PRODUCT AND ENGINEERING MANUAL 4.3 SECONDARY FRAMING TABLE OF CONTENTS Table of Contents ........................................................................................................... 1 SF0010PE - Secondary Framing .......................................................................... 2 SF0020PE - “Z” Section Properties....................................................................... 3 SF0030PE - “C” Section Properties ...................................................................... 4 SF0040PE - “S” Section Properties ...................................................................... 5 AG0001 - “Z” Roof Purlins..................................................................................... 6 SF0050PE - “Z” Wall Girts (Inset/Flush) ............................................................... 7 SF0060PE - “Z” Wall Girts (Bypass Bolted Clips) ................................................. 8 SF0065PE - “Z” Wall Girts (Bypass Welded Clips) ............................................... 9 SF0070PE –Open-Web Welded Joists ............................................................... 10 SF0071PE -Open-Web All Bolted Joists ............................................................. 11 SF0072PE – Open Web Bolted Joists Detail Continued ..................................... 12 ClearBay CFR ..................................................................................................... 13 SF0080PE - Cold-Formed Box Beams ............................................................... 14 SF0090PE - Standard Purlin Spacing (Gable Building) ...................................... 15 SF0100PE - Standard Purlin Spacing (Single Slope Building) ........................... 16 SF0110PE - Standard Girt Spacing .................................................................... 17 4.3.1

04_03

  • Upload
    nsriitm

  • View
    127

  • Download
    13

Embed Size (px)

Citation preview

Page 1: 04_03

PRODUCT AND ENGINEERING MANUAL4.3 SECONDARY FRAMING

TABLE OF CONTENTS

Table of Contents ........................................................................................................... 1 SF0010PE - Secondary Framing .......................................................................... 2 SF0020PE - “Z” Section Properties ....................................................................... 3 SF0030PE - “C” Section Properties ...................................................................... 4 SF0040PE - “S” Section Properties ...................................................................... 5 AG0001 - “Z” Roof Purlins ..................................................................................... 6 SF0050PE - “Z” Wall Girts (Inset/Flush) ............................................................... 7 SF0060PE - “Z” Wall Girts (Bypass Bolted Clips) ................................................. 8 SF0065PE - “Z” Wall Girts (Bypass Welded Clips) ............................................... 9 SF0070PE –Open-Web Welded Joists ............................................................... 10 SF0071PE -Open-Web All Bolted Joists ............................................................. 11 SF0072PE – Open Web Bolted Joists Detail Continued ..................................... 12 ClearBay CFR ..................................................................................................... 13 SF0080PE - Cold-Formed Box Beams ............................................................... 14 SF0090PE - Standard Purlin Spacing (Gable Building) ...................................... 15 SF0100PE - Standard Purlin Spacing (Single Slope Building) ........................... 16 SF0110PE - Standard Girt Spacing .................................................................... 17 

4.3.1

Page 2: 04_03

PRODUCT AND ENGINEERING MANUAL4.3 SECONDARY FRAMING

LAST REVISION DATE: 08/06/04 BY: KMC CHK: RJF

DETAIL NAME IF APPLICABLE SF0010PE.DWG 4.3.2

SF0010PE - SECONDARY FRAMING

1. Standard Secondary Framing consists of Cold Formed “Z” shaped roof purlins and wall girts. “C” shaped wall girts may be used for framed openings and other special applications.

2. “Z” and “C” members are shop punched for simple field bolted connections. 3. “Z” and “C” members are available in either 8 or 10 inch depths. 12 and 14 inch

members depths are available on a limited basis. Consult the plant for specifics. 4. Optional Open-Web joists are available for wide bay applications with spans over

40 feet, and for mezzanine applications. 5. All section properties listed in this section were determined using the proper

provisions of the “Cold-Formed Steel Design Manual”, AISI, 1996 Edition. Any use of these properties for design should also be completed per these provisions.

6. As a standard, all bypass roof purlins and wall girts will utilize a shop welded clip. Bolted clips are also available.

7. Some Nucor Divisions may offer welded clips for inset or flush girts. Contact your NBS Division for availability.

Page 3: 04_03

PRODUCT AND ENGINEERING MANUAL4.3 SECONDARY FRAMING

LAST REVISION DATE: 03/20/12 BY: DLF CHK: EGB

DETAIL NAME IF APPLICABLE SF0020PE.DWG 4.3.3

SF0020PE - “Z” SECTION PROPERTIES

Section D (in.) B (in.) Design t (in.)

Design t Wt.

(#/Ft)

Gross Ix (in^4)

Net Sx (in^3)

Ma (in.-Kip)

8Z054 8.00 2.5 0.054 2.65 7.668 1.506 49.5968Z060 8.00 2.5 0.060 2.95 8.482 1.836 60.4668Z067 8.00 2.5 0.067 3.29 9.470 2.089 68.8078Z075 8.00 2.5 0.075 3.68 10.599 2.374 78.1888Z089 8.00 2.5 0.089 4.37 12.574 2.994 98.5968Z099 8.00 2.5 0.099 4.86 13.984 3.392 111.7208Z105 8.00 2.5 0.105 5.15 14.829 3.648 120.150

10Z060 10.00 2.5 0.060 3.35 14.331 2.264 74.56010Z067 10.00 2.5 0.067 3.74 16.001 2.674 88.08210Z075 10.00 2.5 0.075 4.19 17.910 3.223 106.14410Z089 10.00 2.5 0.089 4.97 0.500 4.063 133.80910Z099 10.00 2.5 0.099 5.53 23.632 4.600 151.50810Z105 10.00 2.5 0.105 5.87 25.062 4.945 162.87210Z120 10.00 2.5 0.120 6.71 28.635 5.658 186.337

12Z075 12.00 3.5 0.075 5.21 33.087 3.916 128.97112Z089 12.00 3.5 0.089 6.18 39.258 5.192 171.00412Z099 12.00 3.5 0.099 6.88 43.664 6.161 202.90912Z105 12.00 3.5 0.105 7.30 46.308 6.596 217.24912Z120 12.00 3.5 0.120 8.34 52.915 7.841 258.244

Page 4: 04_03

PRODUCT AND ENGINEERING MANUAL4.3 SECONDARY FRAMING

LAST REVISION DATE: 03/20/12 BY: DLF CHK: EGB

DETAIL NAME IF APPLICABLE SF0030PE.DWG 4.3.4

SF0030PE - “C” SECTION PROPERTIES

D B DESIGN t DESIGN t Wt. GROSS lx Net Sx MaSECTION (in.) (in.) (in.) (plf) (in^4) (in ^3) (in-kip)8C060 8.00 2.75 0.060 2.95 8.540 1.697 12.5608C067 8.00 2.75 0.067 3.29 9.535 1.996 14.2408C075 8.00 2.75 0.075 3.68 10.670 2.277 16.1808C089 8.00 2.75 0.089 4.37 12.656 2.831 19.6068C099 8.00 2.75 0.099 4.86 14.074 3.255 22.0668C105 8.00 2.75 0.105 5.15 14.924 3.502 23.544

10C060 10.00 2.75 0.060 3.35 14.405 2.098 12.60510C067 10.00 2.75 0.067 3.74 16.083 2.514 14.30010C075 10.00 2.75 0.075 4.19 18.000 3.048 16.26010C089 10.00 2.75 0.089 4.97 21.353 3.857 19.72610C099 10.00 2.75 0.099 5.53 23.746 4.422 22.22010C105 10.00 2.75 0.105 5.87 25.181 4.751 23.719

Page 5: 04_03

PRODUCT AND ENGINEERING MANUAL4.3 SECONDARY FRAMING

LAST REVISION DATE: 03/20/12 BY: DLF CHK: EGB

DETAIL NAME IF APPLICABLE SF0040PE.DWG 4.3.5

SF0040PE - “S” SECTION PROPERTIES

D B DESIGN t DESIGN t Wt. GROSS lx Net SxSECTION (in.) (in.) (in.) (plf) (in^4) (in ^3)

8S075 8.00 3.625 0.075 4.19 12.97 2.5318S089 8.00 3.625 0.089 4.97 15.39 3.1078S099 8.00 3.625 0.099 5.53 17.11 3.5338S105 8.00 3.625 0.105 5.87 18.14 3.7948S120 8.00 3.625 0.120 6.71 20.72 4.527

12S075 12.00 3.625 0.075 5.21 33.04 3.89412S089 12.00 3.625 0.089 6.18 39.20 5.19412S099 12.00 3.625 0.099 6.88 43.60 6.17112S105 12.00 3.625 0.105 7.30 46.23 6.61312S120 12.00 3.625 0.120 8.34 52.82 7.839

Page 6: 04_03

PRODUCT AND ENGINEERING MANUAL4.3 SECONDARY FRAMING

LAST REVISION DATE: 08/06/04 BY: KMC CHK: RJF

DETAIL NAME IF APPLICABLE AG0001.DWG 4.3.6

AG0001 - “Z” ROOF PURLINS

NOTES:

1) ALL PURLIN CONNECTIONS UTILIZE ½” DIAMETER BOLTS. 2) “Z” PURLINS HAVE SYMMETRICAL FLANGES FOR EASE OF ERECTION. 3) “Z” PURLINS ARE ECONOMICAL FOR SPANS UP TO AND INCLUDING 40

FEET.

Page 7: 04_03

PRODUCT AND ENGINEERING MANUAL4.3 SECONDARY FRAMING

LAST REVISION DATE: 02/09/01 BY: CDM CHK: RJF

DETAIL NAME IF APPLICABLE SF0050PE.DWG 4.3.7

SF0050PE - “Z” WALL GIRTS (INSET/FLUSH)

Page 8: 04_03

PRODUCT AND ENGINEERING MANUAL4.3 SECONDARY FRAMING

LAST REVISION DATE: 08/06/04 BY: KMC CHK: RJF

DETAIL NAME IF APPLICABLE SF0060PE.DWG 4.3.8

SF0060PE - “Z” WALL GIRTS (BYPASS BOLTED CLIPS)

Page 9: 04_03

PRODUCT AND ENGINEERING MANUAL4.3 SECONDARY FRAMING

LAST REVISION DATE: 08/06/04 BY: KMC CHK: RJF

DETAIL NAME IF APPLICABLE SF0065PE.DWG 4.3.9

SF0065PE - “Z” WALL GIRTS (BYPASS WELDED CLIPS)

Page 10: 04_03

PRODUCT AND ENGINEERING MANUAL4.3 SECONDARY FRAMING

LAST REVISION DATE: 06/11/09 BY: AES CHK:

DETAIL NAME IF APPLICABLE SF0070PE.DWG 4.3.10

SF0070PE –OPEN-WEB WELDED JOISTS

Page 11: 04_03

PRODUCT AND ENGINEERING MANUAL4.3 SECONDARY FRAMING

LAST REVISION DATE: 06/11/09 BY: AES CHK:

DETAIL NAME IF APPLICABLE SF0071PE.DWG 4.3.11

SF0071PE -OPEN-WEB ALL BOLTED JOISTS

Page 12: 04_03

PRODUCT AND ENGINEERING MANUAL4.3 SECONDARY FRAMING

LAST REVISION DATE: 10/31/11 BY: RT CHK: EGB

DETAIL NAME IF APPLICABLE SF0072PE.DWG 4.3.12

SF0072PE – OPEN WEB BOLTED JOIST DETAIL CONTINUED

Page 13: 04_03

PRODUCT AND ENGINEERING MANUAL4.3 SECONDARY FRAMING

LAST REVISION DATE: 10/23/09 BY: AES CHK:

DETAIL NAME IF APPLICABLE 4.3.13

CLEARBAY CFR • This system is only available for projects with roof joists and CFR panels. • The ClearBay CFR system was set in place to minimize joist bridging by utilizing

the capacity of the CFR roof panel system. This reduction in bridging will also result in a reduction of cost.

• ClearBay CFR is available in a welded and all bolted option. • These joists will be detailed the same as our typical roof joist system. The

reduced bridging will be specified by Vulcraft. • Click the link below to see the predetermined bridging rows and spacing for bays

that are 40’ to 60’in width. Any bay sizes other than these would be custom quoted. This table only applies to ClearBay CFR projects. ClearBay CFR Bridging Locations

Page 14: 04_03

PRODUCT AND ENGINEERING MANUAL4.3 SECONDARY FRAMING

LAST REVISION DATE: 10/23/09 BY: AES CHK:

DETAIL NAME IF APPLICABLE 4.3.14

SF0080PE - COLD-FORMED BOX BEAMS 1. Cold-formed box beams consist of two “C” or “S” sections, forming a cold-formed “tube”. 2. These tubes may be square or rectangular in shape. 3. The height of the box beam matches the purlin depth. The depth of the box beam will be 8”,

10”, or 12”, depending on the design requirements of a particular project. 4. Cold-formed box beams are typically used as a replacement for the eave strut, eave purlin, or

strong-back eave beam. 5. Standard connection for the box beam to primary framing member is with either (2) or (4) ½”

diameter A325 bolts per end.

Page 15: 04_03

PRODUCT AND ENGINEERING MANUAL4.3 SECONDARY FRAMING

LAST REVISION DATE: 10/11/11 BY: RT CHK: EGB

DETAIL NAME IF APPLICABLE SF0090PE.DWG 4.3.15

SF0090PE - STANDARD PURLIN SPACING (GABLE BUILDING)

* INDICATES ODD SPACE AS FOLLOWS: ROOF SLOPE

< 1/2:12 ≥ 1/2:12

PURLIN SPACE MIN. = 1’-10” MAX = 3’-10”MIN. = 1’-10” MAX = 5’-6”

NOTE: THESE SPACINGS ARE TO BE USED FOR BOTH NUCOR “CFR”™ AND NUCOR “CLASSIC ROOF”™ SYSTEMS. WITH NUCOR “CFR”™ ROOF (UL CLASS 90, UL 580, CONSTRUCTION NO. 590).

- MAXIMUM PURLIN SPACING IS 5’-0” W/ PURLINS. - MAXIMUM PURLIN SPACING IS 5’-6” W/ JOISTS.

Page 16: 04_03

PRODUCT AND ENGINEERING MANUAL4.3 SECONDARY FRAMING

LAST REVISION DATE: 10/11/11 BY: RT CHK: EGB

DETAIL NAME IF APPLICABLE SF0100PE.DWG 4.3.16

SF0100PE - STANDARD PURLIN SPACING (SINGLE SLOPE BUILDING)

* INDICATES ODD SPACE AS FOLLOWS: ROOF SLOPE

< 1/2:12 ≥ 1/2:12

PURLIN SPACE MIN. = 1’-10” MAX = 3’-10”MIN. = 1’-10” MAX = 5’-6”

NOTE: THESE SPACINGS ARE TO BE USED FOR BOTH NUCOR “CFR”™ AND NUCOR “CLASSIC ROOF”™ SYSTEMS. WITH NUCOR “CFR”™ ROOF (UL CLASS 90, UL 580, CONSTRUCTION NO. 590).

- MAXIMUM PURLIN SPACING IS 5’-0” W/ PURLINS. - MAXIMUM PURLIN SPACING IS 5’-6” W/ JOISTS.

Page 17: 04_03

PRODUCT AND ENGINEERING MANUAL4.3 SECONDARY FRAMING

LAST REVISION DATE: 02/09/01 BY: CDM CHK: RJF

DETAIL NAME IF APPLICABLE SF0110PE.DWG 4.3.17

SF0110PE - STANDARD GIRT SPACING