Utility-Function-Driven Energy-Efficient Cooling in Data Centers

Preview:

DESCRIPTION

Utility-Function-Driven Energy-Efficient Cooling in Data Centers. Authors: Rajarshi Das, Jeffrey Kephart , Jonathan Lenchner , Hendrik Hamamn IBM Thomas J. Watson Research Center Presented by: Shivashis Saha University of Nebraska-Lincoln. Outline. Introduction Related Work - PowerPoint PPT Presentation

Citation preview

Utility-Function-Driven Energy-Efficient Cooling in Data Centers

Authors:Rajarshi Das, Jeffrey Kephart, Jonathan Lenchner, Hendrik Hamamn

IBM Thomas J. Watson Research Center

Presented by:Shivashis Saha

University of Nebraska-Lincoln

2

Outline

• Introduction• Related Work• Data Center Energy Balance• Utility Functions– Multiplicative utility functions– Additive utility functions

• Experiments• Conclusion

3

Introduction• Data center energy management– “50% of existing data centers will have insufficient

power and cooling within two years” – “Power is the second-highest operating cost in

70% of all data centers”– “Data centers are responsible for the tens of

millions of metric tons of carbon dioxide emissions annually --- more than 5% of the total global emissions”

4

Introduction• Why use autonomic computing?– Large, difficult to manage, complex– Management problem is both qualitatively similar

to and quantitatively harder than that of managing IT alone.

5

Contributions

• Apply utility functions to save energy– Tradeoff between energy and temperature– Control parameters:• Fan speed• On/off states of individual Computer Room Air

Conditioning (CRAC)

• Proposed model show 12% reduction in energy without violating temperature contraints

6

Related Work

• Saving more energy is not good if administrator does not want that!– Proposed model is flexible

• Apply computational fluid dynamics modeling to complex data center environments

• Temperature aware workload placement based on inlet temperature or heat recirculation

7

Data Center Energy Balance• PDC, power to run data center is split using

switch gear equipment into:– Path to power the IT equipments– Path to power the supporting equipments

8

Data Center Energy Balance• The support path may include– Power for pumping coolant to and from CRACs to

the chiller and to and from the chiller to the cooling tower

• Power path for IT equipments include– Conversion loss due to the uninterruptible power

supply (UPS) systems– Losses associated with the power distribution PPDU

– The UPS systems are located outside the raised floor area

9

• The total power on the floor:

• PIT is the power consumed by the IT equipments• Total CRAC fan power and CDU pump power:

• The relation between fan power PCRACi and relative fan speed Θi

Data Center Energy Balance

10

Data Center Energy Balance

• Under steady state condition, the total raised floor power equal to the total cooling power

– The reduced fan speed reduces the air flow:

11

Data Center Energy Balance

• All raised floor power needs to be cooled by the chilling system, which required power for refrigeration

– COP: the coefficient of performance of the chiller system (assume, average COP = 4.5)

12

Data Center Energy Balance

• Reducing CRAC fan speeds, the fan power is reduced

• This reduces both the raised floor power and the power needed from chiller system

• However, reducing fan speed also increases the server inlet temperature

A tradeoff between energy consumption and the temperature!!!

13

Utility Functions

• Data center operators responsible for the physical environment tend not to be concerned about application level performance, e.g. performance, availability, or security

• They are more concerned about cost, energy, temperature, and hardware lifetimes

• There are two CRAC units, whose fan speeds are Θ1 and Θ2

14

Utility Functions• Multiplicative utility functions

15

Utility Functions

The previous utility function is very harsh!

16

Utility Functions• Additive utility functions

17

Experiments

18

Experiments

19

Experiments

20

Experiments

Each CRAC was:1. Turned off2. Turned on at lowest speed (60%)3. Turned on at max speed (100%)

21

Experiments

22

Experiments• Snorkels were placed

23

Experiments

24

Conclusion

• Use of utility functions in data centers• Total reduction of energy consumption by 14% • Dynamic aspects of utility functions are not yet

considered• Investigation of techniques combining dynamic

workload scheduling with dynamic workload migration

Thanks!