2006-03-30 Substation Automation Products Training
Product Integration with Control IED REC 670Introduction
SubstationAutomation Products
Training
2
©A
BB
Po
we
r T
ech
nolo
gie
s A
B,
200
5
2006-03-30 Substation Automation Products Training
Contents
Introduction Training equipment Software tools to be used Purpose of this course
Engineering workflow Network setup IED engineering Communication Engineering
Horizontal GOOSE Vertical, command and event handling
Connection to the MicroSCADA PRO
3
©A
BB
Po
we
r T
ech
nolo
gie
s A
B,
200
5
2006-03-30 Substation Automation Products Training
Introduction-training equipment
One PC, for MicroSCADA and Engineering tools
Two IED 670 relays, REC670
One switch
Simulators
Backup Panel
Line Bay
Bus Coupler Bay
Engineering WorkstationMicroSCADA station PC
Local Control Panel
4
©A
BB
Po
we
r T
ech
nolo
gie
s A
B,
200
5
2006-03-30 Substation Automation Products Training
Introduction-Training equipment
TRM
AD1 AD2
PSM
GSMI/O
SLM
LDCM(4 pieces)
NUM
11*CAN 3*PCI
OEM
Hardware in training IED’sBIM, BOM, IOM, MIM, TRM 6U+ 6I
5
©A
BB
Po
we
r T
ech
nolo
gie
s A
B,
200
5
2006-03-30 Substation Automation Products Training
Introduction-software tools to be used
PCM600 IED Engineering
CCT Communication engineering System engineering
MicroSCADA Pro Control, System supervision etc.
6
©A
BB
Po
we
r T
ech
nolo
gie
s A
B,
200
5
2006-03-30 Substation Automation Products Training
Introduction-purpose of this course
Engineer a minor SA-system with IED670 relays and MS Pro This course will include
PCM600 introduction
CAP531 engineering
GDE engineering
Parameterisation of IED670
Communication engineering, horizontal and vertical
Engineering of MS Pro application for IED670 relays
7
©A
BB
Po
we
r T
ech
nolo
gie
s A
B,
200
5
2006-03-30 Substation Automation Products Training
Introduction-purpose of this course
Result after 3 days.
LocalControl
Panel
Local operation
Remote operation
8
©A
BB
Po
we
r T
ech
nolo
gie
s A
B,
200
5
2006-03-30 Substation Automation Products Training
Introduction – Engineering Workflow
Network set-up Network architecture IP-addressing
PCM600 CAP531 PST GDE SMT
CCT Communication engineering
OPC Server HSI e.g. MicroSCADA
Picture engineering Data base engineering OPC DA Client
9
©A
BB
Po
we
r T
ech
nolo
gie
s A
B,
200
5
2006-03-30 Substation Automation Products Training
IEC61850 engineering for REx 670 (bottom up way)
.icd
Super-
.icdCAP531Exit CAP531
1 Configure Rex 670 with CAP531
2 Save configuration and exit CAP531
3 Merge .icd-files from all IED’s in PCM600
.icd
IED #n
.icd
IED #2
.icd
IED #1
.scd
4 Export .scd-fileto CCT
CCT
5 Engineer whole S/S communication and I/O section with CCT:
a) Dataset in IEDb) Report control
blockc) GOOSE
d) Input block
Output per IED
Input per IED
.scd
Export to PCM 600
PCM 600SMT
6 Connect attributes of input blocks with functions per IED with PCM 600 / SMT
.ccf
Download .ccf to IED
7 Download .ccf with PCM 600 / SMTto REx 670
10
©A
BB
Po
we
r T
ech
nolo
gie
s A
B,
200
5
2006-03-30 Substation Automation Products Training
Introduction-Engineering workflow Network set up
Type of switches Functionality, supplier etc.
Type of network Arrangement, redundancy etc
Addressing IP-addressing range (Intranet)
Parameterization of the switches
11
©A
BB
Po
we
r T
ech
nolo
gie
s A
B,
200
5
2006-03-30 Substation Automation Products Training
Introduction-Engineering workflow
Network Set up IP-Addressing
Class A Class B Class CAddress range 0.0.0.0 –
127.255.255.255
128.0.0.0 – 191.255.255.255
192.0.0.0 –
223.255.255.255
Intranet range 10.0.0.0 –
10.255.255.255
172.16.0.0 –
172.31.255.255
192.168.0.0 –
192.168.255.255
Network mask 255.0.0.0 255.255.0.0 255.255.255.0
# of nets 1 16 256
# of members 16777214 65524 254
12
©A
BB
Po
we
r T
ech
nolo
gie
s A
B,
200
5
2006-03-30 Substation Automation Products Training
Introduction-Engineering workflow
Network Set up Parameterization of the switches
Example, for Ruggetcom switches the VLAN parameter must be set to No, otherwise GOOSE is not working
13
©A
BB
Po
we
r T
ech
nolo
gie
s A
B,
200
5
2006-03-30 Substation Automation Products Training
IED Engineering PCM600 Tool box for engineering tools
CAP531 (1131 programming tool), used for application configuration
PST tool, for parameterization of the relays
GDE tool, Graphical Display Editor
SMT tool, Signal Matrix Tool, define inputs-outputs, GOOSE, LED’s
Introduction-Engineering workflow
14
©A
BB
Po
we
r T
ech
nolo
gie
s A
B,
200
5
2006-03-30 Substation Automation Products Training
Communication Engineering CCT Communication Configuration Tool
GOOSE Horizontal communication
Introduction-Engineering workflow
•Data set•GSE control block•MAC Address
15
©A
BB
Po
we
r T
ech
nolo
gie
s A
B,
200
5
2006-03-30 Substation Automation Products Training
Communication Engineering CCT Communication Configuration Tool
Vertical communication, command and event handling
Introduction-Engineering workflow
•Data set•RCB’s Report•Parmetrization of RCB’s
16
©A
BB
Po
we
r T
ech
nolo
gie
s A
B,
200
5
2006-03-30 Substation Automation Products Training
Introduction- Connection to MicroSCADA
Engineering steps OPC server engineering
Creation of a MicroSCADA application
Modification in SYS_BASCON file
Create the database
Engineer the single line diagram