.
-1
12Y
It should be noticed that the network modeling is all
frequency domain based. This naturally leads to the harmonic
case estimation procedure, since it consists of applying the
derived equations for the fundamental and for each of the
harmonic frequencies [3-8]. In the case of general waveforms
this is no longer the situation, since the frequency spectrum is
no more discrete, but continuous. This more general injection
pollution problem is discussed next.
IV. GENERALWAVEFORMCURRENT INJECTION
Although general waveforms require a continuous
frequency spectrum description, it is possible to very closelyapproximate this spectrum by sampling it at a sufficiently
dense discrete number of points. This can be done by
uniformly sampling the voltages and currents on the jw-axis
(of the Laplace plane), satisfying the Nyquist frequency [1].
Therefore, eqs. (6) and (7) are successfully applied so as to
uniformly sample the values of the pair of vectors (V2, I2) . At
the end of this sampling evaluations, each of the elements of
V2 and I2 may now form a complex vector ordering its
frequency sampled values.
Clearly, it is not necessary to evaluate for positive and
negative frequencies, since one may use the symmetry and
antisymmetry properties for the corresponding spectrum realand imaginary parts. However, the final vectors must contain
all those values.
Applying the IFFT (Inverse Fast Fourier Transform)
operator to each of the frequency domain described vectors
results the equivalent time-domain pair of vectors (v2, i2)
7/29/2019 04524745
3/5
3
The proper choice of sampling frequency is strongly
dependent of the analysis objectives. In the case of harmonics
this is quite obvious, choosing a sampling frequency of at
least twice the highest harmonic frequency. For general
waveforms, the usual constraint is related to spikes or any
other fast varying situation to be registered. The faster the
transient, the higher the sampling frequency.
Window length is a second parameter to be considered. If a
continuous recovery is necessary, subsequent windows shouldhave their results concatenated by known procedures [1].
Larger window length imply heavier computation and delay in
applying the IFFT. The designer will have to balance between
larger window length with less concatenation to next window
effort or smaller windows (faster IFFT) with a larger number
of concatenation to next window operations. The decision
depends on the application.
V. ILLUSTRATIVECASE
The chosen illustrative case is based on the meshed six
buses system shown in Figure 3, slightly modified from the
original WSCC (Western System Coordinating Council)
unifilar diagram [10].
1,026 3,7
j0,0586j0,0625
0,0085 j0,072 0,0119 j0,1008
0,032
j0,161
0,01j0,088
0,017
j0,092
0,039
j0,17
1
2 8
5 6
4
7
9
10
11
12
13
14
15
j0,0576
-j4,399
-j5,9878
-j5,5844-j3,5274
-j3,878-j4,151
0,913
j0,311
j0,2707 j0,3287
0,6831,02SWING
3
1,016 0,7 1,032 2,0
0,996 -4,0 1,013 -3,7
1,026 -2,2
I1
I3I2
Fig. 3 Case Sudy Network
Computer synthesized current waveforms, besides the
usual 60 Hz currents indicated in the figure, were injected into
the buses. These currents are composed not only by
fundamental and harmonic components, but they also include
non-harmonic modulating sinusoids as well as exponentially
decreasing magnitude spikes of random nature.
The set of bus injected current spectrum magnitude is
shown in Figure 4. The legend identifies the corresponding
bus numbering. As it is possible to observe, it was supposed
buses 1, 2 and 3 are the external connections, while buses 5, 6
and 8 are those were non-linear loads could be connected. The
synthesized waveforms occupy practically all the frequency
spectrum.
Fig. 4 Magnitude of the Bus Injected Currents
The unknown vectors, (V2, I2), are estimated from the pair
of known vectors (V1, I1), following eqs. (6) and (7),
sweeping the frequency axis, up to the Nyquist frequency. In
the sequence, the estimated frequency-domain pair of vectors,
(V2, I2), is IFFT mapped back into time-domain (v2, i2). The
result offers an almost perfect match between original and
reconstructed waveforms.
This is illustrated in Figure 5 displaying bus 8 original and
estimated currents. It is possible from this figure to observe
the complexity of the recovered waveform.
Fig. 5 Injected Current in Bus 8
Figure 6 represents the detail of bus 8 current also
exhibiting almost perfect match between original and
recovered waveforms.
7/29/2019 04524745
4/5
4
Fig. 6 Injected Current in Bus 8 Detail
Figure 7 displays details of the bus 6 injected currents,
while figures 8 and 9 shows bus 5 currents, the whole windowand a detail, respectively. Purposely the waveforms are
severely distorted with respect to the desired sinusoidal
waveform. This was done in order to emphasize the methods
possibilities.
All the figures indicate a very close match between original
and recovered currents. It is possible to detect, mostly in the
details, almost unnoticeable mismatches.
Real life data will not fit as nicely as those, computer
synthesized, used in the illustrative case. There will exist
sampling time uncertainties as well as quantization effects,
from A/D conversion to arithmetic word length nonlinear
effects, altering the exact results. The author is now pursuing
this line of research.
Fig. 7 Injected Current in Bus 6 Detail
Fig. 8 Injected Current in Bus 5
Fig. 9 Injected Current in Bus 5 - Detail
VI. COMPUTATIONALCOMPLEXITY
Although simple, the method involves a tremendous
computational load. This load is strongly dependent on the
size of the network under analysis and on the number of times
one should obtain , one for each sampled frequency.-1
12Y
It is possible to reduce this computational load by
restricting the sampling rate, but this is not always possible, as
previously discussed. A second approach is to obtain at a
reduced number of points, generating the remaining samples
by interpolation procedures. Multirate digital signal methods
are available for this purpose [1].
-1
12Y
This last approach was used in the illustrative case
resulting a reduction of at least an order of magnitude in the
computational load. This result is not always possible to
generalize.
7/29/2019 04524745
5/5
5
It is strongly connected to the network under examination
and a good hint on the result might come from the
interpretation of in eq. (6). It acts as the impedance
matrix mapping port 1 currents into voltages in port 2. For
instance for the chosen ports, in the used network, this almost
reduces in low frequencies to series RL sub networks. As a
result the impedance elements in have almost constant
real part, while the imaginary part varies linearly withfrequency. A simple linear interpolation procedure would
work as well as the more sophisticated used. This simple case
will probably be found repeatedly due to the very nature of
power networks.
-1
12Y
-1
12Y
VII. CONCLUSIONS
A new method is presented in order to estimate general
pollution injection in the electric energy network. The
approach is general, not being restricted to radial topology
power networks.
The original network is modified by the introduction of
extra monitoring ports, simplifying the network description
and allowing establishing a one to one relation betweenunknown injections and monitoring port measurements. A
mathematical description of the transformed network, leads to
a close form solution to the problem.
It is shown, for the general type of waveform injection case
that one may sequentially operate in frequency and time
domains alternating from one to the other. The approach leads
to very accurate signal reconstructions, as illustrated with a
meshed type of network. The injected pollution was not
limited to harmonics, but included modulating signals and
random generated spikes. A digital signal multirate approach
is suggested in order to reduce computational complexity in
large networks. The idea being to evaluate a reduced number
of inverse matrices and digitally interpolate the missingvalues.
VIII. REFERENCES
[1] S.K.MITRA, Digital Signal Processing A Computer-Based Approach,
McGraw-Hill, 1998
[2] N. BALABANIAN and T. A. BICKART, Network Theory, John Wiley
and Sons, 1969.
[3] A. C. PARSONS, W. M. GRADY, E. J. POWERS and J. C. SOWARD,
"A Direction Finder for Power Quality Disturbances Based upon
Disturbance Power and Energy", Proceedings of the 8th International
Conference on Harmonics and Quality of Power, pp. 693 to 699, Greece,
October 1998.
[4] A. TESHOME, "Harmonic source and type identification in a radial
distribution system," in Proc. 1991 IEEE Industry Applications Society
Annual Meeting, pp. 1605-1609.
[5] H. MA and A. A. GIRGIS, "Identification and tracking of harmonic
sources in a power system using a kalman filter," IEEE Transactions on
Power Delivery, vol. 11, no. 3, pp. 1659-1665, July 1996.
[6] V. L. PHAM, K. P. WONG, N. R. WATSON, and J. ARRILLAGA, "A
method of utilizing non-source measurements for harmonic state
estimation," ELSEVIER Electric Power Systems Research, vol. 56, pp.
231-241, May 2000.
[7] J. ARRILLAGA, M. H. J. BOLLEN, and N. R. WATSON, "Power
quality following deregulation," (invited paper) Proceedings of the
IEEE, vol. 88, no. 2, pp. 246-261, Feb. 2000.
[8] J. SZCZUPAK and G.P.B.CASTRO,Estimao e Localizao de
Fontes Poluidoras de Harmnicos, XVII SNPTEE, Brazil, 2003.
[9] J. SZCZUPAK, R. A. F. CHACON, P. A. M-S. DAVID, "Real TimePrecise Harmonic Estimation", Proceedings of the 13th Power System
Computation Conference, PSCC, vol.: II, pp. 1063 to 1069, Throndheim,
Norway, 1999.
[10] M. A. PAI e P. W. SAUER, Power System Dynamics and Stability,
Prentice Hall, 1998.
[11] S. HAYKIN, Adaptive Filter Theory, Prentice Hall, Upper Side River,
NJ, third edition, 1996.
IX. BIOGRAPHY
Jacques Szczupak (Fellow, IEEE) is an Electrical Engineer, graduated in
1964 (UFRJ), M.Sc. in 1967 (UFRJ) and Ph.D. in 1975 (University of
California). He was a professor in COPPE/UFRJ, leader of the Signal
Processing group (CEPEL) and is now a full professor at PUC-RIO. He is the
technical director of Engenho. Dr. Szczupak participated in different
committees and working groups, was editor of many technical magazines,
founded the IEEE Circuits and Systems Rio de Janeiro Chapter and was
Circuits and Systems Region IX President. His areas of interest include
Instrumentation, Signal Processing, Energy, Quality and Simulation.