DF-60601:A1 • 12/07/2010 — Page 1 of 6 MS-9200UDLS(E) Rev 3 Intelligent Addressable FACP with Built-In Communicator Addressable Fire Alarm Control Panel DF-60601:A1 • A1-60 52422cov.jpg General The Fire•Lite MS-9200UDLS Rev 3 with Version 5.0 firmware is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator/Transmitter) all on one circuit board. This compact intelligent addressable control panel has an extensive list of powerful features. While the MS-9200UDLS Rev 3 may be used with an SLC configured in the CLIP (Classic Loop Interface Protocol) mode, it can also operate in LiteSpeed™ mode—Fire•Lite’s latest polling technology—for a quicker device response time. LiteSpeed’s patented technology polls 10 devices at a time. This improvement allows a fully-loaded panel with up to 198 devices to report an incident and activate the notification cir- cuits in under 10 seconds. With Litespeed polling, devices can be wired on standard twisted, unshielded wire up to a distance of 10,000 feet. The MS-9200UDLS Rev 3’s quick-remove chassis protects the electronics during construction. The backbox can be installed allowing field wiring to be pulled. When construction is com- pleted, the electronics can be quickly installed with just two bolts. New features for Rev 3 with Version 5.0 firmware include removable terminal blocks, improved transient protection, additional secondary ANN-BUS, and increased power for the resettable and remote sync outputs. Available accessories include ANN-BUS devices as well as ACS LED, graphic and LCD annunciators, and reverse polar- ity/city box transmitter. The integral DACT transmits system status (alarms, superviso- ries, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. It also allows remote and local programming of the control panel using the PS-Tools Upload/ Download utility. In addition, the control panel may be pro- grammed or interrogated off-site via the public switched tele- phone network. Any personal computer with Windows® XP or greater, a compatible modem, and PS-Tools—the Fire•Lite Upload/Download software kit—may serve as a Service Termi- nal. This allows download of the entire program or upload of the entire program, history file, walktest data, current status and system voltages. The panel can also be programmed through the FACP’s keypad or via a standard PS-2 computer keyboard, which can be plugged directly into the printed circuit board. This permits easy typing of address labels and other programming information. Version 5.0 firmware supports the following: Primary and Sec- ondary ANN-bus devices, AD355 (LiteSpeed), USB port, NAC circuit diagnostics, a new report has been added to the walk- test that lists untested devices, new device types added: audio telephone type code for ACC 25/50ZST, Photo Supervisory and auto-resettable Drill (non-latching). The FireWatch Series internet monitoring modules IPDACT-2 and IPDACT-2UD permit monitoring of alarm signals over the Internet saving the monthly cost of two dedicated business telephone lines. Although not required, the secondary tele- phone line may be retained providing backup communication over the public switched telephone line. NOTE: Unless otherwise specified, the term MS-9200UDLS is used in this document to refer to both the MS-9200UDLS and the MS-9200UDLS(E) FACPs (Fire Alarm Control Panels). Features Listed to UL standard 864, 9th edition. On-board DACT. Remote site or local USB port upload/download, using PS- Tools. Four (4) Style Y (Class B) NAC circuits, which can be con- verted to four (4) Style Z (Class A) circuits with optional ZNAC-92 converter module. (Up to 6.0 amps total NAC power when using optional XRM-24B.) Selectable strobe synchronization for System Sensor, Wheelock, and Gentex devices. Remote Acknowledge, Silence, Reset and Drill via address- able monitor modules or LCD-80F, ANN-80 or Legacy ACS Annunciators. ANN-BUS for connection to following optional modules (cannot be used if ACS annunciators are used): ANN-80(-W) Remote LCD Annunciator ANN-I/O LED Driver ANN-S/PG Printer Module ANN-RLY Relay Module ANN-LED Annunciator Module ANN-RLED Annunciator Module alarms only ROME Relay Option Module Enclosure ACS/TERM: ACS Annunciators: Up to 32 Legacy ACM Series annun- ciators (ACM-16AT or ACM-32 series). Cannot be used if ANN-BUS devices are used. Terminal-mode Annunciators: Up to 32 Legacy LCD-80F remote annunciators.

Ms 9200 udls(e)

Embed Size (px)

Citation preview

Page 1: Ms 9200 udls(e)

DF-60601:A1 • 12/07/2010 — Page 1 of 6

MS-9200UDLS(E) Rev 3Intelligent Addressable FACP with Built-In Communicator

Addressable Fire Alarm Control Panel

DF-60601:A1 • A1-60

52422cov.jpg

GeneralThe Fire•Lite MS-9200UDLS Rev 3 with Version 5.0 firmwareis a combination FACP (Fire Alarm Control Panel) and DACT(Digital Alarm Communicator/Transmitter) all on one circuitboard. This compact intelligent addressable control panel hasan extensive list of powerful features.

While the MS-9200UDLS Rev 3 may be used with an SLCconfigured in the CLIP (Classic Loop Interface Protocol) mode,it can also operate in LiteSpeed™ mode—Fire•Lite’s latestpolling technology—for a quicker device response time.LiteSpeed’s patented technology polls 10 devices at a time.This improvement allows a fully-loaded panel with up to 198devices to report an incident and activate the notification cir-cuits in under 10 seconds. With Litespeed polling, devices canbe wired on standard twisted, unshielded wire up to a distanceof 10,000 feet.

The MS-9200UDLS Rev 3’s quick-remove chassis protects theelectronics during construction. The backbox can be installedallowing field wiring to be pulled. When construction is com-pleted, the electronics can be quickly installed with just twobolts.

New features for Rev 3 with Version 5.0 firmware includeremovable terminal blocks, improved transient protection,additional secondary ANN-BUS, and increased power for theresettable and remote sync outputs.

Available accessories include ANN-BUS devices as well asACS LED, graphic and LCD annunciators, and reverse polar-ity/city box transmitter.

The integral DACT transmits system status (alarms, superviso-ries, troubles, AC loss, etc.) to a Central Station via the publicswitched telephone network. It also allows remote and localprogramming of the control panel using the PS-Tools Upload/Download utility. In addition, the control panel may be pro-grammed or interrogated off-site via the public switched tele-phone network. Any personal computer with Windows® XP orgreater, a compatible modem, and PS-Tools—the Fire•LiteUpload/Download software kit—may serve as a Service Termi-nal. This allows download of the entire program or upload ofthe entire program, history file, walktest data, current statusand system voltages. The panel can also be programmedthrough the FACP’s keypad or via a standard PS-2 computerkeyboard, which can be plugged directly into the printed circuitboard. This permits easy typing of address labels and otherprogramming information.

Version 5.0 firmware supports the following: Primary and Sec-ondary ANN-bus devices, AD355 (LiteSpeed), USB port, NACcircuit diagnostics, a new report has been added to the walk-test that lists untested devices, new device types added: audiotelephone type code for ACC 25/50ZST, Photo Supervisoryand auto-resettable Drill (non-latching).

The FireWatch Series internet monitoring modules IPDACT-2and IPDACT-2UD permit monitoring of alarm signals over theInternet saving the monthly cost of two dedicated businesstelephone lines. Although not required, the secondary tele-phone line may be retained providing backup communicationover the public switched telephone line.

NOTE: Unless otherwise specified, the term MS-9200UDLS isused in this document to refer to both the MS-9200UDLS and theMS-9200UDLS(E) FACPs (Fire Alarm Control Panels).

Features• Listed to UL standard 864, 9th edition.• On-board DACT.• Remote site or local USB port upload/download, using PS-

Tools.• Four (4) Style Y (Class B) NAC circuits, which can be con-

verted to four (4) Style Z (Class A) circuits with optionalZNAC-92 converter module. (Up to 6.0 amps total NACpower when using optional XRM-24B.)

• Selectable strobe synchronization for System Sensor,Wheelock, and Gentex devices.

• Remote Acknowledge, Silence, Reset and Drill via address-able monitor modules or LCD-80F, ANN-80 or Legacy ACSAnnunciators.

• ANN-BUS for connection to following optional modules (cannotbe used if ACS annunciators are used):

– ANN-80(-W) Remote LCD Annunciator

– ANN-I/O LED Driver– ANN-S/PG Printer Module– ANN-RLY Relay Module

– ANN-LED Annunciator Module– ANN-RLED Annunciator Module alarms only– ROME Relay Option Module Enclosure

• ACS/TERM: – ACS Annunciators: Up to 32 Legacy ACM Series annun-

ciators (ACM-16AT or ACM-32 series). Cannot be used ifANN-BUS devices are used.

– Terminal-mode Annunciators: Up to 32 Legacy LCD-80Fremote annunciators.

Page 2: Ms 9200 udls(e)

Page 2 of 6 — DF-60601:A1 • 12/07/2010

• EIA-232 printer/PC interface (variable baud rate) on maincircuit board, for use with optional UL-listed printer PRN-6F.

• Integral 80-character LCD display with backlighting.

• Real-time clock/calendar with automatic daylight savingscontrol.

• Detector sensitivity test capability (NFPA 72 compliant).• History file with 1,000-event capacity.• Maintenance alert warns when smoke detector dust accu-

mulation is excessive.• Automatic device type-code verification.

• One person audible or silent walk test with walk-test log andprintout.

• Point trouble identification.• Waterflow (nonsilenceable) selection per monitor point.• System alarm verification selection per detector point.

• PAS (Positive Alarm Sequence) and presignal delay perpoint (NFPA 72 compliant).

NOTE: Only detectors may participate in PAS.

SLC LOOP:

• SLC can be configured for NFPA Style 4, 6, or 7 operation.• SLC supports up to 198 addressable devices per loop (99

detectors and 99 monitor, control, or relay modules).• SLC loop maximum length 10,000 ft. (3,000 m.).

See installation manual for wire tables.

NOTIFICATION APPLIANCE CIRCUITS (NACS):

• Four onboard NACs with additional NAC capability usingoutput control modules (CMF-300 or CMF-300-6). The fourClass B NACs can be converted to four Class A NACs withoptional ZNAC-92 converter module.

• Silence Inhibit and Auto Silence timer options.• Continuous, March Time, Temporal or California code for

main circuit board NACs with two-stage capability.• Selectable strobe synchronization per NAC.

• 2.5 amps maximum per each NAC circuit.NOTE: Maximum 24VDC system power output is shared amongall NAC circuits and 24VDC special-application auxiliary poweroutputs. Total available output is 3.0 amps. Using the optionalXRM-24B transformer increases 24VDC output to 6.0 amps.

PROGRAMMING AND SOFTWARE:

• Autoprogram (learn mode) reduces installation time.

• Custom English labels (per point) may be manually enteredor selected from an internal library file.

• Three Form-C relay outputs (two programmable).• 99 software zones.• Continuous fire protection during online programming at the

front panel. • Program Check automatically catches common errors not

linked to any zone or input point.• OFFLINE PROGRAMMING: Create the entire program in

your office using a Windows®-based software package(order programming kit PS-Tools, separately). Upload/download system programming locally to the MS-9200UDLS Rev 3 in less than one minute.

• USB upload/download programming with standard Male-Ato Male-B cable.

User Interface

LED INDICATORS

• AC Power (green)

• Fire Alarm (red)

• Supervisory (yellow)

• Alarm Silenced (yellow)• System Trouble (yellow)• Maintenance/Presignal (yellow)

• Disabled (yellow)• Battery Fault (yellow)• Ground Fault (yellow)

KEYPAD CONTROLS

• Acknowledge/Step• Alarm Silence

• Drill• System Reset (lamp test)• 16-key alpha-numeric pad (similar to telephone keypad)

• 4 cursor keys• Enter

Product Line InformationMS-9200UDLS: 198-point addressable Fire Alarm ControlPanel, one SLC loop. Includes 80-character LCD display, sin-gle printed circuit board mounted on chassis, and cabinet. 120VAC operation.

MS-9200UDLSE: Same as MS-9200UDLS, except with 240VAC operation.

4XTMF Reverse Polarity Transmitter Module: Providessupervised output for local energy municipal box transmitter,alarm, and trouble.

ZNAC-92: Optional converter module which converts four (4)Style Y (Class B) NAC circuits to four (4) Style Z (Class A) cir-cuits.

PK-CD Programming software for Windows®-based PC com-puter (cable not included), available on www.firelite.com.

DP-9692: Optional dress panel for MS-9200UDLS Rev 3.

TR-CE: Optional trim Ring for semi-flush mounting.

BB-26: Battery backbox, holds up to two 25 AH batteries andCHG-75.

BB-55F: Battery box, houses two 55 AH batteries.

CHG-75: Battery charger for lead-acid batteries with a ratingof 25 to 75 AH.

CHG-120F: Remote battery charging system for lead-acid bat-teries with a rating of 55 to 120 AH. Requires additional BB-55F for mounting.

BAT Series: Batteries, see data sheet DF-52397.

XRM-24B(E): Optional transformer. Increases system poweroutput to 6.0 amps. Use XRM-24BE with MS-9200UDLS Rev3(E).

PRT/PK-CABLE: Cable printer/personal computer interfacecable; required for printer or for local upload/download pro-gramming and updating panel firmware.

PRN-6F: UL listed compatible event printer. Uses tractor-fedpaper.

IPDACT-2/2UD, IPDACT Internet Monitoring Module:Mounts in bottom of enclosure with optional mounting kit (PNIPBRKT). Connects to primary and secondary DACT tele-phone output ports for internet communications over customerprovided ethernet internet connection. Requires compatibleTeldat VisorALARM Central Station Receiver. Can use DHCPor static IP. (See data sheet DF-60407 or DF-52424 for moreinformation.)

Page 3: Ms 9200 udls(e)

DF-60601:A1 • 12/07/2010 — Page 3 of 6

IPBRKT: Mounting kit for IPDACT-2/2UD in common enclo-sure.

IPSPLT: Y-adaptor option allows connection of both paneldialer outputs to one IPDACT-2/2UD cable input.

COMPATIBLE ANNUNCIATORS

ANN-80(-W): LCD Annunciator is a remote LCD annunciatorthat mimics the information displayed on the FACP LCD dis-play. Recommended wire type is un-shielded. (Basic model isred; order -W version for white; see DF-52417.)

ANN-LED: Annunciator Module provides three LEDs for eachzone: Alarm, Trouble and Supervisory. Ships with red enclo-sure (see DF-60241).

ANN-RLED: Provides alarm (red) indicators for up to 30 inputzones or addressable points. (See DF-60241).

ANN-RLY: Relay Module, which can be mounted inside thecabinet, provides 10 programmable Form-C relays. (See DF-52431.)

ROME: Relay Option Module Enclosure. Provides one ANN-RLY Relay Module already installed. The ROME Series pro-vides mounting space for one additional Relay Module or oneaddressable Multi-module. (See Installation Sheet PN 53530.)

ANN-S/PG: Serial/Parallel Printer Gateway module provides aconnection for a serial or parallel printer. (See DF-52429.)

ANN-I/O: LED Driver Module provides connections to a usersupplied graphic annunciator. (See DF-52430.)

ACM-8RF: Relay module provides 8 Form-C 5.0 amp relays.

ACS-LED Zone Series: LED-type fire annunciators capable ofproviding up to 99 software zones of annunciation. Available inincrements of 16 or 32 points to meet a variety of applications.

LDM Graphic Series: Lamp Driver Module series for use withcustom graphic annunciators.

LCD-80F (Liquid Crystal Display) point annunciator:80-character, backlit LCD-type fire annunciators capable ofdisplaying English-language text.

NOTE: For more information on Compatible Annunciators for usewith the MS-9200UDLS Rev 3, see the following data sheets (doc-ument numbers) ACM-8RF (DF-51555), ACS/ACMSeries (DF-52378), LDM Series (DF-51384), LCD-80F (DF-52185).

LITESPEED COMPATIBLE ADDRESSABLE DEVICES

All feature a polling LED and rotary switches for addressing.

CP355: Addressable low-profile ionization smoke detector.

SD355: Addressable low-profile photoelectric smoke detector.

SD355T: Addressable low-profile photoelectric smoke detec-tor with thermal sensor.

SD355R: Addressable remote test capable detector for usewith D355PL or DNR(W) duct smoke detector housings.

H355: Fast-response, low-profile heat detector.

H355R: Fast-response, low-profile heat detector with rate-of-rise option.

H355HT: Fixed high-temperature detector that activates at190F/88C.

AD355(A): Low-profile, intelligent, “Adapt” multi-sensor detec-tor (B350LP base included).

BEAM355: Intelligent beam smoke detector.

BEAM355S: Intelligent beam smoke detector with integralsensitivity test.

D355PL: Innovair Flex low-flow non-relay duct-detector hous-ing. SD355R included.

DNRW: Innovair Flex low-flow non-relay duct-detector hous-ing, with NEMA-4 rating. Watertight. (Order SD355R sepa-rately.)

MMF-300: Addressable Monitor Module for one zone of nor-mally-open dry-contact initiating devices. Mounts in standard4.0" (10.16 cm.) box. Includes plastic cover plate and end-of-line resistor. Module may be configured for either a Style B(Class B) or Style D (Class A) IDC.

MDF-300: Dual Monitor Module. Same as MMF-300 except itprovides two Style B (Class B) only IDCs.

MMF-301: Miniature version of MMF-300. Excludes LED andStyle D option. Connects with wire pigtails. May mount indevice backbox.

MMF-302: Similar to MMF-300, but may monitor up to 20 con-ventional two-wire detectors. Requires resettable 24 VDCpower. Consult factory for compatible smoke detectors.

Page 4: Ms 9200 udls(e)

Page 4 of 6 — DF-60601:A1 • 12/07/2010

CMF-300: Addressable Control Module for one Style Y/Z(Class B/A) zone of supervised polarized Notification Appli-ances. Mounts directly to a 4.0" (10.16 cm.) electrical box.Notification Appliance Circuit option requires external 24 VDCto power notification appliances.

CRF-300: Addressable relay module containing two isolatedsets of Form-C contacts, which operate as a DPDT switch.Mounts directly to a 4.0" (10.16 cm.) box, surface mount usingthe SMB500.

BG-12LX: Addressable manual pull station with interface mod-ule mounted inside.

I300: Fault Isolator Module. This module isolates the SLC loopfrom short circuit conditions (required for Style 6 or 7 opera-tion).

SMB500: Used to mount all modules except the MMF-301 andM301.

MMF-300-10: Ten-input monitor module. Mount one or twomodules in a BB-2F cabinet (optional). Mount up to six mod-ules on a CHS-6 chassis in a BB-6F.

MMF-302-6: Six-zone interface module for compatible conven-tional two-wire detectors. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6chassis in a BB-6F.

CMF-300-6: Six-circuit supervised control module. Mount oneor two modules in a BB-2F cabinet (optional). Mount up to sixmodules on a CHS-6 chassis in a BB-6F.

CRF-300-6: Six Form-C relay control module. Mount one ortwo modules in a BB-2F cabinet (optional). Mount up to sixmodules on a CHS-6 chassis in a BB-6F.

NOTE: 1) For more information on Compatible AddressableDevices for use with the MS-9200UDLS Rev 3, see the followingdata sheets (document numbers): AD355 (DF-52324), BG-12LX(DF-52013), CMF-300-6 (DF-52365), CRF-300-6 (DF-60379),CMF/CRF Series (DF-52130), CP355 (DF-52383), D355PL (DF-52398), H355 Series (DF-52385), I300 (DF-52389), MMF-300Series/MDF-300 (DF-52121), MMF-300-10 (DF-52347), MMF-302-6 (DF-52356), SD355/SD355T (DF-52384). 2) Legacy 300Series detection devices such as the CP300/CP350, SD300(T)/SD350(T) and older modules such as the M300, M301, M302,C304, and BG-10LX are not compatible with LiteSpeed polling. Ifthe SLC contains one of these devices, polling must be set forstandard LiteSpeed protocol. Please consult factory for furtherinformation on previous 300 Series devices.

Wiring RequirementsWhile shielded wire is not required, it is recommended that allSLC wiring be twisted-pair to minimize the effects of electricalinterference. Wire size should be no smaller than 18 AWG(0.78 mm²) and no larger than 12 AWG (3.1 mm²). The wiresize depends on the length of the SLC circuit. Refer to thepanel manual for wiring details.

( )

Page 5: Ms 9200 udls(e)

DF-60601:A1 • 12/07/2010 — Page 5 of 6

Page 6: Ms 9200 udls(e)

Page 6 of 6 — DF-60601:A1 • 12/07/2010

This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate.

We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105.www.firelite.com

Made in the U.S. A.

System Capacity• Intelligent Signalling Line Circuits....................................... 1 • Addressable device capacity .......................................... 198• Programmable software zones ......................................... 99

• ACS Annunciators ............................................................ 32• ANN-bus devices.............................................................. 16

Electrical SpecificationsAC Power: MS-9200UDLS Rev 3: 120 VAC, 60 Hz, 3.0 amps.MS-9200UDLS Rev 3E: 240 VAC, 5 0 Hz, 1.5 amps. Wire size:minimum 14 AWG (2.00 mm²) with 600 V insulation.

Battery charger capacity: 7 AH - 18 AH batteries. Up to two18 Ah batteries can be housed in the FACP cabinet. Largerbatteries require an external battery charger such as the CHG-75 or CHG-120, and a separate battery cabinet such as theBB-26 or NFS-LBB.

Communication Loop: Supervised and power-limited.

Notification Appliance Circuits: Each terminal block pro-vides connections for two Style Y (Class B) for a total of fourStyle Y (Class B) or with an optional ZNAC-92 module con-verts to four Style Z (Class A) NACs. Maximum signaling cur-rent per circuit: 2.5 amps. End-of-Line Resistor: 4.7K ohm, 1/2watt (P/N 71252 UL listed) for Style Y (Class B) NAC. Refer topanel documentation and Fire•Lite Device Compatibility Docu-ment for listed compatible devices.

Two Programmable Relays and One Fixed Trouble Relay: Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30VAC (resistive). Form-C relays.

Special Application Non-resettable Power (24 VDC Nomi-nal): Jumper selectable (JP4) for conversion to resettablepower output. Up to 1.0 amp total DC current available fromeach output. Power-limited.

Special Application Resettable Power (24 VDC nominal):Jumper selectable (JP6) for conversion to non-resettablepower. Up to 1.0 amp total DC current available. Refer to theFire•Lite Device Compatibility Document for listed compatibledevices.

Remote Sync Output: Remote power supply synchronizationoutput. Nominal special application power: 24 VDC. Maximumcurrent: 300 mA. End-of-Line Resistor: 4.7K ohm. Outputlinked to NAC 1 control. Supervised and power-limited.

Telephone Interface: Unless used with Teldat VISORALARM,requires dedicated business telephone number with a mini-mum of 5 volts DC (off-hook voltage). Obtain dedicated phoneline directly from your local phone company. Do not use sharedphone lines or PBX (digital) type phone line extensions.

Cabinet SpecificationsDoor: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x0.12" (.30 cm.) deep. Backbox: 19.00" (48.26 cm.) high x

16.65" (42.29 cm.) wide x 5.20" (13.34 cm.) deep. Trim Ring(TR-CE): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide.

Shipping SpecificationsWeight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00” (50.80 cm.)high x 22.5” (57.15 cm.) wide x 8.5” (21.59 cm.) deep.

Temperature and Humidity RangesThis system meets NFPA requirements for operation at 0 –49°C/32 – 120°F and at a relative humidity 93% ± 2% RH(noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, theuseful life of the system's standby batteries and the electroniccomponents may be adversely affected by extreme tempera-ture ranges and humidity. Therefore, it is recommended thatthis system and its peripherals be installed in an environmentwith a normal room temperature of 15 – 27°C/60 – 80°F.

NFPA StandardsThe MS-9200UDLS Rev 3 complies with the following NFPA72 Fire Alarm Systems requirements:

– LOCAL (Automatic, Manual, Waterflow and SprinklerSupervisory).

– AUXILIARY (Automatic, Manual and Waterflow) (requires4XTMF).

– REMOTE STATION (Automatic, Manual, Waterflow andSprinkler Supervisory) (Where a DACT is not accepted,the alarm, trouble and supervisory relays may be con-nected to UL 864 listed transmitters. For reverse polaritysignaling of alarm and trouble, 4XTMF is required.)

– PROPRIETARY (Automatic, Manual, Waterflow andSprinkler Supervisory).

– CENTRAL STATION (Automatic, Manual, Waterflow andSprinkler Supervisory).

– OT, PSDN (Other Technologies, Packet-switched DataNetwork)

Agency Listings and ApprovalsThe listings and approvals below apply to the basic MS-9200UDLS Rev 3 control panel. In some cases, certain mod-ules may not be listed by certain approval agencies, or listingmay be in process. Consult factory for latest listing status.

• UL Listed: S624• FM approved • CSFM: 7165-0075:0208

• MEA: 120-06-EFor ULC-listed version, see DF-60599.

FireLite® Alarms® is a registered trademark of Honeywell International Inc.Wheelock® is a registered trademark of and Exceder™ is a trademark ofCooper Notification.©2010 by Honeywell International Inc. All rights reserved. Unauthorized useof this document is strictly prohibited.

SYSTEM SPECIFICATIONS