MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
Ensure that you read and understand these instructions BEFORE operating the equipment.
Please pay particular attention to the Safety Warnings.
WARNINGS1. TheSearchlineExcelgasdetectoriscertifiedforandintendedforuseinpotentiallyhazardousareas.
Install and use the Searchline Excel gas detector in accordance with the latest regulations.
2. For installations in Europe, the Code of Practice SELECTION, INSTALLATION AND MAINTENANCE OF ELECTRICAL APPARATUS FOR USE IN POTENTIALLY EXPLOSIVE ATMOSPHERES should be strictly observed. General recommendations are given in EN 60079-14:2008 & IEC 60079-14:2007. Refer to EN 60079-29-2:2007 & IEC 60079-29-2:2007 in Europe or the appropriate local or national regulations.
3. For installations in North America, the national Electrical Code (NFPA 70 - 1990) or later issues should be strictly observed.
4. Elsewhere, the appropriate local or national regulations should be used.
5. The Searchline Excel gas detector must be properly earthed to protect against electrical shock and minimise electrical interference. For electrical installation design considerations refer to Section 3.
6. Operators must be fully aware of the action to be taken if the gas concentration exceeds an alarm level.
7. Dismantling or repair of equipment should be carried out in the safe area only.
8. Test gases may be toxic and/or combustible. Refer to Material Safety Sheets for appropriate warnings.
9. Do not drill holes in any housing as this will invalidate the explosion protection.
10. In order to maintain electrical safety, the unit must not be operated in atmospheres with more than 21% oxygen.
11. Ensurethattheboltswhichsecureflameproofenclosuresarefullytightened.Thesecuringboltsusedaremadefromaspecialcertifiedgradeofsteel.OnlyboltssuppliedbyHoneywellAnalyticsshouldbefittedforthispurpose.
12. Do not open the enclosure in the presence of an explosive atmosphere.
13. The transmitter unit contains high voltages when operational. These are discharged when the unit is removed from its enclosure.
14. TheconduitandcableglandsfittedtoSearchlineExcelshouldnotbemodified.If,however,itbecomesnecessarytomakemodificationstheymustcomplywiththerelevantnationalCodesof Practice.
15. The optical energy emitted by the Searchline Excel is less than 20mW/mm2.
16. Searchline Excel Cross-Duct should only be used to detect gas mixtures where methane is the main constituent (>70%) and the balance is C2 - C6 hydrocarbons.
Safety
3
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
Cautions1. Use only approved parts and accessories with the Searchline Excel gas detector.
2. To maintain safety standards, commissioning and regular maintenance of the Searchline Excel gas detector shouldonlybeperformedbyqualifiedpersonnel.
Important Notices1. HoneywellAnalyticscantakenoresponsibilityforinstallationand/oruseofitsequipmentifthisisnotdonein
accordance with the appropriate issue and/or amendment of the manual.
2. The user of this manual should ensure that it is appropriate in all details to the exact equipment to be installed and/oroperated.Ifindoubt,theusershouldcontactHoneywellAnalyticsforadvice.
3. Effect of explosive atmosphere on materials.
Searchline Excel is made from materials which exhibit good resistance to corrosive and solvative substances. The Exd enclosures are made from 316 stainless steel and the explosion protected windows are made from toughenedsodalimeglass.HoneywellAnalyticsarenotawareofanysignificanteffectsofexplosiveatmospheresuponthesematerials.ContactHoneywellAnalyticsoroneoftheiragentsforspecificqueries.
Special Conditions of UseInordertocomplywiththeATEX/IECExCertification,thefollowingspecialconditionsofusemustbeadheredto:-
1. The integral supply cables must be mechanically protected and terminated in a suitable terminal or junction facility.
2. Thecoverfixingscrewsshallbestainlesssteelgrade12.9minimum,gradeA2-80orgradeA4-80(onlyuseHoneywellsuppliedscrews)
Everyefforthasbeenmadetoensuretheaccuracyofthisdocument,however,HoneywellAnalyticscanassumeno responsibility for any errors or omissions in this document or their consequences.
HoneywellAnalyticswouldgreatlyappreciatebeinginformedofanyerrorsoromissionsthatmaybefoundinthe content of this document.
For information not covered in this document, or if there is a requirement to send comments/corrections about thisdocument,pleasecontactHoneywellAnalyticsusingthecontactdetailsgivenonthebackpage.
HoneywellAnalyticsreservetherighttochangeorrevisetheinformationsuppliedinthisdocumentwithoutnotice and without obligation to notify any person or organisation of such revision or change. If information isrequiredthatdoesnotappearinthisdocument,contactthelocaldistributor/agentorHoneywellAnalytics.
Safety
4
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
Section Page
1. Introduction 7
2. Overview 9
2.2 Transmitter and Receiver Unit 10
2.2.1 Transmitter 10
2.2.2 Receiver 10
2.2.3 Mounting Block 11
2.3 HeatedReflectorPanel 11
3. Installation and Operation 12
3.1 Introduction 12
3.2 Siting and Mounting 12
3.2.1 General 12
3.2.2 Location for Best Coverage 12
3.2.3 Location to Maximise Reliability and Availability 12
3.2.4 Beam Path 13
3.2.5 Orientation 13
3.2.6 Access for Cleaning 14
3.3 Electrical Connections 14
3.3.1 General 14
3.3.2 Transmitter and Receiver Connections via DVC100 (M) MK2 15
3.3.3 Transmitter and Receiver Connections via DX100 (M) 15
3.3.4 Transmitter and Receiver Connections 16
3.3.5 Remote Installations 17
3.4 Power Supply 17
3.4.1 General 17
3.4.1.1 Transmitter and Receiver Unit 17
3.4.1.2HeatedReflectorPanel 17
3.4.2 Power Supply Connections - Turbo heating Disabled 19
3.5 Installation Procedure 20
3.5.1 General 20
3.5.2 Mechanical Installation 20
3.5.2.1 Transmitter and Receiver Unit 20
3.5.2.2HeatedReflectorPanel 21
Contents
5
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
Section Page
3.5.3 Electrical Installation 22
3.6 Commissioning 22
3.6.1 General 22
3.6.2 Connecting the Interrogator 22
3.6.3 Power Up 24
3.6.4 Setting the Real-Time Clock 25
3.6.5 Initialising the Searchline Excel Cross-Duct Gas Detector 26
3.6.6 Functional check 28
3.6.7 Finish 28
3.7 System Controller Calibration 29
3.8 Installation Checks/ Tests 30
4. Maintenance 35
4.1 Inspection and Cleaning 35
4.2 Re-zero 36
4.3 Functional Checking 36
4.3.1 Functional Checking with Gassing Cell (Short Range versions only) 36
4.3.2 Functional Checking with Test Filters 37
5. Problem Solving 38
6. Specifications 42
6.1 System 42
7. Certification 43
7.1 General 43
7.2 Conduit Technical Characteristics (ATEX, IECEx version) 44
7.3 CertificationLabelsATEX,IECEx 44
7.3.1 Transmitter 44
7.3.2 Receiver 45
7.3.3HeatedReflectorPanel 46
7.3.4 System Diagram 47
7.4CertificationlabelsUL 48
7.4.1 Transmitter 48
Contents
6
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
Section Page
7.4.2 Receiver 49
7.4.3HeatedReflectorPanel 50
7.4.4 System Diagram With DX100M Termination Unit 51
8. Warranty Summary 52
AppendixA-HandheldInterrogator 53
A.1 Introduction 53
A.2 Overview 53
A.3 Connection to System 54
A.4 Basic User Tasks 55
A.5 Menus 56
A.5.1 Main Menu 57
A.5.2 Display Menu 57
A.5.3 Calibrate Menu 58
A.5.4 Diagnose Menu 63
A.5.5ConfigMenu 65
A.5.6 Chg Mode 67
A.5.7 Power Off 67
A.6 PROBLEM SOLVING 67
Appendix B - Glossary 68
B.1 Terminology 68
B.2 Open Path Detector Measurement Units 69
B.3 Abbreviations 69
Appendix C - Accessories & Spare Parts 70
C.1 System Units 70
C.2 General 70
Contents
7
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
The Searchline Excel Cross-Duct Gas Detector is an open path infrared gas detector for methane.
It will detect hydrocarbon gas mixtures where methane is the main constituent (>70% of the composition with the balance being C2 - C6hydrocarbons).ForothergasmixturespleasecontactHoneywellAnalyticsforadvice.
SearchlineExcelCross-Duct isspecificallydesigned forusewhere thepath length isbetween0.5and5metres for applications such as air intake ducts. It consists of a Transmitter and Receiver unit, and a separate HeatedReflectorPanel.
The detector operates on the principle of infrared (IR) absorption. If a cloud of methane gas is present, part of the infrared light is absorbed by the gas, causing a reduction in the signal received that is proportional to the amount of gas in the beam.
The detector output signal is proportional to 0-100%LEL (Lower Explosive Limit) of gas.
Searchline Excel Cross-Duct is suitable for use in Zone 1 or 2 hazardous areas (International) and for Class 1 Division 1 or 2 area applications (North America).
Note: THE INFRARED BEAM IS INVISIBLE AND EYE SAFE.
Thishandbookconsistsofthefollowingparts:
• Chapter 1 Introduction
• Chapter 2 Overview
A brief description of the system components
• Chapter 3 Installation and Operation Important information regarding detector positioning, electrical connections, power supply requirements, mechanical installation and commissioning, including an installation check list
• Chapter 4 Maintenance Regular maintenance requirements and instructions for functional checks
• Chapter 5 Problem Solving
• Chapter6 Specifications
• Chapter7 Certification
• Appendix A Handheld Interrogator
• Appendix B Glossary
• Appendix C Accessories & Spare Parts
1. Introduction
8
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
Information noticesThetypesofinformationnoticesusedthroughoutthishandbookareasfollows:
Caution: Indicates hazardous or unsafe practice which could result in minor injury to personnel, or product or property damage.
Note: Provides useful/helpful/additional information.
If more information beyond the scope of this technical handbook is required please contact HoneywellAnalytics.
Associated DocumentsDX100SeriesTerminationUnitsTechnicalHandbook PartNo:2104M0701
DVC100(M)MK2TerminationUnitQuickStartGuide PartNo:2104M0409
WARNING
Indicates hazardous or unsafe practice that could result in severe injury or death to personnel.
1. Introduction
9
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
2.1 IntroductionSearchlineExcelCross-DuctgasdetectorconsistsofaTransmitterandReceiverunit,andaHeatedReflectorPanel.TheTransmitterandReceiverunitgeneratesanddetectstheinfraredbeam.TheHeatedReflectorPanelismountedattheoppositesideoftheducttoreflectthebeamfromtheTransmitterbacktotheReceiver.
Note: THE INFRARED BEAM IS INVISIBLE AND EYE SAFE.
TherearetworangesofSearchlineExcelCross-Ductgasdetector.Theseare:
Version Path Length (m) Path Length (ft) Certification
Short Range: 0.5 — 2.5m (20in — 8ft) ATEX, IECEx, UL
Long Range: 2.5 — 5m (8ft — 15ft) ATEX, IECEx
ThelongrangegasdetectorusesalargerReflectorPanelthantheshortrangeversion.
2. Overview
Heated Reflector Panel
Mounting Plate
Mounting Block
Transmitter
Conduit
ReceiverJunction Box (type DVC100 (M) MK2)
10
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
2.2 Transmitter and Receiver Unit
2.2.1 TransmitterTheTransmitterproducesanintense,collimatedinfraredbeamfromaXenonarcflashlamp.TheTransmitterwindow is heated to minimise condensation and frosting. During particularly cold operating conditions, the heating of the Transmitter window is increased to turbo levels. The turbo mode can be disabled if not required.
ElectricalconnectionstotheTransmitteraremadeviawireswhichrunthroughtheprotective,flexibleconduit.There are three Transmitter wires, red (+24V), black (0V) and green/yellow (GND).
Note: The infrared beam is invisible and eye safe.
2.2.2 ReceiverThe Receiver collects infrared radiation from the Transmitter and performs measurements to enable methane gas in the beam path to be detected.
The Receiver output signal is 4 - 20mA available as a source or sink option. The output is calibrated for a range of 0 to 100% LEL methane.
Note: The detector uses the duct width in the calculation of gas reading – it is essential that this is specified correctly during installation (See Appendix B.2 for the explanation of how open path gas detectors measure gas concentration)
Output signal levels below 4mA are used to indicate Fault (0mA), Inhibit (2mA), Beam Blocked (2.5mA) and Low Signal (3mA).
TheReceivercommunicateswiththeSHC1HandheldInterrogatorusinganRS485output.TheSHC1isusedto perform commissioning, functional testing and diagnostic procedures.
The Receiver window is heated to minimise condensation and frosting.
ElectricalconnectionstotheReceiveraremadeviawireswhichrunthroughtheprotectiveflexibleconduit.There are six Receiver wires, red (+24V), black (0V), white (4 - 20mA), orange (RS485 A), blue (RS485 B) and green/yellow (GND).
2. Overview
Air Shield
Slot for test filter
Gas In/Out
Gassing Cell
Transmitter
Mounting Block
Beamsplitter
Receiver
11
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
2.2.3 Mounting BlockThe Transmitter andReceiver are factory aligned and fixed to amounting block. They should not bedisassembled. The mounting block has a top cover which can be removed to clean the Transmitter and Receiverwindows.Insidethemountingblockthereisanangledwindow(thebeamsplitter)whichreflectsthebeam into the Receiver.
Themountingblockhastwofeaturesforfunctionalchecking-agascellandaslotforplastictestfilters.
2.3HeatedReflectorPanelTheHeatedReflectorPanelconsistsofaretro-reflectorsealedinadouble-glazedunit,withanintegralheaterto minimise condensation and frosting.
TheReflectorPanelshouldbemountedoppositetheTransmitterandReceiverunit,andperpendiculartothebeam.
TheReflectorrequiresanominal24Vpowersupply.
2. Overview
12
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
3.1 Introduction
Before designing or specifying an installation for Searchline Excel Cross-Duct, it is strongly recommended that the installation design authority reads all of this chapter and considers how the information and recommendations provided can be applied to their installation(s).
Ifyouhaveanyqueriesconcerningyourinstallationdesign,contactHoneywellAnalyticsoryourlocalagents.
HoneywellAnalyticsiscommittedtoensuringthatcustomersachievereliableoperationoftheirSearchlineExcel Cross-Duct Gas Detectors. For this reason, Searchline Excel Cross-Duct should only be installed by fully trainedpersonnel(trainedbyHoneywellAnalyticsoraHoneywellAnalyticsauthorisedtrainer).
This training will provide the installer with a clear understanding of the Searchline Excel Cross-Duct product and the associated accessories and tools. It will also provide familiarity with the installation, alignment and commissioning procedures, plus installation assessment skills to identify potential problem areas.
Foreachinstallation,aninstallationchecksheetshouldbecompletedandreturnedtoHoneywellAnalyticsortheir agents. Details of this check sheet are given at the end of this chapter.
Note: THE INFRARED BEAM IS INVISIBLE AND EYE SAFE.
3.2 Siting and Mounting
3.2.1 GeneralWhen designing an installation for a Searchline Excel Cross-Duct gas detector it is important to give consideration to where it is to be located, what potential sources of problems may be encountered in this location and how the unit is to be mounted and supported.
Caution: TheTransmitter,ReceiverandReflectorPanelunitshaveheatedwindowstominimisecondensationandfrosting.However,partialobscurationoftheReflectorandinparticularliquidwatercondensationontheReflectorcancausenegativedrift,whichhastheeffect of raising the alarm threshold. Wherever possible protect the Searchline Excel Cross-Duct from dirt and condensation by mounting well inside the duct and ideally downstreamoffilters/dampers.
3.2.2 Location for Best CoverageThe placement of gas detectors should be determined following the advice of experts having specialist knowledge of gas dispersion, experts having knowledge of the process plant system and equipment involved, safety and engineering personnel. The agreement reached on the location of detectors should be recorded.
3. Installation and Operation
WARNING
The national Code of Practice regaurding selection, installation and maintenance of electrical apparatus for use in potentially explosive
atmospheres must be complied with at all times.
13
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
3.2.3 Location to Maximise Reliability and AvailabilityForoptimumperformance,takecaretoavoidareaswheretheunitsmaybeadverselyaffectedbythefollowing:
Vibration - Angular vibration of the structure to which Excel units are attached should be kept to less than ±0.5°. Where possible, avoid locations where high levels of vibration will be directly induced into the mounting structure.Ifcloseproximitytosignificantsourcesofvibrationisunavoidable,takestepstoreducecouplingof this vibration and maximise the rigidity of the mounting structure.
Mounting Rigidity – The duct wall thickness should be suitable to maintain rigidity of the Searchline Excel Cross-Duct mounting to within ±0.5°.
Intense Heat-Exceliscertifiedandspecifiedforoperationinenvironmentsupto+65°C.Ifsourcesofintenseheat(flarestacks,intensesunlight,etc.)arepresent,asunshade(PartNo:2104B2323)orsimilarshieldshouldbefittedtotheunittoprotectitfromexcessiveheating.
Sources of Heavy Contamination - Avoid locations where high levels of contaminants will persistently be blown onto the unit windows. Potential sources of heavy contamination include generator/turbine exhausts, flarestacks,drillingequipment,processvents/chimneysetc. If sourcesofheavycontaminationcannotbeavoided,considerfittingextrashieldingand/orprovidinggoodaccessformoreroutinecleaning.
Snow and Ice in Ambients Below -20°C - The heated optics on Excel units will melt snow or ice on the windows in ambient temperatures down to approximately -20°C. Below this temperature, snow or ice blown onto the window will not be melted until the ambient temperature rises. If long-term, outdoor operation in very cold climates is intended, it is recommended that extra shielding/covers are employed to prevent snow/ice from being blown onto the windows and building up.
Accidental Impact-Locationswherethereisasignificantlikelihoodofequipment,personnelormovingobjectsaccidentally knocking Excel units out of alignment should where possible be avoided. If such locations cannot be avoided, measures including improved mechanical protection and warning notices should be considered. Since the Transmitter and Receiver protrude from the duct wall, adequate precautions should be taken to protect personnel.
Intense Electromagnetic Fields - Searchline Excel Cross-Duct complies with EN50270 and as such is well protectedfrominterferencebyelectromagneticfields.However, locationsincloseproximitytoradio/radartransmitters,heavyelectricalplantandhighvoltagepowercablesmayexperiencefieldstrengthsinexcessofthosespecifiedinthestandard.Wherepossible,suchlocationsshouldbeavoidedorunitsshouldbeinstalledasfaraspossiblefromthesourceoftheelectromagneticfield.Measuresincludingadditionalscreening,filteringandtransientsuppressionmayalsobeofbenefitinsuchlocations.
To ensure optimum performance, do not cover the Excel with insulation, and allow free air movement around the unit.
3.2.4 Beam PathThe path of the infrared beam inside the duct is unlikely to be affected by obstructions, however, consideration shouldbegiventoavoid:
• Steam vents
• Splash and spray
3. Installation and Operation
14
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
3.2.5 OrientationTheSearchlineExcelCross-Ductunitsshouldbemountedonvertical,flatsurfacessuchthattheopticalaxisishorizontal.Ensurethesurfaceisrigidandstable.Fitadditionalsupportspriortoinstallationifnecessary(see note on Vibration, above).
TheHeatedReflectorPanelshouldbemounteddirectlyopposite,andperpendiculartotheopticalaxisoftheTransmitter and Receiver unit. If the duct walls are not exactly vertical or parallel, the position of the cut out for the retro panel must be adjusted to compensate.
It is not advisable to install the Cross-Duct Excel on the top or bottom of the duct. In this orientation the ReflectorPanelortheTransmitterandReceiverunitwillbevulnerabletothebuildupofcontamination.
3.2.6 Access for CleaningSearchlineExcelCross-DuctTransmitterandReceiverunitandHeatedReflectorPanelwillneedtobecleanedregularly.InthecaseoftheReflectorPanelitmayneedtoberemovedfromtheducttocleanthewindow.Itisadvisabletoprovideanaccesspointintheduct,adjacenttothereflectorpanel,toallowittobecleaned.
3.3 Electrical Connections
3.3.1 GeneralSearchline Excel Cross-Duct complies with the EN50270. In order to maintain compliance with these standards it is essential that the electrical installation of Excel is engineered correctly.
Electrical installation standards vary for different countries, companies and applications and it is the responsibility of the installation design authority to determine the applicable standards and ensure compliance with them. WhendesigningelectricalinstallationsforExcel,HoneywellAnalyticsrecommendthattheinstallationdesignauthorityconsidersthefollowing:
a. The unit cases should not, if possible, be connected to electrically noisy (dirty) metalwork or conductors. Preferably, the case (internally connected to the green/yellow GND wire) should be connected to a low noise instrument (clean) earth. See also para e. below. In order to facilitate electrical isolation of the SearchlineExcelfromanoisyearthanisolationkitissupplied.Thiskitshouldbefittedasstandardunlesslocal regulations forbid this.
b. Theentirelengthofthefieldcablingconnectedtoeachunitshouldbefullyshielded.Thisshouldbeconnectedto a low noise (clean) earth.
c. The low noise instrument (clean) earth system should only be connected to safety earth (usually dirty) at a single point on the entire site/installation. This connection should be made in such a manner that it does not introduce noise onto the low noise instrument earth. Star earthing arrangements minimise earth current crosstalk.
d. Theshieldsofthefieldcablingshouldnotbeconnectedsuchthatearthloopsareproduced,orinamannerthat will result in the shields carrying large currents from heavy plant or equipment.
e. Ideally,thefieldcableshieldshouldbeconnectedtotheunitsgreen/yellowGNDwire,providingasingle,continuous earth shield. This connection must not be allowed to complete an earth loop.
f. The earth bonding arrangement must ensure that the maximum peak voltage between the unit case earth andanyfieldcableconductorislessthan350V.VoltagesinexcessofthiscancausepermanentdamagetotheunitsRFIprotectionfilters.
g. The use of a single, screened cable for each gas detector ensures maximum screening and minimum crosstalk.Cabling arrangementswhich use a single cable for connecting a number of fielddevicescompromise screening, increase the potential for crosstalk and prevent implementation of true star earthing.
3. Installation and Operation
15
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
h. Any electrical interference induced onto the 4 - 20mA loop conductors by the installation must be kept below the levels necessary to comply with the general requirements of EN 60079-29-2 and IEC 60079-29-2. In practice, this means that peak noise currents induced on the current loop should be no greater than ± 0.25mA
j. The 0V rail of the control card/control system is directly connected to one side of the 4 - 20mA current sensing resistor. Electrical noise on this rail is therefore directly connected to the 4 - 20mA input. In order to avoid additional noise being induced on the 0V rail, it should not be commoned with the safety earth/ground, which frequently carries a high level of electrical noise.
k. All electrical equipment connected to the gas detector should comply with EN50270.
l. The24Vsupplyshouldbefreefromlargetransientsandfluctuations.
m. Thefieldcablingconductorsshouldhavesufficientcrosssectionalareatoensurethattheminimumsupplyvoltage applied to the gas detector is 18V.
n. Searchline Excel Cross-Duct Receivers should not be installed in close proximity to the antennae of high powered radio, radar and satellite communication equipment.
3.3.2 Transmitter and Receiver Connections via DVC100 (M) MK2
3.3.3 Transmitter and Receiver Connections via DX100 (M)
3. Installation and Operation
Field Wiring
+24VDC IN (Terminal 1)0V (Terminal 3)
4-20mA (Terminal 5)Earth Terminal
MOD BUS DRAIN (Terminal 9)MOD BUS A (Terminal 10)MOD BUS B (Terminal 11)
Earth Terminal+24V (Terminal 2)
0V (Terminal 4)
Cross-DuctTransmitter Wiring
Cross-DuctReceiver Wiring
R5485 (B) (Blue) (Terminal 8)R5485 (A) (Orange) (Terminal 7)4-20mA (White) (Terminal 6)Earth (Green / Yellow) (Earth Terminal)+ 24VDC (Red) (Terminal 2)0V (Black) (Terminal 4)
16
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
3.3.4 Transmitter and Receiver Connections
3. Installation and Operation
1 6
1
6
Cross-Duct Reciever Connections
Control Cabinet Connections
Cross-Duct Transmitter Connections
Modbus A
Blue (B)
Orange (A)
Red (+24VDC)
White (4-20mA)
Black (0V)
Green/Yellow (Earth)
Modbus B
+24VDC - in4-20mA - out
0VDC - in
Red (+24VDC) Black (0V)
Green/Yellow (Earth)
Safety/ protec-tive ground
Screen Modbus Drain
DX100 (M) Junction BoxCable Shield
Instrument (clean) Earth
The earth bonding arrangement mustensure that the maximum peak voltagebetween the unit case earth and any field cable conductor is less than 350V.Voltages in excess of this can causepermanent damage to the unit’s RFIprotection filters.
AB
Ex d or Ex e Junction BoxSHC Protection Device
Flying Lead
(Tempo-rary Con-nection)
SHC1
Transmitter Connections
Controller Connections
Receiver Connections
Black 0V4-20mAGND0V+24V
BRN4-20mA
BLU
Red +24VGreen/ GND
2-wire crimp ferrules
Earth Terminal
GRN/YEL GNDWHITE 4-20mAORANGE ABLUE BRED +24VBLACK 0V
Earth
Cable Shield
17
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
3.3.5 Remote Installations Forremoteordifficult-to-accessinstallations,theDVC100(M)/DX100(M)canbepositionedinaconvenientlocation by using an intervening junction box (e.g. PL6I2/AKRON/Killark) attached to the Transmitter and Receiver unit’s mounting plate.
A maximum cable length of 1km between the unit and the DVC100 (M)/ DX100 (M) is permissible (RS485 compliant).
3.4 Power Supply
3.4.1 GeneralThe Searchline Excel Cross-Duct gas detector is designed to be operated from a nominal 24V DC supply. The supply voltage at the terminals must be within the range 18 to 32V for the Transmitter and Receiver unit, and withintherange18to28VfortheHeatedReflectorPanel.
3.4.1.1 Transmitter and Receiver Unit
TheTransmitterandReceiverunitmaximumpowerconsumptionandcablelengthsareasfollows:
Unit TypeMaximum PowerConsumption (W)
Maximum Cable Length(m) with 1.5mm2
Conductors (12 ohms/km)
Maximum Cable Length(m) with 2.5mm2
Conductors (7.6 ohms/km)
Transmitter and Receiver 13 340 540
Notes:
1. Control room supply voltage assumed to be +24V.
2. Standard configuration of the Transmitter is with turbo heating enabled.
Terminal sizes: DVC 100 (M) 0.5mm2 - 4mm2 (20AWG - 12AWG) DX100 (M) 0.5mm2 - 4mm2 (20AWG - 12AWG) HA Junction Box 00780-A-0100 0.5mm2 - 6mm2 (20AWG - 10AWG)
3.4.1.2HeatedReflectorPanel
TheHeatedReflectorPanel requires18-28Vdcsupplyvoltage.Because it isa resistiveheater, thepowerconsumptiondependsonthesupplyvoltage.Powerconsumptioncanbecalculatedasfollows:-
Power = V2 where V is the supply voltage and R is the resistance of the heater
Toensuresufficientheatingoverawiderangeofsupplyvoltage,twoconnectionoptionsareavailable,whichuse different heater resistances depending on the supply voltage available (>20V or 18-20V).
3. Installation and Operation
R
18
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
ShortRangeHeatedReflectorPanel(Partnumbers2104B0715,2104B0717)
Terminal Identification Wire ColourCustomer Connection
(>20V)Customer Connection
(<20V)Heater Resistance
(R)
1 White 0V 0V
2 Black or Brown >20Vdc 100Ω3 Blue 18-20Vdc 68Ω6 Green Earth Earth
LongRangeHeatedReflectorPanel(Partnumber2104B0716)
Terminal Identification Wire ColourCustomer
Connection (>20V)Customer
Connection (<20V)Heater Resistance (R)
1 White 0V 0V
2 Black or Brown >20Vdc 33Ω3 Blue 18-20Vdc 23Ω6 Green Earth Earth
Important:IftheTransmitterandReceiverunitsharesapowersupplycablewiththeHeatedReflectorPanel, a check must be made to verify that a minimum voltage of 18V is available at the TransmitterandReceiverwhentheReflectorPanelisoperating.
3. Installation and Operation
Terminal 6
Terminal 3Terminal 2Terminal 1
Conduit
External Earth (GND) Insulating Adaptor Field Wiring
Earth (GND) Terminal
19
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
3.4.2 Power Supply Connections - Turbo heating DisabledWhen connected as shown in section 3.3 Transmitter and Receiver Connections the Transmitter has turbo heating mode enabled.
This means that during conditions of low ambient temperature, additional heating power is applied to the unit’s window to minimise condensation, frosting and snow buildup.
If the application/installation does not require turbo heating, power consumption can be reduced by disabling this mode.
The turbo heating is disabled by reversing the power supply connections to the Transmitter as shown in the following diagram. All other connections remain the same.
Notes:
1. Only Transmitters have turbo mode heating which can be disabled. The Receiver uses proportional heating, which cannot be disabled.
2. Even with turbo mode heating disabled the Transmitter window still receives standard levels of heating.
3. Do not reverse the Receiver power supply connections. This will not damage the unit, but the unit will not work.
3. Installation and Operation
Junction BoxTransmitter Connections
Reverse these connections to disable turbo-heating Cable Shield
Control Cabinet Connections
Black 0V+24V DC Supply
Tx +24V
Tx 0V
Instrument (Clean) Earth
0V DC SupplyRed +24V
Green/ GND Yellow
20
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
3.5 Installation Procedure
3.5.1 GeneralInstalling the Searchline Excel Cross-Duct is done in two stages. First the duct is prepared, and the Excel componentsmechanicallyfixedinplace.Secondly,theelectricalwiringisconnected.TheTransmitterandReceiver assembly must be fully assembled and mounted to the duct structure before making the electrical connections.
3.5.2 Mechanical InstallationVerify that the equipment to be installed is correct for the type of installation required (i.e. short or long range.)
3.5.2.1 Transmitter and Receiver Unit
Identifytheholesinthemountingplateusingthefollowingdrawingandtable:
3. Installation and Operation
155m
m
100mm
Identity Quantity Size Used for
A 4 M6 tapped Mounting block mounting
B 8 6.5mmMounting plate to support
bar mounting
C 2 14mmClearance for support bar
fixing nuts
D 1 10mm Drain for mounting block
E 1 25mmCross-Duct optical measurement path
F 1 M6 tapped
DVC100 (M) junction box mounting
(used in conjunction with bottom two F1 holes)
F1 4 M6 tappedDVC100 (M) MK2 junction
box mounting
G 4 M6 tappedBARTEC junction box
mounting
H 2M10
tappedDX100 (M) junction box
mounting
NOTE: If unused, the top two F1, top two G and the F holes should be blanked off to avoid leakage from the duct. Use the 5 off M6 x 8 screws, single coil washers and plain washers supplied.
21
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
3. Installation and Operation
(1) Stick the supplied self-adhesive mounting plate cut-out template onto the duct wall in the position chosen for the Transmitter and Receiver unit.
Note: The intersection of the bold lines on the template (point X) corresponds with the centre of the unit’s infrared beam.
(2) AtthisstageitisadvisabletomarkthecorrespondingpositionfortheReflectorPanelontheoppositesideoftheduct.SticktheReflectorPanelcut-outtemplatetotheoutsideoftheductwalloppositetheTransmitter and Receiver.
Ensure that point X* on the Reflector Panel template is directly opposite point X on the mounting plate template.
(3) Drill 10 mounting holes (diameter 7mm) in the positions marked G on the Transmitter and Receiver unit template.
(4) Cut a rectangular aperture in the duct wall.
Follow outline H.
(5) Check that the path from the aperture to the opposite wall of the duct is clear and unobstructed.
(6) Measure the distance (in metres) across the duct.
Record this distance as it is required later during commissioning.
(7) Insert the two mounting plate support bars through the aperture and attach them to the inside of the duct, using an M6 nut and washer screwed onto the stud in each support bar.
Check that the threaded holes in the support bars line up with the holes drilled in the duct.
(8) Attach the mounting plate, Transmitter and Receiver unit and junction box assembly.
Use M6 x 20 cap head screws and washers for the mounting plate.
(9) Run the Transmitter and Receiver conduits into the junction box cable entries. (see 3.5.3 (2)).
3.5.2.2HeatedReflectorPanel
(1) Ifnotalreadyinplace,sticktheReflectorPanelcut-outtemplatetotheoutsideoftheductwalloppositethe Transmitter and Receiver.
Ensure that point X* is directly opposite point X on the mounting plate template. This ensures that the beam from the Transmitter hits the centre of the reflector.
(2) Drill six mounting holes (7mm diameter) in the positions marked J on the template.
(3) Following outline K, cut a square aperture in the duct wall.
(4) InsertthetwoReflectorPanelsupportbarsthroughtheapertureandattachthemtotheinsideoftheduct,using an M6 nut and washer screwed onto the stud in each support bar.
Check that the threaded holes in the support bars line up with the holes drilled in the duct.
(5) Fit four M6 x 20 cap head screws into the holes in the support strips leaving approximately 5mm of thread exposed on the outside of the duct.
(6) Slottheretro-reflectorassemblyovertheheadsofthescrewsandallowitsweighttobesupportedonthe exposed sections of thread.
(7) Tightenthefourscrewstoclamptheretro-reflectorassemblyinposition.
22
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
3.5.3 Electrical Installation(1) Isolate all associated power supplies and ensure that they remain OFF until the instruction in the
commissioning procedure to apply power.
See section 3.6 Commissioning. If the units are to be installed with junction boxes other than DVC100(M)/DX100 (M) types, ensure that the boxes have:
a. M20 cable gland entries for BASEEFA units, or 3/4 NPT for UL
b. terminals for five wires and an earth.
(2) RemovetheM20blankingplugs(iffitted)andattachtheSearchlineExcelCross-DuctTransmitterandReceiver cables to their junction box.
Fit the locking rings (if supplied) before terminating the cables in the junction box.
(3) Fit approved cable glands to the junction box cable entries.
Use sealing washers where necessary to maintain the ingress protection rating.
(4) Fit approved blanking plugs to all unused cable entries.
(5) Make electrical connections. See section 3.3.
3.6 Commissioning
3.6.1 GeneralDuringcommissioningtheSHC1HandheldInterrogatorisusedtocommunicatewiththeSearchlineExcelCross-Duct.FulldetailsoftheSHC1HandheldInterrogatorcanbefoundinAppendix A.
Thecommissioningprocessconsistsofthefollowingsteps:
• Connect the Handheld Interrogator to the gas detector
• Power up the gas detector and set the interrogator for operation with Excel
• Set the Excel real time clock
• Initialise the Excel gas detector
• Functionalcheckwithtestfilters
• Finish
3.6.2 Connecting the InterrogatorConnecttheSHC1HandheldInterrogatortothegasdetectorinoneofthefollowingways:
• viaaHoneywellAnalyticsDVC100(M)/DX100(M)JunctionBox-connecttheInterrogator directly to the junction box via the IS socket, e.g.
3. Installation and Operation
ESC
CalibratorType SHC1
23
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
• viaanothertypeofjunctionbox,e.g.HawkePL612-usingtheSHCProtectionDevice.
See the following diagram and description and Appendix C - Spare Parts
Notes:
1. The protection device must always be used for this type of connection.
2. A hot work permit may be required for this procedure.
Carryoutthefollowingproceduretoconnectusingtheprotectiondevice.:
(1) Isolate all power supplies.
(2) Remove the cover of the junction box.
(3) HardwiretheflyingleadoftheSHCProtectionDevicetothecommunicationslinkterminalsintheboxasshown:
(4) ConnecttheInterrogatortotheISconnectorontheendoftheSHCProtectionDevice.
3. Installation and Operation
Flying LeadIS Connector
Junction Box
To Receiver SHC Protection Device Flying Lead
Blue B
Orange A
Black 0V
White 4-20mA
Red +24V
Green/Yellow GND
24
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
3. Installation and Operation
ESC
Z - SHC1 EXCELInterrogator
CalibratorType SHC1
3.6.3 Power Up(1) ApplypowertotheSearchlineExcelCross-DuctTransmitterandReceiverandHeatedReflectorPanel
units.
(2) Press and hold the (Enter) key on the Interrogator keypad for at least two seconds. This switches on the unit.
Note: Full details of the SHC1 Handheld Interrogator can be found in Appendix A.
TheInterrogatordisplaysthefollowingstart-upmessageforapproximatelythreeseconds:
Z - SCH1 Excel Interrogator 4V0
(3) Quickly check the type of connected detector shown on the top line of the message.
The display shows Excel or Optima+ or Optima.
(4) If the unit displays Optima+ or Optima immediately press the ESC key on the keypad.
The ESC key must be pressed within 3 seconds to have any effect. Also see Appendix A, section 5.6.
This toggles the Interrogator mode between Excel, Optima Plus and Optima.
The start-up message is updated and displayed again for 3 seconds then the unit displays the Main menu, which is the top level of its Interrogator’s menu style interface, as follows:
Main Display v
The first line of the display shows the current level in the menu tree and the second line displays a sub-menu title, action or data.
v
25
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
3.6.4 Setting the Real-Time ClockThe gas detector clock needs to be initially set so that faults, events, etc., can be accurately recorded and tracked for diagnostic purposes.
(1) Select Calibrate from the Main menu by pressing the (up) and (down) keys on the keypad to navigate through the menu options.
(2) Press (Enter) on the Interrogator keypad to display the Calibrate menu.
(3) Select SetTime/Date from the Calibrate menu.
(4) Press Enteronthekeypadandaninitialsettimedisplaysimilartothefollowingappears:
Time 09:26 09
The top line shows the current time and the second line shows the new hours setting.
(5) Set the hour using the up and down keys on the keypad.
(6) Press Enter on the keypad and the new minutes setting is now displayed on the second line.
Time 09:26 09:26
(7) Set the minutes using the up and down keys on the keypad.
(8) Press Enteronthekeypadandthedisplayforsettingthedatenowappearsasfollows:
Date 20APR03 20
The second line shows the new day setting.
(9) Set the day using the up and down keys on the keypad.
(10) Press Enter on the keypad and the new month setting is then displayed.
(11) Repeat the procedure to set the month and year.
(12) When complete press Enter on the keypad to return to the Calibrate menu.
Notes:
1. The time and date will not be updated unless both are entered and accepted without error.
2. Pressing ESC on the keypad at any time, aborts the current setting immediately and returns to the previous setting or menu option.
3. Installation and Operation
vv
vv
vv
26
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
3.6.5 Initialising the Searchline Excel Cross-Duct Gas DetectorIn this part of the procedure details about the gas detector must be entered so that the Interrogator can then complete the commissioning of the gas detector using the correct data.
(1) Select CALIBRATE from the Main menu.
Press the and keys on the keypad to navigate through the menu options..
(2) Press on the interrogator keypad to display the calibrate menu
(3) Select INSTALL from the calibrate menu.
(4) Press ontheinterrogatorkeypadandthefollowingisdisplayed:
System Type Duct Mount
The gas detector type cannot be changed.
(7) Press on the keypad and the current path length setting in metres is displayed, e.g.
Path Length 2.5
(8) Set the path distance (in metres, to the nearest 0.1metre) between the transmitter and receiver unit and thereflectorpanel.
Use the and keys on the keypad.
Note: Do not double the distance, enter only the duct width.
IMPORTANT – THE PATH LENGTH IS USED TO CALCULATE THE GAS READING. ENSURE THAT IT IS ENTERED CORRECTLY
(9) Press onthekeypadandthefollowingmessageisdisplayed:
When finished the interrogator displays the following message for at least three seconds:
The following message is now displayed:
No alignment adjustments are provided. If the mechanical installation is satisfactory Searchline Excel Cross-Duct can now be initialised.
3. Installation and Operation
vv
vv
Self Test Please Wait
Checks Passed
SIG: TGT:
27
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
(10) Press onthekeypadandthedisplayshows:
(11) Press andthedisplaywillshowthefollowingmessagewhilsttheunitisinitialising:
When the gas detector has completed initialisation, the following message is displayed for three seconds:
The display changes to show:
(12) Press on the keypad. The installation is now complete.
If Excel does not initialise, check that:
• the actual duct width agrees with the value entered in step 8 above.
• the reflector panel is clean and fitted securely.
• the reflector panel is mounted opposite the Transmitter and Receiver unit, and perpendicular to the beam
For further help see Chapter 5, Problem Solving.
3. Installation and Operation
Signals OK
Ensure Zero gas then press Enter
Zero Cal OK
Installation complete
Press Enter to release 4-20mA
28
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
3.6.6 Functional checkCarryoutafunctionalcheckusingplastictestfilters(partnumber2104N3000).Plastictestfiltersinsertedinthe measuring path produce infrared absorption which approximates that of methane gas.
ThefunctionaltestfilterssuppliedfortestingSearchlineExcelCross-Ductdonothaveaspecifiedgasreadingrange.Instead,theyaremarkedwithlettersBtoH,withthereadingproducedbyeachfilterincreasingfromfilterBtofilterH.
TheprocedurefortestingaSearchlineExcelCross-Ductusingthefunctionaltestfiltersisasfollows:-
(1) Select DISPLAY from the Calibrate menu. (This inhibits the Searchline Excel Cross-Duct output).
(2) Remove the top cover from the mounting block.
The cover is retained by 3 x M4 captive bolts, and a chain attaches the lid to the mounting block when opened. There are no electrical hazards inside the mounting block and a hot work permit is NOT required.
(3) Insertasuitablefunctionaltestfilter(seetablebelow)intotheslotinthemountingblockinfrontofthereceiver.
Duct Width Minimum Test Filter Recommended Test Filter
0.5 - 0.75m B B
0.75 - 1.0m B C
1.0 - 1.5m C D
1.5 - 2.0m D E
2 - 3m E F
3 - 4m F G
4 - 5m F H
(4) Record the gas reading that is produced. This reading should be treated as correct and should be used to verify correct operation in the future.
(5) Removethetestfilterandreplacethetopcoverofthemountingcell.
(6) UsingtheSHC1HandheldInterrogatorreleasetheSearchlineExcelsignaloutput.
The output can be released by pressing ESC followed by on the keyboard
3.6.7 FinishTofinishthecommissioningprocess:
(1) Select the Power Off option from the interrogator Main menu
(2) Press on the keypad
Alternatively, press the and ESC keys simultaneously for a fast power off.
Notes:
1. The SHC1 Handheld Interrogator powers down automatically after five minutes of inactivity in order to preserve battery life.
2. The fast power off facility and auto power off are disabled when a menu option is selected that modifies the unit’s configuration.
(3) Disconnect the interrogator from the Excel gas detector, reversing the steps described in section 3.6.2.
3. Installation and Operation
29
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
3.7 System Controller CalibrationThis procedure is used to set up the system controller using the Searchline Excel Cross-Duct gas detector. Achosenfixedoutputsignal issentfromthegasdetectortothesystemcontrollerallowingcalibrationofthe 0 - 100% scale of the controller without having to use gas. The steps use procedures described in the previous section.
Tocalibratethecontrollercarryoutthefollowingprocedure:
(1) Connect the Interrogator to the gas detector.
See Connecting the Interrogator to Searchline Excel Cross-Duct Gas Detector.
(2) Turn on the Interrogator.
See Powering Up.
(3) Select Calibrate from the main menu.
Press the up and down keys on the keypad to navigate through the menu options.
(4) Press Enter on the Interrogator keypad and the Calibrate menu is displayed.
(5) Select Force 4-20 from the Calibrate menu.
(6) Press Enteronthekeypadandadisplaysimilartothefollowingappears:
(7) Use the up and down keys on the keypad to set the displayed output current to the desired value.
The values can be changed in steps of 0.1mA in the range 1mA to 21mA.
(8) Press Enter on the keypad.
This selects the currently displayed value and forces the gas detector to output that current. Once complete adisplaysimilartothefollowingappears:
(9) Carry out checks on the controller by following the instructions in the controller documentation.
(10) When checks are complete press ontheInterrogatorkeypadandthefollowingdisplayappears:
(11) Press Enter on the keypad.
The following message is displayed:
The fixed output is released and the gas detector returns to normal operation.
3. Installation and Operation
4-20 current 4.5 mA vv
Fixed 4-20 mA Press Enter vv
Press Enter to Release 4-20 vv
4-20 Released
30
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
(12) Turn off the Interrogator and disconnect it from the gas detector.
Note: The recommended alarm level settings for Searchline Excel Cross-Duct are as follows:-
Operating range Minimum low alarm Maximum high alarm
0.5m - 2.0m 20%LEL 40%LEL
2.0m – 5.0m 10%LEL 30%LEL
3.8 InstallationChecks/TestsThe following information is for the guidance of personnel carrying out installation checks/tests on Searchline ExcelCross-Duct.Ingeneralitshouldbenotedthat:
• SearchlineExcelCross-Ductshouldonlybeinstalledbyfullytrainedpersonnel,trainedbyHoneywellAnalyticsoranauthorisedHoneywellAnalyticstrainer.
• Detailed information concerning installation, alignment and commissioning is provided in this Technical Handbook.
• SearchlineExcelCross-Ductisexplosionprotectedbyacertified,flameproofenclosure.
• Carefullyreadthesafetywarnings,cautionsandcertificationdetailsinthishandbook.
• Ensure that they have been complied with, before and during the installation.
• A copy of the subsequent Installation Check Sheet should be completed for each Searchline Excel Cross-Ductgasdetectorinstalled.InordertohelpHoneywellAnalyticstoprovideefficientassistance/serviceintheeventofproblems,thesheetshouldbereturnedtoHoneywellAnalyticsortooneoftheir agents.
3. Installation and Operation
31
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
Searchline Excel Cross-Duct: Installation Check SheetCUSTOMER/OPERATOR
SITE / FACILITY
SYSTEMTYPE: Short Range Long Range OPERATING RANGE
GASTABLE: METHANE
DETECTORLOCATION:
TAGNO.(TX/RX): TAGNO.(Reflector):
SERNO.(TX/RX): SERNO.(Reflector):
MODSTATE(TX/RX):MOD STATE (Reflector)
CERTIFICATION:
CHECK/TEST TRANSMITTER/RECEIVER CHECK/TEST REFLECTOR
Mount Rigidity Mount Rigidity
Vibration: Vibration:
Excessheat: ExcessHeat:
SupplyVoltage: Supply Voltage
Earthing: Earthing:
RFI/EMC RFI/EMC
Contaminants: Contaminants:
BEAMOBSTRUCTIONS/BLOCKS:
(cont.)
TESTFILTER: (B–H) Response: %LEL Pass: Fail:
4-20 mA LOOP INTEGRITY Pass: Fail: Untested:
FAULT/WARNINGLOG: Clear: Faults/Warnings:
(cont.)
INSTALLATIONSATISFACTORY: Yes: No: SIGNED:
INSTALLED BY (PRINT) DATE:
IF INSTALLATION UNSATISFACTORY, REASONS
RECOMMENDATIONS
CUSTOMERNOTIFIED:
SYSTEMSTATUS: Operational: Nonoperational:
3. Installation and Operation
32
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
3. Installation and Operation
The following notes are to help the installer enter the correct information onto the check sheet.
Site/Facility
Enter the name and geographical location of the site/facility.
Operating Range
Enterthedistance(preferablyinmetres),betweentheTransmitterandReceiverunitandtheHeatedReflectorPanel.
Detector Location
Enter the location/position of the detector
Tag No
Enter the Tag No,orequivalent,thathasbeenallocatedtotheTransmitterandReceiverunitandtheReflectorPanel.
Mod State
Enter the Mod Stateoftheunitsasindicatedontheircertification/productlabels.
Certification
Enterthecertificationoftheunits,e.g.
ATEX, IECEx, UL
Mount Rigidity
When pushed hard and released, the mount/supporting structure should return quickly to its original position andshouldnotwobbleorsway.Ifthemount/supportisunacceptable,brieflydescribetheproblem,e.g.
Mount wobbles unacceptably
Vibration
Check the installation and its close surrounds for potential or existing sources of excessive vibration. Such sources could include heavy plant/machinery, turbines, generators etc.
Excess Heat
Checktheinstallationanditssurroundsforpotentialsourcesofexcessiveheat.Theunitisspecifiedupto+65ºC.Potentialsourcesofexcessiveheat includedirectsunlight inhotclimates,flare-stacks,generator/turbine exhausts and steam vents.
Enter a brief description, e.g.
Flare-stack 2 metres away
33
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
Supply Voltage
Checkthatthesupplyvoltageappliedtotheunitiswithinthespecified18Vto32Vrange(TransmitterandReceiver)or18to28Vrange(HeatedReflectorPanel)andisstable.Enterthesupplyvoltageandstability,e.g.
22.5V, stable, 19V,+2Vfluctuation
Earthing
Inspect the earth connections to the units. If the unit is connected to local metalwork or the safety/general use earth, enter ‘Local Safety. If the unit has been isolated from local metalwork/ earths and is connected to a clean, instrument earth, enter Instrument earth. (See section 3.3, Electrical Connections).
RFI/EMC
Assess the installation, cabling and its close surrounds for known/potential sources of excessive RF/Electromagnetic Interference. Such sources could include radio/radar transmission antennae, high voltage switch-gear, large electrical generators/motors etc.
SearchlineExcelCross-DuctcomplieswiththemoststringentrequirementsspecifiedinEN50270.Itisthereforemorelikelythatthefieldcablingwillpickupinterferencedirectlyonthe4-20mAand0Vconnectionsandthatthis will affect the reading received at the control room.
Enterbriefdetailsofknown/potentialEMIsourcesthatarewithinfivemetresofthegasdetectorand/oritscabling. If cable is unscreened or inadequately protected, note concerns.
Examplesofthesortofinformationtoenterare:
10m cable, unscreened, Radar, 2m from Receiver, Cable routed over 400kW generator
(See section 3.3 Electrical Connections).
Contaminants
Assess the installation and its surrounds for sources of contaminants that could build up on the unit’s windows. Such contaminants could include oil mist, heavy sea spray, drilling mud, dirty exhaust fumes, wave splash etc.
If there is a realistic possibility that such contaminants could cause a significant problem, enter a briefdescription, e.g.
Drilling mud spray, Diesel generator exhaust
Test Filter
After completing the installation procedure, enter the DISPLAY mode and test the gas detector response with aplastictestfilter.Enterthenominalvalueofthetestfilter,andtheunit’sdisplayedresponse.Whentestinginfuture,usethesametestfilterandcomparetheresponsetothevalueobtainedatinstallation.SeeChapter4, Maintenance.
4 - 20mA Loop Integrity
Test the 4 - 20mA loop integrity by forcing the unit to output a known current and monitoring this at the control room or with a multimeter inserted into the loop. Mark the appropriate box.
3. Installation and Operation
34
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
Fault/WarningLog
Check the fault/warning log. In order for the unit to complete installation satisfactorily, the ACTIVE FAULTS log must be CLEAR.UsetheHandheldInterrogatortodiagnoseandremedyallACTIVE FAULT.
Wherever possible, it is recommended to CLEAR any ACTIVE WARNINGS, since these may lead to faults in the future.
Faults/Warning
Enter any ACTIVE FAULTS or ACTIVE WARNINGS that could not be cleared from the log, e.g.
BEAM BLOCK, E_ZERO_NOT_CALIBRATED
Installation Satisfactory
OnlyfullytrainedpersonneltrainedbyHoneywellAnalyticsorHoneywellAnalyticsauthorisedtrainerscandeclare an installation satisfactory. Mark the YESboxandsigntheformif:
a. having completed the installation and testing, the unit is operating correctly, and
b. in the trained installer’s opinion, the unit should continue to operate reliably in this installation/ operating environmentprovidingthatnothingsignificantabouttheinstallation/environmentischanged.
If the unit is not operating correctly or there are aspects of the installation/ operating environment which in the trained installer’s opinion could or will result in unreliable operation, mark the NO box.
Reasonsfordeclaringaninstallationunsatisfactorycouldinclude:
excessivemovement/vibrationofunit’smounting, received signal levels too low,
supply voltage too low, 4 - 20mA loop integrity faults,
unclearable active faults, any prevailing or probable condition which is known to unacceptably reduce reliability or availability
If Installation is Unsatisfactory, Reasons
Brieflystatetheprincipalreasonswhytheinstallationisunsatisfactory,e.g.
Excessivemovement,insufficientreceivedsignallevels,Unitoverheatedbyintensesunlight
Recommendations
Brieflydescribe the recommendedactionswhichneed tobeperformed inorder tomake the installationsatisfactory, e.g.
Mountingrequiresbracing/stiffening, Provide correct supply voltage
CustomerNotified
Makesurethattherelevantcustomer/operatorisnotifiedoftheinstallationproblem(s).Markboxaccordingly.
System Status
Upon leaving, note the gas detectors status, i.e. operational or nonoperational.
3. Installation and Operation
35
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
4. Maintenance
The Searchline Excel Cross-Duct maintenance should include regular cleaning of the Transmitter and Receiver unitwindowsandtheHeatedReflectorPanel,re-zerooftheCross-DuctunitandfunctionaltestusingTestFilters (2104N3000).
Note: The objective is to keep the windows clean. The rate of build up of contamination depends on local site conditions. It is recommended that the installation is closely monitored during the first few weeks of operation to establish how frequently cleaning will be required.
Depending on the local regulations and site conditions, cleaning and functional testing of the gas detector can be carried as described in the following sub-sections. The gas detector should remain powered during these procedures.
Caution: Searchline Excel Cross-Duct does not contain any user serviceable parts. Do not open or disassemble the Transmitter and Receiver unit (other than as instructed), or the Heated ReflectorPanel.Thewarrantyofunitswhichhavebeenopenedisinvalidated.
Note: THE INFRARED BEAM IS INVISIBLE AND EYE SAFE.
4.1 Inspection and CleaningCaution: Do not use solvents or abrasives on the Searchline Excel Cross-Duct units.
(1) Inspect the Searchline Excel Cross-Duct units, junction boxes and cabling for signs of physical damage.
(2) UsingtheSHC1HandheldInterrogatorinhibittheSearchlineExcelCross-Ductsignaloutput.
Since the signal output may vary during cleaning, due to the optical path being disturbed, it is important to inhibit the analogue output. The quickest way to inhibit the Excel output is to select DISPLAY from the Calibrate menu.
(3) To access the Transmitter and Receiver windows, and the beamsplitter, remove the top cover from the mounting block.
The cover is retained by 3 x M4 captive bolts, and a chain attaches the lid to the mounting block when opened. There are no electrical hazards inside the mounting block and a hot work permit is NOT required.
(4) Clean any dust or dirt from the Transmitter and Receiver windows and the beamsplitter using soapy water or window cleaner and a soft cloth.
(5) Replace the top cover of the mounting block.
(6) LoosenthefixingswhichsecuretheHeatedReflectorPanelandremoveitfromtheductwall.
(7) CleananydustordirtfromtheHeatedReflectorPanelusingsoapywaterorwindowcleanerandasoftcloth.
(8) ReplacetheReflectorPanelontheductwallandtightenfixings.
(9) UsingtheSHC1HandheldInterrogatorreleasetheSearchlineExcelsignaloutput.
The output can be released by pressing ESC followed by on the keyboard.
(10)Re-zerothesystem(seesection4.2).
To reduce the need for cleaning, it is possible to connect a supply of compressed air to the Air Shield port on themountingblock(seediagraminsection4.3).Theairshieldportistheoneclosesttotheduct.Byflowingclean air into the mounting block (which then moves out into the duct), the build up of contamination inside the mounting block will be reduced. It is essential that this air supply is oil and dirt free. Precautions such as afilterandaliquidtrapshouldbeinstalledintheair-line.
36
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
4.2 Re-zero(1) UsingtheSHC1HandheldInterrogator,selectCalSensor from the Calibrate menu. The analogue output
will be inhibited. (See Appendix A for details about how to use the Interrogator).
Note There must be no gas in the system beam path whilst this procedure is carried out.
(2) Thefollowingmessageisdisplayed:
(3) PressEnter.Thefollowingmessageisdisplayedwhilethecalibrationoperationisbeingperformed:
(4) Ifthecalibrationissuccessful,thefollowingmessageisdisplayedforaperiodofthreeseconds:
(5) UsingtheSHC1HandheldInterrogatorreleasetheSearchlineExcelsignaloutput.
The output can be released by pressing ESC followed by on the keyboard.
4.3 Functional Checking
4.3.1 Functional Checking with Gassing Cell (Short Range versions only)Searchline Excel Cross-Duct incorporates a built in gassing cell for functional test purposes. In order to use the gassing cell, the mounting block lid must be in place, to maintain a gas tight seal.
Beforeusingthegassingcellforthefirsttime,removetheendsoftheplasticnozzles(withaknifeorwirecutters). Rubber end caps are used to seal the tubes afterwards.
4. Maintenance
Ensure Zero Gas Press Enter
Processing Data Please Wait...
Zero Calibrated
Air Shield
Slot for test filter
Gas In/Out
Gassing Cell
Transmitter
Mounting Block
Receiver
37
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
Togetthebestaccuracywhenusingthegassingcell:
(1) Ensurethatthegassingcellcontainsfreshair,andperformazerocalibrationontheExcel
(2) ApplythetestgasandallowsufficienttimetofullyfillthegassingcellandcheckthattheSearchlineExcelCross-Duct output stabilises.
A flow rate of less than 0.5 litres per minute is advisable, to avoid pressurising the gassing cell.
(3) For a methane calibrated unit tested with 100%v/v methane (UL version) or 88%v/v methane (ATEX, IECEx version),theexpectedreadingcanbecalculatedfrom:
Gasreading=100%LEL/(2xductwidth)
A few examples are shown in the following table, and the tolerance to be applied is ± 20% of reading or ± 10%LEL (whichever is greater). The variability in the readings is due to a number of factors such as variation in air pressure,flowrate,andtolerancesinthegascomposition.
Test GasUL version
Test GasATEX, IECEx version
Duct Width Expected Reading
100% v/v Methane 88%v/v Methane 0.5m 100%LEL ± 20%LEL100% v/v Methane 88%v/v Methane 0.8m 60%LEL ± 12%LEL100% v/v Methane 88%v/v Methane 1.0m 50%LEL ± 10%LEL100% v/v Methane 88%v/v Methane 1.5m 33%LEL ± 10%LEL100% v/v Methane 88%v/v Methane 2.0m 25%LEL ± 10%LEL100% v/v Methane 88%v/v Methane 2.5m 20% LEL ± 10%LEL
(4) Aftercheckingthereading,ensurethatthegasisflushedoutofthegassingcell,withcleanairornitrogen,untilthereadingreturnstozero.
(5) Finally replace the rubber caps over the gassing ports.
4.3.2 Functional Checking with Test FiltersFunctionalcheckingoftheSearchlineExcelCross-Ductcanalsobedoneusingplastictestfilters(partnumber2104N3000).Plastictestfiltersinsertedinthemeasuringpathproduceinfraredabsorptionwhichapproximatesthat of methane gas. For the procedure see section 3.6.6.
Comparethegasreadingtotheoriginalvaluerecordedforthisunitwhentestedwiththisfilter.Providedthatthe reading is within ±15% LEL of the original value, the unit is working correctly.
Ifthegasreadingisnotwithintheexpectedrangeitispossiblethattheunitneedscleaningorre-zeroing.See section 4.1.
4. Maintenance
WARNING:
Testsgasesmaybeflammableand/ortoxic.Takeappropriateprecautionswhen handling
WARNING:
Take the necessary precautions to ensure safety when dealing with high concentration gases
38
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
5. Problem Solving
The majority of gas detector problems/faults can be diagnosed and corrected using the installation kit.
Theinstallationkitincludes:
• SHC1 Handheld Interrogator
• setoffunctionaltestfilters
An electrical multimeter is also useful when diagnosing electrical/wiring problems.
Refer to the troubleshooting tables in this chapter for a list of problems, possible causes and actions.
Caution: Searchline Excel Cross-Duct does not contain any user serviceable parts. Do not open or disassembletheTransmitterandReceiverunit,ortheHeatedReflectorPanel.Thewarrantyof units which have been opened is invalidated.
Note: THE INFRARED BEAM IS INVISIBLE AND EYE SAFE.
RS485 Modbus signal errors may occur when Excel is connected via a DXI00 (M) Termination Unit and is interrogated/commanded from a network control centre. For troubleshooting these issues refer to the DX100 Series Termination Units Technical Handbook.
If, after following the recommendations in this section, the problem persists, please make available the following informationbeforecontactingHoneywellAnalytics:
• Installation Check Sheet See Chapter 3.
• Any error message DisplayedontheHandheldInterrogatorscreen.
• Any error code DisplayedontheHandheldInterrogatorscreen.
Fault/Problem Causes Remedies
No mA output Electrical installation problem
1) Check that the +24V supply is reaching the unit. Voltage at the unit should be between +18V and +32V.
2) Check cables and connections to the unit, especially the 4-20mA loop connections.
3) Check that the unit has the correct type of 4-20mA output sink/source for use with the controller that it is connected to.
Output is 0mA (nominal)
Unit is in FAULT conditionConnect the SHC1 Interrogator to the unit and use its DIAGNOSTIC menu options to ascertain the reason for the FAULT report.
Beam block Check that beam path is clear from the Transmitter and Receiver to the Reflector. Remove any obstruction if present.
Heavy contamination of opticsCheck the Transmitter and Receiver windows and the Heated Reflector Panel for build up of contamination. Clean the windows if required. Re-zero unit.
Output is 2.5mA. (BEAM BLOCK)
Beam path is blocked Check that beam path is clear from the Transmitter and Receiver to the Reflector. Remove any obstruction if present.
Output is 3mA(LOW SIGNAL)
Heavy contamination of opticsCheck the Transmitter and Receiver windows and the Heated Reflector Panel for build up of contamination. Clean the windows if required. Re-zero unit.
39
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
Output is 2mA(INHIBIT)
Unit has been inhibited by the Interrogator
Release output from INHIBIT state using SHC1 Interrogator.
Unit executing power-up routine
1) Wait for 1 minute. When power-up routine is completed satisfactorily the unit’s output should exit the INHIBIT state.
2) If unit remains in INHIBIT, check the +24V supply is reaching the unit. If the voltage is below +18V or is fluctuating above and below +18V, the unit may be being prevented from completing power-up. (This is an electrical installation problem.)
Comms Error 99 reported by Interrogator software
Wrong communication mode selected on the Interrogator
1) Select Change Mode option on the Interrogator.
2) Change the communication mode to Excel
Interrogator software version is incompatible with Excel software version
Version 1V0 Interrogator software to be used with Excels running 1V0 software.
Version 2V0 Interrogator software can be used with Excels running 2V0 software or higher.
Version 3V0 and 3V1 Interrogator software can be used with Excels running 3V0 software or higher.
The latest version of Interrogator software is 4V0. This version works with 3V0 and higher Excels, Optima and Optima Plus.
Comms Error 100 reported by Interrogator software
Incorrect communication connection
1) Check that Interrogator is correctly plugged into the IS socket on the DVC100(M)/DX100(M) junction box.
2) Check that the RS485 A and B wires from the Excel unit have been connected to the correct terminals inside the DVC100(M)/DX100(M) junction box
Excel unit is not powered up Check that the +24V supply is reaching Excel unit correctly. The Supply voltage at unit should be between +18V and +32V.
Interrogator battery lowCheck the Interrogator battery and replace if low. See Appendix A. Section A.4
Interrogator Installation Failed message when attempting initialisation
The installation has failed to meet the acceptable criteria for signal levels
1) Check that the signal levels reaching the Receiver are greater than 0.7 and less than 1.5. If not, check that the Reflector Panel is mounted opposite the Transmitter and Receiver unit and perpendicular to the beam.
2) Check that the correct range has been entered for the installed path length.
3) Check that there are no objects obscuring part or all of the beam path.
4) Check that the windows of the Receiver and Transmitter and the Heated Reflector Panel are clean.
5) Check that the structures that the Transmitter and Receiver are mounted on are stable and free from significant angular movement/vibration.
6) Check that there is no gas in the beam - which prevents successful zeroing.
5. Problem Solving
40
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
No signal or very low signal at Receiver
The beam path has become obscured
Check that the beam path is clear from Transmitter and Receiver to the Reflector Panel. Remove any obstruction if present.
No output from Transmitter
1) Check that the Transmitter is flashing. When viewed on the axis, an orange flash can be seen coming from the Transmitter.Alternatively, listen for a distinct ticking sound when the lamp flashes.
Note: The infrared beam is invisible and eye safe.
2) If the Transmitter is not flashing, check that the +24V supply is reaching the Transmitter correctly.
Unit does not respond exactly as expected to test filters
Plastic test filters are only an approximate simulation of gas
Searchline Excel units are calibrated on real gas. This results in a variation of the response of different Excel units to plastic test filters. See section 3.6.6
1) Check that the response to the test filters is within the limits stated in this handbook compared to the response obtained at initial installation. See section 4.3.2
2) Check that the correct test filter is being used.
Contamination of windows
1) Check the Transmitter and Receiver and Heated Reflector Panel windows for build up of contamination. Clean windows if required. See Chapter 4.
2) Re-zero unit.
Drift of unit’s zero position1) Verify that there is no gas in the beam path.
2) Re-zero the unit
Unit appears to be reporting a negative gas reading on the 4-20mA
Misinterpretation of INHIBIT, BEAM-BLOCK or LOW SIGNAL currents that are output on the 4-20mA
Searchline Excel does not report negative gas readings on the 4-20mA.
1) Configure controller/PLC to interpret and present currents below 4mA correctly, or
2) Familiarise operators with the interpretation of sub 4mA output currents from Excel as follows:
FAULT 0mA INHIBIT 2mA BEAM-BLOCK 2.5mA LOW SIGNAL 3mA, or3) Reconfigure the INHIBIT, BEAM-BLOCK and LOW SIGNAL
currents output by the Excel unit.
Diagnostics report Neg Gas Reading
Contamination of windows
1) Check the Transmitter and Receiver and Heated Reflector Panel windows for build up of contamination. Clean windows if required. See Chapter 4.
2) Re-zero the unit.
Negative drift of unit’s zero position
Re-zero the unit
Diagnostics report Baseline Drift
Contamination of windows
1) Check the Transmitter and Receiver and Heated Reflector Panel windows for build up of contamination. Clean windows if required. See Chapter 4.
2) Re-zero the unit.Drift of unit’s baseline Re-zero the unit
5. Problem Solving
41
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
Diagnostics reportBad Temperature
Unit has been operated at a temperature outside its specified and certified range
1) When Ex certified equipment is operated outside its certified range, its type approval certification is invalidated along with its warranty. Such equipment should be removed from service in potentially explosive atmospheres.
2) Investigate the cause of the excessive temperature excursion and take steps to prevent recurrence. (e.g. fit sunshade or heat-shield, or relocate detector, etc.)
Diagnostics report Supply Fault
Incorrect supply voltage reaching unit
1) Check that the +24V supply voltage reaching the unit (it should be between +18V and +32V).
2) Identify the cause of incorrect supply voltage reaching the unit and rectify.
Diagnostics reportDSP Fault
Fault on the unit’s digitalPCB
If this fault is displayed when the unit is interrogated, it cannot be remedied in the field.
Diagnostics report NV-RAM Fault
A fault has been detected in the NV-RAM
If this fault is displayed when the unit is interrogated, it cannot be remedied in the field.
DiagnosticsreportRTC Fault
The time and date recordbeing stored by the RealTime Clock (RTC) has been lost
1) Re-enter the time and date using the Interrogator.
2) Cycle the power applied to the unit.
3) Verify that the time and date record was maintained after cycling the power.
DiagnosticsReport Volt Ref Fault
Voltage reference faultdetected
If this fault is displayed when the unit is interrogated, it cannot be remedied in the field.
5. Problem Solving
42
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
6.Specifications
6.1 System
Available Gases Methane
Range0 - 100%LEL
UL version - LEL level 5%v/v
ATEX, IECEx version – LEL level 4.4%v/v
Minimum Low Alarm Setting
20%LEL (0.5 – 2.0m) 10%LEL (2.0 - 5.0m)
Maximum High Alarm Setting
40%LEL (0.5 – 2.0m) 30%LEL (2.0 – 5.0m)
Path LengthShort Range 0.5 - 2.5mLong Range 2.5 - 5.0m
Speed of Response T90 less than 1 second
Output signal4 — 20mANormal operation(0 —100%LEL)
0mAFault
2mAInhibit
2.5mABeam blockConfigurable
3mALow signalConfigurable
Operating Temp.The Searchline Excel Cross-Duct operating temperature range is -40 °C to 50 °C (-40 °F to 122 °F).An internal duct temperature of up to 60 °C (140 °F) is acceptable, provided the ambient temperature outside the duct at the Transmitter and Receiver unit is within the operating range.
Humidity 0 — 99%RH Non-condensing
Pressure 91.5kPa — 105.5kPa (915 — 1055mBar, non-compensated)
Repeatability±10%LEL (<1metre duct width)
±2.5%LEL (1 - 5metre duct width)
TemperatureDrift (-40°C to+65°C)
±10%LEL @ zero±15%LEL @60%LEL
Warm-up Time Less than 5 minutes (operational), Less than 1 hour (fully stabilised)
Power Supply Receiver and Transmitter: 18 to 32V, Heated Reflector Panel: 18 to 28V
Power Consumption Tx/Rx total: 13W maximum Reflector: supply voltage dependent
Enclosure Material 316 Stainless Steel
Weight
Tx/Rx including mounting plate 13kg
Reflector panel
5kg (short range)
10kg (long range)
Vibration 2 — 60Hz, maximum peak to peak amplitude 1mm.
Divergence/ Misalignment Tolerance
Tx/Rx ±1.5° Reflector Panel ±5° (at 5m)
IP rating IP66 and 67
6.2 Response to other gasesSearchline Excel Cross-Duct is a methane gas detector. It should only be used to detect gas mixtures where methane is the main constituent (>70%) and the balance is C2 - C6 hydrocarbons.
43
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
7.Certification
7.1 GeneralTheSearchlineExcelCross-DuctTransmitterandReceiverunitiscertifiedtoExdandhasthefollowingATEX,IECExandULapprovalsforworldwideacceptance:
ATEX, IECEx
II 2 G Ex d IIC T5 (Tamb -40 to +65°C) Gb
Ex d IIC T6 (Tamb -40 to +40°C)
Certificatenumbers:
BAS98ATEX2165X
IECEx BAS 09.0100X
UL
Class 1 Groups B, C, D
Class1Zone1AExdIIB+Hydrogen(Amb-40°Cto+65°C)
File No. E91044
TheSearchlineExcelCross-DuctHeatedReflectorPaneliscertifiedtoExdandhasthefollowingATEXandULapprovalsforworldwideacceptance:
ATEX
II 2 G Ex d IIC Gb T3 (Tamb -40 to +60°C)
Certificatenumber:
Baseefa06ATEX0226X
UL
Class 1, DIV 1, Groups B, C, D
Tamb -40 to +60°C
File No. E91044
The Searchline Excel system has been designed, built and tested to meet the latest European standards for Radio Frequency Immunity (RFI). It has been tested and approved to BS EN 50270.
44
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
7.Certification
7.2 Conduit Technical Characteristics (ATEX, IECEx version)
Ingress Protection IP66 and 67.
Temperature Rating -40 to +105ºC.
ConstructionA helically wound galvanised steel core with cotton packing and enhanced oil resistant PVC covering. Covering material displays good resistance to dilute acids, alkalis and hydrocarbon products.
Colour Grey
Electrical Flash Voltage More than 24kV.
Insulation Resistance More than 100M ohms.
Connector Pull off Classifica-tion
FRG04: Heavy.
Conductor Crush Classification FRG04: Heavy.
Flame Propagation Flame dies in less than 30 seconds after ignition source is removed.
Approvals Bureau Veritas.
45
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
7.3CertificationLabelsATEX,IECEx
7.3.1 Transmitter
7.3.2 Receiver
7.Certification
46
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
7.3.3HeatedReflectorPanel
7.Certification
47
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
7.3.4 System Diagram
7.Certification
H
AZA
RD
OU
S A
REA
TRA
NSM
ITTE
R/S
ENSO
R E
NTR
Y
SUPP
LY E
NTR
YSA
FE A
REA
OPT
ION
AL
CO
NTR
OL
EQU
IPM
ENT
NO
TE 1
OPT
ION
AL
TRA
NSM
ITTE
R/
SEN
SOR
TER
MIN
ATIO
N U
NIT
DVC
100
(M) M
K2
Bas
eefa
03A
TEX0
261
IEC
Ex B
AS
09.0
125
AN
Y SU
ITA
BLE
ATE
X/IE
CEx
A
PPR
OVE
D S
ENSO
R/D
ETEC
TOR
SEN
SOR
EN
TRY
SEN
SOR
/D
ETEC
TOR
AN
Y SU
ITA
BLE
ATE
X/IE
CEx
A
PPR
OVE
D S
ENSO
R/D
ETEC
TOR
CO
MM
UN
ICAT
ION
SFI
XED
SO
CK
ET I.
S.O
UTP
UT
TO C
ALI
BR
ATO
R(F
AC
TORY
FIT
TED
)
HA
ND
HEL
DC
ALI
BR
ATO
RTY
PE S
CH
1B
asee
fa03
ATEX
0073
IEC
Ex B
AS
09.0
120
NO
TES
:1.
A
PPA
RAT
US
WH
ICH
IS U
NS
PE
CIF
IED
EX
CE
PT
TH
AT IT
MU
ST
NO
T B
E S
UP
PLI
ED
FR
OM
, NO
R
C
ON
TAIN
IN N
OR
MA
L O
R A
BN
OR
MA
L
CO
ND
ITIO
NS
, A S
OU
RC
E O
F P
OTE
NTI
AL
WIT
H
R
ES
PE
CT
TO E
AR
TH IN
EX
CE
SS
OF
250V
rms
O
R 2
50V
d.c
.2.
IN
STA
LL IN
CO
MP
LIA
NC
E W
ITH
IEC
600
79-1
43.
E
NTR
IES
: AN
Y S
UIT
AB
LY A
PP
RO
VE
D E
x e,
Ex
d, IE
CE
x e
& IE
CE
x d
CA
BLE
GLA
ND
/CA
BLE
.4.
E
NTR
IES
MU
ST
BE
SE
ALE
D T
O P
RO
VID
E A
DE
GR
EE
OF
PR
OTE
CTI
ON
OF
AT L
EA
ST
IP54
.5.
S
EN
SO
R E
NTR
Y: E
ITH
ER
DIR
EC
TLY
C
ON
NE
CTE
D O
R V
IA S
UIT
AB
LE G
LAN
D
- S
EE
NO
TE 3
.
48
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
7.Certification
7.3.5 ATEX Special Conditions of Safe Use
7.3.5.1 Transmitter and Receiver The integral supply cables must be mechanically protected and terminated in a suitable terminal or junction facility.
Thecoverfixingscrewsshallbegrade12.9minimum.
7.3.5.2HeatedReflectorPanelThe integral supply cables must be mechanically protected and terminated in a suitable terminal or junction facility.
In addition to the integral earth conductor, external equipotential bonding may be maintained via the rear mounting thread.
49
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
7.4CertificationlabelsUL
7.4.1 Transmitter
7.4.2 Receiver
7.Certification
50
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
7.4.3HeatedReflectorPanel
7.Certification
51
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
7.4.4 System Diagram With DX100(M) Termination Unit
7.Certification
TER
MIN
ATIO
NU
NIT
DX
100
(M)
UL
FILE
E13
6193
CO
MM
UN
ICAT
ION
SFI
XE
DS
OC
KE
TI.S
.O
UTP
UT
TOC
ALI
BR
ATO
R.
(FA
CTO
RY
FITT
ED
)
NO
TE2
CO
NTR
OL
EQ
UIP
ME
NT
NO
TE1
SE
NS
OR
AN
YS
UIT
AB
LEU
LLI
STE
DO
RC
LAS
SIF
IED
EX
PLO
SIO
NP
RO
OF
AP
PAR
ATU
S.
HA
ND
HE
LDC
ALI
BR
ATO
RTY
PE
SH
C1
UL
FILE
E13
6193
NO
TES
:
1.A
PPA
RAT
US
WH
ICH
ISU
NS
PE
CIF
IED
EX
CE
PT
THAT
ITM
US
TN
OT
BE
SU
PP
LIE
DFR
OM
,NO
RC
ON
TAIN
INN
OR
MA
LO
RA
BN
OR
MA
LC
ON
DIT
ION
SA
SO
UR
CE
OF
PO
TEN
TIA
LW
ITH
RE
SP
EC
TTO
EA
RTH
INE
XC
ES
SO
F25
0Vrm
sO
R25
0Vd.
c.
2.W
IRIN
GFR
OM
THE
HA
ND
HE
LDC
ALI
BR
ATO
R(S
HC
1)TO
THE
TER
MIN
ATIO
NU
NIT
(DX
100)
ISN
OT
TOE
XC
EE
D15
ME
TRE
SM
AX
.
3.IN
STA
LLE
QU
IPM
EN
TIN
CLU
DIN
GFI
ELD
WIR
ING
INA
CC
OR
DA
NC
EW
ITH
AR
TIC
LES
OF
THE
NAT
ION
AL
ELE
CTR
ICA
LC
OD
EFO
RD
IVIS
ION
1HA
ZAR
DO
US
LOC
ATIO
NS
.
SE
NS
OR
EN
TRY
(CO
ND
UIT
CO
NN
EC
TIO
NR
EQ
UIR
ED
WIT
HS
EA
L)
NO
NH
AZA
RD
OU
SA
RE
AS
UP
PLY
EN
TRY
(CO
ND
UIT
CO
NN
EC
TIO
NR
EQ
UIR
ED
WIT
HS
EA
L)
OP
TIO
NA
LTR
AN
SM
ITTE
RS
EA
RC
HLI
NE
EX
CE
LFI
LEN
o.E
9104
4
TRA
NS
MIT
TER
EN
TRY
P(C
ON
DU
ITC
ON
NE
CTI
ON
PR
EQ
UIR
ED
WIT
HS
EA
L)
HA
ZAR
DO
US
(CLA
SS
IFIE
D)L
OC
ATIO
NC
LAS
S1
DIV
.1G
RO
UP
SB
,C,D
.
52
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
HoneywellAnalyticswarrantstheSearchlineExcelCross-Ductagainstdefectivepartsandworkmanshipandwill repair or (at its option) replace any instruments which are or may become defective under proper use within 36monthsfromdateofshipmentfromHoneywellAnalytics.
This warranty does not cover consumable items, normal wear and tear or damage caused by accident, abuse, improper installation, poisons, contaminants or abnormal operating conditions. Under no circumstances shall HoneywellAnalyticsliabilityexceedtheoriginalpurchasepricepaidbythebuyerfortheproduct.
AnyclaimundertheHoneywellAnalyticsProductWarrantymustbemadewithinthewarrantyperiodandassoon as reasonably possible after a defect is discovered. In the event of a warranty claim please contact your localHoneywellAnalyticsServicerepresentative.
Thisisasummary,forfullwarrantytermspleaserefertotheHoneywellAnalytics“GeneralStatementofLimitedProduct Warranty” available upon request.
8. Warranty Summary
53
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
A.1 IntroductionThisappendixprovidesreferenceinformationabouttheSHC1HandheldInterrogator.
The interrogator provides the user end of a two-way communication link between the Excel system and the operator.
Itfeaturesfacilitieswhichlettheoperatorconfigure,align,functionallytestanddiagnosefaultsinthesystem.
Theappendixgives:
• an overview of the interrogator features
• information about how to connect the interrogator to the Excel systems
• basic user tasks, including switching on/off and changing the battery
• a detailed description of the menus which the interrogator provides
• problem solving information if trouble occurs when using the interrogator
Details of how to use the interrogator for different tasks with the system are given in Chapter 3 and Chapter 4 of this handbook.
A.2 OverviewThe interrogator consists of an LCD screen and four keypad buttons. It links to the Excel Receiver unit via an ISconnectorontheendofaflexiblecableconnectedtotheassociatedjunctionbox.
SHC1 Handheld Interrogator Main Features
Appendix A - Handheld Interrogator
ESC
Z - SHC1 EXCELInterrogator
CalibratorType SHC1
LCD screen
Up key
Enter key
Down key
Escape key
54
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
The interrogator is powered by a standard 9V battery and has a management system which reduces power consumption by placing the unit in an idle mode when it is waiting for user input or for a communication operation to complete.
The interrogator also features a 2k byte non-volatile RAM (NV-RAM) split into two sections. These sections are used to store the current operating mode and a backup copy.
Liquid Crystal Display ScreenThis screen consists of a two-line, 16-character dot-matrix liquid crystal display (LCD). The screen displays messages which communicate information from/to the user.
It displays a menu system that enables the user to select the command mode for the system, and can also displayinformationaboutthesystemconfigurationanditssettings,plusanyerrormessages.
Keypad ButtonsThe four keypad buttons are used to provide operator input in response to messages shown on the display.
Thisincludesmenuoptionselectionsandchangingparametervalues.Thefourbuttonsare:
UpMove to the previous menu option, list item, or increase a displayed data value. Move to the next menu option, list item, or decrease a displayed data value.
Down
ESC Escape Quit the current menu level or operation and return to the previous menu, e.g. stop displaying a list, abort a command. No change if already at the top level.
Enter Select, i.e. Invoke/accept, the currently displayed menu option, list item, data value, or configuration change.
Note: If the and keys are used to advance beyond the end of a list a wrap around to the other end of the list occurs.
A.3 Connection to SystemDetails of how to connect the interrogator to the Searchline Excel Cross-Duct are given in Chapter 3. The diagram shows a typical example.
Note: If connecting via a non-HA junction box then the SHC Protection Device needs to be used.
Appendix A - Handheld Interrogator
ESC
CalibratorType SHC1
55
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
A.4 Basic User TasksSwitching On
(1) Press for two seconds.
The unit recalls its previously set operating mode, i.e. EXCEL, OPTIMA or OPTIMA PLUS, and displays the following message for approximately three seconds:
The unit then displays the top level of the menu style interface in the following way:
During use the first line of the display shows the current level in the menu tree.
The second line displays the sub menu title, action to be invoked, or data value to be checked/changed.
Note: To change the operating mode at switch-on, e.g. from OPTIMA to EXCEL, press the ESC key whilst the initial message is displayed. This changes the mode and re-displays the message.
Switching Off(1) Select the Power Off option from the Main Menu,
Alternatively press the and ESC buttons simultaneously for a fast power off.
Notes:
1. The unit powers down automatically after five minutes of non-use.
2. The fast power off facility and auto power off are disabled when a menu option is selected that modifies the interrogator’s configuration.
Changing the BatteryTofit/replacethebatteryproceedasfollows:
(1) Loosen the four rear cover screws. Use a 2.5mm Allen hexagon key.
(2) Carefully lift the front half of the interrogator away from the rear cover. Ensure that the flexible connector between the keypad and the electronics module is not damaged.
(3) Unclip and remove the battery.
(4) Fit the new battery, reuse the protective sleeve.
(5) Carefullyrefitthefronthalfoftheinterrogatortotherearcover. Ensure that the flexible connector lies flat.
(6) Tighten the four rear cover screws.
Appendix A - Handheld Interrogator
Z - SHC1 Excel Interrogator 4V0
Main Displayvv
56
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
Appendix A - Handheld Interrogator
A.5 MenusThe interrogator top level menu structure and menu choices are as follows.
All menu options are implemented by pressing the keypad key. The menu options and types are shown in the diagram:
where:
D a single set of data is displayed.
DL a list of data is displayed - use the and keys to navigate the entries in the list.
Sub another menu of options is displayed when this choice is selected - use the and keys to navigate the sub menu choices.
Sw the displayed option is immediately activated.
Tog the displayed option is toggled between three choices using the and keys.
Chapter 3 and Chapter 4 of this handbook describe how the Interrogator and menus are used when the system is being installed/in use.
Main Menu: Display
Main Menu: Calibrate
Main Menu: Diagnose
Main Menu: Config
Main Menu: Chg Mode
Main Menu: Power Off
Display: Gas Reading
Display: Signal
Magnitude
Display: Dynamic Reserve
Display: S/W Version
Calibrate: Display
Calibrate: Install
Calibrate: Set Time
Calibrate: Cal Sensor
Calibrate: Force mA
Calibrate: Normal mA
Calibrate: Show Status
Sub Sub Sub
DL
DL
Sub
D
DL
Sub
D
D
DD
Tog
DL
Sw
Sub
Sw
DL
Sw
Sub Sw D
57
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
A.5.1 Main MenuThismenuconsistsofthefollowingsubmenuoptions:
Display Display gas and other unit readings.
Calibrate Installandcalibratethesystem,forcetheanalogueoutput,showthecalibrationcoefficientsor show the instrument status.
Diagnose Inspect the fault and warning logs, perform a self-test or perform a soft reset.
Config Readtheconfigurationparametersoftheunit,updatetheuserconfigurationparameters.
Chg Mode Toggle the operating mode of the interrogator.
Power Off Switch the interrogator off.
A.5.2 Display MenuThissubmenudisplaysgasandotherunitreadings.Ithasthefollowingoptions:
Gas Reading Display the gas type and system status.
Signal magnitude Show the level of the sample and reference signals.
Dynamic Reserve Shows the acceptable drop in signal level before beam block occurs as a percentage of the current signal level.
S/WVersion Displays the system software version and the current time and date.
Gas ReadingDisplaythegastypeandsystemstatus.Thedisplayisinthefollowingformat:
where: gggggggg Gas name. For a special gas table this shows <Gnnn> where nnn is the identifier.
rrrrrr Gas reading.
uuuu Measurement units.
/ Thisisastatuscharacterwhichindicatesoneofthefollowing:
/ - A spinning line shows the system is operating normally i.e. in a fully active state.
| - A stationery line shows the system is in an inactive state.
W - Active Warning.
F - Active Fault.
B - Beam Block.
A - Alarm
Appendix A - Handheld Interrogator
Excel gggggggg rrrrrr uuuu /
58
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
Signal MagnitudeShowthelevelofthesampleandreferencesignals.Thedisplayisinthefollowingformat:
where: aaaaaaa Signal magnitude for the sample channel.
bbbbbbb Signal magnitude for the reference channel.
Dynamic ReserveShows the acceptable drop in signal level before beam block occurs as a percentage of the current signal level.Thedisplayisinthefollowingformat:
where: xxx.xx The acceptable drop in signal level before beam block measured as a percentage of the current signal level.
S/WVersionDisplaysthesystemsoftwareversionandthecurrenttimeanddate.Thedisplayisinthefollowingformat:
where: vvVvv Version number of the Excel system software.
hh.mm System time as hours and minutes.
dd/mm/yy System date as day of the month, month number and the last two digits of the year.
A.5.3 Calibrate MenuThissubmenuisusedwheninstallingandcalibratingthesystem.Ithasthefollowingoptions:
Display Display system readings.*
Install Direct the alignment and initialisation of the system.*
Set Time Set the system real time clock time and date.
Cal Sensor Calibratethesystemzero.*
Force mA Fix the 4-20mA analogue output at a selected level.
Normal mA Restore the analogue output to its normal output state.
Show Status Showthecalibrationandconfigurationstatusofthesystem.
The options marked with an asterisk, (*), require the system’s analogue 4-20 output to be inhibited during their operation. Where this occurs then the following sequence is automatically added to the affected operation.
Appendix A - Handheld Interrogator
Sample: aaaaaaa Ref: bbbbbbb
Dynamic Reserve: xxx.xx %
Excel S/W vvVvv hh:mm dd/mm/yy
59
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
Before the selected sub menu operation is started the following message is displayed for at least three seconds:
The analogue output is inhibited and the chosen sub menu operation proceeds. After the sub menu operation is completed, or aborted by pressing the ESCkey,thefollowingmessageisdisplayed:
Press toreleasethe4-20receiveroutputandthefollowingmessagewillbedisplayedforthreeseconds:
DisplayDisplay system readings. This choice is the same as the GAS READING DISPLAY option on the DISPLAY MENU.
Notes:
1. The 4-20 output is inhibited during the display. See the earlier description.
2. No spinning line is displayed as the receiver is not in a fully activated state.
InstallThis choice is used to complete the alignment and commissioning operations after the system is mechanically andelectricallyinstalled.Itprovidesasequentialsetofoperationsto:
• view the system type
• set the system path length
• perform a system self test
• check system alignment
• initialise the system and make it live
Note: The 4-20 output is inhibited during this procedure. See the earlier description.
System Type
TheinitialdisplayafterInstallischosenisinthefollowingformat:
Appendix A - Handheld Interrogator
Inhibiting 4-20 Please Wait
Press Enter To Release 4-20
4-20 Released
System Type tttttttt
60
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
where: tttttttt Systemtype.Thesystemtypedisplayedisoneofthefollowing:
Display Text System Type
Duct Mount 0.5 - 5m range system
Note: It is not possible to change the system type. This is set during calibration and configuration of the unit at the factory.
Path Length
Thefollowingmessageisdisplayed:
where: nnnn The path length in metres.
Thefollowingrangesofpathlengthcanbeentered:
System Type Minimum Range (m) Maximum Range (m) Step Size (m)
Duct Mount 0.5 5 0.1
Self Test
Thisstartsthesystemselftestprocess.Thefollowingmessageisdisplayed:
Whenfinishedtheinterrogatordisplaysthefollowingmessageforatleastthreeseconds:
Thefollowingmessageisnowdisplayed:
Alignment
No alignment adjustments are provided for the Searchline Excel Cross-Duct. If the mechanical installation is satisfactory Searchline Excel Cross-Duct can now be initialised.
Press Enter onthekeypadandthedisplayshows:
Appendix A - Handheld Interrogator
Path Length nnnn vv
Self Test
Please Wait
Checks Passed
Signals OK
SIG: TGT:
61
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
Press Enterandthedisplaywillshowthefollowingmessage:
This message is displayed for three seconds at the end of a successful initialisation process.
Note: The Searchline Excel system is live after a successful initialisation.
Set TimeThis option lets you set the system’s time and date.
The initial display after SET Time is chosen is in the following format:
where: hh Hours.
mm Minutes.
Whenfirstdisplayedonlythecurrenthourisshown.
All settings are adjusted by means of the and keys on the keypad. After setting the hour the minutes are displayed.
After the time has been entered then the same process is used to set the date which is displayed in the followingformat:
Appendix A - Handheld Interrogator
Ensure Zero Gas then press Enter
Zero Cal OK
Installation complete
Time HH:MM hh:mm vv
Date DD/MM/YY dd/mm/yy vv
62
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
where: dd Day.
mm Month.
yy Last two digits of the year.
Note: The time and date will not be updated unless both are entered and accepted without error.
Cal SensorThismenuoptionzerosthesystem.
Notes:
1. The 4-20 output is inhibited during this procedure. See the earlier description.
2. There must be no gas in the system beam path whilst this procedure is carried out. The following message is displayed:
Thefollowingmessageisdisplayedwhilethecalibrationoperationisbeingperformed:
Ifthecalibrationissuccessful,thefollowingmessageisdisplayedforaperiodofthreeseconds:
Force mAThisoptionallowsthesystemsanalogueoutputsignaltobeadjustedtoafixedlevel,e.g.whensettingupasystemcontroller.Thefollowingmessageisdisplayed:
where: mmmmm Current to output.
This is adjusted using the and keys over the range 1mA to 21mA in steps of 0.1mA. After adjustment the outputisforcedtothesetlevelandthefollowingmessageisdisplayed:
where: mmmmm Analogue output current previously set.
Appendix A - Handheld Interrogator
Ensure Zero Gas Press Enter
Processing Data Please Wait...
Zero Calibrated
Fixed: mmmmmm mA Press Enter
O/P current mA mmmmmm vv
63
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
Normal mAThis menu option returns the system to its normal analogue output state, irrespective of its previous state. If successful,thefollowingmessageisdisplayedforthreeseconds:
Show StatusThismenuoptiondisplaysthecalibrationandconfigurationstatusofthesystem.Thestatusinformationisdisplayedinthefollowingformat:
where: cccccccc... Titleofthecalibrationstatusfield.
sssssssss Current state of calibration.
The different settings from the list are selected using the and keys on the keypad.
Thecalibrationstatusfieldsandvaluesaregivenbelow:
Calibration Status Fields Display Text False State True State
Temperature Cal. Temp Sensor Uncalibrated Calibrated
Zero Calibration Zero Ratio Uncalibrated Calibrated
Span Calibration Span Sensitivity Uncalibrated Calibrated
4-20mA Calibration Analogue Output Uncalibrated Calibrated
Det. Temp. Comp. T Compensation Uncalibrated Calibrated
Det. Sens. Comp. Det Sensitivity Uncalibrated Calibrated
Installation Installation Required Complete
Valid Date Time Date and Time Estimated Set
Loop Test Analogue Check Failed Passed
A.5.4 Diagnose Menu
Thissubmenuhasthefollowingoptions:
Active Faults Display the active faults in the system.
Active Warns Display the active warnings in the system.
Self Test Perform a diagnostic system self test.
Soft Reset Reset the system.
Active FaultsThis menu option displays operational faults when the system is in service.
Appendix A - Handheld Interrogator
4-20mA Released
ccccccccccccccc
64
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
If there are one or more faults present, then the faults are displayed one at a time.
Use the and keys to navigate the list.
Ifnoactivefaultsarepresentthedisplayshowsthefollowingforthreeseconds:
The Diagnose sub menu is then displayed.
Ifthereareoneormorefaultspresent,thedisplayshows:
where: F Indicates that the message displayed is a fault.
hh:mm Time the fault occurred.
DD/MM/YY Date the fault occurred.
eeeeeee Fault description. See the following table for a list of error messages.
See also Chapter 6, Problem Solving.
Display Text Fault Description Meaning
Bad 4-20mA Loop ERR_EXCEL_LOOP_FAULT A fault has occurred in the 4-20mA signal loop.
DSP Fault ERR_EXCEL_DSP_FAULT Fault on the gas detector’s digital PCB.
Hardware Fault ERR_EXCEL_HW_FAULT A hardware fault has occurred.
NV-RAM Fault ERR_EXCEL_FRAM_FAULT A fault has been detected in the unit’s NV-RAM.
RTC Fault ERR_EXCEL_RTC_FAULTThe time and date record stored by the RealTime Clock (RTC) has been lost.
Software Fault ERR_EXCEL_SW_FAULT An gas detector software error has occurred.
Supply Fault ERR_EXCEL_SUPPLY_FAULT Incorrect supply voltage reaching the gas detector. Active WarnsThis menu option displays the active warnings in the system. They are displayed in the same way as described for Active Faults except that a W is displayed instead of Fonthefirstlineofthedisplay.
Display Text Fault Description Meaning
Alarm ERR_EXCEL_LOG_ALARM The Excel log has become damaged.
Bad Temperature ERR_EXCEL_TEMPERATURE_LIMITUnit has been operated at a temperature outside its specified and certified range.
Baseline Drift ERR EXCEL_DRIFT_LIMIT Drift of unit’s baseline.
Beam Blocked ERR_EXCEL_BEAM_BLOCKEDThe infrared beam between the Transmitterand Receiver has become blocked.
Neg Gas Reading ERR_EXCEL_NEGATIVE_DRIFT Negative drift of gas detector’s zero position.
Not Installation ERR_EXCEL_BAD_INSTALLATION Incorrect gas detector installation has occurred.
None Present
F-hh:mm DD/MM/YY eeeeeeeeeeeeeeee
Appendix A - Handheld Interrogator
65
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
Overrange ERR_EXCEL_OVERRANGE An overrange signal has occurred.
Power Failed ERR EXCEL_LOG_POWER_FAIL The gas detector has suffered an internal power failure.
Reset Occurred ERR_EXCEL_RESET A gas detector reset has occurred.
Time Adjusted ERR_EXCEL_LOG_TIME_ADJUST The Excel log time has been changed.
Uncalibrated ERR_EXCEL_UNCALIBRATED The gas detector requires calibration.
Volt Ref Fault ERR_EXCEL_VOLTAGE_REF_FAIL Voltage reference fault detected.
Self TestThis option lets you start a system diagnostic self test.
Thefollowingmessageisdisplayedduringtheselftestprocess:
The following message is displayed for three seconds at the end of a successful self test process.
Soft ResetThis option lets you reset the system.
Thismessageisdisplayedduringtheresetprocess:
Thefollowingmessageisdisplayedforthreesecondswhentheprocessiscompleted:
A.5.5ConfigMenuThissubmenu letsyouchecktheconfigurationparametersof theunitandupdatetheuserconfigurationparameters.Ithasthefollowingoptions:
Show Gas Showthegasrelatedconfigurationparameters.
ShowConfig Showtheuserrelatedconfigurationparameters.
Show Install Showtheinstallationrelatedconfigurationparameters.
Show GasThisoptiondisplaystheusefulgastableconfigurationparametersinthefollowingway:
Appendix A - Handheld Interrogator
Processing Data Please Wait
Processing Data Please Wait
Unit Reset
cccccccccccccccc vvvvvvvvv
Checks Passed
66
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
where: ccccccc... Titleoftheconfigurationsetting.
vvvvvvvv Setting value.
Note: The settings are not field configurable:
Gas Configuration Parameters
Display Text Min Value Max Value Step Size
Gas ID Gas Ident
01 = Methaneall other IDs shown as G<nnn>
255 1
Gas Units Gas Units %LEL (Cross-Duct only)
Effective Full Scale Gas Full Scale 0.1 100000 0.05
ShowConfigThisoptiondisplaystheconfigurationparameterstheusercansetinthesamewayasfortheShowGasoption.Theconfigurablesettingsandvaluesareshowninthefollowingtable:
Configuration Parameters Display Text Min Value Max Value Step Size Default Values
Protocol Address Digital Address 0 255 1 0
Time to Block Block Warn Time 5s 600s 5s 30
Time to Fault Block Fault Time 0s 600s 5s 120
Max Response Maximum T90 1s 60s 1s 60
Analogue Style Analogue Mode Alarm or Continuous C
Inhibit Current Inhibit mA 0mA 3mA 0.05mA 2.0
Block Current Blocked mA 0mA 4mA 0.05mA 2.5
Low Signal Current Low Signal mA 0mA 4mA 0.05mA 3.0
Low Signal Level Low Signal % 0% 90% 1% 33%
Alarm Threshold Alarm Threshold 10% 100% 1% 20%
Report fault due to blockage
RPRT Blocked Fault Enable or Disable E
Show InstallThisoptiondisplaystheinstallationconfigurationparametersinthesamewayasfortheShowGasoption.Theconfigurablesettingsandvaluesareshownbelow:
Installation Configuration Parameters
Display Text Description
Path Length Path Length 0.5m min 5m max 0.1m steps
Appendix A - Handheld Interrogator
67
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
A.5.6 Chg ModeThis menu option toggles the operating mode of the interrogator between Excel, Optima and Optima Plus to matchthegasdetectoritisattachedto.Wheninvokedthemodeisdisplayedintheidentificationbanner(thesameastheonedisplayedwhentheunitisswitchedon)forthreesecondsasfollows:
where: aaaaaa The type of gas detector that the interrogator is currently set to, i.e. Excel, OPTIMA or OPTIMA PLUS.
A.5.7 Power OffThis menu option switches the interrogator off.
Alternatively press the and ESC buttons simultaneously for a fast power off.
Notes:
1. The unit powers down automatically after five minutes of non-use.
2. The fast power off facility and auto power off are disabled when a menu option is selected that modifies the unit’s configuration.
A.6 PROBLEM SOLVINGInterrogator problems that occur during communication with the system or as a result of a command failure willbedisplayedinthefollowingformat:
where: eee Error code.
ssssssss... Textual description of the error.
If an error message of this kind is displayed note down the error code and text description and contact HoneywellAnalytics.
Appendix A - Handheld Interrogator
Z - SHC1 aaaaaa Interrogator 4V0
Error: eee ssssssssssssssss
68
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
B.1 Terminology
Ex d
FlameprooforexplosionproofwithintheconfinesoftheEuropeanseriesofstandardsEN60079.Anenclosurethat can withstand the pressure developed during the internal explosion of an explosive mixture and that prevents transmission of the explosion to the explosive atmosphere surrounding the enclosure.
Ex e
IncreasedsafetywithintheconfinesoftheEuropeanseriesofstandardsEN60079appliedtoelectricalapparatusthat does not produce arcs or sparks in normal service, in which additional measures are applied so as to give increased security against the possibility of excessive temperatures.
Instrument Assisted Alignment (IAA)
AmethodofcommissioningtheExcelsystemusingtheassociatedelectronicHandheldInterrogatordevice.The process will not allow the Excel system to initialise unless the alignment of the Receiver and Transmitter is correct and the signal strength is correct.
IS
Intrinsicallysafe,apparatusinwhichthecircuitsthemselvesareincapableofcausingignitionofaflammablegas.
Lower Explosive Limit (LEL)
Thevolumeofflammablegasorvapourinairbelowwhichanexplosivegasatmospherewillnotbeformed.
RS485
An industry-wide serial communication link protocol.
Turbo heating
Increased Transmitter window heating at low operating temperatures.
Appendix B - Glossary
69
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
B.2 Open Path Detector Measurement UnitsOpenpathdetectorsmeasuretheamountofgaspresent inthebeam.However,theycannotdiscriminatebetween a low concentration gas cloud over a large area and a high concentration gas cloud in a small area. Generally, gas readings of LEL.m (Lower Explosive Limit metres) are used. LEL.m is calculated by multiplying thesizeofagascloudbyitsconcentration.
Anopenpathalarmsetat1LEL.mwouldbetriggeredbyanyofthesituationsshownbelow:
The Searchline Excel Cross-Duct operates with a very short path length, making it reasonable to assume that the gas concentration is uniform across the duct. Therefore Searchline Excel Cross-Duct uses the duct width to convert the measured gas reading from LEL.m to %LEL. It is important that the duct width is entered correctlyduringcommissioningotherwisethedetectorcouldreportasignificantunderoroverreadofgasconcentration.
B.3 AbbreviationsEMC Electro-Magnetic Compatibility
IAA Instrument Assisted Alignment
IP Ingress Protection
IR Infrared
IS Intrinsically Safe
LEL Lower Explosive Limit
NPT National Pipe Thread
RFI Radio Frequency Interference
UL Underwriters Laboratories
Appendix B - Glossary
100% LEL
1m
2m
10m
ESC
CalibratorTypeSHC1
ESC
CalibratorType SHC1
50% LEL
ESC
CalibratorTypeSHC1
ESC
CalibratorType SHC1
10% LEL
ESC
CalibratorTypeSHC1
ESC
CalibratorType SHC1
70
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
C.1 System UnitsThe following table lists the different types of system units and provides the part numbers for the various certificationoptions.
All types of Transmitters and Receivers include conduit and glands.
Short Range 0.5m – 2.5m
2104N0011Short range cross duct system 0.5m to 2.5m. ATEX approved, current source with DVC100M MK2 interface box and single tile heated reflector panel
2104N0031Short range cross duct system 0.5m to 2.5m. ATEX approved, current sink with DVC100M MK2 interface box and single tile heated reflector panel
2104N1010Short range cross duct system 0.5m To 2.5m. UL approved, current source including single tile heated reflector panel
2104N1030Short range cross duct system 0.5m To 2.5m. UL approved, current sink including single tileheatedreflectorpanel
Long Range 2.5m – 5.0m
2104N0021Long range cross duct system 2.5m to 5.0m. ATEX approved, current source with DVC100M MK2 interface box and four tile heated reflector panel
2104N0041Long range cross duct system 2.5m to 5.0m. ATEX approved, current sink with DVC100M MK2 interface box and four tile heated reflector panel
C.2 General
Accessories
Handheld Interrogator and accessories
04230-A-1001 Hand Held Interrogator ATEX Certified (4V0 software) for Optima, Optima Plus and Excel
2104B2351 Hand Held Interrogator UL Certified (4V0 software) for Optima, Optima Plus and Excel
2108B1455 Hand Held EEPROM upgrade (4V0)
04320-A-1025 SHC Protection Device Module and Lead
2104B6250 SHC Calibrator Connector System 10m
DVC/DX Interfaces
2104B6212 DVC100M MK2 Termination Unit ATEX with MODBUS capability
2104B2382 DX100M XP Termination Unit UL with MODBUS capability
Installation Accessories
2104D0295 Sun/Heat Shade (Deluge Cover)
00780-A-0100 Honeywell Analytics Junction Box
210-190-045 Killark Junction Box (excludes terminals)
2992A0071 Conduit Assembly for Excel UL certified
0230-0069 Stainless Steel enclosure NEMA 4X 3/4” NPT UL
02104-N-9880 Upgrade to Nickel Plated Glands
Appendix C - Accessories & Spare Parts
71
MAN0889_Issue 3_03/13 Searchline Excel Cross-Duct Technical Handbook
Gas Test Equipment
2104N3000 Searchline Excel Cross-Duct Test filters kit & Manual
2108D0271 Remote Gassing Pipe
Manuals (Hard Copy)
Note: Electronic copies of the manuals are supplied on CD with each instrument
2104M0520 Searchline Excel Cross-Duct Technical Handbook (English)
2104M0409 DVC100(M) MK2 Termination Unit Quick Start Guide Guide (English)
2104M0701 DX100 Series Termination Units Technical Handbook (English)
2104M0524 Searchline Excel Cross-Duct Test Filter Leaflet (English)
Cross-Duct
2104B0715 Heated Reflector Panel for Short Range ATEX
2104B0717 Heated Reflector Panel for Short Range UL Certified
2104B0716 Heated Reflector Panel for Long Range ATEX
2104D2537 Retro-reflector mounting plate for Long Range
2104D2536 Retro-reflector mounting plate for Short Range
2104D2505 Mounting plate, Cross-Duct, Stainless Steel
2104D2506 Support strap, Cross-Duct mounting plate
2104D2542 Support strap, Cross-Duct retro-reflector for Long Range
2104D2541 Support strap, Cross-Duct retro-reflector for Short Range
Appendix C - Accessories & Spare Parts
Issue 3 03/2013
H_MAN0889_EMEAI
2104M0520_A03993
©2013HoneywellAnalytics 1268
3
Please Note:While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions. Data may change, as well as legislation and you are strongly advised to obtain copies of the most recently issued regulations, standards and guidelines. This publication is not intended to form the basis of a contract.
Contact Honeywell Analytics:
Find out more
www.honeywellanalytics.com
Europe, Middle East, Africa, IndiaLife Safety Distribution AGJavastrasse 28604 HegnauSwitzerlandTel: +41 (0)44 943 4300Fax: +41 (0)44 943 4398India Tel: +91 124 4752700gasdetection@honeywell.com