Pluri-MX-MN.doc Page 1 sur 3
STS Maintenance des systèmes de production
Bobines de déclenchement MX-MN
Savoirs associés
S10.2 Opération de maintenance corrective et préventive S10.8 Communication technique
73Schneider Electric - Circuit breakers, UL
C60UL 489, UL489A, UL1077
OF, SD, MX + OF, MN
Multi 9 SystemElectrical auxiliaries
Remote trippingRemote tripping is possible by means of a shunt trip (MX + OF) or undervoltage release (MN). A tripped device is indicated by a red indicator fl ag on the front panel.
MX + OF shunt trip
When energized, trips the associated device :b equipped with an O + F switch that indicates the “open” or “closed” position of the v
devicerealize a self-interrupting allowing the control circuit to remain on.v
Wiring diagrams
MN Undervoltage Release
When the voltage drops to 70–35% of the supply voltage, the associated device b trips and is prevented from reclosing until the supply voltage is restored:
uses emergency stop via push buttonv uses safety feature on circuit supplying several machines preventing uncontrolled v
restarting of the motors.
Wiring diagrams
C1C21214
u >
D1D2
u <
L or +
N or -
D1 D2
u <
IEC
Etude pluritechnologique Nom Prénom
Nom Prénom
Compétences C 22 Analyser l’organisation fonctionnelle, C23 Chaine d’énergie, C24 Chaine d’information C 15 Identifier les risques pour les personnes ou l'environnement, définir et respecter les mesures de prévention adaptées
Grille d’évaluation du TP
EVALUATION DE LA COMPETENCE C 12 et C22
Actions liées à l’activité Indicateurs de performance
0
1
2
3 Identification du fonctionnement des bobines de déclenchement Le rôle des bornes des
appareils sont identifiés
Schéma de mise en oeuvre Les schémas sont justes et repérés.
Mise en œuvre, mesure des performances Fonctionnement et test des performances attendues
. Saisie sous winrelais Schéma réalisés et repérés
EVALUATION DE LA COMPETENCE C 15 Identifier les risques pour les personnes ou l'environnement, définir et respecter les mesures de prévention adaptées
Actions liées à l’activité Indicateurs de performance
0
1
2
3
Identifier les situations dangereuses Les situations dangereuses sont identifiées
Préciser les mesures de sécurité Les mesures de sécurité sont identifiées
Le choix de l’outillage est adapté Les conditions de sécurité sont respectées
NOTE /20
Tâches professionnelles
T 13 Mettre en œuvre les solutions d’amélioration
Prérequis
S5.2 Approche fonctionnelle, S5.4 Solutions constructives, S6.4 Conversion de l’énergie
Pluri-MX-MN.doc Page 2 sur 3
CONDITIONS DE REALISATION
- Durée : 3h dans la zone maintenance. - Documentation : Le dossier technique est sur l’espace numérique de travail Platine régime du neutre, oscilloscope
PROBLEMATIQUE, ORDRE DE TRAVAIL
Mettre en œuvre une solution de déclenchement de disjoncteur, vérifier les performances de
l’installation
Présentation : La bobine de déclenchement a pour rôle de déclencher le disjoncteur qui isolera le circuit en défaut.
Il existe deux types de bobines :
La bobine à émission de courant ;
La bobine à manque de tension ;
La Bobine à émission de courant : déclenche le disjoncteur si cette bobine reçoit sa tension assignée de déclenchement.
La bobine à manque de tension : déclenche le disjoncteur si cette bobine ne reçoit plus sa tension assignée.
Contrôle d’un disjoncteur avec deux arrêts d’urgence :
Réaliser deux schémas qui permettent de contrôler un disjoncteur avec 2 arrêts d’urgence. (câblage à repérer au contrôleur)
Le premier avec une bobine MN
Le second avec une bobine MX, sur ce dernier montage, un buzzer doit retentir s’il y a déclenchement du disjoncteur
Valider le schéma en réalisant le câblage. Vous câblerez la maquette régime du neutre coté IT.
Le disjoncteur piloté par les arrêts d’urgence doit remplacer Q32.
Proposer et mettre en oeuvre une procédure qui permette de mesurer le temps de déclenchement des disjoncteurs.
Les deux schémas sont à rendre. Il sont réalisés sous winrelais.
Documentation :
73Schneider Electric - Circuit breakers, UL
C60UL 489, UL489A, UL1077
OF, SD, MX + OF, MN
Multi 9 SystemElectrical auxiliaries
Remote trippingRemote tripping is possible by means of a shunt trip (MX + OF) or undervoltage release (MN). A tripped device is indicated by a red indicator fl ag on the front panel.
MX + OF shunt trip
When energized, trips the associated device :b equipped with an O + F switch that indicates the “open” or “closed” position of the v
devicerealize a self-interrupting allowing the control circuit to remain on.v
Wiring diagrams
MN Undervoltage Release
When the voltage drops to 70–35% of the supply voltage, the associated device b trips and is prevented from reclosing until the supply voltage is restored:
uses emergency stop via push buttonv uses safety feature on circuit supplying several machines preventing uncontrolled v
restarting of the motors.
Wiring diagrams
C1C21214
u >
D1D2
u <
L or +
N or -
D1 D2
u <
IEC
73Schneider Electric - Circuit breakers, UL
C60UL 489, UL489A, UL1077
OF, SD, MX + OF, MN
Multi 9 SystemElectrical auxiliaries
Remote trippingRemote tripping is possible by means of a shunt trip (MX + OF) or undervoltage release (MN). A tripped device is indicated by a red indicator fl ag on the front panel.
MX + OF shunt trip
When energized, trips the associated device :b equipped with an O + F switch that indicates the “open” or “closed” position of the v
devicerealize a self-interrupting allowing the control circuit to remain on.v
Wiring diagrams
MN Undervoltage Release
When the voltage drops to 70–35% of the supply voltage, the associated device b trips and is prevented from reclosing until the supply voltage is restored:
uses emergency stop via push buttonv uses safety feature on circuit supplying several machines preventing uncontrolled v
restarting of the motors.
Wiring diagrams
C1C21214
u >
D1D2
u <
L or +
N or -
D1 D2
u <
IEC
Pluri-MX-MN.doc Page 3 sur 3
73Schneider Electric - Circuit breakers, UL
C60UL 489, UL489A, UL1077
OF, SD, MX + OF, MN
Multi 9 SystemElectrical auxiliaries
Remote trippingRemote tripping is possible by means of a shunt trip (MX + OF) or undervoltage release (MN). A tripped device is indicated by a red indicator fl ag on the front panel.
MX + OF shunt trip
When energized, trips the associated device :b equipped with an O + F switch that indicates the “open” or “closed” position of the v
devicerealize a self-interrupting allowing the control circuit to remain on.v
Wiring diagrams
MN Undervoltage Release
When the voltage drops to 70–35% of the supply voltage, the associated device b trips and is prevented from reclosing until the supply voltage is restored:
uses emergency stop via push buttonv uses safety feature on circuit supplying several machines preventing uncontrolled v
restarting of the motors.
Wiring diagrams
C1C21214
u >
D1D2
u <
L or +
N or -
D1 D2
u <
IEC
Maquette de câblage régime du neutre : coté IT Attention la tension en sortie de transformateur est 230v triphasé. Donc 230v entre phases et 127v entre phase et neutre.
10 Institut Schneider Formation / MDG9AD605 / 10-97
Régimes du neutre & protection des personnes
R1 R2 R3
CPI
Q1
Q21 Q22
Q32 Q33
Ph1Ph2Ph3N
PE
Bp2 Bp3
H1 H2 H3
1 kΩ
16 A
10 A
300 mA
10 A
300 mA
6 A
300 mA
6 A
30 mA
U = 25 VLU = 25 VL U = 50 VL
D'U R G E N
CE
ARRET
RARB
0 à 1 A0 à 1 s
Surface de travail régime IT
Disjoncteur Q32 à remplacer
Par le disjoncteur de la maquette
Disjoncteur piloté par les bobines de déclenchement
Arrêts d’urgence permettant le
déclenchement