AutomatictransferswitchesATK series
Planet-SWITCHPlanet-SWITCHPlanet-SWITCHPlanet-SWITCHPlanet-SWITCHPlanet-SWITCH
Planet-DIN
Planet-LOGIC
Planet-DIN
Planet-LOGIC
Planet-DIN
Planet-LOGIC
Planet-DIN
Planet-LOGIC
Planet-DIN
Planet-LOGIC
Planet-DIN
Planet-LOGIC
General characteristicsThe automatic transfer switch “ATK” is used for theautomatic changeover of the load from the “main line” toa “secondary line”.It is made of a single unit in an insulated housing andhas two outgoings for the “automatic” and/or “manual”control of contactors or circuit breakers.MANUAL CHANGEOVERThis mode consents to the manual changeover from onesource to another and viceversa.AUTOMATIC CHANGEOVERThis mode automatically enables the switching of twolines within a time period, adjustable between 0.5 and120 seconds.The control of the two line contactors or circuit breakersis achieved in a safe and reliable manner by means of asafety system with internal electromechanical interlockof the ATK unit.
Operational characteristics– Rated supply voltage: 24VDC (ATK20) -
230VAC (ATK40)– Voltage range: 0.7-1.35% Us (ATK20)
0.8-1.2% Us (ATK40)– Maximum current consumption: 250mA (ATK20) -
45mA (ATK40)– Rated current: 100mA (ATK20) - 35mA (ATK40)– Connection time: 100%– Maximum voltage ripple: 10% (ATK20)– Power loss ride through (MPU circuit): ≥300ms– Galvanic isolation between control network and
internal circuits– True RMS control of supplt voltage– Microprocessor supervision of functions– Membrane keypad and 3 digit display– 11 signalling LEDs– Adjustable tripping limits and time– AUT-MAN-TEST operating mode– 1 “Main” L-L voltage measurement input– 1 “Secondary” L-L voltage measurement input– 100-415VAC rated voltage control– 70-500VAC L-L voltage range– 50 or 60Hz rated frequency– Full scale measurement accuracy: ±1% ±1digit– 2 output relays (16A Ith changeover contact) for “Main”
and “Secondary” contactor or circuit breaker control– 1 alarm output relay (8A Ith changeover contact)– IP41 on front, IP54 with sealable cover (order
separately)– IP20 at rear.
Set upThe set up contemplates the following setting parameters:– Max voltage limit for “Main” and “Secondary” lines– Min voltage limit for “Main” and “Secondary” lines– Min-Max limit tripping delay for “Main” and
“Secondary” lines– Min-Max limit delay at voltage return for “Main” and
“Secondary” lines– Changeover/interlock control time for circuit breakers
control of “Main” and “Secondary” lines.
Selling points– Microprocessor supervision– Easy and simple installation– RMS voltage measurements (full scale accuracy: ±1%
±1digit)
Reference standardsCompliant with standards: IEC/EN50081-1,IEC/EN50082-2, IEC/EN61010-1, IEC/EN60068-2-6,IEC/EN60068-2-27, IEC/EN60529, IEC/EN61000-4-11and EN50011.
Order code Description Qty Wtperpkgn° [kg]
ATK20 Automatic transfer switch, 1 0.70024VDC auxiliary supply
ATK40 Automatic transfer switch, 1 0.900230VAC auxiliary supply
PACR IP54 front protection cover 1 0.107
Automatic transfer switches
PD39
GB
03 0
2
144
144
62
9
52
31
PACR
®
ATK
AUTOMATICTRANSFERSWITCH
AUT ON/OFF
MAIN LINE ON
SEC LINE ON
OPEN ALL LINES
TEST
SETUP
POWER ON
ALARM
LOAD
SECONDARYLINE
MAINLINE
DIMENSIONS (mm)
WIRING DIAGRAM
ATK...
LOVATO ELECTRIC S.P.A.CONTROL SOLUTIONSFOR INDUSTRY
VIA DON E. MAZZA, 1224020 GORLE (BG) ITALYTEL. +39 0354282111
INTERNATIONAL SALES DIPARTMENT:TEL. +39 0354282281FAX +39 0354282400
Web: www.LovatoElectric.comE-mail: [email protected]