www.coopercontrol.com
1
1. Toggle Load 1
2. Toggle Load 2
3. Toggle Load 3
4. Raise Dimmer 5%
5. Lower Dimmer 5%
6. Load 1, 2, 3 Off
General
Exam
Reading
Raise
Lower
All Off
General
Exam
Reading
All Off
Access to daylight and personal control of electric light improves the health and well being of patients, reduces anxiety and increases overall patient satisfaction. Simple to use, labeled controls allow hospital staff to provide quality care. Including energy saving strategies such as daylighting, which provides up to 30% savings, and code requirements like integral UL 924 relays qualifies the Room Controller as an outstanding solution for the private patient room.
The Room Controller QuicKit is shipped preconfigured to work out-of-the-box, minimizing installation and setup time, while ensuring maximum energy savings. Using this design guide to specify your room with a Room Controller QuicKit catalog number will guarantee that after installation the lighting control system will work immediately as defined on this application guide.
Summary
Room Controller - Semi-Private Patient Room w/Daylight Dimming and Pillow Speaker Integration
room Controller Sample plaCement layout (12’ x 16’)
Nor
mal
pow
er
conn
ectio
nR
C3D
EH
CFo
r Pat
ient
Roo
ms
(3 R
elay
+ 3
Dim
mer
+ 1
Em
erge
ncy)
Low
er
All
Off
Rai
se
Rea
ding
Exa
m
Gen
eral
Em
erge
ncy
pow
er
conn
ectio
n
RC-6TSB-HC2-*Patient Station
Day
light
sen
sor
(DS
RC
-FM
OIR
)
Exa
mLo
ad (2
)
Gen
eral
Em
erge
ncy
(Tra
cks
with
Loa
d (1
)
Gen
eral
Load
(1)
Gen
eral
Load
(1)
Gen
eral
Load
(1)
Gen
eral
Load
(1)
Gen
eral
Em
erge
ncy
(Tra
cks
with
Loa
d (1
)
Exa
mLo
ad (2
)
Day
light
sen
sor
(DS
RC
-FM
OIR
)
RC-4TSB-HC1-*Patient Station
Em
erge
ncy
pow
er
conn
ectio
n
All Off
Reading
Exam
General
Gen
eral
Exa
m
Rea
ding
Rai
se
All
Off
Low
er
Gen
eral
Exa
m
Rea
ding
Rai
se
All
Off
Low
er
RC
3DE
HC
For P
atie
nt R
oom
s(3
Rel
ay +
3 D
imm
er +
1 E
mer
genc
y)N
orm
al p
ower
co
nnec
tion
RC-6TSB-HC2-*Patient Station
General
Exam
Reading
All Off RC-4TSB-HC1-*Patient Station
RC-6TSB-HC2-*Patient Station
Gen
eral
Exa
m
Rea
ding
Rai
se
All
Off
Low
er
RC-6TSB-HC2-*Patient Station
Nur
se C
all S
yste
m a
nd
Ent
erta
inm
ent S
yste
m(b
y ot
hers
)
ccTV
12
3
45
67
89
PREV
0
13
ALL
ON
/OFF2
MU
TE
SLEE
PO
PTIO
N
CH
AN
NEL
VOLU
MEVO
LUM
EC
HA
NN
EL
OPTIO
NSLEEP
MU
TE
2
ALL
ON
/OFF
31
0PR
EV
98
76
54
32
1
TVcc
Rea
ding
- Lo
ad (3
)
GP
CS
-3Z-
DIM
Gre
enga
te P
atie
nt C
ontro
l Sta
tion
3 sw
itch
zone
s 3
dim
min
g zo
nes
w/ A
ll Zo
ne b
utto
n
RC
3DE
HC
GP
CS
-3Z-
DIM
Gre
enga
te P
atie
nt C
ontro
l Sta
tion
3 sw
itch
zone
s 3
dim
min
g zo
nes
w/ A
ll Zo
ne b
utto
n
Nur
se C
all S
yste
m a
nd
Ent
erta
inm
ent S
yste
m(b
y ot
hers
)
Rea
ding
- Lo
ad (3
)
RC
3DE
HC
Integrated CapabIlItIeS Cooper lIghtIng guaranteed CompatIble FIxtureS
Refer to these Cooper Lighting data sheets for lighting layouts and illuminance value information.
RC-4TSB-HC1 RC-6TSB-HC2
UL924
DaylightingControl
UL924
ManualControl
UL924
Integration
Room Controller QuicKitRCQK-HC3E-HC1-HC2-HC2-3ZD-D1-P-W
• Manual On
• Patient personal control from pillow speaker, 3 relay On/Off and 3 dimming zones
• Direct integration with most major Nurse Call Systems
• Providing users with wall-based dimming controls to adjust the lighting levels to meet their needs
• Automatic multi-zone daylight dimming out-of-the-box
• High-end trim/tuning to define target light levels guarantees energy savings
• BMS integration for HVAC control based on Occupancy
Control SequenCe
1. Toggle Load 1
2. Toggle Load 2
3. Toggle Load 3
4. Load 1, 2, 3 Off
Fail-Safe Room Controller Patient Room Lighting Layouts
Product Legend (per patient bed)
Qty1: RC3DEhC3 relay + 3 DImmer + 1 emergency relay
Qty1: RC-4tSB-hC1-Wgeneral, eXam, reaDIng, all off
Qty1: RC-6tSB-hC2-Wgeneral, eXam, reaDIng, raISe, lower, all off
Qty1: GPCS-3Z-DIM3 on/off & 3 Zone DImmIng PaTIenT conTrolS
Qty1: GG37P37PIn connecTor for gPcS-3Z-DIm moUnTeD on HeaDwall
Qty1: DSRC-FMOIRDaylIgHT SenSor
Qty1: GGRJ45-10-GqUIcKconnecT caBle 10’
Qty1: GGRJ45-50-GqUIcKconnecT caBle 50’
Single box packaging with wiring detail and inStallation
DOWNLIGht FIXtURES
RECESSED FIXtURES
for gUaranTeeD comPaTIBIlITy refer To PreferreD cooPer lIgHTIng fIXTUre InformaTIon Below.
Half Lights
All Off
Full Lights
Raise
Lower
RC3DE
Entry Lighting
All Off
RC3D
General
Exam
Reading
All Off
cc
TV
1 2 3
4 5 67 8 9
PREV 0
1 3ALLON/OFF
2
MUTE
SLEEP OPTION
CHANNEL VOLUME
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
Half Lights
All Off
Full Lights
Raise
Lower
RC3DE
Entry Lighting
All Off
RC3D
General
Exam
Reading
All Off
cc
TV
1 2 3
4 5 67 8 9
PREV 0
1 3ALLON/OFF
2
MUTE
SLEEP OPTION
CHANNEL VOLUME
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
Half Lights
All Off
Full Lights
Raise
Lower
RC3DE
Entry Lighting
All Off
RC3D
General
Exam
Reading
All Off
cc
TV
1 2 3
4 5 67 8 9
PREV 0
1 3ALLON/OFF
2
MUTE
SLEEP OPTION
CHANNEL VOLUME
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
Half Lights
All Off
Full Lights
Raise
Lower
RC3DE
Entry Lighting
All Off
RC3D
General
Exam
Reading
All Off
cc
TV
1 2 3
4 5 67 8 9
PREV 0
1 3ALLON/OFF
2
MUTE
SLEEP OPTION
CHANNEL VOLUME
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
Half Lights
All Off
Full Lights
Raise
Lower
RC3DE
Entry Lighting
All Off
RC3D
General
Exam
Reading
All Off
cc
TV
1 2 3
4 5 67 8 9
PREV 0
1 3ALLON/OFF
2
MUTE
SLEEP OPTION
CHANNEL VOLUME
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
Half Lights
All Off
Full Lights
Raise
Lower
RC3DE
Entry Lighting
All Off
RC3D
General
Exam
Reading
All Off
cc
TV
1 2 3
4 5 67 8 9
PREV 0
1 3ALLON/OFF
2
MUTE
SLEEP OPTION
CHANNEL VOLUME
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
Half Lights
All Off
Full Lights
Raise
Lower
RC3DE
Entry Lighting
All Off
RC3D
General
Exam
Reading
All Off
cc
TV
1 2 3
4 5 67 8 9
PREV 0
1 3ALLON/OFF
2
MUTE
SLEEP OPTION
CHANNEL VOLUME
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
Half Lights
All Off
Full Lights
Raise
Lower
RC3DE
Entry Lighting
All Off
RC3D
General
Exam
Reading
All Off
cc
TV
1 2 3
4 5 67 8 9
PREV 0
1 3ALLON/OFF
2
MUTE
SLEEP OPTION
CHANNEL VOLUME
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
Half Lights
All Off
Full Lights
Raise
Lower
RC3DE
Entry Lighting
All Off
RC3D
General
Exam
Reading
All Off
cc
TV
1 2 3
4 5 67 8 9
PREV 0
1 3ALLON/OFF
2
MUTE
SLEEP OPTION
CHANNEL VOLUME
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
UL924
Emergency
www.coopercontrol.com
2
In developing a patient room lighting control solution, Cooper Controls found existing methods for providing patients control over natural and electric lighting levels to be inadequate. Control solutions that rely on existing off-the-shelf pillow speakers and nurse call station interfaces are severely limited in functionality. On/Off only control of a limited number of lighting zones is typical for these systems.
To adress this issue, Cooper Controls developed a line of proprietary pillow speakers designed specifically to support the control of natural and electric light.
These units offer the following features:• Support for up to three zones of electric lighting control• An all zones On/all zones Off function• Independent Raise/Lower control of each zone• Shade Raise/Lower function• Standard pillow speaker functionality including nurse call and television control• Sealed design reduces potential risk of infectious fluids or solids settling into the unit, even in the speaker area• High-impact case material is designed to withstand over 100 drops onto a concrete floor without impacting its functionality• Standard interface to leading nurse call stations
These exceptionally functional control devices interface with a state of art, small form factor lighting control panel. This panel is capable of supporting a digital switch network. Multiple digital switch stations maybe used in conjunction with the pillow speaker to provide additional control points for staff and visitors.
pIllow Speaker Control FunCtIonalIty
RC-6TSB-HC2-*Wallstation
Lower
Raise
RC-4TSB-HC1-*Wallstation
QuickConnect coupler (GGRC-COUPLER)
Adjustable daylight sensor dome
Daylight sensor(DSRC-FMOIR)
BLACK - Hot(120/277 VAC)
WHT/ORG or WHT/BLKNeutral
BLUE - Relay In(120/277 VAC)
Lighting Load (1)
Lighting Load (2)
Lighting Load (3)
YELLOW
RED
Violet - Dimmer 1
Requires 0-10V dimming ballasts
Connect up to four wallstations per Room
Controller
Quick connect cables are pre-terminated and included in the Room Controller QuicKit and measured to fit typical room layouts
Gray - Dimmer 1
Gray - Dimmer 2Violet - Dimmer 2
Violet - Dimmer 3Gray - Dimmer 3
Cooper Controls 203 Cooper Circle Peachtree City, GA 30269. USA
Tel: +1-800-553-3879 Fax: +1-800-954-7016 Email: controls@cooperindustries.comWebsite: www.coopercontrol.com
Room Controller - RC3DEHCThree Relay + Three Dimmers Wiring Diagram + One Emergency Relay
Drawing Name: RC3DEHC-PatientRoomWiring.dwg
PURPLE
Drawing Date: 1/10/2013
Button 5: Press and hold decrease zone 5%Button 4: Press and hold increase zone 5%
Button 2: Toggle Load (2)Button 1: Toggle Load (1)
*Immediately provides multi-zone daylight dimming upon powerup
BLUE - Emergency Power In(120/277 VAC)
YELLOWEmergency Power OUT
Emergency Lighting Load(Tracks with normal lighting YELLOW load)
EMERGENCY NEUTRAL
All Off
Reading
Exam
General General
Exam
Reading
All Off
Button 3: Toggle Load (3)
Button 6: Load (1), (2), (3) Off
Button 3: Toggle Load (3)
Button 1: Toggle Load (1)Button 2: Toggle Load (2)
Button 4: Load (1),(2),(3) Off
General
Exam
Reading
GG37PGreengate 37 Pin ReceptacleProvided by Cooper Controls for pillow speaker connection
GPCSGreengate Patient Control StationProvided by Cooper Controls
Note:Use only wiring supplied with the GG37P receptacle.Only the Greengate Patient Control Station sall be connected to a GG37P Receptacle
Eight conductors of the 37 conductor healthcare cable.
To Nurse Call System and Entertainment System (by others)
0-10V Dimming Zone Note: The 0-10V dimming zones within the Room Controller can be wired and controlled independent of the connected loads. This allows a each load to have a dedicated 0-10V dimming zone or a single load to have up to three 0-10V dimming zones.
Emergency Note: Emergency load tracks with normal lighting YELLOW load for On/OFF. If dimming it will be adjusted with the dimming zone it is connected to. Upon loss of normal power to the RC3DE, the emergency load will be forced On and full bright to 100%.
In room ladderless testing is done by pressing the "All Off" button four times, within 3 seconds.
The RC3DE is UL 924 listed.
VOLU
ME
CHAN
NEL
OPTI
ON
SLEE
PM
UTE
2AL
LON
/OFF
3
10
PREV
98
76
54
32
1
TVcc
Room Controller - Semi-Private Patient Room w/Daylight Dimming and Pillow Speaker Integration
www.coopercontrol.com
3
mountIng the room Controller
wIrIng dIagram
ConneCtIonS
daylIght SenSor CeIlIng loCatIon
Sample load Zoning(for example purposes only)
Sample placement diagram(for example purposes only)
room Controller 0-10V dimming ConnectionsDimmer 1: Near the WindowDimmer 2: Middle of RoomDimmer 3: Far from Window
The daylight sensor will automaticallyprovide multi-zone daylight dimming based on this wiring configuration.
room Controller and Smart devices use Click & go Connections1. Wallstations (up to four)2. Slider Station Connection (one)3. Occupancy Sensors (up to two)4. Daylight Sensor (one)5. Receptacle Control or BMS Output6. Switchpack (controlled with Load 1 for
alternate voltage)
WindowLoad 1
Dim
mer 1
ExamLighting
Load 3D
imm
er 3
Reading Light
Load 2D
imm
er 2 General Lighting
Window
Load 1D
imm
er 1
ExamLighting
Load 3D
imm
er 3R
eading Light
Load 2D
imm
er 2General Lighting
Window
Room Controller(above ceiling over headwall)
Patient Wallstation
DaylightSensor
GPC
SG
reengate Patient C
ontrol Station
GG
37P
General
Exam
Reading
Raise
All Off
Lower
All O
ff
Reading
Exam
General
General
Exam
Reading
All O
ff
GG
37P
GPC
SG
reengate Patient C
ontrol Station
Room Controller(above ceiling over headwall)
Window
DaylightSensor
Patient Wallstation
Patient Wallstation
Patient Wallstation
Lower
All Off
Raise
Reading
Exam
General
cc TV
12
3
45
67
89
PREV
0
13
ALL
ON
/OFF
2
MU
TE
SLEEPO
PTION
CH
AN
NEL
VOLU
ME VO
LUM
EC
HA
NN
EL
OPT
ION
SLEE
P
MU
TE
2 ALL
ON
/OFF
31
0PR
EV
98
76
54
32
1
TV cc
For semi-private rooms where you would need multiple Room Controllers, each would mount above the ceiling in the space it is controlling, typically above the headwall so it can be easily wired to the 37pin connector and Nurse Call System. The Room Controller includes breakouts for direct conduit connection limiting the need for additional junction boxes. Mount the Room Controller using the keyhole slots at the top and secure to the wall using the holes at the bottom of the Room Controller
Connect conduit to the line voltage breakout connections and connect the line and load wires. Connect low voltage cables either through the low voltage breakout openings or by connecting low voltage conduit to the breakouts on the low voltage side of the Room Controller.
Dimmer 3 Dimmer 2 Dimmer 1+ - -+ + -
0-10V Dimming
0-10V Violet (+)0-10V Gray (-)
4325 6
1
Room Controller - Semi-Private Patient Room w/Daylight Dimming and Pillow Speaker Integration
DSRC-FMOIR(Multi-zone
daylight sensor)
Wallstation
Room Controller(Above Ceiling Over Headwall)Normal Power
(Line In & Load Out)
Emergency Power(Line In & Load Out)
0-10V Dimmer Wiring(low voltage, class 2)
Lower
All Off
Raise
Reading
Exam
General General
Exam
Reading
All Off
GPCS(Greengate Patient
Control Station)
GG37P(Greengate 37 Pin Receptacle
for GPCS control station connection)
Connections to Nurse Call Stations and Entertainment System
Connections to Room Controller
Wallstation
ccTV
12
34
56
78
9PREV
01
3ALL
ON/OFF
2M
UTESLEEP
OPTION
CHANNEL
VOLUME
1. Mount the daylight sensor one to two times the window height from the window wall.
2. Position the sensor so its arrow is pointed toward the nearest window.3. Ensure the daylight sensor is not obstructed or looking directly at electric
light.4. For narrow spaces mount the daylight sensor near the window facing into
the space.
60°
Area viewed bydaylight sensor
www.coopercontrol.com
4
orderIng (per patIent bed)
healthCare applICatIon button FunCtIonalIty
pre-deFIned wallStatIonS and pIllow Speaker model numberS
rC-4tSb-hC1 rC-6tSb-hC2
room ControllerQuicKit
types of Space and ControlHC3E - Healthcare Patient Room (RC3DEHC) pillow Speaker
3Z - 3 Relay On/Off control
3ZD - 3 Relay On/Off, 3 zone dimming control
2Z - 2 Relay On/Off control
2ZD - 2 Relay On/Off, 2 zone dimming conrtol
daylightD1 - Multi-zone Daylight Sensor
DH - Multi-zone Daylight Sensor w/
Handheld Remote optionsP - Plug Load
B - BMS/Egress
Station ColorW - White
G - Gray
V - Ivory
B - Black
patient Stations (Choose up to 4)HC1 - General, Exam, Reading, All Off
HC2 - General, Exam, Reading, Raise, Lower, All Off
programno.
button textControl
type
Function(unless a target level is indicated, the dimmer output will default to daylight sensor control)
1 General Toggle Load 1 (yellow) ON and OFF
2 Exam Toggle Load 2 (red) ON and OFF
3 Reading Toggle Load 3 (purple) ON and OFF
6 Raise Raise Raise All Dimmers†
7 Lower Lower Lower All Dimmers†
16 All On PresetLoad 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON
8 All Off PresetLoad 1 (yellow) OFF, Load 2 (red) OFF, Load 3 (purple) OFF
†Final dimmer output level is determined by the fol lowing combination:• High end trim level• Daylighting contribution
If enough natural l ight is entering the space and either of these features has been implemented, raise commands from pushbuttons or the Greengate Patient Control Station wil l not override or raise the l ighting above the target threshold implemented by these advanced energy savings methods.
additional Information:Emergency relay wil l always work under normal conditions with Load 1 (yellow lead).
Alternate Voltage Switchpack: Click & Go connected alternate voltage switchpacks wil l always track with Load 1 (yellow lead).
General
Exam
Reading
All Off
General
Exam
Reading
Raise
Lower
All Off
Catalog #
Project
Comments
Prepared by
Type
Date
Room Controller - Semi-Private Patient Room w/Daylight Dimming and Pillow Speaker Integration
ACC130085
gpCS-2Z gpCS-2Z-dIm gpCS-3Z gpCS-3Z-dIm
7
4
1
8
5
2 3
6
9
TVPOWER
CHANNEL VOLUME
Gen4
OPTION
MUTEPREV
SLEEP
0
ALLON/OFF
LIGHTS1 3
7
4
1
8
5
2 3
6
9
TVPOWER
CHANNEL VOLUME
Gen4
OPTION
MUTEPREV
SLEEP
0
ALLON/OFF
LIGHTS1 3
LIGHTDIM
7
4
1
8
5
2 3
6
9
TVPOWER
CHANNEL VOLUME
Gen4
OPTION
MUTEPREV
SLEEP
0
ALLON/OFF
LIGHTS1 3
2
7
4
1
8
5
2 3
6
9
TVPOWER
CHANNEL VOLUME
Gen4
OPTION
MUTEPREV
SLEEP
0
ALLON/OFF
LIGHTS1 3
2
LIGHTDIM
Input button IconControl
type
Function(unless a target level is indicated, the dimmer output will default to daylight sensor control)
1 (General)
1
2
ALLON/OFF
3
ToggleLoad 1 (yellow) ON and OFF, Sets Raise/Lower control action to control Dimmer 1
2 (Exam)
1
2
ALLON/OFF
3
ToggleLoad 2 (red) ON and OFF, Sets Raise/Lower control action to control Dimmer 2
3 (Reading)
1
2
ALLON/OFF
3 ToggleLoad 3 (purple) ON and OFF, Sets Raise/Lower control action to control Dimmer 3
6 (All)
1
2
ALLON/OFF
3
ToggleLoad 1 (yellow), Load 2 (red), Load 3 (purple) ON and OFF, Sets Raise/Lower control action to control dimmers 1, 2 and 3
Raise
1
2
ALLON/OFF
3
Raise
Raise the selected dimmer zone.† Zone controlled is based on last GPCS button that was pressed. To control all zones together, ensure that the ALL button is pressed prior to raising the zones.
Lower
1
2
ALLON/OFF
3
Lower
Lower the selected dimmer zone. Zone controlled is based on last GPCS button that was pressed. To control all zones together, ensure that the ALL button is pressed prior to raising the zones.
†Final dimmer output level is determined by the fol lowing combination:• High end trim level• Daylighting contribution
If enough natural l ight is entering the space and either of these features has been implemented, raise commands from pushbuttons or the Greengate Patient Control Station wil l not override or raise the l ighting above the target threshold implemented by these advanced energy savings methods.
additional Information:Emergency relay wil l always work under normal conditions with Load 1 (yellow lead).
Alternate Voltage Switchpack: Click & Go connected alternate voltage switchpacks wil l always track with Load 1 (yellow lead).
RCQK - HC3E - HC1-HC2 - 3ZD - D1 - P - W
*Catalog number automatically includes low voltage connection cable, wallplates and connectors based on room type and configuration.
*For site specific engraving, please see the Room Controller Wallstation custom engraving form on the Cooper Controls website
† These dimming wallstations can only be used with dimming Room Controllers (RC3D, RC3D2, RC3DE)
†† Slider stations can not be used if a wallstation with Raise/Lower buttons are used
pIllow Speaker FunCtIonalIty
Recommended