View
224
Download
0
Category
Preview:
Citation preview
36
TRIAC
Resistance temperature detector
1-channel PID controllerTRM210 is a 1-channel PID controller available in di�erent enclosure variants: for wall and for pan-el mounting. This device is intended for measur-ing, displaying and controlling di�erent physical process variables such as temperature, pressure, humidity, etc. Universal analog input and optional outputs provide particular fl exibility for using this device in di�erent areas of industry, agriculture and utilities. This process controller also features a digital input for remote start/stop of the control process.
TRM210PROCESS CONTROLLERS
Functions and features:• Measuring the process value and its
transformation according to the sensor type• Displaying the process values and confi guration
parameters on two 4-digit LED displays• Scaling and fi ltering the input signal• Signal correction• PID control (pulse or analog) or on-o� control• Autotuning function• Stand-alone control• Manual control• Network control (RS485 interface) with
akYtec, Modbus RTU and Modbus ASCII protocols as a Slave
• Signal retransmission using analog output 4-20 mA or 0-10 V
• Alarm output• Sensor / input error and Loop Break Alarm
detection• Error indication• Remote start / stop using digital input• Confi guration via the functional keys
1 channel for controlling
Thermocouple
Analog input 4-20 mA
Analog input 0-1 V
1 digital input
On-o� control
Relay output
Solid state relay
Analog output 4-20 mA
Analog output 0-10 V
NPN transistor
RS485 interface
Modbus RTU/ASCII protocol
PID control
Ambient temperature
Output type on request
Enclosure:
H1(96 x 96 x 70 mm)
H3(105 x 130 x 65 mm)
H2(96 x 48 x 100 mm)
We will be glad to assist you! Tel.: (+34) 968 162 005 - Email: comercial@sensovant.com www.sensovant.com- Web:
37
TRM210. X . X
EnclosurePanel 96 x 96 x 70 mm H1
Panel 96 x 48 x 100 mm H2
Wall 105 x 130 x 65 mm H3
Output typeRelay output RNPN transistor TTRIAC CSolid state relay SAnalog output 4-20 mA IAnalog output 0-10 V U
TRM210PROCESS CONTROLLERS
Areas of application:The PID controller TRM210 is designed for creating automatic control and regulation systems of various technological processes in di�erent areas of industry, agriculture and utilities
Technical Data:Power supply 230 (90...264) V AC; 50 (47...63) HzPower consumption, max. 6 VAAnalog input 1Digital input 1Optional outputs 2Sampling rate, max. 1 sInterface RS485Protocols Modbus RTU / ASCII, akYtecBaud rate 2.4...115.2 kbit/sAmbient temperature +1...+50 °C
EnclosureType H1 H2 H3
Enclosure 96 x 96 x 70 mm 96 x 48 x 100 mm 105 x 130 x 65 mm
IP Code front IP54 front IP54 IP44
Input signal
RTDIEC Pt50, Pt100
GOST 50P, 100P, 50M, 100M, Cu50, Cu100
TCIEC B,J, N, K, S, R, A, T
GOST L, A-2, A-3Standard signals 0-5 mA, 0-20 mA, 4-20 mA, -50...+50 mV, 0-1 V
Outputs
R Relay 1 A (PID control) / 8 A (alarm), 30 V DC / 230 V ACT NPN 200 mA, 40 V DC
C TRIAC 50 mA (240 V AC, constantly open),500 mA (f ≤ 50 Hz, pulse duration 5 ms)
S SSR 100 mA, 4…6 V DC
I 4-20 mA 0…36 V, max. 1 kohm
U 0-10 V 15…36 V, min. 2 kohm
Ordering code:Standard variants: Description: Enclosure:
TRM210-H1.RR 2DO (Relay) Panel 96 x 96 mm
TRM210-H2.RR 2DO (Relay) Panel 96 x 48 mm
TRM210-H3.RR 2DO (Relay) Wall 105 x 130 mm
TRM210-H1.SR 1DO (SSR) + 1DO (Relay) Panel 96 x 96 mm
TRM210-H2.SR 1DO (SSR) + 1DO (Relay) Panel 96 x 48 mm
TRM210-H3.SR 1DO (SSR) + 1DO (Relay) Wall 105 x 130 mm
TRM210-H1.UR 1AO (0-10 V) + 1DO (Relay) Panel 96 x 96 mm
TRM210-H2.UR 1AO (0-10 V) + 1DO (Relay) Panel 96 x 48 mm
TRM210-H3.UR 1AO (0-10 V) + 1DO (Relay) Wall 105 x 130 mm
TRM210-H1.IR 1AO (4-20mA)+1DO (Relay) Panel 96 x 96 mm
TRM210-H2.IR 1AO (4-20 mA)+1DO (Relay) Panel 96 x 48 mm
TRM210-H3.IR 1AO (4-20 mA)+1DO (Relay) Wall 105 x 130 mm
We will be glad to assist you! Tel.: (+34) 968 162 005 - Email: comercial@sensovant.com www.sensovant.com- Web:
38
TRM210PROCESS CONTROLLERS
Sensor 1 Input 1
Input 2
Output 1
Output 2
Heating element 1T
Signaling
"Start / Stopregulate"
TRM 210
PID
ON/OFF+LBA
RS485
230 (90...264) V AC
PSIntegrrated
voltage sours24 V DC
TRM 210 TRM 210
TRM 210
T T
Heating element 1
4-20 mA
T
SSR ~4-20 mA(0-10 V) (0-10 V)
4-20 mAHeating element 1
TRM 210 TRM 210
TRM 210
T T
Heating element 1
4-20 mA
T
SSR ~4-20 mA(0-10 V) (0-10 V)
4-20 mAHeating element 1
1. PID control and signal retransmission over the analog output 4-20 mA or 0-10 V.
2. PID control and alarm output.3. PID control of an analog control valve and alarm
output.
Typical application cases
1.
2.
3.
START/STOP
START/STOP
We will be glad to assist you! Tel.: (+34) 968 162 005 - Email: comercial@sensovant.com www.sensovant.com- Web: