MEP Sample Set - The TJX Companies, Inc.AutoCAD SHX Text
E1 LIGHTING PLAN LIGHTING PLAN E2 POWER PLAN POWER PLAN E2a POWER
PLAN - SUPPLEMENTAL POWER PLAN - SUPPLEMENTAL E3 PANEL SCHEDULES
AND ONE-LINE DIAGRAM PANEL SCHEDULES AND ONE-LINE DIAGRAM E4
ELECTRICAL DETAILS ELECTRICAL DETAILS M0 MECHANICAL NOTES &
SCHEDULES MECHANICAL NOTES & SCHEDULES M1 MECHANICAL PLAN
MECHANICAL PLAN M2 MECHANICAL DETAILS MECHANICAL DETAILS P0
PLUMBING NOTES & SCHEDULES PLUMBING NOTES & SCHEDULES P1
PLUMBING PLAN PLUMBING PLAN P2 PLUMBING PLANS AND RISER DIAGRAMS
PLUMBING PLANS AND RISER DIAGRAMS P3 PLUMBING GENERAL
DETAILSPLUMBING GENERAL DETAILS
AutoCAD SHX Text
AutoCAD SHX Text
ALL DRAWINGS IN THIS SET ARE CONCEPTUAL IN NATURE, PROVIDED AS A
GUIDE ONLY. THESE "TJX SAMPLE MEP PLANS" SHALL BE USED TO ASSIST
LANDLORD CONSULTANTS IN DEVELOPING A SITE SPECIFIC CONSTRUCTION
DOCUMENT SET PER THE LEASE REQUIREMENTS. ALL ITEMS WITHIN THIS
DOCUMENT, INCLUDING BUT NOT LIMITED TO SIZING, QUANTITIES,
LOCATIONS, AND MANUFACTURERS SHALL CONFORM TO THE REQUIREMENTS SET
FORTH IN THE APPLICABLE TJX GUIDE SPECIFICATIONS REFERENCED IN THE
LEASE.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTES ARE INCLUDED THROUGHOUT THE SAMPLE MEP SET TO ASSIST
THE SITE ADAPT CONSULTANT IN UNDERSTANDING THE TENANT'S DESIGN
INTENT. DESIGNER NOTES DO NOT COVER EVERY SITUATION THAT MAY BE
ENCOUNTERED BY THE SITE ADAPT CONSULTANT. THE SITE ADAPT CONSULTANT
IS COMPLETELY RESPONSIBLE FOR THE DESIGN OF THE SITE ADAPTED
PROJECT, INCLUDING SITE SPECIFIC LOAD CALCULATIONS, AND COMPLIANCE
WITH ALL REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. PROJECT
SPECIFIC SITE ADAPTED MEP DRAWINGS SHALL BE PREPARED UNDER THE
SUPERVISION OF PROFESSIONAL ENGINEERS LICENSED IN THE JURISDICTION
HAVING AUTHORITY OVER THE PROJECT. ALL SITE ADAPT CONSULTANTS SHALL
PERFORM ALL NECESSARY DUE DILIGENCE. THIS INCLUDES COORDINATION
WITH THE AUTHORITY HAVING JURISDICTION, THE FIRE DEPARTMENT, AND
ALL SERVING UTILITY COMPANIES. DETAILS INCLUDED IN THE SAMPLE MEP
SET SHALL BE MODIFIED BY THE SITE ADAPT CONSULTANT TO COMPLY WITH
SPECIFIC REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION FOR THE
SITE ADAPTED PROJECT. ITEMS THAT SHALL BE COORDINATED INCLUDE, BUT
ARE NOT LIMITED TO: ELECTRICAL METER/CT CONFIGURATION, AVAILABLE
FAULT CURRENT, FIRE ALARM SYSTEM NOTIFICATION REQUIREMENTS,
EMERGENCY LIGHTING REQUIREMENTS, EXIT SIGNAGE REQUIREMENTS, HVAC
LOAD CALCULATIONS, HVAC CONDENSATE DISPOSAL REQUIREMENTS, DOMESTIC
WATER PRESSURE AND WATER QUALITY, AVAILABLE NATURAL GAS PRESSURE
(WHEN APPLICABLE), AND SANITARY SEWER INVERT AND CONNECTION
REQUIREMENTS.
AutoCAD SHX Text
AutoCAD SHX Text
THIS SHEET IS PART OF THE CONSTRUCTION DOCUMENTS, OTHER SHEETS
INCLUDING SPECIFICATIONS APPLY. INFORMATION SHOWN HEREON IS
SCHEMATIC IN NATURE AND NOT TO BE USED AS A SHOP DRAWING;
THEREFORE, INCLUDE ALL MODIFICATIONS REQUIRED TO CONFORM TO SITE
CONDITIONS AND THE EQUIPMENT AND MATERIAL USED. VERIFY LOCATIONS
AND DIMENSIONS OF ALL ARCHITECTURAL AND STRUCTURAL ELEMENTS AS
SHOWN ON THEIR RESPECTIVE DOCUMENTS, THESE ELEMENTS ARE SHOWN FOR
REFERENCE AND SHALL BE VERIFIED PRIOR TO CONSTRUCTION AND THE
ENGINEER ASSUMES NO LIABILITY FOR THE ACCURACY OF THESE ELEMENTS.
NO DESIGN RESPONSIBILITY IS ASSUMED FOR ANY PORTION OF THE WORK
THAT THE PROFESSIONAL ENGINEER HAS NOT SIGNED AND SEALED PER STATE
REQUIREMENTS.
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT LOGO AND
ADDRESS
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT SEAL AND
SIGNATURE
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: COORDINATE SALES FLOOR LIGHT FIXTURE TYPES FOR
PROJECTS WITH ACT CEILINGS WITH PROJECT SPECIFIC TJX C-SET.
AutoCAD SHX Text
DESIGNER NOTE: ONLY USE LIGHTING ZONE "c" and "d" IF REQUIRED BY
APPLICABLE LOCAL LOCAL CODE.
AutoCAD SHX Text
AutoCAD SHX Text
ENSURE THAT ALL ROWS OF LIGHT FIXTURES ARE STRAIGHT AND LEVEL PRIOR
TO OPENING OF STORE. SUPPLY ALL APPURTENANCES NEEDED TO PROVIDE A
COMPLETE AND OPERATION INSTALLATION. PAINT ALL CONDUITS, CHANNEL,
RODS, AND APPURTENANCES TO MATCH STRUCTURE. PROVIDE AND INSTALL ALL
MATERIALS NECESSARY TO ENSURE PROPER SEISMIC BRACING AS REQUIRED
PER CODES.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CONDUIT AND BOX SUPPORTED AS REQUIRED BY FIELD CONDITIONS
TYPICAL
AutoCAD SHX Text
AutoCAD SHX Text
BEAM CLAMP TYPICAL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SUPPORT RESTRAINT CLIP MINIMUM (4) PER LIGHT FIXTURE, SECURELY
ATTACHED TO CIELING GRID PER N.E.C. 410.36(B)
AutoCAD SHX Text
#12 SAFETY WIRE TIED TO SAFETY WIRE SUPPORT HOLES & FASTENED TO
BLDG. STRUCTURE. MINIMUM (2) SAFETY WIRES PER LIGHT FIXTURE PLACED
AT DIAGONAL CORNERS. IF CEILING SYSTEM IS FIRE RATED, WIRES ARE TO
BE DISTINGUISHABLE BY COLOR OR TAGGING PER NEC 300.11(2)
AutoCAD SHX Text
AutoCAD SHX Text
EXPOSED T-BAR CEILING
AutoCAD SHX Text
NOTE: ALL WIRES ARE TO BE TAUT WITH A MINIMUM OF 3 TIGHT TURNS
AROUND SELF - TYPICAL. FIXTURE INSTALLATION TO COMPLY WITH ASTM
C636-96 AND U.B.C. SECTION 25.213
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
EMERGENCY REMOTE LIGHT HEADS AND EXIT SIGN, WALL MOUNTED, SEE
SPECS.
AutoCAD SHX Text
CEILING MOUNTED SINGLE OCCUPANCY SENSOR SWITCH (PIR) (REFER TO TJX
SPECIFICATIONS FOR PRODUCT INFORMATION.)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SINGLE OCCUPANCY SENSOR SWITCH (PIR) (REFER TO TJX SPECIFICATIONS
FOR PRODUCT INFORMATION.) +46" OR AS NOTED.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SUPPORT MOUNTING DETAIL
AutoCAD SHX Text
AutoCAD SHX Text
1. ZONE 'a' - EMPLOYEE LIGHTING = INTERLOCK W/BURGLAR ALARM SYSTEM
ZONE 'a' - EMPLOYEE LIGHTING = INTERLOCK W/BURGLAR ALARM SYSTEM
SUCH THAT WHEN THE SYSTEM IS DISARMED THE EMPLOYEE LIGHTING TURNS
ON. WHEN BURGLAR ALARM IS ARMED THE EMPLOYEE LIGHTING SHALL TURN
OFF. ZONE 'a' SHALL CONTROL THE FOLLOWING LOADS: 50% OF SALES
GENERAL LIGHTING (ALTERNATING ROWS) PROCESSING ROOM LIGHTING
EMPLOYEE SUPPORT AREAS FITTING ROOM GENERAL LIGHTING UH-1, BB-1,
EH-1 EF-1, EF-2, EF-3 2. ZONE 'b' - CUSTOMER LIGHTING = CONTROLLED
BY NOVAR TIME SCHEDULE & ZONE 'b' - CUSTOMER LIGHTING =
CONTROLLED BY NOVAR TIME SCHEDULE & SHALL BE CAPABLE OF
MANUALLY REDUCING THE GENERAL SALES LIGHTING BY 50%. ZONE 'b' SHALL
CONTROL THE FOLLOWING LOADS: 50% OF SALES GENERAL LIGHTING
(ALTERNATING ROWS) FITTING ROOM MIRROR LIGHTING SALES PERIMETER
TRACK LIGHTING JEWELRY CASE LIGHTING 3. ZONE 's' - SIGN &
CANOPY LIGHTING = CONTROLLED BY NOVAR PHOTOCELL ZONE 's' - SIGN
& CANOPY LIGHTING = CONTROLLED BY NOVAR PHOTOCELL & TIME
SCHEDULE. ZONE 'e' SHALL CONTROL THE FOLLOWING LOADS: STOREFRONT
SIGNS EXTERIOR CANOPY LIGHTING 4. ZONE 'e' - EXTERIOR WALLPACK
LIGHTING = CONTROLLED ONLY BY NOVAR ZONE 'e' - EXTERIOR WALLPACK
LIGHTING = CONTROLLED ONLY BY NOVAR PHOTOCELL. ZONE 'e' SHALL
CONTROL THE FOLLOWING LOADS: EXTERIOR WALLPACK LIGHTING 5. ZONE 'c'
- DAYLIGHT AREA LIGHTING = CONTROLLED BY NOVAR PHOTOCELL ZONE 'c' -
DAYLIGHT AREA LIGHTING = CONTROLLED BY NOVAR PHOTOCELL & SHALL
BE CAPABLE OF MANUALLY TURNING OFF THE LIGHTS IN DAYLIGHT AREAS.
ZONE 'c' SHALL CONTROL THE FOLLOWING LOADS: DAYLIGHT AREAS 6. ZONE
'd' - DISPLAY LIGHTING = CONTROLLED BY NOVAR TIME SCHEDULE. ZONE
'd' - DISPLAY LIGHTING = CONTROLLED BY NOVAR TIME SCHEDULE. ZONE
'd' SHALL CONTROL THE FOLLOWING LOADS: SALE PERIMETER TRACK
LIGHTING
AutoCAD SHX Text
NOTE: LIGHTING PATTERN MUST REMAIN AS DRAWN AND : LIGHTING PATTERN
MUST REMAIN AS DRAWN AND ADHERE TO THIS PLAN. ALL LIGHT FIXTURES IN
SALES AREA WILL BE MOUNTED @ 12'-0"
AutoCAD SHX Text
A.F.F. TO THE UNDERSIDE OF THE FIXTURE. (SEE EXCEPTIONS). G.C. MUST
COORDINATE ALL M.E.P. TRADES TO ENSURE. PLEASE CONTACT TJX PROJECT
MANAGER AND M.O.D. IMMEDIATELY IF THERE ARE ANY FIXTURE SPACING OR
MOUNTING HEIGHT CONFLICTS. TJX WILL NOT BE RESPONSIBLE FOR COSTS
INCURRED FOR INCORRECT INSTALLATION AND MOUNTING OF LIGHT FIXTURES
WITHOUT PRIOR NOTIFICATION TO TJX P.M. OR M.O.D..
AutoCAD SHX Text
LIGHTING PLAN NOTES
AutoCAD SHX Text
SEE SHEET E2 FOR POWER REQUIREMENTS FOR MIRROR LIGHTS
(TYPICAL).
AutoCAD SHX Text
AutoCAD SHX Text
MOUNT DOCK LIGHT @ 6'-6". SEE POWER PLAN SHEET E2 FOR POWER
REQUIREMENTS.
AutoCAD SHX Text
A. EXIT SIGNS, EMERGENCY AND NIGHT LIGHTS SHALL BE CONNECTED TO AN
UNSWITCHED LIGHTING CIRCUIT, NOT CONTROLLED BY OCCUPANCY SENSORS,
SWITCHES, CONTRACTORS, OR RELAY PANEL.
AutoCAD SHX Text
GENERAL LIGHTING NOTES
AutoCAD SHX Text
B. REFER TO "RECESSED LIGHTING FIXTURE SUPPORT DETAIL", SHEET E1,
FOR INFORMATION ON SUPPORT OF ALL 2' X 4' RECESSED LIGHT
FIXTURES.
AutoCAD SHX Text
C. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN AND DETAILS FOR
EXACT LOCATION OF ALL LIGHTING FIXTURES AND OTHER EQUIPMENT
INSTALLED IN THE CEILING SYSTEM. VERIFY EXACT MOUNTING HEIGHTS AND
FINISHES WITH ARCHITECT PRIOR TO ROUGH-IN.
AutoCAD SHX Text
D. REFER TO POWER PLANS FOR LOCATIONS OF ELECTRICAL
EQUIPMENT.
AutoCAD SHX Text
E. ELECTRICAL J-BOX FOR ALL OVERHEAD TYPE LIGHTS TO BE WITHIN 4' OF
EACH ACTUAL LIGHT FIXTURE.
AutoCAD SHX Text
F. SALES FLOOR LIGHTING SHALL BE CIRCUITED EVER OTHER ROW TO
OPERATE WITH BUILDING MANAGEMENT SYSTEM (SEE E4 SHEET).
AutoCAD SHX Text
G. SALE FLOOR LIGHTS (NON-EMERGENCY) TO BE MOUNTED AT 12'-0" A.F.F.
(UNLESS NOTED OTHERWISE ON TJX C-SET). MECHANICAL, ELECTRICAL, AND
PLUMBING TO BE MOUNTED WITH ADEQUATE CLEARANCE BETWEEN TOP OF
LIGHTING FIXTURES AND ROOF DECK.
AutoCAD SHX Text
AutoCAD SHX Text
1. STORE LIGHTING (SALES & SUPPORT) SHALL INCORPORATE QUANTUM
ELM2 TYPE FIXTURES TO ACT AS EMERGENCY LIGHTS. NUMBER OF FIXTURES
TO BE DETERMINED BY CODE.
AutoCAD SHX Text
2. NL-FIXTURES WILL BE WIRED BEFORE A SWITCH OR CONTACTOR.
(FIXTURES WILL RUN 24 HOURS)
AutoCAD SHX Text
3. PROCESSING ROOM LIGHTING TO BE MOUNTED AT 13' AFF. (LIGHTING TO
BE COORDINATED WITH HVAC & STRUCTURAL STEEL)
AutoCAD SHX Text
AutoCAD SHX Text
4. TYPE A4 PENDANT LIGHTING FITTED WITH LOCKING PLUG. NEMA L5-20P
20A, 125V NEMA L7-20P 20A, 277V E.C. TO FURNISH AND INSTALL
APPROVED LOCKING RECEPTACLE AT OPEN DECK CEILING, PER REQUIRED
VOLTAGE. NEMA L5-20R 20A, 125V NEMA L7-20R 20A, 277V
AutoCAD SHX Text
5. SECURE EXCESS CORD WITH TIE STRAP ABOVE LIGHT FIXTURE.
COORDINATE WITH TJX PROJECT MANAGER.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
POSITION TRACK HEADS 2, 5 AND 8 TO ILLUMINATE GRAPHICS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1/8" = 1'-0"
AutoCAD SHX Text
AutoCAD SHX Text
CONNECT SALES AREA EM FIXTURES 'R' & EXIT SIGNS 'E' TO CIRCUIT
'HA-29'.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CA01N 165L 277 EZ1 LP830 CS78WL20 (277 V) CA01N 165L 120 EZ1 LP830
CS16WL20 (120 V)
AutoCAD SHX Text
CA01N 165L 277 EZ1 LP830 CS78WL20 (277 V) CA01N 165L 120 EZ1 LP830
CS16WL20 (120 V)
AutoCAD SHX Text
E.C. TO FURNISH LOCKING RECEPTACLE AT OPEN DECK CEILING (SEE NOTE
4)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CA01N 165L 277 EZ1 LP835 CS78WL20 (277 V) CA01N 165L 120 EZ1 LP835
CS16WL20 (120 V)
AutoCAD SHX Text
CA01N 165L 277 EZ1 LP835 CS78WL20 (277 V) CA01N 165L 120 EZ1 LP835
CS16WL20 (120 V)
AutoCAD SHX Text
E.C. TO FURNISH LOCKING RECEPTACLE AT OPEN DECK CEILING (SEE NOTE
4)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PRSTP16LEDLX100L35KEX/LDW/HC240P277(L7-20) PR16DR16CNFRPT (277V)
PRSTP16LEDLX100L35KEX/LDW/HC240P120(L5-21) PR16DR16CNFRPT
(120V)
AutoCAD SHX Text
PRSTP16LEDLX100L35KEX/LDW/HC240P277(L7-20) PR16DR16CNFRPT (277V)
PRSTP16LEDLX100L35KEX/LDW/HC240P120(L5-21) PR16DR16CNFRPT
(120V)
AutoCAD SHX Text
E.C. TO FURNISH LOCKING RECEPTACLE AT OPEN DECK CEILING (SEE NOTE
4)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CAN USE ELM6-LED, ELM-LT, or other Emergency lights in the Acuity
ELM family
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: USE DAYLIGHT LIGHTING ZONE "c" AS REQUIRED BY
APPLICABLE CODE.
AutoCAD SHX Text
DESIGNER NOTE: PROVIDE EXTERIOR EMERGENCY LIGHTING AS REQUIRED BY
LOCAL CODE. WHERE REQUIRED, ADD EM OPTION TO 'K3' FIXTURE(S). IF
LOCAL AUTHORITY REQUIRES SEPARATE EMERGENCY LIGHT EOR SHALL CHOOSE
FROM ACUITY'S LITHONIA LINE.
AutoCAD SHX Text
HA-6 ZONE 's'
AutoCAD SHX Text
HA-4 ZONE 'e'
AutoCAD SHX Text
H. ALL TRACK IS TO BE MOUNTED ON UNISTRUT. ALL UNISTRUT TO BE
PAINTED WHITE & HUNG AS REQUIRED FROM STRUCTURE ABOVE. ALL
TRACK USED IN THE STORE IS TO BE WIRED FROM 120V PANEL.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
LA-9 ZONE 'b'
AutoCAD SHX Text
LA-1 ZONE 'b'
AutoCAD SHX Text
LA-3 ZONE 'b'
AutoCAD SHX Text
LA-5 ZONE 'b'
AutoCAD SHX Text
LA-7 ZONE 'b'
AutoCAD SHX Text
DESIGNER NOTE: TRACK LIGHTING CIRCUITS SHOWN FOR REFERENCE ONLY.
EOR SHALL PROVIDE CIRCUITING AS REQUIRED PER NEC TRACK LIGHTING
CALCULATIONS OR PROVIDE CURRENT LIMITING DEVICES AS REQUIRED TO
MEET ENERGY CODE REQUIREMENTS. ALL TRACK LIGHTING TO BE 120V.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: NOT ALL LIGHT FIXTURES SHOWN ARE USED ON THIS SAMPLE
SET. CURRENT PROTOTYPICAL FIXTURES SHOWN FOR REFERENCE ONLY. MODIFY
LIGHT FIXTURE SCHEDULE PER TJX MASTER SCHEDULE TO MATCH ACTUAL
PROJECT REQUIREMENTS OF THE SPECIFIC BRAND. REFER TO PROJECT
SPECIFIC C-SET. EOR SHALL VERIFY LIGHT FIXTURE SPECIFICATION
NUMBERS ARE CORRECT & LIGHT FIXTURE WATTAGES ARE ACCURATE WITH
MANUFACTURER OR VENDOR.
AutoCAD SHX Text
DESIGNER NOTE: SALES AREA LIGHTING CIRCUITS SHOWN FOR REFERENCE
ONLY. EOR SHALL PROVIDE CIRCUITING AS REQUIRED AND PROVIDE PROPER
CALCULATIONS. SALES AREA MUST BE CIRCUITED WITH ZONES EVERY OTHER
ROW AS SHOWN.
AutoCAD SHX Text
DESIGNER NOTE: FITTING ROOM, PROCESSING ROOM, OFFICES, RESTROOM
& ADDITIONAL EMPLOYEE USED AREAS LIGHTING CIRCUITS SHOWN FOR
REFERENCE ONLY. EOR SHALL PROVIDE CIRCUITING AS REQUIRED AND
PROVIDE PROPER CALCULATIONS. THESE AREAS MUST BE ON EMPLOYEE
CONTROL ZONE AS SHOWN.
AutoCAD SHX Text
DESIGNER NOTE: LIGHT FIXTURE 'L' IS EQUIPPED WITH EMERGENCY
LIGHTING FEATURE FOR EMERGENCY EGRESS AT EXTERIOR DOORS. IF LOCAL
AUTHORITY REQUIRES SEPARATE EMERGENCY LIGHT EOR SHALL CHOOSE FROM
ACUITY'S LITHONIA LINE.
AutoCAD SHX Text
DESIGNER NOTE: EMERGENCY LIGHTING SHOWN FOR REFERENCE AND IS ONLY
INTENDED TO BE MINIMUM REQ'D PER TYPICAL C-SET. FINAL QUANTITY AND
LOCATIONS OF EMERGENCY LIGHTING SHALL BE PROVIDED BY EOR AND SHALL
SATISFY LOCAL CODE REQUIREMENTS.
AutoCAD SHX Text
DESIGNER NOTE: EXTERIOR LIGHTING SHOWN FOR REFERENCE ONLY. EOR
SHALL PROVIDE EXTERIOR LIGHTING AS REQUIRED SPECIFIC TO EACH
STORE.
AutoCAD SHX Text
DESIGNER NOTE: EXTERIOR LIGHT FIXTURES MUST BE TJX PROTOTYPICAL
FIXTURES UNLESS THERE IS A REQUIREMENT TO MATCH EXISTING SHOPPING
CENTER FIXTURES.
AutoCAD SHX Text
ALL TRACK IS TO BE MOUNTED TO UNISTRUT. ALL UNISTRUT TO BE
FURNISHED & INSTALLED BY ELECTRICAL CONTRACTOR, PAINTED WHITE
& HUNG WITH AC CABLE AS REQUIRED FROM STRUCTURE ABOVE. ALL
TRACK USED IN THE STORE IS TO BE WIRED FROM 120V PANEL.
AutoCAD SHX Text
DESIGNER NOTE: MOUNTING HEIGHT SHALL BE DETERMINED AND COORDINATED
WITH SITE SPECIFIC TJX C-SET. CONDITIONS SUBJECT TO CHANGE PER
LOCATION AND CHAIN.
AutoCAD SHX Text
AutoCAD SHX Text
J. LIGHT FIXTURES SHALL BE PURCHASED BY CONTRACTOR THRU TENANT'S
NATIONAL ACCOUNT. NO SUBSTITUTIONS ALLOWED. REFER TO APPROVED
VENDOR LIST IN TJX CRITERIA SET.
AutoCAD SHX Text
K. WIRING CONNECTIONS TO EXTERIOR WALL MOUNTED FIXTURES SHALL BE
WEATHER TIGHT. USE WEATHERPROOF JUNCTION BOXES, FITTINGS, COVER
PLATES, ETC. AS REQUIRED TO PREVENT ENTRY OF WATER INTO WIRING
BOXES.
AutoCAD SHX Text
DESIGNER NOTE: TYPE H3, H4 & H5 USED IN HOMEGOODS STORE FORMAT
FOR PERIMETER VALANCE LIGHTING.
AutoCAD SHX Text
DESIGNER NOTE: TYPE Q USED IN COMBO STORE FORMAT OVER SINGLE
QUE.
AutoCAD SHX Text
DESIGNER NOTE: TYPE O5 USED TJ MAXX STORES WITH ACT FOR WALL
WASHERS AROUND PERIMETER OF STORE
AutoCAD SHX Text
AutoCAD SHX Text
ALL DRAWINGS IN THIS SET ARE CONCEPTUAL IN NATURE, PROVIDED AS A
GUIDE ONLY. THESE "TJX SAMPLE MEP PLANS" SHALL BE USED TO ASSIST
CONSULTANTS IN DEVELOPING A SITE SPECIFIC CONSTRUCTION DOCUMENT SET
PER THE LEASE REQUIREMENTS. ALL ITEMS WITHIN THIS DOCUMENT,
INCLUDING BUT NOT LIMITED TO SIZING, QUANTITIES, LOCATIONS, AND
MANUFACTURERS SHALL CONFORM TO THE REQUIREMENTS SET FORTH IN THE
APPLICABLE TJX SPECIFICATIONS REFERENCED IN THE LEASE. ALL
EQUIPMENT, WIRING, PIPING, ETC. SHALL BE SIZED PER ACTUAL PROJECT
CONDITIONS AND APPLICABLE CODES AS ENFORCED BY THE AUTHORITY HAVING
JURISDICTION.
AutoCAD SHX Text
AutoCAD SHX Text
FEATURE. RE: C-SET
AutoCAD SHX Text
FEATURE. RE: C-SET
AutoCAD SHX Text
FEATURE. RE: C-SET
AutoCAD SHX Text
FEATURE. RE: C-SET
AutoCAD SHX Text
FEATURE. RE: C-SET
AutoCAD SHX Text
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
LIGHTING CONTROLS - ALL SWITCHES, OCCUPANCY SENSORS, RELAY PANEL
CONTROLS, ETC.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: ALL SUSPENDED LIGHTS, WITH-IN 15' OF CONCENTRIC
DIFFUSERS SHALL BE HUNG WITH THREADED ROD. SAME FOR HANGING SIGNS.
REFER TO TJX SPECIFICATION SECTION 16A.18 FOR ADDITIONAL
INFORMATION.
AutoCAD SHX Text
AutoCAD SHX Text
THIS SHEET IS PART OF THE CONSTRUCTION DOCUMENTS, OTHER SHEETS
INCLUDING SPECIFICATIONS APPLY. INFORMATION SHOWN HEREON IS
SCHEMATIC IN NATURE AND NOT TO BE USED AS A SHOP DRAWING;
THEREFORE, INCLUDE ALL MODIFICATIONS REQUIRED TO CONFORM TO SITE
CONDITIONS AND THE EQUIPMENT AND MATERIAL USED. VERIFY LOCATIONS
AND DIMENSIONS OF ALL ARCHITECTURAL AND STRUCTURAL ELEMENTS AS
SHOWN ON THEIR RESPECTIVE DOCUMENTS, THESE ELEMENTS ARE SHOWN FOR
REFERENCE AND SHALL BE VERIFIED PRIOR TO CONSTRUCTION AND THE
ENGINEER ASSUMES NO LIABILITY FOR THE ACCURACY OF THESE ELEMENTS.
NO DESIGN RESPONSIBILITY IS ASSUMED FOR ANY PORTION OF THE WORK
THAT THE PROFESSIONAL ENGINEER HAS NOT SIGNED AND SEALED PER STATE
REQUIREMENTS.
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT LOGO AND
ADDRESS
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT SEAL AND
SIGNATURE
AutoCAD SHX Text
AutoCAD SHX Text
RESTROOM, LOUNGE, JANITOR, & DRESSING ROOM (WHEN APPLICABLE)
EXHAUST FANS, WILL BE A CONTROLLED/SWITCHED CIRCUIT, RUN THROUGH
THE GE LIGHTING RELAY PANEL ON THE "EMPLOYEE" CIRCUIT. WHEN
REQUIRED, ELECTRIC ROOM AND/OR SYSTEMS ROOM EXHAUST FANS WILL BE A
24 HOUR LIVE CIRCUIT CONTROLLED BY IN LINE THERMOSTAT SET AT 80°
DEGREES. SEE SPEC.BOOK FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
COMMUNICATIONS GENERAL NOTES
AutoCAD SHX Text
1. CONDUIT ENDS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT
CABLE CONDUIT ENDS SHALL BE PROVIDED WITH NYLON BUSHINGS TO PROTECT
CABLE FROM DAMAGE. BUSHINGS SHALL BE PROVIDED BY ELECTRICAL
CONTRACTOR. 2. AT TELEPHONE OUTLETS, PROVIDE 2 " DEEP, SINGLE GANG
WALL BOX & " AT TELEPHONE OUTLETS, PROVIDE 2 " DEEP, SINGLE
GANG WALL BOX & " 12" DEEP, SINGLE GANG WALL BOX & " 12"
CONDUIT WITH PULL STRING STUBBED OUT TO ABOVE ACCESSIBLE CEILING.
3. AT DATA & CABLE OUTLETS, PROVIDE 2 " DEEP, SINGLE GANG WALL
BOX & " AT DATA & CABLE OUTLETS, PROVIDE 2 " DEEP, SINGLE
GANG WALL BOX & " 12" DEEP, SINGLE GANG WALL BOX & " 34"
CONDUIT WITH PULL STRING STUBBED OUT TO ABOVE ACCESSIBLE CEILING.
4. AT TELEPHONE/DATA & TECHNOLOGY OUTLETS, PROVIDE 3" DEEP,
2-GANG WALL AT TELEPHONE/DATA & TECHNOLOGY OUTLETS, PROVIDE 3"
DEEP, 2-GANG WALL BOX WITH 2-GANG PLASTIC RING & 1" CONDUIT
WITH PULL STRING STUBBED OUT TO ABOVE ACCESSIBLE CEILING. 5. PUBLIC
ADDRESS & CLOCK SYSTEM WIRING SHALL BE INSTALLED IN CONDUIT.
PUBLIC ADDRESS & CLOCK SYSTEM WIRING SHALL BE INSTALLED IN
CONDUIT. 6. ELECTRICAL CONTRACTOR TO PROVIDE & INSTALL WIREMOLD
EXTENSION ELECTRICAL CONTRACTOR TO PROVIDE & INSTALL WIREMOLD
EXTENSION ADAPTERS #5751 FLUSH TYPE FOR COLUMN MOUNTED PHONES
(PHONES BY TENANT).
AutoCAD SHX Text
ELECTRICAL SYMBOLS LEGEND
AutoCAD SHX Text
HOME RUN TO PANEL, CIRCUIT NUMBERS, PHASE, NEUTRAL & GROUND
CONDUCTORS INDICATED ALONG WITH ISOLATED GROUND CONDUCTOR IF
APPLICABLE CONDUIT INSTALLED CONCEALED ABOVE CEILING OR IN WALL OR
AT ROOF STRUCTURE, PAINT TO MATCH STRUCTURE AS APPLICABLE CONDUIT
INSTALLED CONCEALED BELOW FLOOR SLAB OR UNDERGROUND AC OR DC
CONTROL VOLTAGE WIRING SIMPLEX RECEPTACLE, +18" OR AS NOTED DUPLEX
RECEPTACLE, +18" OR AS NOTED ISOLATED GROUND DUPLEX RECEPTACLE,
+18" OR AS NOTED, ORANGE COLOR QUADRUPLEX RECEPTACLE, +18" OR AS
NOTED ISOLATED GROUND QUADRUPLEX RECEPTACLE, +18" OR AS NOTED,
ORANGE COLOR MULTI-RECEPTACLE SYSTEM (PLUGMOLD), INSTALL AS NOTED
POWER POLE JUNCTION BOX JUNCTION BOX WITH BLANK COVER PLATE (FOR
FUTURE USE) & " CONDUIT WITH PULL STRING STUBBED 34" CONDUIT
WITH PULL STRING STUBBED ABOVE CEILING (OR AS INDICATED BY TJX
PROJECT MANAGER FOR AREAS WITH OPEN STRUCTURE ABOVE), +18" OR AS
NOTED DISCONNECT SWITCH, MOUNT AS NOTED, VERIFY REQUIREMENTS WITH
EQUIPMENT SERVED EXHAUST FAN MOTOR CONNECTION, COORDINATE WITH
MECHANICAL CONTRACTOR PUSH BUTTON, MOUNT AS NOTED DOOR BELL CHIME
OR BUZZER, MOUNT AS NOTED CONTROL TRANSFORMER, INSTALL AS NOTED
HVAC SENSING DEVICE @ +60", VERIFY LOCATIONS W/NOVAR, PROVIDE
BACK-BOX & " CONDUIT TO UNIT 34" CONDUIT TO UNIT INDICATED
TELEPHONE BOX-WALL HUNG, INSTALL AS NOTED WITH " CONDUIT WITH PULL
STRING STUBBED ABOVE 34" CONDUIT WITH PULL STRING STUBBED ABOVE
CEILING (OR AS INDICATED BY TJX PROJECT MANAGER FOR AREAS WITH OPEN
STRUCTURE ABOVE) TELEPHONE BOX-DESK SET, INSTALL AS NOTED WITH "
CONDUIT WITH PULL STRING STUBBED ABOVE 34" CONDUIT WITH PULL STRING
STUBBED ABOVE CEILING (OR AS INDICATED BY TJX PROJECT MANAGER FOR
AREAS WITH OPEN STRUCTURE ABOVE) TELEPHONE/DATA BOX, INSTALL AS
NOTED WITH 1" CONDUIT WITH PULL STRING STUBBED ABOVE CEILING (OR AS
INDICATED BY TJX PROJECT MANAGER FOR AREAS WITH OPEN STRUCTURE
ABOVE) WIREMOLD ALA4800B SURFACE MOUNTED RACEWAY ELECTRIC DOOR
STRIKE, SEE SPECS. PUSH BUTTON, HEIGHT AS NOTED. LOW VOLTAGE WIRING
CONDUIT & JUNCTION BOX BY G.C. W/PULL WIRE. (WIRING BY
OTHERS)
AutoCAD SHX Text
AutoCAD SHX Text
NOTES: REFER TO LIGHT FIXTURE SCHEDULE & SYMBOL LIST FOR
SPECIFICATION & INFORMATION ON ALL LUMINAIRES. REFER TO
SPECIFICATIONS & PLAN NOTES FOR DETAILED DESCRIPTION OF ALL
DEVICES SHOWN IN THIS SCHEDULE, PROVIDED BY THIS CONTRACTOR.
MOUNTING HEIGHTS INDICATED ARE MEASURED FROM FINISHED FLOOR TO THE
CENTERLINE OF THE DEVICE UNLESS NOTED OTHERWISE.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
G.C./E.C. TO PROVIDE A 110VAC, CONTINUOUSLY ELECTRIFIED & NOT
CONTROLLED BY A SWITCH, DUPLEX OUTLET AT THE CONDUIT TERMINATION
POINT ABOVE THE VESTIBULE CEILING. G.C./E.C. TO PROVIDE AN 18"x18"
(MINIMUM) ACCESS PANEL AT THIS LOCATION IN THE EVENT THE VESTIBULE
IS A HARD CEILING.
AutoCAD SHX Text
G.C. RESPONSIBLE TO CONTRACT "STANLEY ACCESS TECHNOLOGIES" TO
PROVIDE & INSTALL VESTIBULE SLIDING DOORS.
AutoCAD SHX Text
G.C. ELECTRICIAN RESPONSIBLE FOR ALL FINAL CONNECTIONS TO SLIDING
DOORS.
AutoCAD SHX Text
DUPLEX OUTLET FOR FUTURE CART CONTAINMENT SYSTEM. (LOCATE 6" ABOVE
VESTIBULE FINISHED CEILING) CENTERED BETWEEN INTERIOR DOORS.
CONTINUOUSLY ELECTRIFIED AND NOT CONTROLLED BY A SWITCH.
AutoCAD SHX Text
G.C. ELECTRICIAN TO PROVIDE (1) 120 V. 20 AMP DEDICATED CIRCUIT FOR
THE INTERIOR SET OF DOORS AND (1) 120 V. 20 AMP DEDICATED CIRCUIT
FOR THE EXTERIOR SET OF DOORS. ( LOCATE 6"ABOVE FINISHED CEILING)
(1) 10 AMP LINE TO EACH DOOR OPERATOR. ELECTRICAL TERMINATIONS BY
E.C.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
1. VERIFY EXACT LOCATIONS OF HVAC EQUIPMENT, CONDUIT STUB-UPS &
POWER VERIFY EXACT LOCATIONS OF HVAC EQUIPMENT, CONDUIT STUB-UPS
& POWER CONNECTIONS PRIOR TO ROUGH-IN. 2. VERIFY EXACT
LOCATION, MOUNTING HEIGHTS & CONDUIT ROUTING FOR ALL VERIFY
EXACT LOCATION, MOUNTING HEIGHTS & CONDUIT ROUTING FOR ALL
THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS & CO2 SENSORS
WITH TEMPERATURE CONTROLS CONTRACTOR PRIOR TO ROUGH-IN. 3. REFER TO
MECHANICAL DRAWINGS FOR ADDITIONAL ELECTRICAL REQUIREMENTS. REFER
TO MECHANICAL DRAWINGS FOR ADDITIONAL ELECTRICAL REQUIREMENTS.
COORDINATE PROVISIONS FOR ALL CONTROL CONDUIT & WIRING AS
REQUIRED FOR INTERLOCKING OF FANS, MOTORS, ETC. REFER TO
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. 4. ALL DEVICES
INSTALLED ON HVAC EQUIPMENT SHALL BE MOUNTED ON A ALL DEVICES
INSTALLED ON HVAC EQUIPMENT SHALL BE MOUNTED ON A NON-REMOVABLE
PANEL OF THE EQUIPMENT. THIS LOCATION SHALL BE COORDINATED WITH THE
MECHANICAL AND/OR PLUMBING CONTRACTOR PRIOR TO COMMENCING ANY
ROUGH-IN WORK.
AutoCAD SHX Text
AutoCAD SHX Text
1. FIRE ALARM CABLING SHALL BE INSTALLED IN CONDUIT. FIRE ALARM
CABLING SHALL BE INSTALLED IN CONDUIT. 2. DUCT TYPE SMOKE DETECTORS
SHALL BE FURNISHED, INSTALLED & WIRED BY DUCT TYPE SMOKE
DETECTORS SHALL BE FURNISHED, INSTALLED & WIRED BY MECHANICAL
CONTRACTOR. SEE DETAIL THIS DRAWING. 3. FIRE ALARM SYSTEM HVAC SHUT
DOWN RELAYS SHALL BE PROVIDED & WIRED FIRE ALARM SYSTEM HVAC
SHUT DOWN RELAYS SHALL BE PROVIDED & WIRED TO FIRE ALARM
CONTROL PANEL BY FIRE ALARM CONTRACTOR. E.C. SHALL PROVIDE CONDUIT
WITH PULL STRING FROM RELAY TO HVAC UNIT. UNIT SHUT DOWN CONTROL
WIRING SHALL BE PROVIDED BY MECHANICAL CONTRACTOR.
AutoCAD SHX Text
AutoCAD SHX Text
J-BOX FOR CUSTOMER COUNTER. INSTALL 6" ABOVE BOTTOM OF LIGHT
FIXTURE HEIGHT.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
COORDINATE WALL MOUNTED ELECTRICAL WITH CASH CABINET LOCATION. IF
STOREFRONT GLASS EXISTS BEHIND CABINET, FIELD VERIFY MOUNTING
HEIGHT OF ELECTRICAL WITH TJX PROJECT MANAGER. MOUNT FIRE ALARM
ANNUNCIATOR PANEL IN A VISIBLE LOCATION BEHIND CASHWRAP OR AS
DIRECTED BY AUTHORITY HAVING JURISDICTION. COORDINATE W/TJX
CONSTRUCTION MANAGER. DUPLEX RECEPTACLES FOR 'EAS' SECURITY SHALL
BE CONNECTED TO THE SAME CIRCUIT THROUGHOUT CASH REGISTER AREA.
MOUNT HORIZONTALLY AT 49" AFF. DEDICATED SIMPLEX RECETACLE TO BE
MOUNTED TO END CHECKOUT UNIT. SEE DETAIL SHEET E4 FOR ADDITIONAL
INFORMATION. (3) 2 " CONDUITS TO BE CONCEALED IN FLOOR & WALL
ON SALES AREA SIDE. 12" CONDUITS TO BE CONCEALED IN FLOOR &
WALL ON SALES AREA SIDE. CONDUIT TERMINATION POINT LOCATED UNDER
CASH REGISTER COUNTER. FIELD VERIFY AND COORDINATE EXACT LOCATION.
METAL "PANCAKE" MOLDING #1500 1 " x " x 10'-0" (A) AT FLOOR FOR
WIRING TO DISPLAY CASE 12" x " x 10'-0" (A) AT FLOOR FOR WIRING TO
DISPLAY CASE 12" x 10'-0" (A) AT FLOOR FOR WIRING TO DISPLAY CASE
LIGHTING FIXTURES. ELECTRICAL CONTRACTOR TO FURNISH & INSTALL A
MASTER ON/OFF SWITCH MOUNTED AT REGISTER WELL CABINET TO CONTROL
ON/OFF OF CASE LIGHTING. CASES TO BE LEFT IN THE "ON" POSITION. SEE
SHEET E4 FOR POWER POLE REQUIREMENTS. MAKE FINAL CONNECTION TO
JEWELRY CASE LIGHTING. FOR EACH EXTERIOR SIGN, ELECT. CONTRACTOR
SHALL PROVIDE (3) 20A, 120V CIRCUITS TO (3) 3-GANG JUNCTION BOXES.
MIDDLE JUNCTION BOX SHALL BE CENTERED ON SIGN FIELD, REMAINING
JUNCTION BOXES @ 10'-0" TO CENTERLINE, EITHER SIDE. CONTROLLED BY
B.M.S. CONTACTOR. COORDINATE EXACT LOCATION OF CIRCUITS WITH TJX
SIGN VENDOR & TJX PROJECT MANAGER. SEE SPEC. 16A. PROVIDE 30A,
3P, 480V, NEMA 3R, FUSED DISCONNECT SWITCH MOUNTED ON THE EXTERIOR
WALL FOR TRASH COMPACTOR. DISCONNECT SWITCH SHALL BE WITHIN SIGHT
OF COMPACTOR. COORDINATE REQUIREMENTS WITH COMPACTOR INSTALLER
& PROVIDE FINAL CONNECTION, INCLUDING COMPACTOR CONTROL PANEL.
(3) #8 & (1) #8 GROUND IN 1" CONDUIT. PROVIDE 20A, 120A CIRCUIT
TO POWER SUPPLY FOR CASH OFFICE MANTRAP SYSTEM & EDWARDS
SIGNALING BUILDERS CHIME KIT (C212 SERIES, FURNISHED BY
CONTRACTOR). PROVIDE ALL REQUIRED WIRING, CONDUIT, ACCESSORIES
& CONNECTIONS. VERIFY LOCATIONS OF ALL DEVICES WITH TJX PROJECT
MANAGER. SEE DETAIL 5/E4 FOR ADDITIONAL INFORMATION. PROVIDE (1)
PLUGMOLD AT LP DESK & (2) QUADRUPLEX RECEPTACLES BELOW LP DESK.
SEE DETAIL SHEET E4 FOR ADDITIONAL INFORMATION. VERIFY EXACT
LOCATION WITH TJX PROJECT MANAGER. PROVIDE QUADRUPLEX RECEPTACLE
ABOVE CEILING FOR LOSS PREVENTION EQUIPMENT& TRANSFORMERS.
VERIFY EXACT LOCATION WITH TJX PROJECT MANAGER. PROVIDE 2" CONDUIT
SLEEVE & GOOSENECK THROUGH ROOF FOR SATELLITE CABLES. CONDUIT
SHALL PENETRATE ROOF OUTSIDE OF ROOM BUT WITHIN 5'-0" OF IT'S
PERIMETER. SEE SPEC. BOOK & COORDINATE EXACT LOCATION WITH TJX
PROJECT MANAGER PRIOR TO INSTALLATION. FURNISH & INSTALL REAR
DOOR ALARM CONTROL SYSTEM AT THE STOCKROOM MAN DOOR. PROVIDE 120
VOLT CIRCUIT (UNSWITCHED) AND A LOW VOLTAGE TRANSFORMER (24V/50 VA)
U.L. APPROVED (AS REQUIRED), ABOVE THE HEAD OF THE DOOR (WITHIN
10'-0"). ALARM SHALL BE ACTIVATED BY DOOR CONTACTORS WHEN DOOR IS
OPEN POSITION AND SHALL PRODUCE A CONTINUOUS CHIME TONE. WHEELOCK
38GV29 FROM GRAINGER MODEL #CH121092 & REQUIRED ACCESSORIES.
VERIFY W/TJX P.M. PRIOR TO INSTALLATION. PROVIDE CONNECTION FOR
HAND DRYER. COORDINATE HEIGHT & LOCATION FOR ELECTRIC DRYER
WITH TJX PROJECT MANAGER. PROVIDE REQUIRED SIZED CONDUIT & (2)
JUNCTION BOXES WITH BLANK PLATES AT LOCATION OF FIRE ALARM PANEL.
VERIFY EXACT LOCATION WITH TJX PROJECT MANAGER & LOCAL
AUTHORITY HAVING JURISDICTION PRIOR TO INSTALLATION. COORDINATE ALL
INTEGRATION WITH EXISTING FIRE ALARM SYSTEM AS REQUIRED. PROVIDE
30A, 2P TOGGLE SWITCH WITH (2) #10 & (1) #10 GROUND FOR WATER
HEATER. COORDINATE REQUIREMENTS WITH PLUMBING CONTRACTOR. PROVIDE
JUNCTION BOX FOR COAXIAL CABLE @ 7'-6" AFF. INSTALL HORIZONTALLY
ADJACENT TO DUPLEX RECEPTACLE. INSTALL CONDUIT WITH PULL-STRING TO
6" ABOVE FINISHED CEILING. MOUNT DUPLEX RECEPTACLE FOR STORE
SECURITY SYSTEM ABOVE CEILING, NEAR DOOR. VERIFY EXACT LOCATION
WITH TJX PROJECT MANAGER PRIOR TO INSTALLATION. ROOFTOP UNIT SMOKE
DETECTOR. PROVIDE REMOTE TEST MOUNTED IN LOCATION DICTATED BY LOCAL
FIRE AUTHORITY. IF MOUNTED TO NEAREST COLUMN, PLACE ON TELEPHONE
SIDE OF COLUMN AND HIGHER THAN SLAT WALL FINISH. CIRCUIT 'LB-34'.
(TYPICAL FOR ALL ROOFTOP UNITS). COORDINATE WITH GENERAL
CONTRACTOR. . MOUNT DUPLEX RECEPTACLE ABOVE FINISHED CEILING FOR
FUTURE P.V.M. VERIFY EXACT LOCATION WITH TJX PROJECT MANAGER PRIOR
TO INSTALLATION. PROVIDE POWER POLE FOR JEWELRY COUNTER POWER &
DATA. VERIFY EXACT LOCATION WITH TJX PROJECT MANAGER. SEE DETAIL
SHEET E4 FOR ADDITIONAL INFORMATION. VIBRATING BELL &
WEATHERPROOF PUSH BUTTON. PROVIDE 120V CIRCUIT (UNSWITCHED). VERIFY
W/TJX P.M. PRIOR TO INSTALLATION. JUNCTION BOX MOUNTED AT 48"
A.F.F. FOR DRESSING ROOM MIRROR LIGHT CONNECTION. MAKE FINAL
CONNECTION. LOCATE FOR EMPLOYEE TIME CLOCK. MOUNT AT 54" A.F.F.
COORDINATE EXACT LOCATION OF MANAGER'S OFFICE DEVICES W/TJX PROJECT
MANAGER PRIOR TO ROUGH-IN. MOUNT DEVICES IN THIS ROOM @ 41" A.F.F.
UNLESS NOTED OTHERWISE. PROVIDE POWER POLE FOR POP COOLER
RECEPTACLE. VERIFY EXACT LOCATION WITH TJX PROJECT MANAGER. PROVIDE
MATCHING RECEPTACLE. PROVIDE 20-AMP DEDICATED DUPLEX RECEPTACLE @
7'-6" AFF. INSTALL HORIZONTALLY CENTERED ON WALL. WEATHER PROOF
GFCI RECEPTACLE SHIPPED LOOSE W/ROOF TOP UNIT. FINAL INSTALLATION
& CONNECTION BY ELECTRICAL CONTRACTOR.
AutoCAD SHX Text
AutoCAD SHX Text
NOTE: : JEWELRY COUNTERS ARE SUPPLIED BY TJX. FINAL CONNECTION BY
ELECTRICAL CONTRACTOR.
AutoCAD SHX Text
DESIGNER NOTE: VERIFY TRASH COMPACTOR VOLTAGE. 480V/3P = 30A
DISCONNECT 208V/3P = 60A DISCONNECT
AutoCAD SHX Text
AutoCAD SHX Text
ALL DRAWINGS IN THIS SET ARE CONCEPTUAL IN NATURE, PROVIDED AS A
GUIDE ONLY. THESE "TJX SAMPLE MEP PLANS" SHALL BE USED TO ASSIST
CONSULTANTS IN DEVELOPING A SITE SPECIFIC CONSTRUCTION DOCUMENT SET
PER THE LEASE REQUIREMENTS. ALL ITEMS WITHIN THIS DOCUMENT,
INCLUDING BUT NOT LIMITED TO SIZING, QUANTITIES, LOCATIONS, AND
MANUFACTURERS SHALL CONFORM TO THE REQUIREMENTS SET FORTH IN THE
APPLICABLE TJX SPECIFICATIONS REFERENCED IN THE LEASE. ALL
EQUIPMENT, WIRING, PIPING, ETC. SHALL BE SIZED PER ACTUAL PROJECT
CONDITIONS AND APPLICABLE CODES AS ENFORCED BY THE AUTHORITY HAVING
JURISDICTION.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
G.C. TO COORDINATE ELECTRIFIED STORE FIXTURES WITH DEPARTMENT
LAYOUTS FROM THE FINAL FIXTURE PLAN.
AutoCAD SHX Text
DESIGNER NOTE: PROVIDE ADDITIONAL JUNCTION BOX FOR CANOPY BLADE
SIGN AS NEEDED. VERIFY WITH TJX PROJECT MANAGER.
AutoCAD SHX Text
DESIGNER NOTE: POWER POLE FOR BEVERAGE COOLER SHOWN FOR REFERENCE
ONLY. IF BEVERAGE COOLER IS LOCATED ON THE WALL, NO POWER POLE IS
REQUIRED.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: EXHAUST FAN EF-4 ONLY REQUIRED WHEN PARTITION
CONSTRUCTION IS FULL HEIGHT. REFER TO MECHANICAL DRAWINGS.
AutoCAD SHX Text
AutoCAD SHX Text
HA-18 ZONE 'a'
AutoCAD SHX Text
DESIGNER NOTE: ALL MECHANICAL INFO SHOWN FOR REFERENCE ONLY. ACTUAL
DESIGN & LOCATIONS SHALL BE BASED ON MECHANICAL ENGINEER'S
CONSTRUCTION DOCUMENTS.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: HVAC CONTROL DEVICES SHOWN FOR REFERENCE ONLY.
ACTUAL LOCATIONS SHALL BE DETERMINED BY NOVAR.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: FIRE ALARM PANEL LOCATION SHOWN FOR REFERENCE ONLY.
EOR SHALL VERIFY EXACT LOCATION WITH LOCAL AHJ.
AutoCAD SHX Text
DESIGNER NOTE: ELECTRIC ROOM LAYOUT SHOWN FOR REFERENCE ONLY. EOR
SHALL LAYOUT ELECTRIC BASED ON C-SET AND/OR EXISTING
CONDITIONS.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: NOTES #8, 11, 16, 19, 22, 23, 25 & 30 DO NOT
APPLY TO HOMEGOODS & HOMESENSE STORES.
AutoCAD SHX Text
DESIGNER NOTE: VESTIBULE DETAIL SHOWN FOR REFERENCE ONLY. ACTUAL
LAYOUT SHALL BE PER TJX C-SET.
AutoCAD SHX Text
DESIGNER NOTE: COMMUNICATION NOTES, FIRE ALARM NOTES & HVAC
NOTES SHOWN FOR REFERENCE ONLY. NOTES SHALL BE REVISED AS NEEDED TO
MEET PROJECT & CODE REQUIREMENTS.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: RTU-6 LOCATION IS NOT ACTUAL. SHOWN HERE FOR
CLARITY. REFER TO HVAC FOR RTU LOCATIONS, SHALL BE LOCATED OVER THE
AREA SERVED.
AutoCAD SHX Text
THIS SHEET IS PART OF THE CONSTRUCTION DOCUMENTS, OTHER SHEETS
INCLUDING SPECIFICATIONS APPLY. INFORMATION SHOWN HEREON IS
SCHEMATIC IN NATURE AND NOT TO BE USED AS A SHOP DRAWING;
THEREFORE, INCLUDE ALL MODIFICATIONS REQUIRED TO CONFORM TO SITE
CONDITIONS AND THE EQUIPMENT AND MATERIAL USED. VERIFY LOCATIONS
AND DIMENSIONS OF ALL ARCHITECTURAL AND STRUCTURAL ELEMENTS AS
SHOWN ON THEIR RESPECTIVE DOCUMENTS, THESE ELEMENTS ARE SHOWN FOR
REFERENCE AND SHALL BE VERIFIED PRIOR TO CONSTRUCTION AND THE
ENGINEER ASSUMES NO LIABILITY FOR THE ACCURACY OF THESE ELEMENTS.
NO DESIGN RESPONSIBILITY IS ASSUMED FOR ANY PORTION OF THE WORK
THAT THE PROFESSIONAL ENGINEER HAS NOT SIGNED AND SEALED PER STATE
REQUIREMENTS.
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT LOGO AND
ADDRESS
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT SEAL AND
SIGNATURE
AutoCAD SHX Text
NOTE: GENERAL CONTRACTOR'S ELECTRICAL ENGINEER/ELECTRICIAN
RESPONSIBLE FOR ALL HUBBELL PLUGTRAK SYSTEM (WALL AND GONDOLA)
CIRCUITRY CALCULATIONS PER THE NATIONAL ELECTRIC CODE. (PLUGTRAK
RECEPTACLES 6" ON CENTER.) ALL PLUGTRAK CIRCUITS CONTROLLED BY
NOVAR ENERGY MANAGEMENT SYSTEM. (4) FOUR CIRCUITS PER GONDOLA
(MIN.) (1) ONE REQUIRED AT EACH SIDE AT CENTER SPLINE & AT BOTH
ENDS.
AutoCAD SHX Text
GONDOLA PLUGTRAK = POWER POLE LOCATED AT THE REAR OF = POWER POLE
LOCATED AT THE REAR OF THE GONDOLA TO WIRE TWO ROWS OF PLUGTRAK.
CENTERLINE OF PLUGTRAK SET @ 8" & 39" FROM THE TOP OF THE
GONDOLA BASE DECK (14" & 43 1/2" A.F.F.). (SEE PROFILE IN THE
HOMEGOODS FIXTURE INSTALLATION MANUAL)
AutoCAD SHX Text
WALL "LAMPS" PLUGTRAK = INSTALL WIRE PLUGTRAK WHERE = INSTALL WIRE
PLUGTRAK WHERE LAMPS INDICATED ON THE WALL. CENTERLINE OF PLUGTRAK
SET @ 8" & 39" ABOVE THE BASE DECK (14" & 43 1/2"
A.F.F.).
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
Box - B2432 - B2432 Cover - S3825 (x2) - S3825 (x2) Flange -
SB3084- SB3084
AutoCAD SHX Text
NOTE: ALL CIRCUITS CONTROLLED BY NOVAR ENERGY MGMNT SYSTEM, ON
CUSTOMER LIGHTING.
AutoCAD SHX Text
NOTE: ALL CIRCUITS CONTROLLED BY NOVAR ENERGY MGMNT SYSTEM, ON
CUSTOMER LIGHTING.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NOTE: MAXIMUM OF 5 FANS PER CIRCUIT. EACH FAN CONTROLED BY A TIMER
SWITCH. SWITCH MOUNTED AT 4'-0" AFF. FAN SPEC: TPI CACU-24W TIMER
SWITCH SPEC: TORK C506H FAN AND TIMER SWITCH PURCHASED BY
G.C.
AutoCAD SHX Text
AutoCAD SHX Text
LOCATE FOR WALL-MOUNTED FAN. FAN TO BE CONTROLLED VIA TORK A506H
6-HOUR SPRING WOUND WALL MOUNTED TIMER & BE ON ZONE 'a'. SEE
DETAIL 3/E2.
AutoCAD SHX Text
DESIGNER NOTE: DETAILS AND KEYED NOTES ARE ASSOCIATED WITH CHAIN
DIFFERENCES RELATED TO HOMEGOODS OR HOMESENSE STORES ONLY. DETAILS
INCLUDED FOR REFERENCE, REFER TO SITE SPECIFIC C-SET FOR DETAILS
AND DIRECTION.
AutoCAD SHX Text
AutoCAD SHX Text
PLUG TRACK (FED VIA POWER POLE): 22':LA-30, 22':LA-32, 22':LA-34,
22':LA-36 (ALL ZONE 'b')
AutoCAD SHX Text
AutoCAD SHX Text
PLUG TRACK (FED VIA POWER POLE): 22':LA-22, 22':LA-24, 22':LA-26,
22':LA-28 (ALL ZONE 'b')
AutoCAD SHX Text
PLUG TRACK (FED VIA POWER POLE): 22':LA-38, 22':LA-40, 22':LA-41,
22':LA-42 (ALL ZONE 'b')
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: PLUGTRAK LAYOUT & CIRCUITING SHOWN FOR REFERENCE
ONLY. PLUGTRAK LAYOUT SHALL BE DICTATED BY TJX C-SET. EOR SHALL
PROVIDE CIRCUITING & LOAD CALCULATIONS @ 75W/FOOT PER NEC. EACH
GRAPHIC ROW OF PLUGTRAK IS ACTUALLY (2) ROWS OF PLUGTRAK.
AutoCAD SHX Text
DESIGNER NOTE: DISPLAY LIGHTING FLOOR RECEPTACLES SHALL BE (2)
DUPLEX RECEPTACLES PER CIRCUIT MAX.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXTERIOR J-BOX MOUNTED 6" ABOVE OVERHEAD DOOR COIL. RIGHT/LEFT OF
ANY EXTERIOR LIGHT FIXTURE. PENETRATION TO BE WEATHERTIGHT.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: REFER TO SPECIFICATION SECTION 1B FOR CHAINS
REQUIRING COMMERCIAL CIRCULATING FANS.
AutoCAD SHX Text
AutoCAD SHX Text
ALL DRAWINGS IN THIS SET ARE CONCEPTUAL IN NATURE, PROVIDED AS A
GUIDE ONLY. THESE "TJX SAMPLE MEP PLANS" SHALL BE USED TO ASSIST
CONSULTANTS IN DEVELOPING A SITE SPECIFIC CONSTRUCTION DOCUMENT SET
PER THE LEASE REQUIREMENTS. ALL ITEMS WITHIN THIS DOCUMENT,
INCLUDING BUT NOT LIMITED TO SIZING, QUANTITIES, LOCATIONS, AND
MANUFACTURERS SHALL CONFORM TO THE REQUIREMENTS SET FORTH IN THE
APPLICABLE TJX SPECIFICATIONS REFERENCED IN THE LEASE. ALL
EQUIPMENT, WIRING, PIPING, ETC. SHALL BE SIZED PER ACTUAL PROJECT
CONDITIONS AND APPLICABLE CODES AS ENFORCED BY THE AUTHORITY HAVING
JURISDICTION.
AutoCAD SHX Text
AutoCAD SHX Text
THIS SHEET IS PART OF THE CONSTRUCTION DOCUMENTS, OTHER SHEETS
INCLUDING SPECIFICATIONS APPLY. INFORMATION SHOWN HEREON IS
SCHEMATIC IN NATURE AND NOT TO BE USED AS A SHOP DRAWING;
THEREFORE, INCLUDE ALL MODIFICATIONS REQUIRED TO CONFORM TO SITE
CONDITIONS AND THE EQUIPMENT AND MATERIAL USED. VERIFY LOCATIONS
AND DIMENSIONS OF ALL ARCHITECTURAL AND STRUCTURAL ELEMENTS AS
SHOWN ON THEIR RESPECTIVE DOCUMENTS, THESE ELEMENTS ARE SHOWN FOR
REFERENCE AND SHALL BE VERIFIED PRIOR TO CONSTRUCTION AND THE
ENGINEER ASSUMES NO LIABILITY FOR THE ACCURACY OF THESE ELEMENTS.
NO DESIGN RESPONSIBILITY IS ASSUMED FOR ANY PORTION OF THE WORK
THAT THE PROFESSIONAL ENGINEER HAS NOT SIGNED AND SEALED PER STATE
REQUIREMENTS.
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT LOGO AND
ADDRESS
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT SEAL AND
SIGNATURE
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1/8" = 1'-0"
AutoCAD SHX Text
SYSTEM LIGHTING CONTROL ZONE INDICATED.
(3) POWER FEEDS FOR BUILDING MANAGEMENT SYSTEM MUST BE
FED FROM THE SAME PANELBOARD AND PHASE.
GROUND FAULT CIRCUIT INTERRUPTING BREAKER
HANDLE LOCK "ON" CLAMP DEVICE
PROVIDE "HACR" TYPE BREAKER FOR ROOF TOP EQUIPMENT
GENERAL NOTES:
CIRCUIT KEY NOTES:
65,000 A.I.C.
N L Y
SWITCHBOARD 'MDP'. THREE SELF-CONTAINED SPLIT-CORE
KWH TRANSDUCER METERS (PULSE OUTPUT) AROUND SERVICE
WIRES TO PANEL WITH BUILT-IN FUSE HOLDERS AND WIRE
LEADS FOR CONNECTION TO PANEL BUS OR LUGS. PROVIDE
EMPTY 3/4"C TO NOVAR EXECUTIVE CONTROLLER. COORDINATE
ALL REQUIREMENTS WITH NOVAR SYSTEM MANUFACTURER.
PANEL
'LA'
1
1
4
N L Y
N L Y
COPPER ONLY
ADDITIONAL INFORMATION.
N L Y
COPPER ONLY
N L Y
UTILITY COMPANY REQUIREMENTS.
N L Y
N L Y
1 " C W
N L Y
N L Y
1 " C W
N L Y
1 " C W
N L Y
N L Y
N L Y
N L Y
AutoCAD SHX Text
DESIGNER NOTE: ELECTRICAL SERVICE AND ONE-LINE DIAGRAM SHALL BE
COORDINATED WITH LOCAL UTILITY AND ALL AUTHORITIES HAVING
JURISDICTION.
AutoCAD SHX Text
AutoCAD SHX Text
ALL DRAWINGS IN THIS SET ARE CONCEPTUAL IN NATURE, PROVIDED AS A
GUIDE ONLY. THESE "TJX SAMPLE MEP PLANS" SHALL BE USED TO ASSIST
CONSULTANTS IN DEVELOPING A SITE SPECIFIC CONSTRUCTION DOCUMENT SET
PER THE LEASE REQUIREMENTS. ALL ITEMS WITHIN THIS DOCUMENT,
INCLUDING BUT NOT LIMITED TO SIZING, QUANTITIES, LOCATIONS, AND
MANUFACTURERS SHALL CONFORM TO THE REQUIREMENTS SET FORTH IN THE
APPLICABLE TJX SPECIFICATIONS REFERENCED IN THE LEASE. ALL
EQUIPMENT, WIRING, PIPING, ETC. SHALL BE SIZED PER ACTUAL PROJECT
CONDITIONS AND APPLICABLE CODES AS ENFORCED BY THE AUTHORITY HAVING
JURISDICTION.
AutoCAD SHX Text
THE WORK INCLUDES PROVIDING NEW MATERIALS, FIXTURES, DEVICES AND
ACCESSORIES NECESSARY FOR A COMPLETE FUNCTIONING ELECTRICAL SYSTEM.
THE WORK ALSO INCLUDES FINAL CONNECTIONS TO MECHANICAL EQUIPMENT
ITEMS PROVIDED BY OTHERS. ALL WORK SHALL BE IN ACCORDANCE WITH THE
AUTHORITY HAVING JURISDICTION, OR ORDINANCES AND SUBJECT TO
INSPECTION.
AutoCAD SHX Text
AutoCAD SHX Text
THE INTENT OF THE DRAWINGS IS TO INDICATE THE GENERAL EXTENT OF
WORK REQUIRED FOR THE PROJECT. THE DRAWINGS FOR ELECTRICAL WORK ARE
DIAGRAMMATIC, SHOWING THE LOCATION, TYPE, DEVICES AND EQUIPMENT
REQUIRED. THE DRAWINGS SHALL NOT BE SCALED FOR EXACT MEASUREMENTS.
PROVIDE ALL FIXTURES, DEVICES ACCESSORIES, OFFSETS, AND MATERIALS
NECESSARY TO FACILITATE THE SYSTEM'S FUNCTIONING AS INDICATED BY
THE DESIGN AND THE EQUIPMENT FURNISHED BY OTHERS.
AutoCAD SHX Text
COORDINATE WITH WORK OF OTHER SECTIONS, AND WITH THE CONSTRAINTS OF
THE EXISTING CONDITIONS OF THE PROJECT SITE. VERIFY EXISTING
CONDITIONS BEFORE BIDDING. REFER TO ARCHITECTURAL/EQUIPMENT
DRAWINGS FOR ADDITIONAL INFORMATION REGARDING EQUIPMENT AND
CASEWORK, AND ELECTRICAL CONNECTIONS REQUIRED.
AutoCAD SHX Text
COMPLY WITH ALL LAWS APPLYING TO ELECTRICAL INSTALLATIONS IN
EFFECT, AND WITH THE MOST RECENT EDITION OF THE ADOPTED ELECTRICAL
CODE. ALL MATERIALS USED SHALL BE NEW AND SHALL CONFIRM TO THE
STANDARDS ESTABLISHED BY UNDERWRITERS LABORATORIES INC.
AutoCAD SHX Text
VERIFY SIZE OF ELECTRICAL SYSTEM BREAKERS, CONDUIT ETC. FOR
EQUIPMENT CONNECTIONS.
AutoCAD SHX Text
PANEL BOARDS SHALL BE AS MANUFACTURED BY GENERAL ELECTRIC, MEETING
UL STANDARDS 50 AND 67 WITH UL LABEL.
AutoCAD SHX Text
ALL PANELBOARDS, SWITCHBOARDS, AND LINE VOLTAGE CONTROL EQUIPMENT
SHALL BE FIELD MARKED TO WARN QUALIFIED PERSONS OF POTENTIAL
ELECTRIC ARC FLASH HAZARDS. MARKING SHALL BE LOCATED SO AS TO BE
CLEARLY VISIBLE TO QUALIFIED PERSONS BEFORE EXAMINATION, ADJUSTING,
SERVICING OR MAINTENANCE OF EQUIPMENT. MARKING SHALL BE SELF
ADHESIVE, COMMERCIAL LABEL CONFORMING TO NEC 110.16 AND ANSI Z535.4
AS MANUFACTURED BY IDEAL OR APPROVED EQUAL.
AutoCAD SHX Text
BREAKERS: THERMAL MAGNETIC TYPE, QUICK-MAKE, QUICK-BREAK, BOLT-IN
TYPE OF SINGLE UNIT CONSTRUCTION. TWO AND THREE POLE BREAKERS SHALL
BE SINGLE UNIT COMMON TRIP TYPE. BREAKERS USED AS SWITCHES FOR 120V
LIGHTING CIRCUITS SHALL BE APPROVED FOR THAT USE AND MARKED "SWD".
WHEN NEW BREAKERS ARE INSTALLED INTO EXISTING PANELS, NEW BREAKERS
SHALL BE OF SAME MANUFACTURER AS EXISTING PANEL AND BE OF EQUAL OR
GREATER AIC RATING AS EXISTING PANEL
AutoCAD SHX Text
CABINETS SHALL BE ONE PIECE CODE GAGE GALVANIZED STEEL WITH
MOUNTING STUDS, WIRING GUTTERS OF AMPLE SIZE AND KNOCKOUTS FOR
CONDUIT CONNECTIONS AS REQUIRED. BUS BARS SHALL BE THW, THHN, THWW
COPPER. BRANCH CIRCUIT WIRING SHALL BE TYPE TW COPPER. FRONTS SHALL
BE ONE PIECE CODE GAGE FURNITURE STEEL WITH ADJUSTABLE FASTENERS.
PROVIDE SURFACE MOUNT UNITS UNLESS OTHERWISE INDICATED. PROVIDE
PLASTIC COVERED TYPEWRITTEN SCHEDULE IDENTIFYING ALL BRANCH
CIRCUITS INSIDE EACH CABINET.
AutoCAD SHX Text
PROVIDE DRY-TYPE ENERGY EFFICIENT TRANSFORMER WHICH SHALL BE NEMA
TP-1 TYPE, ENCLOSED AND VENTILATED WITH KVA AND VOLTAGE RATINGS AS
CALLED FOR ON THE DRAWINGS, WITH (150) DEGREE CLASS "H" INSULATION
AND MINIMUM OF SIX 2-1/2% TAPS. SOUND LEVEL SHALL BE LOW AND
INSTALLATION SHALL INCLUDE KORFUND OR EQUAL VIBRATION DAMPENING
MOUNTS AND FLEXIBLE STEEL CONDUIT FOR PRIMARY AND SECONDARY
CONNECTIONS TO MINIMIZE SOUND TRANSMISSION.
AutoCAD SHX Text
GROUNDING SYSTEM: PERMANENTLY AND EFFECTIVELY GROUND ALL METALLIC
CONDUIT, SUPPORTS, CABINETS, PANEL BOARDS AND SYSTEM NEUTRAL
CONDUCTORS. MAINTAIN CONTINUITY OF EQUIPMENT GROUND THROUGHOUT THE
SYSTEM. GROUND CLAMPS SHALL BE APPROVED TYPE, SPECIFICALLY DESIGNED
FOR GROUNDING. WHERE GROUNDING CONDUCTORS ARE ENCLOSED IN CONDUIT,
GROUND CLAMP SHALL BE OF TYPE WHICH GROUNDS BOTH CONDUCTOR AND
CONDUIT. ALL CIRCUITS IN FLEXIBLE METAL CONDUIT (6'-0" MAXIMUM
LENGTH) SHALL INCLUDE A GROUND WIRE SIZED IN ACCORDANCE WITH NEC
TABLE 250-95.
AutoCAD SHX Text
SIZE CONDUIT TO COMPLY WITH ELECTRICAL CODE FOR NUMBER AND SIZE OF
CONDUCTORS INSTALLED, MINIMUM " ABOVE GRADE. ALL CONDUIT INSTALLED
12" ABOVE GRADE. ALL CONDUIT INSTALLED HORIZONTALLY ABOVE CEILING
SHALL BE SUPPORTED FROM BUILDING STRUCTURE. NO NO CONDUIT SHALL BE
SUPPORTS FROM CEILING GRID OR GRID WIRES. PROVIDE RIGID STEEL
PROVIDE RIGID STEEL CONDUIT OR PVC BELOW GRADE, MINIMUM ". PROVIDE
ELECTRICAL METAL TUBING (EMT) 34". PROVIDE ELECTRICAL METAL TUBING
(EMT) OR "MC" CABLE FOR INTERIOR LOCATIONS. INTERIOR CONNECTORS AND
COUPLINGS SHALL BE SET-SCREW TYPE. CLAMP CONDUIT TO BOXES WITH
BUSHING INSIDE AND LOCKNUT OUTSIDE. FLEXIBLE METAL CONDUIT MAY BE
USED IN LENGTHS 6' OR LESS.
AutoCAD SHX Text
CONDUCTORS: INSULATED SOFT ANNEALED 98% PURE COPPER WITH COLOR
CODING, B AND S GAGE, #10 AND SMALLER TO BE SOLID, #8 AND LARGER TO
BE STRANDED, MINIMUM #12 UNLESS OTHERWISE INDICATED.
AutoCAD SHX Text
DEVICES SHALL BE MANUFACTURED BY LEVITON OR EQUAL. ALL DEVICES
SHALL BE WHITE COLOR WITH BRUSHED ALUMINUM COVER PLATES. STANDARD
DUPLEX RECEPTACLES SHALL BE GROUNDING TYPE, 20A, NEMA WD-2 STANDARD
5-20R, BACK AND SIDE WIRED. ISOLATED GROUND RECEPTACLES SHALL BE
LEVITON 5262-IG AND ORANGE IN COLOR. OTHER DEVICES SHALL BE
INDICATED ON THE DRAWINGS, OR AS REQUIRED BY THE EQUIPMENT ITEM
INTENDED TO BE SERVED. WHERE SWITCHES ARE GROUPED, PROVIDE
GANGPLATES. NO RESIDENTIAL GRADE DEVICES ALLOWED.
AutoCAD SHX Text
LAYOUT BRANCH CIRCUIT WIRING AND ARRANGEMENT OF HOME RUNS FOR
MAXIMUM ECONOMY AND EFFICIENCY. INCREASE WIRE SIZE IF VOLTAGE DROP
EXCEEDS 3% OR CIRCUIT LENGTH EXCEEDS 100 FEET.
AutoCAD SHX Text
CONCEAL WIRING SYSTEM ABOVE SUSPENDED CEILINGS OR IN WALL WHERE
POSSIBLE. INSTALL CONDUIT AND MC CABLE PARALLEL TO BUILDING LINES,
AND TO CLEAR ALL OPENING, DEPRESSIONS, PIPES, DUCTS, STRUCTURE,
ETC. SUPPORT PER NEC.
AutoCAD SHX Text
INSTALL CONDUIT CONTINUOUS BETWEEN BOXES AND CABINETS WITH NO MORE
THAN FOUR (4) 90 DEGREE BENDS. SECURELY FASTEN IN PLACE WITH
STRAPS, HANGERS AND STEEL SUPPORTS AS REQUIRED. REAM CONDUIT ENDS
BEFORE INSTALLATION AND THOROUGHLY CLEAN BEFORE INSTALLATION.
OPENINGS SHALL BE PLUGGED OR COVERED TO KEEP CONDUIT CLEAN.
TERMINALS ON SWITCHES AND OUTLETS SHALL NOT BE USED TO "FEED THRU"
TO THE NEXT SWITCH OR OUTLET. THE DISCONNECTION OR REMOVAL OF A
RECEPTACLE, FIXTURE, OR OTHER DEVICE FED FROM A BOX SHALL NOT
INTERFERE WITH OR INTERRUPT THE CONDUCTOR CONTINUITY.
AutoCAD SHX Text
ADJUSTING AND TESTING: ALL ELECTRICAL EQUIPMENT SHALL BE ADJUSTED
AND TESTED FOR PROPER OPERATION. COMPLETED WIRING SYSTEM SHALL BE
FREE FROM SHORT CIRCUITS.
AutoCAD SHX Text
TOUCHUP AND CLEANING: TOUCHUP OR REFINISH DAMAGED SURFACES OF
FIXTURES AND EQUIPMENT EXPOSED TO VIEW. CLEAN FIXTURES, GLASSWARE
AND LAMPS BY APPROVED METHODS, READY FOR USE.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: USE THIS SPACE TO PROVIDE LIGHTING COMPLIANCE FORMS
AS REQUIRED BY LOCAL CODE AUTHORITY.
AutoCAD SHX Text
AutoCAD SHX Text
DESIGNER NOTE: G.E. RELAY PANEL SCHEDULE ZONES & CIRCUITS SHOWN
AS REFERENCE ONLY. SCHEDULE SHALL BE COMPLETED BASED EACH PROJECT.
ALL CONTROLLED CIRCUITS MUST BE SHOWN IN SCHEDULE. G.E. RELAY PANEL
SCHEDULE IS REQUIRED FOR EACH PROJECT FOR FINAL APPROVAL. PROVIDE
(2) RELAY PANELS WHEN MORE THAN 48 CIRCUITS ARE REQUIRED TO BE
CONTROLLED (ONLY HOMEGOODS & HOMESENS). ALL RELAY PANELS WILL
HAVE 48 SPACES.
AutoCAD SHX Text
DESIGNER NOTE: MECHANICAL CONNECTIONS ARE FOR REFERENCE ONLY. ALL
MECHANICAL INFO SHALL BE BASED ON MECHANICAL ENGINEER'S
CONSTRUCTION DOCUMENTS.
AutoCAD SHX Text
DESIGNER NOTE: ADDITIONAL PANEL(S) MAY BE REQUIRED FOR HOMEGOODS
& HOMESENSE STORES.
AutoCAD SHX Text
THIS SHEET IS PART OF THE CONSTRUCTION DOCUMENTS, OTHER SHEETS
INCLUDING SPECIFICATIONS APPLY. INFORMATION SHOWN HEREON IS
SCHEMATIC IN NATURE AND NOT TO BE USED AS A SHOP DRAWING;
THEREFORE, INCLUDE ALL MODIFICATIONS REQUIRED TO CONFORM TO SITE
CONDITIONS AND THE EQUIPMENT AND MATERIAL USED. VERIFY LOCATIONS
AND DIMENSIONS OF ALL ARCHITECTURAL AND STRUCTURAL ELEMENTS AS
SHOWN ON THEIR RESPECTIVE DOCUMENTS, THESE ELEMENTS ARE SHOWN FOR
REFERENCE AND SHALL BE VERIFIED PRIOR TO CONSTRUCTION AND THE
ENGINEER ASSUMES NO LIABILITY FOR THE ACCURACY OF THESE ELEMENTS.
NO DESIGN RESPONSIBILITY IS ASSUMED FOR ANY PORTION OF THE WORK
THAT THE PROFESSIONAL ENGINEER HAS NOT SIGNED AND SEALED PER STATE
REQUIREMENTS.
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT LOGO AND
ADDRESS
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT SEAL AND
SIGNATURE
AutoCAD SHX Text
MC-4 DPS
2 COND
NOTES: (1) ALL LOW VOLTAGE SIGNAL WIRING SHALL BE 20-GAUGE MINIMUM.
THE MINIMUM INDUCTIVE LOAD (LOCK) POWER WIRE GAUGE SHALL BE
DETERMINED PER THE SDC WIRE GAUGE CHART. ALL WIRING (SINGLE OR
MULTI-CONDUCTOR) SHALL BE COLOR CODED WITHOUT SPLICES. A MINIMUM OF
TWO SPARE CONDUCTORS IS RECOMMENDED. (2) SPECIFY VOLTAGE WHEN
ORDERING PRODUCTS. VOLTAGE IS NOT SPECIFIED ON THIS WIRE DIAGRAM.
BE SURE ALL PRODUCTS ARE VOLTAGE COMPATIBLE. (3) ALL WIRING MUST
CONFORM TO NATIONAL, STATE AND LOCAL CODES. (4) ALWAYS CONSULT WITH
THE AUTHORITY HAVING JURISDICTION (AHJ) BEFORE INSTALLATION. (5)
WHERE REQUIRED BY CODE.
Components
Description Electric Strike Power Supply w/Dual Interlock Circuit
Board Momentary SPDT - Push Button Switches Magnetic DPS
Switches
Part Number 55-A24U 631RFA x UR2A 15-2 X SPDT x MOM MC-4
Manufacturer SDC SDC SDC SDC
Method of Operation
The above layout is identified as a Mantrap "B". Both openings have
mechanical locks that are latched & unlatched by electric
strikes. Access / Egress: Entering is accomplished by either
mechanical key or push button control from inside a cash room.
Egress is free at all times.
55-A
ELECTRIC
STRIKE
A5 A6 A7 A8 A9 A10 B5 B6 B7 B8 B9 B10
STATION A OUTPUT
STATION B OUTPUT
R EL
AY R
EL AY
R EL
AY R
EL AY
R EL
AY R
EL AY
E1 E2 E3 E4 E5 E7 E8E6A1 A2 A3 A4 B4B2 B3B1
STATION A OUTPUT
STATION B OUTPUT
DIP SWITCH 1 2 3 4 5 6 7 8
ON
- +
24 VDC OUTPUT
STANDBY BATTERY CONNECTION
A
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
SENS/SW
SENS/SW
SENS/SW
SENS/SW
SW/SENS
SW/SENS
SW/SENS
SW/SENS
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
R L Y 1
R L Y 2
R L Y 3
SENS/SW
SENS/SW
SENS/SW
SENS/SW
SW/SENS
SW/SENS
SW/SENS
SW/SENS
AutoCAD SHX Text
MASTER ON/OFF SWITCH TO CONTROL ON/OFF CASE LIGHTING. SWITCH TO BE
LOCATED 6" FROM FRONT FACE OF CABINET.
AutoCAD SHX Text
AutoCAD SHX Text
NOVAR INTERFACE SUMMARY (REFER TO TJX SPECIFICATIONS FOR DETAIL
INFORMATION) 1) GENERAL CONTRACTOR A) PROVIDE AND INSTALL A 4'X8'
PLYWOOD BACKBOARD IN THE ELECTRIC ROOM FOR NOVAR TO MOUNT THEIR
PROVIDE AND INSTALL A 4'X8' PLYWOOD BACKBOARD IN THE ELECTRIC ROOM
FOR NOVAR TO MOUNT THEIR EQUIPMENT. PHONE AND ETHERNET JACKS FOR
THE NOVAR SAVVY CONTROLLER WILL ALSO BE LOCATED ON THIS BOARD BY A
SEPARATE TJX VENDOR. 2) MECHANICAL CONTRACTOR A) HORIZONTALLY MOUNT
A 2X4 J-BOX WITH CONDUIT (WIREMOLD IF EXPOSED IN FINISHED AREAS) AT
THE LOCATIONS HORIZONTALLY MOUNT A 2X4 J-BOX WITH CONDUIT (WIREMOLD
IF EXPOSED IN FINISHED AREAS) AT THE LOCATIONS DESIGNATED ON THE
NOVAR CONTROLS SITE SPECIFIC PLANS. THE J-BOXES ARE TO BE MOUNTED
AT 60" A.F.F. EXCEPT IN FITTING ROOM LOCATIONS WHERE THE J-BOXES
ARE TO BE MOUNTED AT 84" A.F.F.. ON THE SALES FLOOR, THE J-BOXES
ARE TO BE MOUNTED ON BACK SIDE OF THE COLUMNS WHEN VIEWED FROM
FRONT OF STORE. B) PROVIDE AND INSTALL A PERMANENT STRANDED 18/2
AWG NON SHIELDED CABLE (18/8 IF THE RTU IS EQUIPPED WITH A PROVIDE
AND INSTALL A PERMANENT STRANDED 18/2 AWG NON SHIELDED CABLE (18/8
IF THE RTU IS EQUIPPED WITH A C02 SENSOR WITH THE UNIT) FROM EACH
ROOFTOP UNIT TO THE NOVAR ETM (T-STAT) LOCATION SHOWN ON THE NOVAR
PLAN THAT SUPERSEDES ANY MECHANICAL PLAN LOCATIONS. C) TEMPORARY
THERMOSTATS ARE TO BE INSTALLED AT THE ROOFTOP UNITS. TEMPORARY
THERMOSTATS ARE TO BE INSTALLED AT THE ROOFTOP UNITS. D) HVAC
EQUIPMENT ARE TO HAVE HAD A MANUFACTURER'S RECOMMENDED STARTUP
PROCEDURE PERFORMED AND BE HVAC EQUIPMENT ARE TO HAVE HAD A
MANUFACTURER'S RECOMMENDED STARTUP PROCEDURE PERFORMED AND BE
OPERATIONAL IN ALL MODES BEFORE THE ARRIVAL OF THE NOVAR CONTROLS
REPRESENTATIVE FOR THE FINAL NOVAR INSTALLATION. 3) ELECTRICAL
CONTRACTOR A) PROVIDE AND INSTALL A THREE PHASE CIRCUIT BREAKER (20
AMPS) FOR THE PHASE MONITOR. THIS BREAKER PROVIDE AND INSTALL A
THREE PHASE CIRCUIT BREAKER (20 AMPS) FOR THE PHASE MONITOR. THIS
BREAKER MAY BE INSTALLED IN A LIGHTING DISTRIBUTION PANEL IF THE
PANEL IS OF THE SAME VOLTAGE AS THE MAIN DISTRIBUTION PANEL. B)
INSTALL THE NOVAR PROVIDED CURRENT TRANSFORMERS (CTS). INSTALL THE
NOVAR PROVIDED CURRENT TRANSFORMERS (CTS). C) CONNECT ALL CT WIRING
TO THE PHASE MONITOR. CONNECT ALL CT WIRING TO THE PHASE MONITOR.
D) MOUNT AND POWER THE PHASE MONITOR. MOUNT AND POWER THE PHASE
MONITOR. E) PROVIDE AND INSTALL BMS#1 (20 AMP, 1 POLE BREAKER),
BMS#2 (20 AMP, 1 POLE BREAKER), AND BMS #3 (20 AMP, 1 POLE PROVIDE
AND INSTALL BMS#1 (20 AMP, 1 POLE BREAKER), BMS#2 (20 AMP, 1 POLE
BREAKER), AND BMS #3 (20 AMP, 1 POLE BREAKER) POWER SUPPLY. THESE
BREAKERS MUST ORIGINATE FROM THE SAME PHASE. BMS BREAKERS REQ'D ON
TJE CP PANEL. F) THE INSTALLATION, PROGRAMMING, AND LABELING OF THE
GE SOFTWIRE PANEL IS THE RESPONSIBILITY OF THE ELECTRICAL THE
INSTALLATION, PROGRAMMING, AND LABELING OF THE GE SOFTWIRE PANEL IS
THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
AutoCAD SHX Text
LIGHTING SUMMARY (REFER TO TJX SPECIFICATIONS FOR DETAIL
INFORMATION) 1) NIGHT LIGHTING: NIGHT LIGHTING: A) NIGHT LIGHTS ARE
TO BE ON 24 HOURS A DAY AND ONLY IN THE SALES AREA. NIGHT LIGHTS
ARE TO BE ON 24 HOURS A DAY AND ONLY IN THE SALES AREA. A) THE
CIRCUIT FOR NIGHT LIGHTING IS NOT TO BE CONNECTED TO THE GE RELAY
PANEL, OR EMERGENCY LIGHTING. THE THE CIRCUIT FOR NIGHT LIGHTING IS
NOT TO BE CONNECTED TO THE GE RELAY PANEL, OR EMERGENCY LIGHTING.
THE NOT TO BE CONNECTED TO THE GE RELAY PANEL, OR EMERGENCY
LIGHTING. THE TO BE CONNECTED TO THE GE RELAY PANEL, OR EMERGENCY
LIGHTING. THE NL SHOULD BE ONLY (1) CIRCUIT IN MOST SITUATIONS. B)
NIGHT LIGHTING "RULE OF THUMB" IS (1) NIGHT LIGHT FOR EVERY 3,500
SQUARE FEET OF SALES AREA (ROUND UP), AND NIGHT LIGHTING "RULE OF
THUMB" IS (1) NIGHT LIGHT FOR EVERY 3,500 SQUARE FEET OF SALES AREA
(ROUND UP), AND SHOULD BE EVENLY DISTRIBUTED. (REFER TO TJX
CRITERIA PLAN SHEET (C5) FOR EXACT QUANTITIES & LOCATIONS). 2)
EMERGENCY LIGHTING: EMERGENCY LIGHTING: A) EMERGENCY LIGHTING IS TO
BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE CODES AND AT THE
DIRECTION OF EMERGENCY LIGHTING IS TO BE INSTALLED IN ACCORDANCE
WITH ALL APPLICABLE CODES AND AT THE DIRECTION OF THE GOVERNING
AUTHORITIES. B) AT A MINIMUM, THE EMERGENCY LIGHTING IS TO BE AS
FOLLOWS: AT A MINIMUM, THE EMERGENCY LIGHTING IS TO BE AS FOLLOWS:
1) ALL ROOMS AND SPACES ARE TO HAVE AT LEAST (1) EMERGENCY LIGHT.
ALL ROOMS AND SPACES ARE TO HAVE AT LEAST (1) EMERGENCY LIGHT. 2)
THE SALES AREA IS TO HAVE (1) EMERGENCY LIGHT PER 2,000 SQUARE FEET
OF FLOOR AREA, AND SHOULD BE THE SALES AREA IS TO HAVE (1)
EMERGENCY LIGHT PER 2,000 SQUARE FEET OF FLOOR AREA, AND SHOULD BE
EVENLY DISTRIBUTED THROUGHOUT THE SPACE. PATHS OF EGRESS SHOULD BE
OF PRIMARY COVERAGE. 3) THE STOCK ROOM SHOULD HAVE A MINIMUM OF (4)
EMERGENCY LIGHTS. THE STOCK ROOM SHOULD HAVE A MINIMUM OF (4)
EMERGENCY LIGHTS. C) THE EMERGENCY LIGHTING SYSTEM AND CIRCUITS ARE
NOT TO BE CONNECTED TO THE GE RELAY PANEL AND THE THE EMERGENCY
LIGHTING SYSTEM AND CIRCUITS ARE NOT TO BE CONNECTED TO THE GE
RELAY PANEL AND THE NOT TO BE CONNECTED TO THE GE RELAY PANEL AND
THE TO BE CONNECTED TO THE GE RELAY PANEL AND THE CIRCUITS ARE TO
BE DEDICATED WITH BREAKER LOCKS INSTALLED AT THE PANEL. D) THE
EMERGENCY LIGHTS ARE TO BE LITHONIA LIGHTING, MODEL #ELM2, SELF
CONTAINED BATTERY UNITS. THE EMERGENCY LIGHTS ARE TO BE LITHONIA
LIGHTING, MODEL #ELM2, SELF CONTAINED BATTERY UNITS. 3) SECURITY
LIGHTING: SECURITY LIGHTING: A) EXTERIOR SECURITY LIGHTING INCLUDES
EXTERIOR WALL LIGHT PACKS ATTACHED TO THE BUILDING AS NOTED ON THE
EXTERIOR SECURITY LIGHTING INCLUDES EXTERIOR WALL LIGHT PACKS
ATTACHED TO THE BUILDING AS NOTED ON THE PLANS. THESE ARE GENERALLY
MOUNTED ABOVE ALL EGRESS DOORS FROM THE STORE. B) THE CIRCUITING
FOR THIS IS THROUGH THE GE RELAY PANEL. THE CIRCUITING FOR THIS IS
THROUGH THE GE RELAY PANEL. C) NOVAR WILL CONTROL THIS LIGHTING BY
A SEPARATE CHANNEL IN THE RELAY PANEL. THIS LIGHTING IS OVERRIDDEN
NOVAR WILL CONTROL THIS LIGHTING BY A SEPARATE CHANNEL IN THE RELAY
PANEL. THIS LIGHTING IS OVERRIDDEN BY A LIGHT SENSOR SUPPLIED AND
INSTALLED BY NOVAR. 4) SIGNS AND CANOPY LIGHTS: SIGNS AND CANOPY
LIGHTS: A) THIS INCLUDES THE BUILDING, MALL, LIGHTED UNDER CANOPY,
ETC. SIGNS AS WELL AS ANY CANOPY LIGHTS (IF NOT THIS INCLUDES THE
BUILDING, MALL, LIGHTED UNDER CANOPY, ETC. SIGNS AS WELL AS ANY
CANOPY LIGHTS (IF NOT BEING CONTROLLED BY THE LANDLORD'S HOUSE
PANEL). B) THESE CIRCUITS ARE TO BE RUN THROUGH THE GE RELAY PANEL.
THESE CIRCUITS ARE TO BE RUN THROUGH THE GE RELAY PANEL. C) NOVAR
WILL CONTROL THESE CIRCUITS BY A SEPARATE CHANNEL IN THE RELAY
PANEL. NOVAR WILL CONTROL THESE CIRCUITS BY A SEPARATE CHANNEL IN
THE RELAY PANEL. 5) CUSTOMER LIGHTING: CUSTOMER LIGHTING: A) SALES
AREA: SALES AREA: 1) ONE HALF OF THE SALES AREA CEILING LIGHTS
(ALTERNATE ROWS). ONE HALF OF THE SALES AREA CEILING LIGHTS
(ALTERNATE ROWS). 2) ALL PERIMETER LIGHTING. ALL PERIMETER
LIGHTING. 3) ALL PENDANT LIGHTING. ALL PENDANT LIGHTING. 4) JEWELRY
COUNTER LIGHTING. JEWELRY COUNTER LIGHTING. 5) LAMP DEPARTMENT
PLUGMOLD (ON WALLS AND FLOOR GONDOLAS). LAMP DEPARTMENT PLUGMOLD
(ON WALLS AND FLOOR GONDOLAS). 6) FLOOR OUTLETS FOR LAMP
DEPARTMENT. FLOOR OUTLETS FOR LAMP DEPARTMENT. 7) CEILING MOUNTED
CHANDELIER FIXTURE OUTLETS. CEILING MOUNTED CHANDELIER FIXTURE
OUTLETS. 8) ANY SPECIALTY LIGHTING (I.E. WALL SCONCES, ETC.). ANY
SPECIALTY LIGHTING (I.E. WALL SCONCES, ETC.). B) OFF SALES AREA:
OFF SALES AREA: 1) PENDANT LIGHTS IN THE FITTING ROOM PENDANT
LIGHTS IN THE FITTING ROOM 2) LIGHTED MIRRORS IN THE FITTING ROOM
LIGHTED MIRRORS IN THE FITTING ROOM C) THESE CIRCUITS ARE TO BE RUN
THROUGH THE GE RELAY PANEL. THESE CIRCUITS ARE TO BE RUN THROUGH
THE GE RELAY PANEL. 6) EMPLOYEE LIGHTING: EMPLOYEE LIGHTING: A)
EMPLOYEE LIGHTING IS TO INCLUDE ALL (EXCEPT AS EXCLUDED BELOW)
INTERIOR STORE LIGHTING AND BE RUN EMPLOYEE LIGHTING IS TO INCLUDE
ALL (EXCEPT AS EXCLUDED BELOW) INTERIOR STORE LIGHTING AND BE RUN
THROUGH THE GE RELAY PANEL. THE SALES AREA CEILING LIGHTS IS TO BE
ALTERNATE ROWS. B) ITEMS NOT INCLUDED IN "EMPLOYEE LIGHTING" ARE
NIGHT LIGHTING, EMERGENCY LIGHTING, EXIT LIGHTING, DOCK ITEMS NOT
INCLUDED IN "EMPLOYEE LIGHTING" ARE NIGHT LIGHTING, EMERGENCY
LIGHTING, EXIT LIGHTING, DOCK LIGHTS, "SECURITY LIGHTING", "SIGNS
AND CANOPY LIGHTS", AND "CUSTOMER LIGHTING" AS DESCRIBED ABOVE. C)
EMPLOYEE LIGHTING IS TO INCLUDE ALL EXHAUST FANS EXCEPT THE
ELECTRICAL ROOM EXHAUST FAN THAT IS TO BE EMPLOYEE LIGHTING IS TO
INCLUDE ALL EXHAUST FANS EXCEPT THE ELECTRICAL ROOM EXHAUST FAN
THAT IS TO BE CONTROLLED BY A STAND-ALONE LINE VOLTAGE THERMOSTAT
(SET AT 80° F). THESE CIRCUITS ARE TO BE RUNTHROUGH THE GE RELAY
PANEL. 7) G.E. SOFTWIRE RELAY PANEL PROGRAMMING: G.E. SOFTWIRE
RELAY PANEL PROGRAMMING: A) SOFTWIRING LIGHTING GROUPS SOFTWIRING
LIGHTING GROUPS 1) THE SCM SHALL ALLOW ANY GROUP OF RELAYS WITHIN
THE PANEL TO BE ASSOCIATED ("SOFTWIRED") TO A THE SCM SHALL ALLOW
ANY GROUP OF RELAYS WITHIN THE PANEL TO BE ASSOCIATED ("SOFTWIRED")
TO A CHANNEL USING THE FOLLOWING PROCEDURE: A) ...PRESS AND HOLD
THE CHANNEL PUSH BUTTON FOR SEVERAL SECONDS. THE CHANNEL LED AND
THE LEDS ...PRESS AND HOLD THE CHANNEL PUSH BUTTON FOR SEVERAL
SECONDS. THE CHANNEL LED AND THE LEDS FOR RELAYS CURRENTLY
CONTROLLED BY THAT INPUT WILL BEGIN TO FLASH. B) ...SELECT THE
RELAYS TO BE CONTROLLED. THE LED FOR EACH RELAY "SOFTWIRED" TO THE
CHANNEL ...SELECT THE RELAYS TO BE CONTROLLED. THE LED FOR EACH
RELAY "SOFTWIRED" TO THE CHANNEL SELECTED WILL BE FLASHING ON/OFF.
PRESS THE ASSOCIATED RELAY CONTROL BUTTON TO ADD/DELETE THAT RELAY
TO/FROM GROUP. C) ...PRESS THE CHANNEL PUSH BUTTON AGAIN. THE LEDS
WILL STOP FLASHING AND THE CHANNEL PUSH BUTTON ...PRESS THE CHANNEL
PUSH BUTTON AGAIN. THE LEDS WILL STOP FLASHING AND THE CHANNEL PUSH
BUTTON AND ASSOCIATED SWITCH INPUTS WILL NOW CONTROL THE RELAYS
SELECTED. 2) TURNING A CHANNEL ON/OFF WILL SEQUENCE ALL OF THE
RELAYS WITHIN THAT GROUP ON/OFF INDIVIDUALLY. TURNING A CHANNEL
ON/OFF WILL SEQUENCE ALL OF THE RELAYS WITHIN THAT GROUP ON/OFF
INDIVIDUALLY. B) CONTROLLING A SOFTWIRE GROUP CONTROLLING A
SOFTWIRE GROUP 1) EACH CHANNEL SHALL HAVE AN ASSOCIATED PUSH-BUTTON
WITHIN THE PANEL TO TOGGLE THE CHANNEL ON/OFF EACH CHANNEL SHALL
HAVE AN ASSOCIATED PUSH-BUTTON WITHIN THE PANEL TO TOGGLE THE
CHANNEL ON/OFF 2) EACH CHANNEL SHALL ALSO HAVE TWO SEPARATE SWITCH
OR DRY CONTACT INPUTS THAT WILL ALLOW THE EACH CHANNEL SHALL ALSO
HAVE TWO SEPARATE SWITCH OR DRY CONTACT INPUTS THAT WILL ALLOW THE
CHANNEL TO BE CONTROLLED REMOTELY. 3) THE CHANNEL SHALL RESPOND TO
THE LAST INPUT. THE CHANNEL SHALL RESPOND TO THE LAST INPUT. 4) THE
UNIT SHALL ALLOW A "MASTER CHANNEL" TO BE CONFIGURED TO CONTROL
SEVERAL OF THE ABOVE THE UNIT SHALL ALLOW A "MASTER CHANNEL" TO BE
CONFIGURED TO CONTROL SEVERAL OF THE ABOVE CHANNELS BY SIMPLY
INCLUDING ALL OF THE RELAYS OF THESE "SUB CHANNELS" WITHIN THE
MASTER. C) GROUP STATUS GROUP STATUS 1) EACH CHANNEL PUSH-BUTTON
SHALL INCLUDE A LED STATUS INDICATION. THE LED WILL BE ON WHENEVER
ALL OF EACH CHANNEL PUSH-BUTTON SHALL INCLUDE A LED STATUS
INDICATION. THE LED WILL BE ON WHENEVER ALL OF THE RELAYS WITHIN
THE CHANNEL GROUP ARE ON; AND SHALL GO OFF WHEN ALL OF THE RELAYS
WITHIN THE AND SHALL GO OFF WHEN ALL OF THE RELAYS WITHIN THE GROUP
GO OFF. 2) EACH CHANNEL SHALL ALSO HAVE AN ASSOCIATE DRY CONTACT
CLOSURE OF PILOT CONTACT WHICH TRACKS EACH CHANNEL SHALL ALSO HAVE
AN ASSOCIATE DRY CONTACT CLOSURE OF PILOT CONTACT WHICH TRACKS THE
LED OPERATION DESCRIBED ABOVE. D) CONTROLLING AN INDIVIDUAL RELAY
CONTROLLING AN INDIVIDUAL RELAY 1) EACH RELAY SHALL HAVE AN
ASSOCIATED CONTROL BUTTON WITH LED STATUS INDICATION MOUNTED WITHIN
THE EACH RELAY SHALL HAVE AN ASSOCIATED CONTROL BUTTON WITH LED
STATUS INDICATION MOUNTED WITHIN THE LOW VOLTAGE SECTION OF THE
PANEL.
AutoCAD SHX Text
SINGLE DEDICATED OUTLET TO FACE OUTWARD AND BE MOUNTED BELOW THE
DRAWER AND ABOVE THE ACCESS PANEL.
AutoCAD SHX Text
SINGLE DEDICATED OUTLET TO FACE OUTWARD AND BE MOUNTED BELOW THE
DRAWER AND ABOVE THE ACCESS PANEL.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NOTE: UNUSED LEAD MUST UNUSED LEAD MUST BE PROPERLY INSULATED WITH
WIRENUT OR OTHER APPROVED METHOD.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
SINGLE Q CHECK OUT STAND ELEVATION @ END CHECK OUT (TYPICAL)
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
RECEPTACLES FOR "EAS" SECURITY TO BE LOCATED ON THE SAME CIRCUIT
THROUGHOUT CASH REGISTER AREA. (TYP.)
AutoCAD SHX Text
RECEPTACLES FOR "EAS" SECURITY TO BE LOCATED ON THE SAME CIRCUIT
THROUGHOUT CASH REGISTER AREA. (TYP.)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
RECEPTACLES FOR "EAS" SECURITY TO BE LOCATED ON THE SAME CIRCUIT
THROUGHOUT CASH REGISTER AREA. (TYP.)
AutoCAD SHX Text
AutoCAD SHX Text
RECEPTACLES FOR "EAS" SECURITY TO BE LOCATED ON THE SAME CIRCUIT
THROUGHOUT CASH REGISTER AREA. (TYP.)
AutoCAD SHX Text
AutoCAD SHX Text
NOTE: REFER TO TJX DRAWING C6 POWER PLAN FOR EXACT QUANTITY &
LOCATION OF ALL DEDICATED / ISOLATED GROUND RECEPTACLES SHOWN IN
THE DIAGRAM BELOW.
AutoCAD SHX Text
SINGLE QUE REGISTERS
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
POS AS WELL AS THE CABLE FOR THE TIME CLOCK, ACS AND
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AND SHALL BE KEPT A MINIMUM OF 5'-0" FROM FLUORESCENT
AutoCAD SHX Text
3 ALL LOW VOLTAGE WIRING TO BE INSTALLED ABOVE HUNG CLG.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
2 CABLES TO BE RUN IN ONE PIECE FROM REGISTER
AutoCAD SHX Text
I.G. GROUND TO BE TAGGED OR LABELED AT MAIN ENTRANCE.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PANEL "CP" SHALL BE USED TO SUPPLY ONLY REGISTER EQUIP.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
2 ALL WIRING SHALL BE TYPE "THW" OR "THHN" COPPER
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
3/4" -1 NO. 8 CONNECT DIRECTLY TO MAIN SERVICE GROUND
AutoCAD SHX Text
AutoCAD SHX Text
ALUM. POWER POLE WIREMOLD # NP600C ANCHOR AT CLG. & COUNTER
TOP. (IF APPLICABLE)
AutoCAD SHX Text
UPS UNIT SUPPLIED BY TJX COMPANIES INSTALLED BY GENERAL
CONTRACTOR'S ELECTRICIAN.
AutoCAD SHX Text
*** ALL DELIVERY QUESTIONS SHOULD *** BE DIRECTED TO TJX SYSTEMS
IMPLEMENTATION AT 508-475-8105
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
Liebert GXT4 6kVA UPS and CP Panel for TJX Stores
AutoCAD SHX Text
CIRCUITS TO FEED, ISOLATED GROUNDED RECEPTACLES AND ALL REGISTER
LOCATIONS.
AutoCAD SHX Text
TJX LIEBERT GXT4 6kva UPS installation guidelines LIEBERT CONTACT
INFORMATION LIEBERT TECHNICAL SUPPORT PHONE: 800 - 222 - 5877
Option #1 Hardware Support EMAIL:
[email protected]
GENERAL INFORMATION: GCs or Electrical Contractors are not required
to purchase the UPS. TJX provides all units from a third party
location; DO NOT CALL LIEBERT WITH DELIVERY CONCERNS. The units are
a Liebert GXT4 6kva tower UPS - 16.9” (H) x 6.8” (W) x 26.1” (D)
and weigh 132 pounds total. The units arrive in (H) x 6.8” (W) x
26.1” (D) and weigh 132 pounds total. The units arrive in (W) x
26.1” (D) and weigh 132 pounds total. The units arrive in (D) and
weigh 132 pounds total. The units arrive in three separate boxes
via FEDEX Wiring diagram is included on the TJX criteria, sheet C7.
Installation does NOT require Liebert to be onsite. INSTALLATION:
Electrical Contractor responsibilities: Unpack/set/place the UPS,
placement must conform to local and national codes. UPS ships in
three boxes, UPS, Internal Battery pack and SNMP card. Please refer
to the UPS Manual, ships with the unit, for proper installation.
Starts on Page 12. Terminate wiring at input and output of UPS.
Ensure distribution wiring, CP Panel, and disconnect are correctly
installed. START UP Electrical Contractor responsibilities: Unit
must be turned on and taken out of BYPASS after installation is
complete. Confirm the UPS is the only source feeding the CP Panel
Call LIEBERT at the above number to troubleshoot any issues with
Start up Provide support for LIEBERT if wiring issues arise during
Start Up. After UPS is Turned on and taken out of BYPASS without
any issues, the TJX PM must be notified that UPS installation is
complete and the UPS is functional without issues.
AutoCAD SHX Text
AutoCAD SHX Text
CIRCUIT NEEDED ONLY WHEN REQUESTED BY SYSTEMS FOR REMOTE COMPUTER
EQUIPMENT CONNECTION AND IG OUTLET.
AutoCAD SHX Text
AutoCAD SHX Text
TYPICAL CP PANEL
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
NOTES: : 1. LIEBERT RECOMMENDED WIRE SIZE, INCLUDING GROUND LIEBERT
RECOMMENDED WIRE SIZE, INCLUDING GROUND WIRE, @ 75° COPPER WIRE IS
10AWG (4mm). MAXIMUMWIRE ACCEPTED BY TERMINAL BLOCK IS 8AWG (6mm).
2. LIEBERT RECOMMENDS INSTALLING A UL489 APPROVED LIEBERT
RECOMMENDS INSTALLING A UL489 APPROVED BREAKER UPSTREAM OF UNIT. 3.
THE INSTALLER MUST PROVIDE CIRCUIT BREAKER THE INSTALLER MUST
PROVIDE CIRCUIT BREAKER PROTECTION ACCORDING TO LOCAL CODES. THE
UTILITY DISCONNECT SHOULD BE WITHIN SIGHT OF THE UPS OR HAVE AN
APPROPRIATE LOCK OUT. MAINTAIN SERVICE SPACE AROUND THE UPS OR USE
FLEXIBLE UPS OR USE FLEXIBLE CONDUIT. 4. THE INSTALLER MUST PROVIDE
OUTPUT DISTRIBUTION THE INSTALLER MUST PROVIDE OUTPUT DISTRIBUTION
PANELS, CIRCUIT BREAKER PROTECTION, OR EMERGENCY DISCONNECTS
ACCORDING TO LOCAL CODES. 5. OUTPUT CIRCUITS MUST NOT SHARE A
COMMON. OUTPUT CIRCUITS MUST NOT SHARE A COMMON. 6. CP PANEL WILL
SERVICE ALL REGISTER POWER, CP PANEL WILL SERVICE ALL REGISTER
POWER, BLADE SERVER, IDF, AND BMS POWER ONLY. NO ONLY. NO . NO
OTHER CIRCUIT TO BE FED FROM CP.
AutoCAD SHX Text
AutoCAD SHX Text
NOTE: : SUB-CONTRACTOR TO FURNISH AND INSTALL THREE (3), 120V
DEDICATED CONTROL CIRCUITS. BMS #1, BMS #2 & BMS #3. THESE
CIRCUITS SHALL BE SOURCED FROM PANEL "CP"
AutoCAD SHX Text
NOTE: : NOVAR SYSTEM REQUIRES (1) 20A/3P CIRCUIT BREAKER AT MDP FOR
PHASE MONITOR.
AutoCAD SHX Text
DETAIL @ L.P. OFFICE
AutoCAD SHX Text
AutoCAD SHX Text
COUNTER SUPPORT (TO BE MOUNTED DIRECTLY NEXT TO THE WALL OR 30
INCHES FROM THE WALL.)
AutoCAD SHX Text
ACOUSTICAL CEILING TILE
AutoCAD SHX Text
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
110V, 24HR PLUG MOLD STRIP MOUNTED CENTRALLY ON WALL ABOVE DESKTOP,
APPROX. 41" AFF ON BREAKER LOCK, DEDICATED CIRCUITS AS
REQUIRED.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CAT5 - CAN BUS
AutoCAD SHX Text
7 X AWG#18 - 6 ZONES CONTROLS USE ONE WIRE FOR EACH ZONE PLUS ONE
COMMON
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ALL DRAWINGS IN THIS SET ARE CONCEPTUAL IN NATURE, PROVIDED AS A
GUIDE ONLY. THESE "TJX SAMPLE MEP PLANS" SHALL BE USED TO ASSIST
CONSULTANTS IN DEVELOPING A SITE SPECIFIC CONSTRUCTION DOCUMENT SET
PER THE LEASE REQUIREMENTS. ALL ITEMS WITHIN THIS DOCUMENT,
INCLUDING BUT NOT LIMITED TO SIZING, QUANTITIES, LOCATIONS, AND
MANUFACTURERS SHALL CONFORM TO THE REQUIREMENTS SET FORTH IN THE
APPLICABLE TJX SPECIFICATIONS REFERENCED IN THE LEASE. ALL
EQUIPMENT, WIRING, PIPING, ETC. SHALL BE SIZED PER ACTUAL PROJECT
CONDITIONS AND APPLICABLE CODES AS ENFORCED BY THE AUTHORITY HAVING
JURISDICTION.
AutoCAD SHX Text
DESIGNER NOTE: DETAILS SHOWN ON THIS SHEET ARE FOR REFERENCE ONLY.
ACTUAL DETAILS SHALL BE PROVIDED FROM THE TJX C-SET SHEET
'C7'.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ALARM SYSTEM ENCLOSURE PANEL "OCTO-INPUTS / RELAYS" 16"H x 16"W x
3.5"D
AutoCAD SHX Text
ALARM SYSTEM CONTROL PANEL (PRIMARY) 16"H x 16"W x 3.5"D
AutoCAD SHX Text
ALARM SYSTEM CONTROL PANEL (PRIMARY) 16"H x 16"W x 3.5"D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
THIS SHEET IS PART OF THE CONSTRUCTION DOCUMENTS, OTHER SHEETS
INCLUDING SPECIFICATIONS APPLY. INFORMATION SHOWN HEREON IS
SCHEMATIC IN NATURE AND NOT TO BE USED AS A SHOP DRAWING;
THEREFORE, INCLUDE ALL MODIFICATIONS REQUIRED TO CONFORM TO SITE
CONDITIONS AND THE EQUIPMENT AND MATERIAL USED. VERIFY LOCATIONS
AND DIMENSIONS OF ALL ARCHITECTURAL AND STRUCTURAL ELEMENTS AS
SHOWN ON THEIR RESPECTIVE DOCUMENTS, THESE ELEMENTS ARE SHOWN FOR
REFERENCE AND SHALL BE VERIFIED PRIOR TO CONSTRUCTION AND THE
ENGINEER ASSUMES NO LIABILITY FOR THE ACCURACY OF THESE ELEMENTS.
NO DESIGN RESPONSIBILITY IS ASSUMED FOR ANY PORTION OF THE WORK
THAT THE PROFESSIONAL ENGINEER HAS NOT SIGNED AND SEALED PER STATE
REQUIREMENTS.
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT LOGO AND
ADDRESS
AutoCAD SHX Text
THIS SPACE RESERVED FOR SITE SPECIFIC CONSULTANT SEAL AND
SIGNATURE
AutoCAD SHX Text
ELECTRICAL DETAILS
NOTE TO DESIGNER: EF-4 TO BE INCLUDED ONLY IF WALL BETWEEN
ELECTRICAL ROOM AND PROCESSING IS FULL HEIGHT - COORDINATE WITH
C-SET
NOTE TO DESIGNER: INCLUDE MECHANICAL VENTILATION TABLE SHOWING
COMPLIANCE WITH ALL APPLICABLE CODES NOTE TO DESIGNER:
ADJUST OUTSIDE AIR VALUES BASED ON VENTILATION REQUIREMENTS
º
º
½
NOTE TO DESIGNER: EQUIPMENT CAPACITIES INDICATED FOR REFERENCE
ONLY. ACTUAL EQUIPMENT SELECTIONS SHALL BE BASED ON TJX
SPECIFICATIONS AND HVAC LOAD CALCULATIONS
NOTE TO DESIGNER: REFER TO TJX OUTLINED SPECIFICATIONS ON AREAS
WHERE ELECTRIC HEAT IS REQUIRED. ADDITIONALLY, PROVIDE REQ'D HEAT
PER CLIMATE ZONES.
AutoCAD SHX Text
PROVIDE BURGLAR BARS IN ALL ROOF AND EXTERIOR WALL PENETRATIONS,
INCLUDING PENETRATIONS REQUIRED FOR ROOF MOUNTED EQUIPMENT LARGER
THAN 12"x12" OR 12"~. BARS SHALL BE 1/2" STEEL RODS @6" O.C. WELDED
IN PLACE AT ALL INTERSECTIONS AND SIDES OF OPENINGS. BARS SHALL BE
SECURELY EMBEDDED IN CONCRETE OR WELDED STEEL FRAMES AS REQUIRED BY
CONSTRUCTION OF ROOF AND/OR WALL.
AutoCAD SHX Text
G.C. TO PROVIDE AND INSTALL BURGLAR BARS OVER EXISTING RTU CURBS
WHERE EQUIPMENT IS TO BE REMOVED, IN ADDITION TO ABOVE NOTED
REQUIREMENT. REFER TO DEMOLITION PLAN FOR CAPPED AND SEALED
EQUIPMENT CURBS.
AutoCAD SHX Text
NOVAR INTERFACE SUMMARY (REFER TO TJX SPECIFICATIONS FOR DETAIL
INFORMATION.) 1. GENERAL CONTRACTOR GENERAL CONTRACTOR 1.1. PROVIDE
4'X8' PLYWOOD BACKBOARD IN ELECTRIC ROOM FOR NOVAR TO MOUNT THEIR
EQUIPMENT. PROVIDE 4'X8' PLYWOOD BACKBOARD IN ELECTRIC ROOM FOR
NOVAR TO MOUNT THEIR EQUIPMENT. PHONE AND ETHERNET JACKS FOR THE
NOVAR CONTROLLER WILL ALSO BE LOCATED ON THIS BOARD BY SEPARATE TJX
VENDOR. 2. MECHANICAL CONTRACTOR MECHANICAL CONTRACTOR 2.1. MOUNT
2X4 J-BOX WITH CONDUIT (WIREMOLD IF EXPOSED IN FINISHED AREAS) AT
LOCATIONS MOUNT 2X4 J-BOX WITH CONDUIT (WIREMOLD IF EXPOSED IN
FINISHED AREAS) AT LOCATIONS DESIGNATED ON NOVAR CONTROLS SITE
SPECIFIC PLANS. THE J-BOXES ARE SHALL BE MOUNTED 60" AFF EXCEPT IN
FITTING ROOM LOCATIONS WHERE J-BOXES SHALL BE MOUNTED 84" AFF. ON
SALES FLOOR J-BOXES SHALL BE MOUNTED ON BACK SIDE OF COLUMNS WHEN
VIEWED FROM FRONT OF STORE. 2.2. PROVIDE PERMANENT STRANDED 18/2
AWG NON SHIELDED CABLE (18/8 IF THE RTU IS EQUIPPED WITH PROVIDE
PERMANENT STRANDED 18/2 AWG NON SHIELDED CABLE (18/8 IF THE RTU IS
EQUIPPED WITH A CO2 SENSOR) FROM EACH ROOFTOP UNIT TO THE NOVAR ETM
(T-STAT) LOCATION SHOWN ON THE NOVAR PLAN THAT SUPERSEDES ANY
MECHANICAL PLAN LOCATIONS. ALL CONTROL DEVICES SHALL BE
APPROPRIATELY IDENTIFIED AND PERMANENTLY ATTACHED. 2.3. TEMPORARY
THERMOSTATS SHALL BE INSTALLED NEAR THE ROOFTOP UNITS. TEMPORARY
THERMOSTATS SHALL BE INSTALLED NEAR THE ROOFTOP UNITS. 2.4. HVAC
EQUIPMENT SHALL HAVE HAD MANUFACTURER'S RECOMMENDED STARTUP
PROCEDURE HVAC EQUIPMENT SHALL HAVE HAD MANUFACTURER'S RECOMMENDED
STARTUP PROCEDURE PERFORMED AND BE OPERATIONAL IN ALL MODES BEFORE
ARRIVAL OF NOVAR CONTROLS REPRESENTATIVE FOR FINAL NOVAR
INSTALLATION. 2.5. IN COLD WEATHER THE CONTRACTOR SHALL PROVIDE
TEMPORARY THERMOSTAT TO OPERATE THE IN COLD WEATHER THE CONTRACTOR
SHALL PROVIDE TEMPORARY THERMOSTAT TO OPERATE THE HEATERS IN
RECEIVING. 2.6. BASEBOARD HEATERS SHALL BE FACTORY EQUIPPED WITH
INTEGRAL THERMOSTATS AND INSTALLED BASEBOARD HEATERS SHALL BE
FACTORY EQUIPPED WITH INTEGRAL THERMOSTATS AND INSTALLED IN ALL
OFFICES, LOUNGE, RESTROOMS, AND SECURITY OFFICES WITH AT LEAST ONE
EXTERIOR WALL WHEN LOCATED IN CLIMATE ZONES 4 AND 5. THE CIRCUITING
FOR BASEBOARD HEATING SHALL BE THROUGH GE RELAY PANEL. 2.7.
ELECTRIC VESTIBULE HEATERS SHALL BE FACTORY EQUIPPED WITH LOW
VOLTAGE CONTROLS, ELECTRIC VESTIBULE HEATERS SHALL BE FACTORY
EQUIPPED WITH LOW VOLTAGE CONTROLS, INCLUDING BUT NOT LIMITED TO
THE FOLLOWING: POWER CONTACTORS, LOW VOLTAGE TRANSFORMER, AND TWO
WIRE FIELD TERMINATION CONTROL POINT. 3. ELECTRICAL CONTRACTOR
ELECTRICAL CONTRACTOR 3.1. REFER TO ELECTRICAL PLANS FOR
REQUIREMENTS AND COORDINATION INFORMATIONREFER TO ELECTRICAL PLANS
FOR REQUIREMENTS AND COORDINATION INFORMATION
AutoCAD SHX Text
PROVIDE EQUIPMENT INDICATED ON THE DRAWINGS, AND AS REQUIRED FOR A
COMPLETE FUNCTIONING SYSTEM. DEFINITIONS: FURNISH MEANS TO SUPPLY
AND DELIVER TO PROJECT SITE, READY FOR INSTALLATION. INSTALL MEANS
TO FURNISH MEANS TO SUPPLY AND DELIVER TO PROJECT SITE, READY FOR
INSTALLATION. INSTALL MEANS TO MEANS TO SUPPLY AND DELIVER TO
PROJECT SITE, READY FOR INSTALLATION. INSTALL MEANS TO INSTALL
MEANS TO MEANS TO PLACE IN POSITION AND MAKE CONNECTIONS FOR
SERVICE OR USE. PROVIDE MEANS TO FURNISH AND INSTALL, COMPLETE
PROVIDE MEANS TO FURNISH AND INSTALL, COMPLETE MEANS TO FURNISH AND
INSTALL, COMPLETE AND READY FOR INTENDED USE. WARRANTY: PROVIDE
LABOR AND MATERIALS TO REPAIR OR REPLACE DEFECTIVE PARTS AND
MATERIALS AS REQUIRED PROVIDE LABOR AND MATERIALS TO REPAIR OR
REPLACE DEFECTIVE PARTS AND MATERIALS AS REQUIRED FOR ONE YEAR
AFTER SUBSTANTIAL COMPLETION OR OWNER ACCEPTANCE OF THE COMPLETED
PROJECT. PROVIDE A SEPARATE LINE ITEM DEDUCT AMOUNT ON THE PROPOSAL
FORM TO DELETE WARRANTY SERVICE, AT THE OWNER'S OPTION.
COORDINATION: COORDINATE WITH THE WORK OF OTHER TRADES, EQUIPMENT
FURNISHED BY OTHERS, REQUIREMENTS OF THE COORDINATE WITH THE WORK
OF OTHER TRADES, EQUIPMENT FURNISHED BY OTHERS, REQUIREMENTS OF THE
OWNER, AND WITH THE CONSTRAINTS OF THE EXISTING CONDITIONS OF THE
PROJECT SITE. DUCT DIMENSIONS: UNLESS OTHERWISE NOTED, DUCT
DIMENSIONS ON THE DRAWINGS ARE INSIDE CLEAR DIMENSIONS. UNLESS
OTHERWISE NOTED, DUCT DIMENSIONS ON THE DRAWINGS ARE INSIDE CLEAR
DIMENSIONS. SHEETMETAL DUCTWORK: PROVIDE SHEETMETAL DUCTWORK
FABRICATED AND INSTALLED IN ACCORDANCE WITH ASHRAE PROVIDE
SHEETMETAL DUCTWORK FABRICATED AND INSTALLED IN ACCORDANCE WITH
ASHRAE AND SMACNA STANDARDS, FOR 1" W.G. PRESSURE CLASS, SEAL CLASS
"A". SHEETMETAL SHALL BE GALVANIZED SHEET STEEL OF LOCK FORMING
QUALITY, WITH G90 ZINC COATING. SHEET STEEL SHALL COMPLY WITH ASTM
A653 STANDARD SPECIFICATION FOR STEEL SHEETMETAL, ZINC COATED
(GALVANIZED) OR ZINC-IRON ALLOY-COATED (GALVANNEALED) BY THE HOT
DIP PROCESS, AND A924 STANDARD SPECIFICATION FOR GENERAL
REQUIREMENTS FOR SHEET, METALLIC-COATED BY THE HOT DIP PROCESS. ALL
ANGLE IRON USED FOR SUPPORT SHALL BE GALVANIZED. CONNECTIONS TO
WALLS OR FLOOR SHALL BE AIR TIGHT WITH ANGLE IRON AND CAULKING.
SEAL ALL DUCT SEAMS, TRANSVERSE AND LONGITUDINAL, AIR TIGHT.
PROVIDE TURNING VANES AT ALL 90º ELBOWS. ELBOWS. ROUND SHEETMETAL
DUCT: PROVIDE SPIRAL SEAM (ALL SIZES) OR SNAP LOCK (DUCT SIZES UP
TO 10" ABOVE CEILINGS) PROVIDE SPIRAL SEAM (ALL SIZES) OR SNAP LOCK
(DUCT SIZES UP TO 10" ABOVE CEILINGS) GALVANIZED STEEL COMPLYING
WITH SMACNA STANDARDS. SPIRAL SEAM DUCTWORK SHALL HAVE SMACNA SEAM
TYPE RL-1. DUCTWORK FITTING AND ACCESSORIES: ALL FITTINGS AND
ACCESSORIES SHALL BE FABRICATED AND INSTALLED IN ALL FITTINGS AND
ACCESSORIES SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH
THE LATEST PUBLISHED STANDARDS FROM SMACNA AND ASHRAE. FLEXIBLE
DUCT: PROVIDE FACTORY ASSEMBLED CLASS 1 AIR DUCT (UL 181) WITH 1"
THICK 1 PCF FIBERGLASS INSULATION AND PROVIDE FACTORY ASSEMBLED
CLASS 1 AIR DUCT (UL 181) WITH 1" THICK 1 PCF FIBERGLASS INSULATION
AND REINFORCED OUTER PROTECTIVE COVER/VAPOR BARRIER. FLEXIBLE DUCT
SHALL MEET NFPA 90A WITH FLAME SPREAD UNDER 25, SMOKE DEVELOPED
UNDER 50, AND SHALL BE RATED FOR MINIMUM 2" W.G. PRESSURE AND 0 TO
250ºF F TEMPERATURE. PROVIDE SCREW-OPERATED METAL ADJUSTABLE
CLAMPING DEVICES. USE TWIST-LOCK TAP COLLARS AT CONNECTIONS INTO
SHEETMETAL DUCTWORK. MAXIMUM EXTENDED LENGTH OF FLEXIBLE DUCT SHALL
NOT EXCEED 4 FEET. EXPOSED DUCTWORK: EXPOSED DUCTWORK SHALL BE
CLEANED OF DEBRIS AND OIL, THEN WIPED DOWN WITH VINEGAR EXPOSED
DUCTWORK SHALL BE CLEANED OF DEBRIS AND OIL, THEN WIPED DOWN WITH
VINEGAR OR OTHER SURFACE PREPARING CHEMICAL TO PREPARE DUCT FOR
PAINT. DUCT SEALANT: PROVIDE POLYMERIC RUBBER TYPE SEALANT FOR USE
ON BOTH INTERIOR LOCATED DUCTWORK AND PROVIDE POLYMERIC RUBBER TYPE
SEALANT FOR USE ON BOTH INTERIOR LOCATED DUCTWORK AND DUCTWORK
EXPOSED TO OUTDOOR CONDITIONS. SEALER SHALL HAVE HIGH BONDING
STRENGTH FOR SURE, FIRST TIME SEALING OF JOINTS IN LOW, MEDIUM, AND
HIGH PRESSURE DUCT SYSTEMS. SEALER SHALL BE HIGH IN SOLID CONTENT.
PROVIDE A TWO PART TAPE SEALING SYSTEM, CONSISTING OF WOVEN FIBER
TAPE IMPREGNATED WITH A GYPSUM MINERAL COMPOUND, AND A MODIFIED
ACRYLIC/SILICONE ACTIVATOR THAT REACTS EXOTHERMICALLY WITH THE
TAPE. TWO PART TAPE SEALING SYSTEM MUST BE RATED FOR BOTH INDOOR
AND OUTDOOR APPLICATION. TAPE SHALL NOT CONTAIN ASBESTOS. DUCT
INSULATION (ALL ROUND SUPPLY DUCT AND ROUND RETURN DUCT ABOVE
CEILING): PROVIDE MINIMUM 1-1/2" THICK PROVIDE MINIMUM 1-1/2" THICK
BLANKET TYPE FIBERGLASS INSULATION COMPLYING WITH ASTM C-553, TYPE
II, WITH FACTORY APPLIED KRAFT BONDED TO ALUMINUM FOIL, REINFORCED
WITH FIBERGLASS VAPOR BARRIER/JACKET. JACKET SHALL CONFORM TO ASTM
C-1136, TYPE II. INSTALLED R VALUE SHALL BE 4.2 OR HIGHER WITH A
0.75 PCF DENSITY. DUCT LINER (ALL RECTANGULAR SUPPLY AND RETURN
DUCT): PROVIDE MINIMUM 1" THICK, 3 PCF DENSITY, NEOPRENE PROVIDE
MINIMUM 1" THICK, 3 PCF DENSITY, NEOPRENE COATED, LONG TEXTILE
FIBER TYPE DUCT LINER, WITH COATING ON THE AIR STREAM SIDE
CONFORMING TO NFPA 90A. DUCT LINER ADHESIVE SHALL BE AS RECOMMENDED
BY DUCT LINER MANUFACTURER, AND SHALL COMPLY WITH ASTM C-916. DUCT
LINER FASTENERS SHALL COMPLY WITH SMACNA "HVAC DUCT CONSTRUCTION
STANDARDS", LATEST EDITION. THERMAL CONDUCTIVITY SHALL BE EQUAL TO
OR LESS THAN 0.26 AT 75°F. ROUND VOLUME DAMPERS: PROVIDE MINIMUM 20
GAUGE GALVANIZED STEEL FRAME AND BLADES, MINIMUM 3/8" SQUARE
PROVIDE MINIMUM 20 GAUGE GALVANIZED STEEL FRAME AND BLADES, MINIMUM
3/8" SQUARE STEEL AXLE, MOLDED SYNTHETIC BEARINGS, WITH LOCKING
POSITION REGULATOR. REGULATOR SHALL BE POSITIONED WITH SHEETMETAL
BRACKET BEYOND DUCT COVERING. WHERE POSITIONING REGULATOR IS NOT
ACCESSIBLE, PROVIDE COUPLING AND EXTENSION ROD WITH REGULATOR FOR
CEILING OR WALL INSTALLATION, AS REQUIRED. RECTANGULAR VOLUME
DAMPERS: PROVIDE MINIMUM 16 GAUGE GALVANIZED STEEL CHANNEL FRAME,
16 GAUGE GALVANIZED PROVIDE MINIMUM 16 GAUGE GALVANIZED STEEL
CHANNEL FRAME, 16 GAUGE GALVANIZED STEEL BLADES, MINIMUM ½"
HEXAGONAL AXLE, MOLDED SYNTHETIC BEARINGS, WITH 3/8" SQUARE PLATED
STEEL CONTROL " HEXAGONAL AXLE, MOLDED SYNTHETIC BEARINGS, WITH
3/8" SQUARE PLATED STEEL CONTROL SHAFT. LINKAGES SHALL BE CONCEALED
IN THE FRAME. OPERATING SHAFT SHALL EXTEND BEYOND FRAME AND DUCT TO
A LOCKING QUADRANT WITH ADJUSTABLE LEVER. MAXIMUM BLADE WIDTH SHALL
NOT EXCEED 6". DUCT TURNING VANES: PROVIDE FABRICATED TURNING VANES
AND VANE RUNNERS, CONSTRUCTED IN ACCORDANCE WITH PROVIDE FABRICATED
TURNING VANES AND VANE RUNNERS, CONSTRUCTED IN ACCORDANCE WITH
SMACNA "HVAC DUCT CONSTRUCTION STANDARDS". PROVIDE TURNING VANES
CONSTRUCTED OF CURVED BLADES, SUPPORTED WITH BARS PERPENDICULAR TO
BLADES, AND SET INTO SIDE STRIPS SUITABLE FOR MOUNTING IN DUCTWORK.
FOLLOW SMACNA GUIDELINES FOR SPACING SUPPORT, AND CONSTRUCTION. ALL
BLADES SHALL BE DOUBLE THICKNESS AIRFOIL TYPE. FLEXIBLE DUCT
CONNECTORS: PROVIDE U.L. LABELED 30 OUNCE NEOPRENE COATED
FIBERGLASS FABRIC DUCT PROVIDE U.L. LABELED 30 OUNCE NEOPRENE
COATED FIBERGLASS FABRIC DUCT CONNECTORS AT DUCT CONNECTIONS TO ALL
VIBRATING EQUIPMENT. DUCT ACCESS DOORS: PROVIDE HINGED ACCESS DOORS
IN DUCTWORK WHERE REQUIRE