Air Conditioners
for Close Control
and Data Centers
TECNAIR LV
CLOSE CONTROL AIR CONDITIONERS
TECNAIR LV
GOST certifi cation
TECNAIR LV
CLOSE CONTROL AIR CONDITIONERSTECNAIR LV
Air Conditioners for Close Control
and Data Centers
high energy effi ciency
and minimum environmental impact
3
Main characteristics
Tecnair LVs P Series air conditioners for
close control are special machines with design
and operating features which clearly differentiate
them from standard air conditioning units.
The total cooling capacity coverage of the
models with direct expansion - OPA with up-
fl ow air discharge and UPA with down-fl ow -
ranges from 7 up to 90 kW.
The same machines are available in chilled
water versions - OPU and UPU - with capacities
of up to approximately 200kW.
The P Series air conditioners offer very
high energy effi ciency values in all operating
conditions which translates into less CO2
emissions and particularly low running costs.
Though optimized for use in data centers and
telephone exchanges, they are equally valid
in special applications such as measurement
laboratories, TV recording studios, musical
instrument storage areas, museums, control
rooms for electricity power stations and railway
junctions and other areas in general where
there are prevalent sensible thermal loads and
crowding is negligible.
Their application is also ideal in widely varied
industrial sectors: optics, electronics, electro-
medical equipment, electronic equipment
production, musical instrument production etc.
In these applications an integrated system of
treatment of the external air may be requested.
ISO 9001Cert. n 273
GOST certifi cation
OPU: with chilled water coil
Models 302 372 422 512 612 662 852 932
Performance
Tot. cooling cap. kW: 31,4 39,2 43,4 53,1 63,1 70,0 89,8 99,6
Sens cooling cap. kW: 28,7 32,2 42,4 47,4 60,0 63,4 71,3 88,7
Airfl ow m3/h: 8.700 8.700 14.500 14.500 17.900 17.900 17.900 22.500
Condenser Model 2xACC 25 2xACC 29 2xACC 32 2xACC 42 2xACC 50 2xACC 55 2xACC 61 2xACC 74
EER 3,40 3,14 3,29 3,25 3,32 3,38 3,47 3,64
LPS:dB(A) 58 58 63 63 68 68 68 69
Dimensions & weight
Lenght mm. 1.410 1.410 1.750 1.750 2.300 2.300 2.300 2.640
Depth mm. 880 880 880 880 880 880 880 880
Height mm. 1.990 1.990 1.990 1.990 990 990 990 1.990
Net weight kg. 300 315 420 440 420 490 315 330
Models 10 20 30 50 80 110 160 220
Performance
Tot. cooling cap. kW: 11,3 19,6 31,7 39,8 70,9 89,3 152,8 178,8
Sens cooling cap. kW: 9,6 15,9 28,4 34,4 61,2 74,1 122,0 148,7
Airfl ow m3/h: 2200 3400 7800 8.300 16000 17.000 26.400 34800
LPS:dB(A) 47 49 57 56 59 61 64 82
Dimensions & weight
Lenght mm. 750 750 860 860 1750 1.750 2.640 3496
Depth mm. 630 630 880 880 880 880 880 880
Height mm. 1990 1990 1990 1990 1990 1.990 1.990 1990
Net weight kg. 155 155 180 250 450 450 650 900
TE
CN
AIR
L
V
Performance as the test conditions TECNAIR LV
OPA: direct expansion air conditioners with air cooled or water
condensers
Models 71 111 141 211 251 301 361 461
Performance
Tot. cooling cap. kW: 7,0 11,4 15,3 21,6 25,6 31,1 38,9 48,1
Sens cooling cap. kW: 6,8 11,1 12,7 20,8 22,6 28,7 36,3 43,9
Airfl ow m3/h: 2200 3200 3200 7000 7000 8700 14.500 14.500
Condenser Model ACC 11 ACC 16 ACC 21 ACC 32 ACC 42 ACC 50 ACC 55 ACC 74
EER 3,01 3,11 3,47 3,29 3,13 3,28 3,50 3,52
LPS:dB(A) 49 49 49 56 56 58 63 63
Dimensions & weight
Lenght mm. 750 750 750 860 860 750 1.750 1.750
Depth mm. 630 630 630 880 880 880 880 880
Height mm. 1990 1990 1990 1.990 1.990 1965 1.990 1.990
Net weight kg. 170 170 170 210 270 270 330 400
22
Upfl ow air supply
serie
P
Performance as the test conditions TECNAIR LV
UPA: direct expansion air conditioners with air cooled or water
condensers
Models 71 111 141 211 251 301 361 461
Performance
Tot. cooling cap. kW: 7,0 11,4 15,3 21,6 25,6 31,1 38,9 48,1
Sens cooling cap. kW: 6,8 11,1 12,7 20,8 22,6 28,7 36,3 43,9
Airfl ow m3/h: 2200 3200 3200 7000 7000 8700 14.500 14.500
Condenser Model ACC 11 ACC 16 ACC 21 ACC 32 ACC 42 ACC 50 ACC 55 ACC 74
EER 3,07 3,43 3,58 3,74 3,26 3,39 3,74 3,67
LPS:dB(A) 49 49 49 56 56 58 63 63
Dimensions & weight
Lenght mm. 750 750 750 860 860 750 1.750 1.750
Depth mm. 630 630 630 880 880 880 880 880
Height mm. 1990 1990 1990 1.990 1.990 1965 1.990 1.990
Net weight kg. 170 170 170 210 255 270 330 400
Models 302 372 422 512 612 662 852 932
Performance
Tot. cooling cap. kW: 31,4 39,2 43,4 53,1 63,1 70,0 89,8 99,6
Sens cooling cap. kW: 28,7 32,2 42,4 47,4 60,0 63,4 71,3 88,7
Airfl ow m3/h: 8.700 8.700 14.500 14.500 17.900 17.900 17.900 22.500
External static pressure (Pa) 30 30 30 30 30 30 30 30
Condenser Model 2xACC 25 2xACC 29 2xACC 32 2xACC 42 2xACC 50 2xACC 55 2xACC 61 2xACC 74
EER 3,50 3,25 3,46 3,40 3,46 3,46 3,55 3,79
LPS:dB(A) 58 58 63 63 68 68 68 69
Dimensions & weight
Lenght mm. 1.410 1.410 1.750 1.750 2.300 2.300 2.300 2.640
Depth mm. 880 880 880 880 880 880 880 880
Height mm. 1.990 1.990 1.990 1.990 990 990 990 1.990
Net weight kg. 300 315 420 440 420 470 315 330
UPU: with chilled water coil
Models 10 20 30 50 80 110 160 220
Performance
Tot. cooling cap. kW: 11,3 19,6 31,7 39,8 70,9 89,3 152,8 178,8
Sens cooling cap. kW: 9,6 15,9 28,4 34,4 61,2 74,1 122,0 148,7
Airfl ow m3/h: 2200 3400 7800 8.300 16000 17.000 26.400 34800
LPS:dB(A) 47 49 57 56 59 61 64 82
Dimensions & weight
Lenght mm. 750 750 860 860 1750 1.750 2.640 3496
Depth mm. 630 630 880 880 880 880 880 880
Height mm. 1990 1990 1990 1990 1990 1.990 1.990 1990
Net weight kg. 155 155 180 250 450 450 650 900
Notes:
The performances are referred to: refrigerant R410; condensing temperature: 45C; inlet air: 24C - 50% RH; for chilled water: 7/12C; The SPL is referred to 2 m distance, 1,5 m height, free fi eld and sound damped discharge mouth. Available static pressure: 30 Pa. EER = Electro Effi ciency Ratio = Total cooling capacity / compressors power input + fans power input. The above performances dont consider the heat generated by the fans which must be added to the thermal load of the system.
TE
CN
AIR
L
V
23
Down fl ow air supply
Recommended