M. R. Salem Mechanical Engineering Department, Faculty of Engineering at Shoubra, Benha University, 108 Shoubra Street, Cairo 11629, Egypt e-mails: [email protected]; [email protected] R. K. Ali Mechanical Engineering Department, Faculty of Engineering at Shoubra, Benha University, 108 Shoubra Street, Cairo 11629, Egypt e-mail: [email protected] R. Y. Sakr Mechanical Engineering Department, Faculty of Engineering at Shoubra, Benha University, 108 Shoubra Street, Cairo 11629, Egypt e-mail: [email protected] K. M. Elshazly Mechanical Engineering Department, Faculty of Engineering at Shoubra, Benha University, 108 Shoubra Street, Cairo 11629, Egypt e-mail: [email protected] Effect of c-Al 2 O 3 /Water Nanofluid on Heat Transfer and Pressure Drop Characteristics of Shell and Coil Heat Exchanger With Different Coil Curvatures This study presents an experimental investigation of the characteristics of convective heat transfer in horizontal shell and coil heat exchangers in addition to the friction factor for fully developed flow through their helically coiled tube (HCT). Five heat exchangers of counterflow configuration were constructed with different HCT-curvature ratios (d) and tested at different mass flow rates and inlet temperatures of c-Al 2 O 3 /water nanofluid in the HCT. The tests were performed for c-Al 2 O 3 with average size of 40 nm and par- ticles volume concentration (u) from 0% to 2% for 0:0392 d 0:1194. Totally, 750 test runs were performed from which the HCT-average Nusselt number ( Nu t ) and fanning friction factor (f c ) were calculated. Results illustrated that Nu t and f c of nanofluids are higher than those of the pure water at same flow condition, and this increase goes up with the increase in u. When u increases from 0% to 2%, the average increase in Nu t is of 59.4–81% at lower and higher HCT-Reynolds number, respectively, and the average increase in f c is of 25.7% and 27.4% at lower and higher HCT-Reynolds number, respec- tively, when u increases from 0% to 2% for d ¼ 0:1194. In addition, results showed that Nu t and f c increase by increasing coil curvature ratio. When d increases from 0.0392 to 0.1194 for u ¼ 2%, the average increase in Nu t is of 130.2% and 87.2% at lower and higher HCT-Reynolds number, respectively, and a significant increase of 18.2–7.5% is obtained in the HCT-fanning friction factor at lower and higher HCT-Reynolds number, respectively. Correlations for Nu t and f c as a function of the investigated parameters are obtained. [DOI: 10.1115/1.4030635] Keywords: heat exchanger, nanofluid, helically coiled tube, curvature, friction 1 Introduction Most of heat transfer enhancement methods are limited by inherent restriction of thermal conductivity of the conventional fluids that are required for high-performance cooling or heating processes [13]. One of the ways to overcome this problem is to replace the conventional fluids with some advanced fluids with higher thermal conductivities. The key idea is to exploit the very high thermal conductivities of solid particles that can be several hundreds of times greater than all of the conventional fluids combined [4]. In most of the industrial applications, increasing the thermal performance of heat exchangers affects directly on energy, mate- rial, and cost savings. The major challenge in designing heat exchangers is to make the equipment compact and achieve a high heat transfer rate with minimum pumping power [5]. Coiled tubes of helical shape are one of the enhancement techniques that are widely used as heat exchangers and have applications in various industries: chemical, biological, petrochemical, mechanical, bio- medical, and others. This wide using of HCTs is because they are compact and promote good mixing of the fluids that increasing the heat transfer coefficients. In addition, this equipment is low cost and of easy construction and maintenance [57]. Due to the extensive application of the HCTs in these fields, knowledge about the heat transfer and pressure drop characteristics is very important. There are several studies in the literature concerning the friction losses due to flowing base fluids in HCTs [817]. These studies reported that an increase in the flow resistance compared with straight tubes. This is due to the centrifugal force caused by the pipe curvature. Correlations were obtained as a function of Re t , d, and Dean number (De). De is a dimensionless group that measures the ratio of the geometric average of inertial and centrifugal forces to the viscous forces, defined according to Eq. (1) in which Re t is the HCT-Reynolds number based on axial flow velocity. Since the secondary flow is induced by centrifugal forces and their interac- tion primarily with viscous forces, De becomes a general measure of the magnitude of the secondary flow.d is a dimensionless coil curvature ratio; it is the ratio of the inner diameter of the HCT (d t;i ) to the mean diameter of the coil curvature (D c ) De ¼ Re t d 0:5 (1) Kumar et al. [18] carried out an experiment on a shell and coil heat exchanger using nonmetallic sisal nanofluid (u 0.5%). They reported that the overall heat transfer coefficient increased with increasing u. It should be noted that their study did not account the effect of d in calculation. Huminic and Huminic [19] numerically studied the heat transfer behavior of CuO/water and TiO 2 /water nanofluids flowing through a counterflow double tube helical heat exchanger under laminar flow condition. The average Contributed by the Heat Transfer Division of ASME for publication in the JOURNAL OF THERMAL SCIENCE AND ENGINEERING APPLICATIONS. Manuscript received May 7, 2014; final manuscript received March 31, 2015; published online June 9, 2015. Assoc. Editor: Mehmet Arik. Journal of Thermal Science and Engineering Applications DECEMBER 2015, Vol. 7 / 041002-1 Copyright V C 2015 by ASME Downloaded From: http://thermalscienceapplication.asmedigitalcollection.asme.org/ on 06/09/2015 Terms of Use: http://asme.org/terms

Effect of γ-Al2O3/Water Nanofluid on Heat transfer and Pressure Drop Characteristics of Shell and Coil Heat Exchanger with Different Coil Curvatures

  • Upload
    benha

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

M. R. SalemMechanical Engineering Department,

Faculty of Engineering at Shoubra,

Benha University,

108 Shoubra Street, Cairo 11629, Egypt

e-mails: [email protected];

[email protected]

R. K. AliMechanical Engineering Department,

Faculty of Engineering at Shoubra,

Benha University,

108 Shoubra Street, Cairo 11629, Egypt

e-mail: [email protected]

R. Y. SakrMechanical Engineering Department,

Faculty of Engineering at Shoubra,

Benha University,

108 Shoubra Street, Cairo 11629, Egypt

e-mail: [email protected]

K. M. ElshazlyMechanical Engineering Department,

Faculty of Engineering at Shoubra,

Benha University,

108 Shoubra Street, Cairo 11629, Egypt

e-mail: [email protected]

Effect of c-Al2O3/Water Nanofluidon Heat Transfer and PressureDrop Characteristics of Shelland Coil Heat Exchanger WithDifferent Coil CurvaturesThis study presents an experimental investigation of the characteristics of convectiveheat transfer in horizontal shell and coil heat exchangers in addition to the friction factorfor fully developed flow through their helically coiled tube (HCT). Five heat exchangersof counterflow configuration were constructed with different HCT-curvature ratios (d)and tested at different mass flow rates and inlet temperatures of c-Al2O3/water nanofluidin the HCT. The tests were performed for c-Al2O3 with average size of 40 nm and par-ticles volume concentration (u) from 0% to 2% for 0:0392 � d � 0:1194. Totally, 750test runs were performed from which the HCT-average Nusselt number (Nut) and fanningfriction factor (fc) were calculated. Results illustrated that Nut and fc of nanofluids arehigher than those of the pure water at same flow condition, and this increase goes upwith the increase in u. When u increases from 0% to 2%, the average increase in Nut isof 59.4–81% at lower and higher HCT-Reynolds number, respectively, and the averageincrease in fc is of 25.7% and 27.4% at lower and higher HCT-Reynolds number, respec-tively, when u increases from 0% to 2% for d ¼ 0:1194. In addition, results showed thatNut and fc increase by increasing coil curvature ratio. When d increases from 0.0392 to0.1194 for u ¼ 2%, the average increase in Nut is of 130.2% and 87.2% at lower andhigher HCT-Reynolds number, respectively, and a significant increase of 18.2–7.5% isobtained in the HCT-fanning friction factor at lower and higher HCT-Reynolds number,respectively. Correlations for Nut and fc as a function of the investigated parameters areobtained. [DOI: 10.1115/1.4030635]

Keywords: heat exchanger, nanofluid, helically coiled tube, curvature, friction

1 Introduction

Most of heat transfer enhancement methods are limited byinherent restriction of thermal conductivity of the conventionalfluids that are required for high-performance cooling or heatingprocesses [1–3]. One of the ways to overcome this problem is toreplace the conventional fluids with some advanced fluids withhigher thermal conductivities. The key idea is to exploit the veryhigh thermal conductivities of solid particles that can be severalhundreds of times greater than all of the conventional fluidscombined [4].

In most of the industrial applications, increasing the thermalperformance of heat exchangers affects directly on energy, mate-rial, and cost savings. The major challenge in designing heatexchangers is to make the equipment compact and achieve a highheat transfer rate with minimum pumping power [5]. Coiled tubesof helical shape are one of the enhancement techniques that arewidely used as heat exchangers and have applications in variousindustries: chemical, biological, petrochemical, mechanical, bio-medical, and others. This wide using of HCTs is because they arecompact and promote good mixing of the fluids that increasing theheat transfer coefficients. In addition, this equipment is low costand of easy construction and maintenance [5–7]. Due to the

extensive application of the HCTs in these fields, knowledgeabout the heat transfer and pressure drop characteristics is veryimportant.

There are several studies in the literature concerning the frictionlosses due to flowing base fluids in HCTs [8–17]. These studiesreported that an increase in the flow resistance compared withstraight tubes. This is due to the centrifugal force caused by thepipe curvature. Correlations were obtained as a function of Ret, d,and Dean number (De). De is a dimensionless group that measuresthe ratio of the geometric average of inertial and centrifugal forcesto the viscous forces, defined according to Eq. (1) in which Ret isthe HCT-Reynolds number based on axial flow velocity. Since thesecondary flow is induced by centrifugal forces and their interac-tion primarily with viscous forces, De becomes a general measureof the magnitude of the secondary flow.d is a dimensionless coilcurvature ratio; it is the ratio of the inner diameter of the HCT(dt;i) to the mean diameter of the coil curvature (Dc)

De ¼ Retd0:5 (1)

Kumar et al. [18] carried out an experiment on a shell and coilheat exchanger using nonmetallic sisal nanofluid (u� 0.5%).They reported that the overall heat transfer coefficient increasedwith increasing u. It should be noted that their study did notaccount the effect of d in calculation. Huminic and Huminic [19]numerically studied the heat transfer behavior of CuO/water andTiO2/water nanofluids flowing through a counterflow double tubehelical heat exchanger under laminar flow condition. The average

Contributed by the Heat Transfer Division of ASME for publication in theJOURNAL OF THERMAL SCIENCE AND ENGINEERING APPLICATIONS. Manuscript receivedMay 7, 2014; final manuscript received March 31, 2015; published online June 9,2015. Assoc. Editor: Mehmet Arik.

Journal of Thermal Science and Engineering Applications DECEMBER 2015, Vol. 7 / 041002-1Copyright VC 2015 by ASME

Downloaded From: http://thermalscienceapplication.asmedigitalcollection.asme.org/ on 06/09/2015 Terms of Use: http://asme.org/terms

diameter of nanoparticles was about 24 nm and u varied between0.5% and 3%. Results showed that the use of nanofluids signifi-cantly enhances the convective heat transfer and the enhancementincreases with De and u.

Hashemi and Akhavan-Behabadi [20] experimentally studiedthe heat transfer and pressure drop characteristics of CuO (50 nm,0.5–2 wt.%)/oil nanofluid flow inside horizontal HCT under lami-nar flow with constant heat flux. Observations showed that theheat transfer coefficient as well as pressure drop is increased byusing nanofluid instead of base fluid. A maximum increase of18.7% in heat transfer coefficient for 10�Ret� 100 was obtainedfor the straight tube, while an increase of 30.4% was obtained forthe HCT, respectively, at the same Ret range.

Kannadasan et al. [21–24] experimentally studied the heattransfer and pressure drop of c-Al2O3 (0.1, 0.4, and 0.8 vol.%)/water nanofluid in HCT of shell and coil heat exchanger. Theexperiments were carried out using only one heat exchanger ge-ometry in horizontal and vertical positions, in addition to counterand parallel flow configurations for 1600<De< 2700 and5200<Ret < 8600. The findings indicated that there is no consid-

erable effect on Nut by changing flow configuration. It was shownalso a considerable increase in the convective heat transfer coeffi-cient and pressure drop with increasing u. Compared to using

pure water, an average increase in Nut and fc was of 45% and21%, respectively, in horizontal position, while the averageincrease in vertical position was of 49% and 25%, respectively.

Numerically and experimentally, Akbaridoust et al. [25] inves-tigated the pressure drop and the convective heat transfer behaviorof laminar CuO (68 nm, 0.1 and 0.2 vol. %)/water nanofluid flowin HCTs at a constant wall temperature. Results showed that moreenhanced heat transfer is observed for HCTs as d increased. Inaddition, utilization of base fluid in HCTs with greater d comparedto the use of nanofluid in straight tubes enhanced heat transfermore effectively. Aly [26] numerically studied the heat transferand pressure drop characteristics of c-Al2O3 (u � 2%)/waternanofluid flowing inside coiled tube-in-tube heat exchangers.Results showed that the heat transfer coefficient increases byincreasing u at the same Ret or De. Moreover, the friction factorincreases with the increase in d and pressure drop penalty isnegligible with increasing u.

Elsayed et al. [27] presented a numerical study to investigatethe combined effect of using helical coils and nanofluids on theheat transfer characteristics and pressure losses in turbulent flowregime. One uniformly heated HCT was used with k of 0.0266and d of 0.0524. Results showed that combining the effects ofc-Al2O3 nanoparticles and tube coiling enhance the heat transfercoefficient by up to 60% compared with that of pure water instraight tube at the same Ret. Also, results showed that the pres-sure drop in HCTs using c-Al2O3 (u ¼ 3%)/water nanofluid is sixtimes that of water in straight tubes (80% of the pressure dropincrease is due to nanoparticles addition).

The present study aims to investigate experimentally the effectof c-Al2O3 (u � 2%)/water nanofluid on characteristics of con-vective heat transfer in horizontal shell and coil heat exchangerswith different coil curvatures over a wide range of HCT-fluidoperating conditions. Present measurements are utilized to intro-duce experimental correlations for the HCT-average Nusselt num-ber and fanning friction factor as a function of HCT-Reynoldsnumber, Prandtl number, and coil curvature ratio.

2 Experimental Setup

The experimental facility employed in the present investigationconsists of heating and cooling units, shell and coil heatexchanger, pumps, measuring devices, valves, and the connectingpipes. As illustrated in Fig. 1, each circuit contains bypass lineand ball valve to control the mass flow rate directed to the heatexchanger. Two identical flow meters (1.7–18 l/min) were used tomeasure the volume flow rates directed to the test section. Twentyeight k-type thermocouples of 0.1 mm diameter were installed

within each test section to measure the temperatures. Four thermo-couples were inserted into the flow streams, at approximately60 mm from the heat exchanger ports, to measure the inlet andexit temperatures of the shell and HCT fluids.

Twenty thermocouples were used to measure the HCT wall sur-face temperatures. They were mounted at ten equally distanced(441.5 mm) positions on the HCT surface, with installing twothermocouples at each position on the outer and inner diameter ofthe coil. To achieve higher accuracy in calculation of flow rate,four thermocouples were installed at inlet and exit of flow metersto record the flow temperature. All thermocouples were connectedto a digital thermometer indicator with resolution of 0.1 �C to dis-play the thermocouples outputs. A digital differential pressuretransducer was employed for measuring the pressure drop of thepure water or c-Al2O3/water nanofluid across the HCT. Two iden-tical 1.5 hp rated power centrifugal pumps were installed to circu-late the hot and cold liquids. Flexible nylon and polyvinylchloride (PVC) tubes were used for all connections.

Figure 2 represents a photograph of the present setup. Two cy-lindrical containers of 50 l made of stainless steel (2 mm wallthickness) were employed as hot and cold fluid tanks. Each tankwas installed inside 2 mm thick galvanized steel tanks with 20 mmgap, which was injected by polyurethane spray foam insulation tominimize the heat loss or gain. An electric heater of 6 kW ratedpower was fixed horizontally at the bottom of the heating tank toheat the pure water or c-Al2O3/water nanofluid to the requiredtemperature. The heat was removed from the water in the coolingtank by two cooling units of 10.5 kW cooling capacity. Sometimesthe two cooling units operate in series, and in other times, in paral-lel manner to prevent thermal overloads. The operations of theelectric heater and the cooler were based on pre-adjusted digitalthermostats, which were used to keep constant temperatures of theliquids directed to both sides of the heat exchanger.

Five configurations of shell and coil heat exchanger were con-structed with different HCT-curvature ratios. Due to the variationof curvature ratio ðd ¼ dt;i=DcÞ, the coil pitch (pc) and conse-quently number of turns (N) are varied to sustain constant coil tor-sion ratio (k ¼ pc=pDc) of 0.0895. The dimensions of the coppertube used in each coil are 4.415 m lengths, 9.52 mm outer diame-ter, and 8.3 mm inner diameter. The characteristic dimensions ofthe different configurations are revealed in Table 1. A photographand schematic diagram of the shell and coil heat exchanger areshown in Fig. 3.

The shell of the heat exchangers was made of mild steel (2 mmwall thickness) and was formed as cylindrical shape. Two nipplesof same material and 4 mm wall thickness were welded on bothends of the shell. The inlet and exit ports of the shell where pipesof constant cross section (100 mm length and 50.8 mm internaldiameter) were welded to the shell. The distance between theseports centers and the neighboring shell end was 50 mm, whichmade the HCT partially block the opening as recommended byKupprn [28]. Ten holes of 1 mm diameter were made in the shellwall to pass the thermocouples to their positions on the HCT sur-face. The holes were drilled directly facing the positions of thethermocouples to provide the smallest length of the thermocouplesin the shell to minimize their effect on the shell flow. Moreover,outer surface of the shell was thermally isolated with thick insula-tion using a layer of each of ceramic fiber, asbestos rope, and glasswool. Finally, all equipments were assembled: the shell and coilheat exchanger, heating and cooling units, pumps, ball valves,connecting lines, and the measuring devices.

3 Nanofluids Preparation

Preparing stable suspension of nanoparticles in the base liquidwas the first step in applying nanofluids as a heat transferworking fluid. The particles used in the nanofluid experiments aregamma-alumina (c-Al2O3) nanopowders, supplied by Inframat

VR

Advanced Materials Corporation, Manchester, CT (99.99% purity,product code 26 N-0801 G, 40 nm average particle size with

041002-2 / Vol. 7, DECEMBER 2015 Transactions of the ASME

Downloaded From: http://thermalscienceapplication.asmedigitalcollection.asme.org/ on 06/09/2015 Terms of Use: http://asme.org/terms

surface area> 200 m2/g). The thermophysical properties of c-Al2O3 nanoparticles are revealed in Table 2.

The c-Al2O3/water nanofluid was prepared in this study withfour different nanoparticles volume concentrations of 0.5%, 1%,1.5%, and 2%. The dispersion of particles in water was done bymixing the required particle volume concentration in the meas-uring flask. Agitator bath generating 3450 rpm was switched onfor 18 hrs daily for two sequential days to get the uniform disper-sion and stable suspension. In addition, to achieve good mixingfor the nanofluid in the heating tank, the nanofluid was pumped inthe HCT for 2 hrs before beginning the experiments. Furthermore,the bypassed line tube was extended to the bottom of heating tank.This tube has closed end while the side surface has numeroussmall holes, which act as nozzles to avoid any settlement of nano-particles. It was observed with naked eyes that there was no sig-nificant settlement of nanoparticles for first six days of staticcondition of nanofluid. Nevertheless, settlement appeared gradu-ally from the seventh day and the complete settlement occurredafter 13 days. This is revealed in Fig. 4 for u ¼ 2%.

Of course, this is one of the disadvantages of nanofluids, but itshould be noted that the 13 days are in static conditions, and dur-ing operation there is no any settlement. In addition, it was seenthat after settlement, the remixing process is very easy andrequires smaller time and power to reproduce good mixture.

Fig. 1 Schematic diagram of the experimental apparatus

Fig. 2 A photograph of the experimental apparatus

Table 1 Characteristic dimensions of the used shell and coil heat exchangers

HCT no. Dc (mm) d pc (mm) itk Lsh (mm) Dsh;i (mm) Dsh;h (mm) N

1 69.5 0.1194 19.52 0.0895 505 271 205.1 20.212 105.0 0.0790 29.52 13.383 140.5 0.0591 39.52 10.004 176.0 0.0472 49.52 7.985 211.5 0.0392 59.52 6.64

Journal of Thermal Science and Engineering Applications DECEMBER 2015, Vol. 7 / 041002-3

Downloaded From: http://thermalscienceapplication.asmedigitalcollection.asme.org/ on 06/09/2015 Terms of Use: http://asme.org/terms

Additionally, there are surfactants that help in increasing the sus-pension period of nanoparticles. Here, they were not used becausethey affect the thermophysical properties of nanofluids and thepresent research aims to study the effect of using pure nanofluid.

4 Experimental Procedures and Data Reduction

The first step in collecting data from the system was to fill theheating tank with pure water or nanofluid, which was preparedwith the required nanoparticles concentration. The cooling tankwas filled with water from the local water supply. Then, theheater, the cooling units, and the pumps were turned on. Inlet tem-peratures of both sides of the heat exchanger were adjusted by

regulating the temperatures of the heating and cooling tanksthrough their thermostats. The flow rates were adjusted throughthe flow meters and the installed valves, which were regulated toobtain the required flow rates in the primary lines and the remain-der is bypassed to the tanks. The range of the operating conditionsis given in Table 3.

During the operation, the steady state condition is conductedwhen the maximum variation of 0:5 �C for each thermocouplereading within 20 min. It should be noted that for heat transfer cal-culations, the fluid properties of the shell and HCT sides were cal-culated at the bulk temperatures, Tsh;m and Tt;m, respectively.While for pressure drop calculations, the HCT water propertieswere calculated at the film temperature, Tf , as recommended bySchmidt [29]. The bulk and film temperatures are calculated asfollows:

Tsh;m ¼ Tsh;i þ Tsh;o

� �=2 (2)

Tt;m ¼ Tt;i þ Tt;o

� �=2 (3)

�Tt;s ¼P

Tt;s

20(4)

Tf ¼ Tt;m þ �Tt;s

� �=2 (5)

The inner surface temperature of the HCT wall was taken equal toouter surface due to very low conduction resistance of the tubewall. The water thermophysical properties were evaluated fromRemsburg [30]. For c-Al2O3/water nanofluid, the thermophysicalproperties were calculated using the following equations [31–34]:

knf ¼ kbf

knp þ 2kbf þ 2u knp � kbf

� �knp þ 2kbf � u knp � kbf

� �" #

þ 5� 104nCuqbfCpbf

ffiffiffiffiffiffiffiffiffiffiffiffiffijT

qnpdnp

s(6)

C ¼ 1722:3u� 134:63ð Þ � 6:04u� 0:4705ð ÞT (7)

n ¼ 0:0017 100uð Þ�0:0841(8)

Fig. 3 (a) A photograph and (b) schematic diagram of the testsection

Table 2 Properties of c-Al2O3 nanoparticles

Thermal conductivity(W=m �C)

Density(kg=m3)

Specific heat(J=kg �C)

36 3600 773

Fig. 4 Photographs of the observed nanoparticles settlement (u ¼ 2%)

Table 3 Range of operating conditions

Parameters Range or value

HCT-side nanofluid flow rate (l/min) 1.7–11.158HCT-side nanofluid inlet temperature (�C) 45, 55, 65Nanoparticles volume concentration (%) 0, 0.5, 1, 1.5, 2Shell-side water flow rate (l/min) 6.018Shell-side inlet temperature (�C) 20

041002-4 / Vol. 7, DECEMBER 2015 Transactions of the ASME

Downloaded From: http://thermalscienceapplication.asmedigitalcollection.asme.org/ on 06/09/2015 Terms of Use: http://asme.org/terms

lnf ¼lbf

1� u½ �2:5þ 5� 104nCuqbf

ffiffiffiffiffiffiffiffiffiffiffiffiffiitjT

qnpdnp

s(9)

qnf ¼ uqnp þ 1� uð Þqbf (10)

Cpnf ¼u qnpCpnp� �

þ 1� uð Þ qbfCpbf� �

qnf

(11)

Prnf ¼lnfCpnf

knf

(12)

The measurements of the flow rates and inlet and outlet tempera-tures of both streams of the heat exchanger were used to calculateheat transfer rates on the HCT and shell sides (Qt and Qsh) asfollows:

Qt ¼ _mtCpt Tt;i � Tt;o

� �(13)

Qsh ¼ _mshCpsh Tsh;o � Tsh;i

� �(14)

Without heat gain or loss from the heat exchanger, there is anenergy balance between the two streams (Qt ¼ Qsh). In the realexperiments, there would always be some discrepancy betweenthe two heat transfer rates. Therefore, the arithmetical average ofthe two, Qave, can be used as the heat load of the exchanger. Forall experimental tests, the heating and cooling loads calculatedfrom the hot and cold sides did not differ by more than 61:8%.

Qave ¼Qtj j þ Qshj j

2(15)

The heat load of the heat exchanger, Qave, was used to calculate

the average heat transfer coefficient for the HCT-side fluid, �ht,

and then the average Nusselt number for the HCT-side fluid, Nut,as follows:

Qave ¼ �htAt;i Tt;m � �Tt;s

� �(16)

Nut ¼�htdt;i

kt

(17)

HCT-Reynolds number can be written as follows:

Ret ¼4 _mt

pdt;ilt

(18)

The overall thermal conductance was calculated from the temper-ature data and flow rates using Eq. (19) as follows:

UoAt;o ¼Qave

DTL:M(19)

DTL:M ¼Tt;i � Tsh;o

� �� Tt;o � Tsh;i

� �ln

Tt;i � Tsh;o

Tt;o � Tsh;i

� � (20)

The fanning friction factor for the fluid in circulation inside theHCT, fc, was calculated with the following equation:

fc ¼DPcdt;i

2Ltqtu2¼

DPcp2qtd5t;i

32Lt _m2t

(21)

Daily and Harleman [35] reported that the developed region inHCTs may be along a distance equal to 50 diameters of the HCT.Also, Nigam et al. [36] presented that the fully developed regionin HCTs is formed after a distance equal to 30 diameters of theHCT. These values represent 5.64–9.4% of the total length of theHCTs used in the present study, which can be neglected and thefully developed profiles are confirmed.

5 Uncertainty Analyses

In general, the accuracy of the experimental results depends onthe accuracy of the individual measuring instruments and techni-ques. It should be noted that according to the manufacturer, uncer-tainty in the HCT outer and inner diameters is 60.01 mm, whichcan be neglected. The uncertainty in the measured coil and shelldimensions was assumed to be 60:5 mm; this was guessed quan-tity from meter scale. In addition, the uncertainty applied to thethermal properties of water was assumed to be 60.1%. The uncer-tainty is calculated based upon the root sum square combinationof the effects of each of the individual inputs as introduced byKline and McClintock [37]. For all experimental runs, the uncer-tainty in Ret was 61:7%. Also, the average uncertainty was 67%

in Nut and 63:7% in fc.

6 Results and Discussions

First, the experimental apparatus and procedures were validated

by comparing the results of Nut for water flowing through the

HCT with Nut reported from literature. From the literature review,it is obvious that there is lack in the correlations required to calcu-late the heat transfer coefficient for applied shell and coil heatexchangers. On the contrary, there are a number of correlations in

the literature for the Nut for water flowing through the HCT withisoflux and isothermal wall boundary conditions. Here, the present

experimental data for Nut were validated with the experimentaldata obtained by Rogers and Mayhew [12], and Xin and Ebadian[38]. In addition, another comparison of the experimental data forHCT-fanning friction factor with the results of White [39] andPrasad et al. [10] was performed. The results of these comparisonsare shown in Fig. 5. From this figure, it can be seen that the exper-imental results for both heat transfer and friction factor calcula-tions are in good agreement with previous studies.

6.1 Heat Transfer Results. A series of 750 experimentswere carried out on the five heat exchangers shown in Table 1,which were constructed with different coil curvature ratios. Theseconfigurations were tested at different mass flow rates and inlettemperatures for the HCT-side as presented in Table 2. Figure 6

illustrates Nut versus HCT-Reynolds number for 0 � u � 2% atTt;i ¼ 55 �C and d ¼ 0:0591 as a sample of the results.

It can be seen that Nut of nanofluids is higher than that of thebase fluid at same flow condition, and this enhancement increaseswith the increase in u. At lower and higher HCT-Reynolds num-

ber, the average increase in Nut is of 12.2% and 13.7%, respec-tively, at u ¼ 0:5% and of 59.4–81%, respectively, at u ¼ 2% ford ¼ 0:1194. While its corresponding average increase ford ¼ 0:0392 is of 22.8% and 14.3%, respectively, at u ¼ 0:5% and

Fig. 5 Validation of the experimental data for HCT (k ¼ 0:0895)

Journal of Thermal Science and Engineering Applications DECEMBER 2015, Vol. 7 / 041002-5

Downloaded From: http://thermalscienceapplication.asmedigitalcollection.asme.org/ on 06/09/2015 Terms of Use: http://asme.org/terms

of 81–74.1%, respectively, at u ¼ 2%. This shows that enhancingheat transfer rates through using nanofluids as a thermal-fluid me-dium can be used to overcome poor heat transfer performance ofpure water. Besides the enhanced thermal conductivity of nano-fluids, the interactions and Brownian motion of nanoparticles andthe resulting disturbance of the boundary layer may be responsiblefor the observed enhancement of heat transfer coefficients ofnanofluids.

The influence of coil curvature on the thermal performance ofthe heat exchanger is studied for 0:0392 � d � 0:1194. A sampleof the results is shown in Fig. 7 for u ¼ 1% and Tt;i ¼ 55 �C.

It is obvious that increasing coil curvature ratio increases theHCT-average Nusselt number. At lower and higher HCT-Reynolds number, the average increase in Nut is of 133.3% and77.4%, respectively, at u ¼ 0:5%, and of 130.2% and 87.2,respectively, at u ¼ 2%, when the coil curvature ratio increasesfrom 0.0392 to 0.1194. This can be attributed to the increase inthe centrifugal force with higher coil curvature ratio, which indu-ces more effective secondary flow. Also, it is clear that increasingHCT-Reynolds number increases the HCT-average Nusselt

number at the same coil curvature ratio. This can be returned tothe effective secondary flow due to centrifugal force, whichincreases at higher Reynolds number.

The influence of HCT-side inlet temperature on the thermalperformance of the heat exchanger is studied for 0% � u � 2%and 0:0392 � d � 0:1194. A sample of the results is presented inFig. 8 for d ¼ 0:0472 and 0:1194 at u ¼ 1%.

For all tested heat exchangers, it is clear that as the HCT-side

inlet temperature increases, Nut goes down at same Reynoldsnumber. This can be attributed to the decrease in Prandtl numberwith increasing fluid temperature.

6.2 Pressure Drop Results. Experimental runs are carriedout to investigate the effects of nanoparticles loading, coil curva-ture, and HCT-fluid inlet temperature on friction factor insideHCT. The nanoparticles volume concentration is varied from 0%to 2% and the HCT-volume flow rate is varied from1:7to11:158l=min at coil inlet fluid temperature of 45 �C;55 �C; and 65 �C. The corresponding dimensionless parametersare 5646 � Ret � 54; 018 and 0:0392 � d � 0:1194. Figure 9presents a sample of the results for the effect of nanoparticlesloading for d ¼ 0:1194 and 0:0392 at Tt;i ¼ 55 �C. Figure 10shows a sample of the results for the effect of coil curvature ratiofor u ¼ 1% at Tt;i ¼ 55 �C.

It is seen from Fig. 9 that fc of nanofluids is higher than that ofthe base fluid at same flow condition, and this increase goes up asu increases. The average increase in fc is of 4.1–7.1% atu ¼ 0:5% and of 25.7–27.4% at u ¼ 2% for d ¼ 0:1194. Whileits corresponding average increase for d ¼ 0:0392 is of14.1–6.9% at u ¼ 0:5% and of 41.5–27.6% at u ¼ 2%. This canbe returned to high viscosity of the nanofluid, which increaseswith increasing the nanoparticles loading in the base fluid.

From Fig. 10, it can be seen that increasing the coil curvatureratio leads to significant increase in fc at the same Ret and Tt;i. Theaverage increase in fc is of 21.4–7.9% at u ¼ 0:5% and of

Fig. 6 Variation of HCT-average Nusselt number with HCT-Reynolds number at different nanoparticles concentrations(Tt;i ¼ 55 �C, d 5 0.0591)

Fig. 7 Variation of HCT-average Nusselt number with HCT-Reynolds number at different HCT-curvature ratios (u ¼ 1%;Tt;i ¼ 55 �C)

Fig. 8 Variation of HCT-average Nusselt number with HCT-Reynolds number at different HCT-inlet temperatures (u ¼ 1%):(a) d ¼ 0:0472 and (b) d ¼ 0:1194

Fig. 9 Variation of HCT-fanning friction factor with HCT-Reynolds number at different nanoparticles concentrations(Tt;i ¼ 55 �C): (a) d ¼ 0:1194 and (b) d ¼ 0:0392

Fig. 10 Variation of HCT-fanning friction factor with HCT-Reynolds number at different HCT-curvature ratios (u ¼ 1%;Tt;i ¼ 55 �C)

041002-6 / Vol. 7, DECEMBER 2015 Transactions of the ASME

Downloaded From: http://thermalscienceapplication.asmedigitalcollection.asme.org/ on 06/09/2015 Terms of Use: http://asme.org/terms

18.2–7.5% at u ¼ 2% when d increases from 0.0392 to 0.1194.This can be attributed to the increase in the centrifugal force,which induces more effective secondary flow. Furthermore, Fig.11 shows a sample of the results for the effect of HCT-side inlettemperature for u ¼ 1%; d ¼ 0:0591. It is clear that the effect ofTt;i on fc is nearly insignificant. This may be returned to the loweffect of viscous force compared with the higher centrifugal force,which is the dominant at HCT-Reynolds number.

7 Thermal Performance Index (TPI)

To be a successful heat transfer fluid, the rise in convectiveheat transfer given by the nanofluid should be higher than the risein pressure drop due to inclusion of nanoscale solid particles inthe base fluid. The TPI is determined using �ht ratio and thepressure drop ratios that are calculated using the values obtainedfor c-Al2O3 (40 nm)/water nanofluid and pure water, as follows[20]:

TPI ¼�ht;nf=�ht;bf

DPc;nf=DPc;bf

(22)

Over the studied range of HCT-Reynolds number, the averageTPI was calculated and the results are illustrated at differentHCT-side inlet temperatures in Fig. 12 for different coil curvatureratios and nanoparticles concentrations.

It obvious that the TPI is more than unity, which states that theenhancement in the heat transfer rate in the HCTs due to usingnanofluids is higher than the corresponding increase in the pres-sure drop. This assures the ability of using c-Al2O3 (40 nm)/waternanofluid in the HCTs with 0:5% � u � 2% as a compound heattransfer enhancement technique inside shell and coil heatexchangers instead of using HCTs only. Moreover, it is shown forall HCTs that increasing u enhances the TPI. Over the studiedrange of HCT-Reynolds number, the average value of TPI is of1.33 and 2.23 at u ¼ 0:5% and u ¼ 2%, respectively. Addition-ally, it is shown that the effect of coil curvature ratio is nearlyinsignificant on the TPI.

Furthermore, over the studied range of HCT-geometricalparameters and nanoparticles concentrations, the average TPI wascalculated and the results are illustrated for different HCT-sideflow rates in Fig. 13. From this figure, it is evident that increasingthe HCT-side flow rate slightly enhances the TPI at lower flowrate, and this enhancement goes down as HCT-side flow rateincreases. The average value of TPI is of 1.66 and 1.85 at _Vt of1.7 l/min and 11.16 l/min, respectively. Moreover, it is observedin Figs. 12 and 13 that increasing HCT-side inlet temperatureslightly enhances the TPI. The average value of TPI is of1.72–1.89 when Tt;i varies from 45 �C to 65 �C, respectively.

8 Correlations for Coiled Tube-Average Nusselt

Number and Fanning Friction Factor

Using the present experimental data, correlations were devel-oped to predict the HCT-average Nusselt number and fanning fric-tion factor. The HCT-average Nusselt number is correlated as afunction of HCT Reynolds, Prandtl numbers, coil curvature ratio,and nanoparticles volume fraction

Fig. 11 Variation of HCT-fanning friction factor with HCT-Reynolds number at different HCT-inlet temperatures (u ¼ 1%;d ¼ 0:0591)

Fig. 12 Variation of the average TPI with HCT-curvature ratio atdifferent nanoparticles concentrations: (a) Tt;i ¼ 65 �C, (b)Tt;i ¼ 55 �C, and (c) Tt;i ¼ 45 �C

Fig. 13 Variation of the average TPI with HCT-volume flow rateat different nanoparticles concentrations

Fig. 15 Comparison of experimental values for HCT-fanningfriction factor with that correlated by Eq. (24)

Fig. 14 Comparison of experimental values for HCT-averageNusselt number with that correlated by Eq. (23)

Journal of Thermal Science and Engineering Applications DECEMBER 2015, Vol. 7 / 041002-7

Downloaded From: http://thermalscienceapplication.asmedigitalcollection.asme.org/ on 06/09/2015 Terms of Use: http://asme.org/terms

Nut ¼ 0:0879 Re0:9833t Pr1:7421

t d0:5408u0:6376 (23)

Equation (23) is applicable for 5702 � Ret � 55; 101, 1155� Det � 18; 669, 1:92 � Prt � 3:9, 0:0392 � d � 0:1194, and0:005 � u � 0:02.

Another correlation was obtained for fanning friction factor inthe HCT within 5646 � Ret � 54; 018, 1139 � Det � 18; 267,0:0392 � d � 0:1194, and 0:005 � u � 0:02

fc ¼ 0:12724 Re�0:1651t d0:0986u0:1204 (24)

Comparisons of the present experimental HCT-average Nusseltnumber and fanning friction factor with those calculated by theproposed correlations are shown in Figs. 14 and 15. It is evidentthat the proposed correlations are in good agreement with thepresent experimental data. It is clearly seen that the data falls ofthe proposed equations within maximum deviation of 617:9%and 65:1% for Nut and fc, respectively.

9 Conclusions

The present work was carried out to investigate the heat transfercharacteristics in shell and coil heat exchanger, in addition to thepressure drop inside the HCTs. The investigated ranges are5702 � Ret � 55; 101, 1155 � Det � 18; 669, 1:92 � Prt � 3:9,0:0392 � d � 0:1194, and 0:005 � u � 0:02. From the study, itcould be concluded that:

• For all HCT-geometric variables and operating conditions,utilization of c-Al2O3 (40 nm)/water nanofluid with u � 2%instead of pure water in the HCTs results in remarkable heattransfer enhancement; this goes up as the nanoparticle con-centration increases. This phenomenon was considered as anattribution to thermal conductivity enhancement and Brown-ian motion effect.

• For same operating conditions, the HCT-geometrical varia-bles have a significant effect on the heat transfer. Accordingto the experimental data, increasing the coil curvature ratioleads to augmenting the heat transfer rate of base fluids aswell as nanofluids. This is because rapid developments ofsecondary flow enhance heat transfer.

• For all HCT-geometric variables, the operating conditions ofthe HCT-side affect directly on their thermal performance.For pure water as well as nanofluids experiments, the heattransfer rate goes up as the mass flow rate increases and asthe fluid inlet temperature decreases. This is because rapiddevelopments of secondary flow, turbulence level, andincreasing Prandtl number enhance heat transfer.

• For all geometric variables and operating conditions, utiliza-tion of c-Al2O3 (40 nm)/water nanofluid with u � 2% insteadof pure water in the HCTs results in remarkable HCT-frictionfactor increase which goes up as the nanoparticle concentra-tion increases. This is due to increasing nanofluid viscosity asthe nanoparticles loading increases.

• For same operating conditions, the HCT-geometrical varia-bles have a significant effect on the HCT-friction factor.According to the experimental data, increasing the coil curva-ture ratio leads to increase the HCT-friction factor for basefluids as well as nanofluids. This is because rapid develop-ments of secondary flow.

• For all HCT-geometric variables, the effect of HCT-fluidinlet temperature on the HCT-friction factor is nearly insig-nificant. This can be attributed to the lower effect of viscosityvariation compared with the centrifugal force.

• For all geometric variables and operating conditions, the TPIis more than unity, which states that the enhancement in theheat transfer rate in the HCTs due to using c-Al2O3/waternanofluid is higher than the corresponding increase in thepressure drop. Therefore, this assures the ability of using c-Al2O3 (40 nm)/water nanofluid in the HCTs with u � 2% as

a compound heat transfer enhancement technique inside shelland coil heat exchangers instead of using HCTs only.

• The TPI increases with increasing nanoparticles concentra-tion and HCT-side inlet temperature. Nevertheless, it isshown that the effect of coil curvature ratio is nearlyinsignificant.

• Correlations for the HCT-average Nusselt number and fan-ning friction factor as a function of the investigated parame-ters are obtained.

Nomenclature

A ¼ area (m2)Cp ¼ specific heat (J=kg �C)

d ¼ diameter (m)D ¼ diameter (m)f ¼ fanning friction factor�h ¼ average convection heat transfer coefficient (W=m2 �C)k ¼ thermal conductivity (W=m �C)L ¼ length (m)m ¼ mass (kg)_m ¼ mass flow rate (kg=s)

N ¼ number of turns of the HCTp ¼ pitch of HCT (m)P ¼ pressure (Pa)Q ¼ heat transfer rate (W)T ¼ temperature (�C)u ¼ mean axial velocity (m=s)U ¼ overall heat transfer coefficient (W=m2 �C)V ¼ volume (m3)

Dimensionless Groups

De ¼ Dean number, Retd0:5

Nu ¼ average Nusselt numberPr ¼ Prandtl numberRe ¼ Reynolds number

Greek Symbols

c ¼ gammaC ¼ modeling function was introduced in Eq. (6)d ¼ dimensionless coil curvature ratio, dt;i=Dc

D ¼ differentialitj ¼ Boltzmann constant,1:3807� 10�23 (J/K)k ¼ dimensionless pitch ratio (coil torsion), pc=pDc

l ¼ dynamic viscosity (kg=ms)n ¼ modeling function was introduced in Eq. (6)p ¼ Pi � a mathematical constant ffi 3:1416q ¼ density (kg=m3)u ¼ nanoparticles volume concentration

Superscripts and Subscripts

ave ¼ averagebf ¼ base fluidc ¼ coil/contactf ¼ film/fluid/core flowh ¼ hydraulici ¼ inner/inlet/internal

LM ¼ logarithmic meanm ¼ meannf ¼ nanofluidnp ¼ nanoparticleo ¼ out/outers ¼ surface

sh ¼ shellt ¼ tube

041002-8 / Vol. 7, DECEMBER 2015 Transactions of the ASME

Downloaded From: http://thermalscienceapplication.asmedigitalcollection.asme.org/ on 06/09/2015 Terms of Use: http://asme.org/terms

Acronyms and Abbreviations

Al2O3 ¼ alumina (aluminum oxide)CuO ¼ copper oxideHCT ¼ helically coiled tubePVC ¼ polyvinyl chlorideTiO2 ¼ titanium oxideTPI ¼ thermal performance indexvol: ¼ volumewt: ¼ weight

References[1] Choi, S. U. S., 1995, “Enhancing Thermal Conductivity of Fluid With Nano-

particles,” Developments and Applications of Non-Newtonian Flow, ASME,New York, FED–Vol. 231/MD–Vol. 66, pp. 99–105.

[2] Li, Q., and Xuan, Y., 2002, “Convective Heat Transfer and Flow Characteristicsof Cu–Water Nanofluid,” Sci. China, Ser. E: Technol. Sci., 45(4), pp. 408–416.

[3] Manca, O., Jaluria, Y., and Poulikakos, D., 2010, “Heat Transfer in Nano-fluids,” Adv. Mech. Eng., 2010, p. 380826.

[4] Das, S. K., Choi, S. U. S., Yu, W., and Pradeep, T., 2007, Nanofluids: Scienceand Technology, Wiley, Hoboken, NJ.

[5] Pimenta, T. A., and Campos, J. B. L. M., 2012, “Friction Losses of Newtonianand Non-Newtonian Fluids Flowing in Laminar Regime in a Helical Coil,”Exp. Therm. Fluid Sci., 36, pp. 194–204.

[6] Gnielinski, V., 1986, “Heat Transfer and Pressure Drop in Helically CoiledTubes,” 8th International Heat Transfer Conference, San Francisco, CA, Vol. 6,pp. 2847–2854.

[7] Zhao, Z., Wang, X., Che, D., and Cao, Z., 2011, “Numerical Studies on Flowand Heat Transfer in Membrane Helical-Coil Heat Exchanger and MembraneSerpentine-Tube Heat Exchanger,” Int. Commun. Heat Mass Transfer, 38(9),pp. 1189–1194.

[8] Austin, L. R., and Seader, J. D., 1973, “Fully Developed Viscous Flow inCoiled Circular Pipes,” AIChE J., 19(1), pp. 85–94.

[9] Mishra, P., and Gupta, N., 1979, “Momentum Transfer in Curved Pipes. 1.Newtonian Fluids,” Ind. Eng. Chem. Process Des. Dev., 18(1), pp. 130–137.

[10] Prasad, B. V. S. S. S., Das, D. H., and Prabhakar, A. K., 1989, “Pressure Drop,Heat Transfer and Performance of a Helically Coiled Tubular Exchanger,” HeatRecovery Syst. CHP, 9(3), pp. 249–256.

[11] Ali, S., 2001, “Pressure Drop Correlations for Flow Through Regular HelicalCoil Tubes,” Fluid Dyn. Res., 28(4), pp. 295–310.

[12] Rogers, G. F. C., and Mayhew, Y. R., 1964, “Heat Transfer and Pressure Lossin Helically Coiled Tubes With Turbulent Flow,” Int. J. Heat Mass Transfer,7(11), pp. 1207–1216.

[13] Austen, D. S., and Soliman, H. M., 1988, “Laminar Flow and Heat Transfer inHelically Coiled Tubes With Substantial Pitch,” Exp. Therm. Fluid Sci., 1(2),pp. 183–194.

[14] Yang, G., Dong, F., and Ebadian, M. A., 1995, “Laminar Forced Convection ina Helicoidal Pipe With Finite Pitch,” Int. J. Heat Mass Transfer, 38(5), pp.853–862.

[15] Yang, G., and Ebadian, M. A., 1996, “Turbulent Forced Convection in a Heli-coidal Pipe With Substantial Pitch,” Int. J. Heat Mass Transfer, 39(10), pp.2015–2022.

[16] Cengiz, Y., Yasar, B., and Dursun, P., 1997, “Heat Transfer and Pressure Dropsin a Heat Exchanger With a Helical Pipe Containing Inside Springs,” EnergyConvers. Manage., 38(6), pp. 619–624.

[17] Rahul, S., Gupta, S. K., and Subbarao, P. M. V., 1997, “An Experimental Studyfor Estimating Heat Transfer Coefficient From Coiled Tube Surfaces in Cross-Flow of Air,” Proceedings of the Third ISHMT-ASME Heat and Mass TransferConference and Fourth National Heat and Mass Transfer Conference, Kanpur,India, Dec. 29–31, pp. 381–385.

[18] Kumar, K. P., Saibabu, J., Rao, K. V. N. S., and Srikanth, D. N., 2008,“Experimental Analysis of Sisal Nanofluids in Shell and Coil Heat Exchanger,”Int. J. Nanosyst., 1(1), pp. 87–90.

[19] Huminic, G., and Huminic, A., 2011, “Heat Transfer Characteristics in DoubleTube Helical Heat Exchangers Using Nanofluids,” Int. J. Heat Mass Transfer,54(19–20), pp. 4280–4287.

[20] Hashemi, S. M., and Akhavan-Behabadi, M. A., 2012, “An Empirical Study onHeat Transfer and Pressure Drop Characteristics of CuO–Base Oil NanofluidFlow in a Horizontal Helically Coiled Tube Under Constant Heat Flux,” Int.Commun. Heat Mass Transfer, 39(1), pp. 144–151.

[21] Mukesh Kumar, P. C., Kumar, J., and Suresh, S., 2012, “Heat Transfer and Fric-tion Factor Studies in Helically Coiled Tube Using Al2O3/Water Nanofluid,”Eur. J. Sci. Res., 82(2), pp. 161–172.

[22] Mukesh Kumar, P. C., Kumar, J., Suresh, S., and Praveen Babu, K., 2012,“Experimental Study on Parallel and Counter Flow Configuration of a Shell andHelically Coiled Tube Heat Exchanger Using Al2O3/Water Nanofluid,” J.Mater. Environ. Sci., 3(4), pp. 766–775.

[23] Mukesh Kumar, P. C., Kumar, J., Suresh, S., and Praveen Babu, K., 2012, “HeatTransfer Enhancement in a Helically Coiled Tube With Al2O3/Water NanofluidUnder Laminar Flow Condition,” Eur. J. Sci. Res., 82(2), pp. 161–172.

[24] Mukesh Kumar, P. C., Kumar, J., and Suresh, S., 2013, “Experimental Investi-gation on Convective Heat Transfer and Friction Factor in a Helically CoiledTube With Al2O3/Water Nanofluid,” J. Mech. Sci. Technol., 27(1), pp.239–245.

[25] Akbaridoust, F., Rakhsha, M., Abbassi, A., and Saffar-Avval, M., 2013,“Experimental and Numerical Investigation of Nanofluid Heat Transfer in Heli-cally Coiled Tubes at Constant Wall Temperature Using Dispersion Model,”Int. J. Heat Mass Transfer, 58(1–2), pp. 480–491.

[26] Aly, W. I. A., 2014, “Numerical Study of Fluid Dynamic and Heat TransferPerformance of Nanofluid in Coiled Tube-in-Tube Heat Exchangers,” EnergyConvers. Manage., 79, pp. 304–316.

[27] Elsayed, A., Al-dadah, R. K., Mahmoud, S., and Rezk, A., 2014, “NumericalInvestigation of Turbulent Flow Heat Transfer and Pressure Drop of Al2O3/Water Nanofluid in Helically Coiled Tubes,” Int. J. Low-Carbon Technol.,2014, pp. 1–8.

[28] Kuppan, T., 2000, Heat Exchanger Design Handbook, Marcel Dekker, NewYork.

[29] Schmidt, E. F., 1967, “Heat Transfer and Pressure Loss in Spiral Tubes,”Chem. Eng. Technol., 39, pp. 781–789.

[30] Remsburg, R., 2001, Thermal Design of Electronic Equipment (ElectronicsHandbook Series), CRC Press, Boca Raton, FL.

[31] Koo, J., and Kleinstreuer, C., 2004, “A New Thermal Conductivity Model forNanofluids,” J. Nanopart. Res., 6(6), pp. 577–588.

[32] Koo, J., and Kleinstreuer, C., 2005, “Laminar Nanofluid Flow in Microheat-Sinks,” Int. J. Heat Mass Transfer, 48(13), pp. 2652–2661.

[33] Pak, B. C., and Cho, Y., 1998, “Hydrodynamic and Heat Transfer Study of Dis-persed Fluids With Submicron Metallic Oxide Particles,” Exp. Heat Transfer,11(2), pp. 151–170.

[34] Xuan, Y., and Roetzel, W., 2000, “Conceptions for Heat Transfer Correlationof Nanofluids,” Int. J. Heat Mass Transfer, 43(19), pp. 3701–3707.

[35] Daily, J. W., and Harleman, D. R., 1966, Fluid Dynamics, Addison-Wesley,Don Mills, ON, Canada.

[36] Nigam, K. D. P., Agarwal, S., and Srivastava, V. K., 2001, “Laminar Convec-tion of Non-Newtonian Fluids in the Thermal Entrance Region of Coiled Circu-lar Tubes,” Chem. Eng. J., 84(3), pp. 223–237.

[37] Kline, S. J., and McClintock, F. A., 1953, “Describing Uncertainties in Single-Sample Experiments,” Mech. Eng., 75(1), pp. 3–8.

[38] Xin, R. C., and Ebadian, M. A., 1997, “The Effects of Prandtl Numbers onLocal and Average Convective Heat Transfer Characteristics in Helical Pipes,”ASME J. Heat Transfer, 119(3), pp. 467–473.

[39] White, C. M., 1932, “Friction Factor and Its Relation to Heat Transfer,” Trans.Inst. Chem. Eng., 18, pp. 66–86.

Journal of Thermal Science and Engineering Applications DECEMBER 2015, Vol. 7 / 041002-9