OWNER'S MANUAL
FLEET POWERINVERTER/BATTERY CHARGERS
FLEET POWER 1000FLEET POWER 2000FLEET POWER 2500
Fleet Power 1000 & 2000 models are certified by UL to comply with FED spec-KKK-A1822, SAEspec-SAE-JRR1, for emergency vehicle application. All models UL and C-UL Listed for Canadian use.
KKK
UL®C
90-0115-0010/97 Fltman.pm65
INTRODUCTION
General safety information for installationand operation is contained throughout thismanual where it applies and are not includedin this summary.
Warnings Warning statements identify condi-tions or practices which could result in personalinjury, loss of life, damage to equipment orother property.
Fuse Replacement For continued protectionagainst the possibility of fire, replace the fuseonly with a fuse of the specified voltage, currentand type rating.
Power Source To avoid damage, operate theequipment only within the specified AC (line)and DC (battery) voltages.
Servicing To reduce the risk of electric shockdo not open this unit. There are no user ser-viceable parts inside. Refer all servicing toqualified personnel.
2
The statements, specifications and instructions in this publication are believed to be correct. No warranty is made, expressed or implied by the seller ormanufacturer with respect to any results or lack thereof from the use of information in this publication and no liability is assumed for any direct orconsequential damages, personal loss or injury. All statements made herein are strictly to be used or relied on at the user's risk.© 1997 Heart Interface Corporation. All rights reserved.
90-0115-0010/97 Fltman.pm65
TABLE OF CONTENTS
3
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Things You Should Know . . . . . . . . . . . . . . . 5Circuit Breaker ProtectionElectronic ProtectionPower SharingPower SwitchRemote Control Programming
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Remote Control Panel . . . . . . . . . . . . . . . . . . 7Remote Power SwitchSystem Status LEDsDC Volts BargraphDC Amps BargraphDip Switches
Equalize or 3-Stage ChargingBattery TypeAuto RangePower SharingDip Switch StatusRemote Control WiringLink 2000 Remote Control
Status LEDs . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dip Switch Programming . . . . . . . . . . 11
Batteries . . . . . . . . . . . . . . . . . . . . 12Battery TypesBattery InterconnectionBattery Bank Ratings and Sizing
Battery Charging . . . . . . . . . . . . . . . . . . 16Conventional Battery ChargersFleet Power Battery ChargerCharging Over-Discharged Batteries
Battery Charger Voltage Table . . . . . . . . . . 21
Installation Precautions . . . . . . . . . . . . . . . 22
Installation . . . . . . . . . . . . . . . . . . . . . . . 23Key Installation PointsLocationGroundingNeutral BondingAC WiringGround Fault Circuit InterruptersRemote Control WiringDC WiringBattery Cable Fusing
Installation Options . . . . . . . . . . . . . . . . . . 29
DC Wiring Options . . . . . . . . . . . . . . . . . . . 32
Troubleshooting . . . . . . . . . . . . . . . . . . . . . .34
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . 36
Specifications . . . . . . . . . . . . . . . . . . . 38
Warranty . . . . . . . . . . . . . . . . . . . . . . 40
90-0115-0010/97 Fltman.pm65
INTRODUCTIONThis owner's manual describes the
Fleet Power Inverter/Chargers from HeartInterface. These units perform three distinctfunctions:1. DC to AC power inverting.2. Automatic transfer switching between inverter power and incoming AC power.3. Automatic 3-Stage Battery charging plus manual battery equalizing.
4. AC to DC power converter.
• The inverters provide regulated 120 VoltAC power and crystal controlled frequencyat 60Hz from a deep cycle battery bank inspecified watts:
FP 1000-12................1000 wattsFP 2000-12................2000 wattsFP 2500-12................2500 watts
The output is a modified sinewave andis compatible with appliances, tools andother 120 VAC equipment. Momentarysurge power of three times the inverterrating is available for starting electric mo-tors. High efficiency insures the longestpossible battery life between recharges.
• The transfer switch allows the Fleet PowerInverter/Chargers to be connected to anexternal AC source and transfer the sourcethrough to the loads. When disconnected,the transfer switch allows automatic switch-ing back to the inverter.
Fleet Power Inverter/Chargers operateas self-contained backup power systems,just add batteries.
• Fleet Power battery chargers are electroni-cally controlled and rated:
FP 1000-12..................50 Amps DCFP 2000-12................100 Amps DCFP 2500-12................130 Amps DC
They are designed to rapidly and optimallyrecharge either wet* or gel* cell deep-cyclebatteries. Battery charging is accomplishedin 3 automatic stages: Bulk Charge, Accep-tance Charge and Float Charge. In addition,using the remote control, a manually-en-gaged Equalizing Charge cycle is possible.
With an external AC source connected,the Fleet Power charger also serves thefunctions of a AC to DC converter to supplyall of the DC loads which are connected tothe battery.
Simple, automatic operation is madepossible by the microprocessor in the FleetPower Inverter/Chargers. In most cases, theunit is left on and no attention or mainte-nance is required.
*Adustable with optional remote
4
90-0115-0010/97 Fltman.pm65
THINGS YOU SHOULD KNOW
The optional Fleet Power RemoteControl Panel provides a power switch,system status LEDs, DC Volts and DC AmpsLED bargraphs. On the back of the remoteis a set of dip switches which allow adjust-ment of the following:
• Manual Initiation of Equalize Charging• Ambient Battery Temperature• Battery Type• Charger Mode (Auto or Controlled)• Power Sharing
Circuit Breaker ProtectionFleet Power Inverter/Chargers are
circuit breaker protected.
The Fleet Power 1000 has a 12 AmpINV/CHG circuit breaker on the front of theunit that protects against sustained inverteroverloads over 1440 watts and the AC inputto the battery charger. The 15 Amp INPUTcircuit breaker on the unit protects theincoming AC circuit which is transferredthrough to the loads via the GFCI.
The Fleet Power 2000 has a 25 AmpINV/CHG circuit breaker that protectsagainst sustained inverter overloads over3000 watts and the AC input to the batterycharger. .
The Fleet Power 2500 has a 30 AmpOUTPUT circuit breaker on the unit thatprotects against sustained inverter over-loads over 3600 watts. The 30 Amp circuitbreaker protects the incoming AC leg whichfeeds the battery charger.
The 30 Amp TRANSFER circuit breaker
on the units protect the incoming AC circuitwhich is transferred through to the loadsconnected by the hardwire output.
The 15 Amp circuit breaker protects theGFCI outlet on the Fleet Power 1000 and2000 models. When a circuit breaker trips,the circuit breaker is reset by pushing thebutton back in.
Electronic ProtectionFast acting electronic circuits protect
the inverter from extreme overloads andshort circuits. Other protection includes alow and high battery cutoff and automaticshutdown if over temperature occurs. Thefault condition must be eliminated beforereset will occur. Example: remove over-load, recharge batteries or allow to cool.Reset by cycling the power switch OFF/ON.
Power SharingWhen connected to shorepower or
using a generator, the battery charger andtransfer functions are engaged. A uniquepower sharing feature automatically reducesthe AC consumption of the battery chargerallowing necessary AC power to the load.This prevents the circuit breaker from trip-ping. This feature can be adjusted usingthe remote control panel. This feature is setat the transfer rating of each unit by default.
5
INPUT
INV/CHG
GFCI
Fleet Power 2000 shown.
90-0115-0010/97 Fltman.pm65
Power SwitchThe Power Switch is located on the
front panel. This switch controls ON/OFFand RESET for the inverter. Expect a 3second delay when the power switch isturned ON before the unit is activated.
If the unit is connected to external ACpower, the battery charger and transferswitch will continue to function, regardlessof the position of the switch.
When external AC power is removedand the power switch is in the ON position,the inverter will automatically be ON. If theswitch is in the OFF position and externalAC power is removed, the inverter will beOFF.
Inverter overload protection, transferswitching, power sharing and batterycharger regulation will all function automati-cally.
If installed with the remote controlpanel, the power switch on the unit shouldbe left in the OFF position. Refer to Re-mote Control Panel, page 7.
OPERATION
6
Power Switch
Fleet Power 1000 shown.
90-0115-0010/97 Fltman.pm65
REMOTE CONTROL PANEL
Volts bargraph will stop indicating batteryvoltage and display the dip switch settings.It will return to indicating battery voltageonly after the unit has been reset.
DC Amps BargraphThese LEDs approximate DC input
current in inverter mode and DC outputcurrent in battery charger mode. Tworanges are used -- below 50 Amps eachsegment represents a 10 Amp increment,above 50 Amps each segment represents a20 Amp increment. Above 130 Amps, aflashing LED segment indicates the valuedisplayed plus 100 Amps (flashing 50 LEDis equal to 50 + 100 or 150 Amps DC).
If a shutdown occurs, the DC Ampsbargraph will stop indicating DC Amps andwill indicate the type of problem . Each LEDsegment indicates a different problem asdescribed in the troubleshooting section onpage 34.
Remote Power SwitchThe switch on the remote is used to
control the inverter and can also be used tocontrol the battery charger function. Whena remote control is used, the power switchon the inverter should be left in the OFFposition.
System Status LEDsThese 4 LEDs monitor the system as
described in the table on page 10.
DC Volts BargraphThese LEDs indicate battery voltage as
measured inside the unit. Each LED seg-ment indicates .5 Volts. If an overloadoccurs and the unit shuts down, the DC
An optional remote control panel isavailable which offers several features notfound on the unit. The remote control panelprovides LED bargraphs which show systemstatus, battery voltage, and DC Amps inboth inverter and charge modes. Thesebargraphs can also display dip switch posi-tions and shut down conditions.
7
90-0115-0010/97 Fltman.pm65
REMOTE CONTROL PANEL
Dip SwitchesOn the back of the Fleet Power remote
control panel is a set of 8 dip switcheswhich are used to make several adjust-ments. On the switch block, each switch isnumbered . . .1 through 8 and the ON posi-tion is indicated. The switch settings can bechanged at any time, even while the unit isoperating. Following is a discussion ofeach adjustment. Refer to the table onpage 11 for dip switch programming.
SWITCH 1 - Manual Equalizing Cy-cling this switch ON for 1 second, then OFF,will initiate an equalizing charge cycle. Thebattery charger must be engaged beforecycling the switch. The dip switch mustalways be returned to the OFF position.If it is left ON, an equalizing charge cyclewill initiate every time the charger isengaged - this could cause battery dam-age.
The equalizing cycle is timed to last 8hours from the time the switch is cycled, atwhich point the charger resumes normalcharging in the float stage.
The battery LED blinks when equaliz-ing. See page 18 for a discussion of thetheory and procedure for battery equalizing.
SWITCH #2 & #3 - Battery Type Gel celland wet cell batteries have slightly differentcharge voltage requirements. Optimumbattery charging is temperature dependent.For these reasons, the dip switches allowfour different battery charger voltage setpoints, depending on battery type andambient temperature:
Cool Wet Cell < 80 degrees F.Warm Wet Cell > 80 degrees F.Cool Gel Cell < 80 degrees F.Warm Gel Cell > 80 degrees F.
Refer to the table on page 21 for thespecific voltages for each setting.
SWITCH #4 - Auto Charge With the switchin the OFF position, the remote panel ON/OFF switch only controls the inverter opera-tion. With the switch turned ON, it allowsthe power ON/OFF switch on the front of theremote to control the battery charger as wellas the inverter.
SWITCH #5 & #6 - Not used for adjust-ments.
SWITCH #7 & #8 - Power Sharing Theseswitches should be set to match the value ofthe circuit breaker which protects the incom-ing AC power. They may also limit theoutput current from the battery charger.
8
BACK VIEWFleet Power Remote Control Panel
90-0115-0010/97 Fltman.pm65
REMOTE CONTROL PANEL
Use the 5 Amp setting for small genera-tors, or for charging deeply dischargedbatteries.
Dip Switch StatusYou can check the position of the dip
switches by quickly cycling the power switchOFF/ON twice. The DC Volts bargraph willcease to display battery voltage and willindicate the settings of each dip switch. Inthis mode the bottom LED will illuminate ifswitch 1 is on; the second LED will illumi-nate if switch 2 is on, etc. Dip switch set-tings are indicated for 10 seconds afterwhich time the display returns to indicatingbattery voltage.
Factory default settings for all dipswitches are in the Off position.
Remote Control WiringThe remote control panel is supplied
with 25 or 50 ft. of telephone cable. Thecable supplied may be 6 conductor, how-ever, only 4 conductor is required. You maybuy standard 4 conductor telephone cableand run up to 50 ft., if desired. Use only asingle length of telephone wire, do notsplice.
Refer to page 11 for the Dip SwitchProgramming chart.
9
90-0115-0010/97 Fltman.pm65
Status LED Purpose
INV/CHRG(Inverter/Charg
Power on light. It will be illuminated whenever thepower switch is on (inverter on) or when there isincoming AC power and the charger comes on.
AC Input
Illuminates when incoming AC power has beenapplied and the transfer relays have engaged.There is a 7-12 second delay from the time the ACis applied and this LED illuminates.
SteadyOverload
Indicates an over-temperature condition, the unit isshut down. It will reset automatically after cooling.
BlinkingOverload
Inverter mode- Shutdown, diagnose problem usingDC Amps bar graph. Charger mode- Thermalshutdown, after cooling reset by cycling powerswitch.
Steady BatteryThis is a High/Low Battery warning condition.Inverter mode: Battery > 15.25 or < 10.50 voltsCharger mode: Battery > 15.25 or < 10.00 volts
BlinkingBattery
Indicates either a shutdown or equalizing.Battery > 15.50 volts, will auto-reset at 15.25.Inverter mode: Battery < 10.00 volts, will auto resetat charger float voltage or upon AC input.Charger mode: Battery < 8.00 volts for 1 minute,remove all DC loads and manually reset by cyclingthe power switch.
STATUS LEDs
10
disconnecting and reapplying shorepower.
90-0115-0010/97 Fltman.pm65
Feature SwitchNumber Set Point
Equalize or3 Stage
Charging
1
ToggleOn/Off
Equalize (Do not leave on.)
Off 3 Stage Charging*
BatteryType
2 3
On On Warm Gel Cell (>80 deg. F.)
Off On Cool Gel Cell (<80 deg. F.)
On Off Warm Wet Cell (>80 deg. F.)
Off Off Cool Wet Cell (<80 deg. F.)*
AutoCharge
4
On Disable: Charger responds to On/Offswitch.
Off Enable: Charger on when ACconnected.*
5 6 Not used.
PowerSharing
7 8
On On 2.5 Amps
Off On 5 Amps
On Off 10 Amps
Off Off 15 Amps*
DIP SWITCH PROGRAMMING
1000 2500
*indicates factory default setting.
5 Amps5 Amps
15 Amps
20 Amps
20 Amps
30 Amps
2000
11
30 Amps* Disabled*
90-0115-0010/97 Fltman.pm65
BATTERIES
BATTERY TYPESUse only deep-cycle batteries with your
Fleet Power Inverter/Charger. These fallinto two broad categories, wet cell and gelcell.
Wet Cell BatteriesTrue deep-cycle wet cell batteries are
characterized by relatively thick plates thatare alloyed with antimony.
Common marine/RV deep-cyclebatteries are acceptable. However, golfcart batteries have better performance andlife. They are 6 Volt batteries that must beused in series pairs. High quality marinedeep-cycle batteries offer good perfor-mance and are available in a wide varietyof sizes. Floor sweeper, fork lift or large 2Volt cells can also offer excellent perfor-mance, if their large size can be accommo-dated.
It should be noted that high antimonydeep-cycle batteries will give off gas as anatural result of charging and will experi-ence some water loss. It is very importantthat the electrolyte level be checkedfrequently and topped off with distilledwater when necessary. Never allow thetops of the plates to be exposed to air, ascontamination of the cell will result. Keep-ing the tops of batteries clean will reduceself-discharging. Always provide ventilationfor the battery storage compartment.
Do not use car batteries or enginestarting batteries of any kind with yourinverter/charger. Beware of any battery thatis rated in Cold Cranking Amps (CCA). Thisis a rating which applies only to enginestarting batteries. In general, most wet cellbatteries that are described as hybrid bat-teries, suitable for either engine starting ordeep-cycle applications, are a compromiseand will give limited life if deeply dis-charged.
Beware of 8-D starting batteries thatare commonly used for starting diesel en-gines. These batteries are not deep-cycle.
12
90-0115-0010/97 Fltman.pm65
BATTERIES
Beware of so-called maintenance-free batteries . These batteries have cal-cium alloyed with the lead and hold theliquid electrolyte in a sponge-like material.They are sealed and water cannot beadded. Do no confuse them with true gelcell batteries, they will not hold up to deepdischarging.
Gel Cell BatteriesGel cell batteries are lead-acid batter-
ies similar in many ways to the common wetcell battery, but differences in the chemistryand construction provide some uniquefeatures.
No Maintenance - There is no need toadd water and the tops of the batteries stayclean. Also, the batteries can be used inany position and may be used without abattery box.
Low Self-Discharging - Unlike wet cellbatteries, the gel cell will hold its charge formonths if left sitting with no load and nofloat charge. They can be stored without aconstant float charge and without fear offreezing.
Low Internal Resistance - The resultof low internal resistance is a higher batteryvoltage under load, which will result inbetter inverter performance on demandinghigh power loads. In addition, this allowsthe gel cell to accept a high rate of charge,a plus for rapid recharging.
The features of the gel cell batteriessolve many common problems. Cycle life ishigh, even under constant deep discharg-ing.
BATTERY INTERCONNECTIONIn most cases you will be using a bank
of two or more batteries with your inverter/charger. You may connect batteries to-gether in two configurations, series andparallel.
SeriesConnecting 2 batteries in series will
double the voltage of the battery bank. Forinstance, two 6 Volt batteries connected inseries will produce 12 Volts. The Amp-hourcapacity of the battery bank will be thesame as each individual battery. Example,two 6 Volt 220 Amp-hour batteries in serieswill produce on 12 Volt 220 Amp-hour bat-tery bank.
Series
++
-
-
13
90-0115-0010/97 Fltman.pm65
BATTERIES
Always use proper terminals for yourinterconnecting battery cables which areappropriate to handle the current.
Battery Bank Ratings and SizingDeep-cycle batteries are usually rated
in Amp-hours . The Amp-hour rating isbased on a 20 hour discharge cycle, there-fore, a 100 Amp-hour battery can deliver 5Amps for 20 hours. If the discharge rate isgreater than 5 Amps, the available Amp-hours are decreased. If the load is in-creased to 100 Amps, only about 45 Amp-hours will be available at this rate of dis-charge.
Another common rating is reservecapacity expressed in minutes. This isderived by placing a 25 Amp load on thebattery and measuring the time until thebattery voltage reaches 10.5 Volts.
Deep-cycle batteries can be dischargedabout 80% before permanent damageoccurs, though shallower cycling will resultin much longer battery life. 50% cycling isgenerally considered to be a good compro-mise between long battery life and a rea-sonably sized battery bank.
ParallelConnecting 2 batteries in parallel will
double the Amp-hour rating of the batterybank, while the voltage will be the same aseach individual battery. Example, two 12Volt 105 Amp-hour batteries in parallel willproduce one 12 Volt 210 Amp-hour batterybank.
+
+
--
Only similar batteries should beconnected together in one bank. Do notconnect old and new batteries together orwet and gel cell batteries together. In theabove drawing, the load is connected to thepositive terminal of the first battery and thenegative terminal of the last battery. Thispractice helps to balance the battery bankand is called cross connecting the batterybank.
Parallel
14
90-0115-0010/97 Fltman.pm65
BATTERIES
To achieve 50% cycling you shouldcalculate your Amp-hour consumptionbetween charging cycles and use a batterybank with twice that capacity.To calculate Amp-hour consumption firstlook at the rating plate on your AC appli-ance or tools. Each appliance or tool will berated in either AC Amps or AC watts or ACVA (Volts-Amps) apparent power. Use oneof the following formulas to calculate the DCAmp-hour draw for a 12 Volt system:
(AC Amps x 10) x 1.1 x hours ofoperation = DC Amp-hours
(AC watts/12) x 1.1 x hours of operation= DC Amp-hours
(AC VA/12) x 1.1 x hours of operation =DC Amp-hours
In all formulas, 1.1 is the factor forinverter efficiency.
Calculate the above for every ACappliance or tool you intend to use on yourinverter. This will give you the total numberof Amp-hours used between recharges.Size your battery bank using this number asa guideline. A good rule to follow is to sizethe battery bank about 2 times larger thanyour total Amp-hour load requirement. Planon recharging when 50% discharged.
Watts
On-Board ComputersQuartz Halogen Flood0.2 HP Bench GrinderHammer Drill3/8" Electric Drill MotorSawzall0.5 HP Bench Grinder1.0 HP Tile Saw0.5 HP Skil® Saw2.0 HP Radial Arm Saw2.5 HP Chain SawHand Blower/VacuumQuartz Halogen Flood11 gal. Air CompressorChain Saw20 gal. Air Compressor10" Table Saw10" Miter SawPlanerCoring System
Loads
200300300500500500750800
120012001200145015001600170018001800180018002000
Typical PowerConsumption
Many electric motors have momentarystarting requirements well above their op-erational rating. Start up watts are listedwhere appropriate. Individual styles andbrands of appliances may vary.
15
90-0115-0010/97 Fltman.pm65
Battery ChargingCompletely recharging wet cell deep-
cycle batteries requires the battery voltageto be raised beyond what is known as thegassing point. This is the voltage at whichthe battery begins to bubble and gas isgiven off. If charging stops short of thispoint, sulfate is left on the plates and dete-rioration of the battery begins. The gassingpoint will vary with battery temperature.
Gel cell batteries must not be chargedto their gassing point. In fact, high voltagecharging which gasses these batteries isharmful to them. They typically require alower bulk charge voltage and a higher floatvoltage. Consult the battery manufacturerfor specifications.
Conventional Battery ChargersMost conventional battery chargers are
single-stage constant voltage chargers.They must stop short of the gassing point orthey will overcharge the battery bank.Therefore, most 12 volt battery chargersbring the battery voltage up to about 13.8Volts.
BATTERY CHARGING
This presents two problems. First,since the battery voltage does not reach thegassing point, sulfate is left on the plates.Second, 13.8 volts is close enough to thegassing point that some gas will escape,and the wet cell battery will need to befrequently topped off with distilled water.
Conventional battery chargers alsosuffer from another inherent characteristic ofdesign, which is a tapering output. Whilethey will deliver their rated current into adeeply discharged battery, as the batterybecomes charged and the voltage rises, theoutput current of the charger tapers down.This taper continues as the battery ischarged, taking a very long time to reach anacceptable recharge.
Fleet Power Battery ChargersFleet Power battery chargers are de-
signed to overcome the limitations of con-ventional chargers by utilizing 3 distinctstages, each designed for optimal recharg-ing of both wet cell and gel cell deep-cyclebatteries.
16
90-0115-0010/97 Fltman.pm65
BATTERY CHARGING
NOTE: Fleet Power battery chargers are onwhenever there is AC power connected tothe charger input, regardless of the condi-tion of the On/Off switch. This feature canbe disabled by setting the dip switch #4(back of the remote) to "On" so that thecharger will also be controlled by the On/Offswitch.
Each time the battery charger is en-gaged, the 3 stages proceed automatically,resulting in an efficient, complete rechargeand safe battery maintenance. Use of theremote control provides the ability to peri-odically apply an 8-hour timed equalizingcharge.
The battery charger stages are:Stage 1 - Bulk Charge During the bulk
charge stage most of the charge current isdelivered to the battery bank. This phase isengaged as soon as the battery charger isactivated. Full rated charger current isdelivered to the battery bank until the bulkcharge voltage limit is reached. This resultsin a relatively rapid recharge.
Generally, a wet cell battery bankshould not be charged up to the gassingpoint at a rate which exceeds 25% of itscapacity. In other words, a 12 volt batterybank of 520 Amp-hours should not becharged at over 130 Amps.
17
90-0115-0010/97 Fltman.pm65
Gel cell batteries can accept a higherrate of charge. Consult the manufacturer forspecifications.
Stage 2 - Acceptance Charge Theacceptance stage immediately follows thebulk charge stage. During this stage thebattery voltage is held constant at the bulkcharge voltage limit and the current gradu-ally ramps down. During this stage thebattery is accepting its final amount ofcharge current and the last of the sulfate onthe plates is removed.
The acceptance stage lasts until thecharge current reaches about 6-7 Amps. Atimer will terminate the acceptance stage ifthis current level is not reached. This timeris set automatically when the dip switchesfor battery type are set. Maximum accep-tance time is 1 hour for wet cells and 3hours for gel cells. Gel cell acceptance timecan be increased because the battery is notgassing. Expect wet cell batteries to gassomewhat during acceptance, this is anecessary part of the charging process.
Stage 3 - Float Charge When theacceptance stage is terminated, eitherbecause the charge current ramped down to6-7 Amps or the timer engaged, batterycharger current will shut off. The unit moni-tors the battery voltage while it drifts downfrom the bulk charge voltage limit. When itreaches the float voltage set point, the floatcharge stage is engaged.
The float charge stage holds the batteryvoltage at a lower level, where it is safe forlong term battery maintenance. During thefloat charge stage, the full output current ofthe battery charger is available to operateany DC appliances that may be on thesystem, while constantly maintaining thefloat charge voltage.
The battery charger remains in the floatcharge stage indefinitely until the charger isdisconnected from incoming AC power.
Stage 4 - Equalizing Charge This isthe only battery charger stage which is notengaged automatically. It must be manuallyinitiated each time it is necessary to equal-ize using a dip switch on the back of theremote control. Applying an equalizingcharge is not possible without the use of aremote.
Periodic equalizing is recommended bymost wet cell deep-cycle battery manufac-turers. There are no firm rules for how oftenan equalizing charge should be applied, butonce a month is a good rule of thumb forbatteries which are regularly cycled, lessoften for systems in only occasional use.
The equalizing charge is a timed, 8-hour cycle. If desired, it can be ended byinterrupting the AC power to the charger atany time during the cycle. Equalizingshould be engaged after the batteries havebeen fully charged by a normal battery
BATTERY CHARGING
18
90-0115-0010/97 Fltman.pm65
charging cycle. The battery voltage willincrease to 16.3 using the cool temperaturewet cell setting. This will cause the batterybank to gas profusely and will accomplishthe following:
1. Removal of residual sulfate. Each timea battery is cycled (discharged and re-charged), a small amount of sulfate is left onthe plates. Over time, this gradual build-upof sulfate will compromise the performanceof the battery. By applying an equalizingcharge, the sulfate is returned back to theelectrolyte, raising the specific gravity andfully exposing the active material of theplates.
2. Bring all cells to the same potential.All lead-acid batteries are made up of indi-vidual 2 Volt cells. As the battery bank iscycled, slight differences in the cells resultin different cell voltages, affecting the over-all charge effectiveness. Equalizing bringsall cells up to the same voltage and theelectrolyte in each cell to the same specificgravity.
3. Mixing up of the electrolyte. Electro-lyte in battery cells tend to separate intolayers of acid and water. The vigorousboiling action of the battery during equaliz-ing serves to physically mix the electrolyte.
BATTERY CHARGING
Equalizing is not required on gel cellbatteries. You will note that if the dipswitches are set in one of the two gel cellpositions, the equalizing charge voltage isthe same as the bulk charge voltage, there-fore, equalizing is equivalent to an 8-houracceptance stage and is not harmful.
To limit the DC current during equaliz-ing to less than 15 Amps, turn on dipswitches 7 and 8 before starting the equal-ize charge. Do not operate AC loads thatare on the output of the inverter/chargerwhen equalizing.
Charging Over-Discharged BatteriesCharging into a battery bank with a
terminal voltage of less than 8 Volts pre-sents a special problem for the unit. If thissituation arises, the unit will attempt tocharge for 1 minute. If the inverter sensesexcessive ripple voltage, it will shut down toprotect itself.
To successfully charge an over-discharged battery, you must remove asmuch DC load as possible. Set dipswitches 7 and 8 to the ON position to limitthe amount of charge current and the result-ing ripple voltage. After the battery voltagehas reached 10 Volts, these switches canbe set to their previous positions.
19
90-0115-0010/97 Fltman.pm65
BATTERY CHARGING
1. Do not equalize gel cell batterieswith the remote programmed for wetcells.2. Always monitor the equalizecharge. Provide proper ventilation forbattery fumes. Do not allow any sparksduring equalizing. If one or more cellsbegin to overflow, terminate the equalizecharge.
3. Check and top off the battery elec-trolyte both before and after theequalizing charge. Do not expose thebattery plates to air. Leave the batterycaps on while equalizing.
4. Remove all loads from the DC sys-tem before equalizing. Some DC loadsmay not tolerate the high charge voltage.
5. Do not leave the equalize dipswitch in the ON position. It must becycled OFF and left in the OFF position.If left ON, the unit will engage the equal-izing cycle every time the battery chargeris engaged.
WARNINGSNote: If a continuous DC load in ex-
cess of the charge rate is placed on thebattery bank, eventually the battery voltagewill drop below 8 Volts and the batterycharger will shut off. This load must besignificantly reduced and the power to thecharger cycled to resume charging.
Blinking of the battery LED on theremote control while charging is a warningthat an over-discharge is imminent and thatthe DC load should be reduced.
NOTE: Equalize only after a regularcharge cycle.
20
90-0115-0010/97 Fltman.pm65
BATTERY CHARGER VOLTAGE SETTINGS
21
dnaepyTyrettaBerutarepmeT
/egatloVkluBemiTxaM
taolFegatloV
ezilauqEegatloV
lleCteWtloV21erutarepmeTmraW
rh1/0.41 1.31 8.51
lleCteWtloV21erutarepmeTlooC
rh1/4.41 5.31 3.61
lleCleGtloV21erutarepmeTmraW
rh3/8.31 3.31 8.31
lleCleGtloV21erutarepmeTlooC
rh3/1.41 6.31 1.41
90-0115-0010/97 Fltman.pm65
INSTALLATION PRECAUTIONS
AC Output
RemoteJack
AC Inputs
ChassisGroundLug
CAUTION To reduce the risk of electricshock and prevent premature failure due tocorrosion, do not mount where exposedto rain or spray .
CAUTION To prevent fire, do not obstructventilation openings. Do not mount in azero clearance compartment, overheatingmay result.
NOTICE The output of this device is notsinusoidal . It has a maximum total har-monic distortion of 47% and a maximumsingle harmonic of 34%.
CAUTION Risk of electrical shock. BothAC & DC voltage sources are terminatedinside this equipment. Each circuit mustbe individually opened before servicing.
CAUTION Risk of electrical shock. Donot remove cover, no user serviceableparts inside. Refer servicing to qualifiedservice personnel.
APPLICATION INFORMATION Providedwith integral electronic protectionagainst AC & DC overloads.
CAUTION This equipment is not igni-tion protected and employs compo-nents that tend to produce arcs orsparks. To reduce the risk of fire orexplosions, do not install in compart-ments containing batteries or flam-mable materials or areas in whichignition-protected equipment is re-quired.
For continued protection against risk ofelectric shock, use only the ground-fault circuit interrupter (GFCI) typereceptacles detailed in this owner'smanual. Other types may fail to operateproperly when connected to this inverter,resulting in a potential shock hazard.
WARNING
22
Fleet Power 2500 shown.
90-0115-0010/97 Fltman.pm65
INSTALLATION
Key Installation Points
The Power Switch must be turned OFFbefore you begin.
1. Observe proper polarity whenconnecting batteries. Reverse DC polaritywill result in damage to the unit and will voidthe warranty. Use care when making theDC connections.
2. Do not back-feed the AC output ofthe inverter with incoming AC power. Aback-feed occurs when AC power fromshore power or generator is connected tothe output of the inverter. This will damagethe inverter and void the warranty. Remem-ber that incoming AC must be fed only tothe AC input and never to the AC output.Always check for AC voltage before con-necting wires to the AC output. Do NOTturn the inverter ON until all AC connectionshave been made. Back-feeding the invertervoids the warranty.
3. Do not connect the AC input to theAC output. In effect, this would be plug-ging the battery charger into the inverter.This could occur if the unit is connected tothe entire leg of a circuit breaker panel, thena circuit breaker on that leg is used to feedthe battery charger. This will cause the unitto oscillate ON and OFF when the unit is ininverter mode.
4. Always use proper wire and con-nectors. The proper battery cable size iscritical because considerable amperageflows in the DC circuit. Fusing the positive
DC cable is required. The AC wire size isdependant on potential current in the circuit.Consult the NEC (National Electric Code)for proper wire gauge.
5. Keep the inverter/charger out ofthe elements and out of direct contactwith water or spray. Remember that theunit is a piece of electronic equipment andtreat it accordingly.
6. Mount the unit as close to thebatteries as possible but not in the pres-ence of flammable fumes or in an enclosedbattery compartment.
7. The connectors for the remotecontrol and the chassis ground bondinglug, as well as for the AC wires, are lo-cated on the bottom of the unit. Be sureto make these connections before boltingthe unit down.
8. You may mount the unit horizon-tally (on a shelf) or vertically (on a wall orbulkhead). If mounted vertically, you mustorient the unit so the switch and the circuitbreakers are facing up and the fan andbattery cables are facing down.
9. Allow several inches of clearancearound the unit and allow for a supply offresh air to the cooling fan. Do not blockany of the vents or louvers. The fan pullsair from outside the unit. It blows air acrossthe internal components, particularly thetransformer and heat sinks, then out theside vents.
23
90-0115-0010/97 Fltman.pm65
INSTALLATION
15. If multiple battery banks are to becharged, a battery selector switch can beinstalled, allowing the banks to be chargedeither individually or simultaneously. Asolenoid can also be used.
10. If installing in a system which in-cludes an existing battery charger or con-verter, make sure these do not operatefrom the inverter output AC power. Thissets up a power loop which, due to ineffi-ciencies, will quickly drain the batteries.
11. Make sure all wiring conforms tolocal and national electrical codes. If indoubt, consult with a qualified electrician.
12. Keep the overall length of eachbattery cable less than 10 feet. If needed,attach short extension cables. Do not useframe ground or a ground bonding systemas a current carrying conductor. Run thenegative cable directly to the battery bank.If the positive and negative cables runparallel to each other, twist the cablestogether. This will minimize the adverseeffects of inductance.
13. To meet electrical codes , a fusemust be installed in the positive batterycable within 18 inches of the battery post.This fuse is intended to protect the batteryand cables against a dead short circuit.The inverter is protected internally and willnot blow a properly sized fuse.
14. DC wiring is generally very simple,the positive and negative cables from theinverter/charger are connected to the houseor auxiliary battery. In the case of multiplebatteries the interconnecting jumper cablesmust be of the same AWG as those sup-plied with the inverter/charger.
GroundingFor safety purposes, the chassis of
the inverter/charger must be connectedto your AC ground system . The chassisground bonding lug is located on the bottomof the unit. This connector can accept twowires, the first is used to connect the unit toAC ground, the second can be used toconnect other AC equipment to ground.
Use bare copper insulated wire, solid orstranded. Strip one end and use a screw-driver to secure it to the chassis groundbonding lug. This wire will connect to theground in your AC electrical system, typi-cally the vehicle chassis. Make sure theconnection is clean and tight.
Do not mount the unit in an enclosedbattery compartment. Take precautionsto keep road dirt and spray off the unit.
WARNING
24
90-0115-0010/97 Fltman.pm65
This procedure will connect the chassisof your unit to AC ground. In addition, theAC input and AC output green wires areconnected to chassis ground. It is importantto connect these wires to the AC ground busin the circuit breaker panel.
Note: The battery cables are not con-nected to ground or the chassis of the unit.
Neutral BondingFor safety purposes, the Fleet Power
inverter/charger unit internally bonds the ACoutput neutral to the AC ground when theunit is OFF or in the inverter mode. Whenincoming AC power is applied and thetransfer switch is engaged, the internalneutral-to- ground bond is automaticallylifted.
This means that when the vehicle isconnected to shore power, the groundingsystem is connected to the shore powerground, where neutral and earth ground arebonded together. This technique insuressafety in all conditions and conforms to therequirements of the NEC.
AC WiringThe AC wires route through the holes in
the bottom of the unit. Use a screwdriver toremove the screws which secure the ACwiring compartment cover plate. Inside, thecompartment is divided into 2 sections, onelabeled AC Input , the other labeled AC
Output . Each side contains 3 pigtails:black, white and green. Six wire nut con-nectors are also provided.
Black Hot or LineWhite NeutralGreen Ground
Conventional metal strain reliefs areprovided. These can be replaced by plasticstrain reliefs for additional corrosion resis-tance or 3/4 inch conduit fittings if the wiringwill be routed through the conduit.
Use proper wire sizes according to theNEC.
AC Input (Fleet Power 1000 and FleetPower 2000): Feed the 3 conductor ACinput wire through the strain relief and intothe AC input compartment. You shouldhave 6 inches of individually insulatedblack, white and green wire. Strip 1/2 inchof insulation off each conductor and connectto the pigtails: black to black, white to whiteand green to green.
AC Input (Fleet Power 2500): Thereare 2 options for configuring the AC input tothe Fleet Power 2500.
Dual Inputs: The internal batterycharger may be fed separately from thetransfer input which feeds the AC loads. Inthis case, connect one 30 Amp feed to thecharger pigtails and another 30 Amp feed tothe transfer switch input.
Connecting the feeds in this way bal-ances the AC loads when 2 legs of incomingAC power are available. These two feedscan be in or out of phase. Transfer will only
INSTALLATION
25
90-0115-0010/97 Fltman.pm65
INSTALLATION
Do not connect incoming AC from anysource to the AC output of the inverter/charger. This is known as back-feedingand will damage the unit and void thewarranty.
connect in the same fashion as the AC inputwires.
If you are not connecting the hardwireoutput wires (Fleet Power 2000 only), makecertain they can not cause a short circuit tothe wiring compartment. Tug firmly on eachconnection to make sure they are secure.Check these connections first if the unit isnot operating properly.
Carefully tuck the wires into the ACwiring compartment. Replace cover plate.
Ground Fault Circuit InterruptersIn order to conform to the NEC, certain
branch circuits must be equipped with aGround Fault Circuit Interrupter (GFCI).Please consult the code or a qualifiedelectrician for details. Any such branchcircuit must be protected by a circuitbreaker consistent with the GFCI rating.Underwriters Laboratories has tested thefollowing GFCI, and its use is recom-mended. Receptacle Type:
Pass & SeymourCatalog Number 1591-RWRated: 15 Amps at 120 Volts AC
Fleet Power 1000 and 2000 inverter/chargers provide an integral GFCI outletwhich is protected by a circuit breaker. ThisGFCI outlet does not protect the hardwireAC output. The hardwire AC output isprotected by a non-GFCI circuit breaker onthe Fleet Power 2000 only. The first outletfrom the hardwire output should be GFCIprotected to comply with applicable codesand standards.
The GFCI Receptacle is designed toprotect from line-to-ground shock hazardswhich could occur from defective power
WARNING
26
occur when power is applied to both inputs.The charger can draw up to 27 Amps onone leg of power and the transfer switch canpass up to 30 Amps from the other leg ofpower.
Single Input: Both the battery chargerand the transfer switch may be fed from thesame AC input. In this case, connect bothpigtails together, black to black, white towhite and green to green.
This allows up to 60 Amps of AC powerto be brought in on a single cable. Up to 30Amps is available to the loads, with thebalance available to power the batterycharger. A single cable should be protectedby a 60 Amp breaker or smaller, and 6gauge wire should be used.
AC Output: On the Fleet Power 1000,AC output is available at the GFCI outletmounted on the unit. On the Fleet Power2000, AC output is available at both theGFCI outlet and at the AC output compart-ment. The AC output for the Fleet Power2500 is available at the AC output compart-ment only. When installing the Fleet Power2000 and 2500, feed the 3 conductor ACoutput wire through the strain relief and
90-0115-0010/97 Fltman.pm65
INSTALLATION
Persons with heart problems or otherconditions which make them susceptible toelectric shock may still be injured byground faults on circuits protected by theGFCI Receptacle. No safety devices yetdesigned will protect against all hazards orcarelessly handled or misused electricalequipment or wiring.
WARNINGthat power is off at the GFCI protectedoutlets. Push the RESET back in andreconnect the appliances one at a time. Adefective appliance which trips the GFCIshould be repaired at once.
If the RESET button will not stay inafter all appliances have been disconnectedfrom the circuit, the GFCI outlet has failed.
If the RESET button does not pop outwhen the TEST button is pressed, protec-tion is lost. Do not use.
Test Reminder: For maximum protec-tion against electrical shock hazard, testyour ground fault circuit interrupter at leastonce a month. Test procedure:
1. Push TEST button. The RESETbutton will pop out. Power is now ON orshore power is ON indicating that the deviceis functioning properly.
2. If RESET does not pop out whentesting, do not use this circuit. Protection islost.
3. To restore power, push the RESETbutton.
Remote Control Wiring
The remote control is supplied with a25 or 50 foot section of telephone cable forconnection to the unit. Simply plug one endof the cable into the remote connector onthe bottom of the unit labeled remote andthe other end into the connector on the backof the remote control panel.
Routing the remote cable away from ACand DC wires will minimize the potential forinterference which may affect the LEDbargraphs.
27
tools or appliances operating from thisdevice. It does not prevent line-to-groundelectric shock, but does limit the time ofexposure to a period considered safe for anormally healthy person. It does not protectpersons against line-to-line, or line-to-neutral faults.
The GFCI Receptacle does not protectagainst short circuits or overloads. This isthe function of the circuit breaker.
Any line-to-ground fault conditionindicated by a tripped GFCI must be cor-rected. Grounded fault conditions aredangerous to personnel and property.Should you identify conditions not describedin these instructions, contact a qualifiedelectrician.
In the event of power failure which hasnot affected the breaker, unplug all cord-connected appliances and tools from theGFCI receptacle, and restore power bypressing in the RESET button on the GFCIreceptacle. To test, press the TEST button.The RESET button will pop out indicating
90-0115-0010/97 Fltman.pm65
INSTALLATION
Fleet Power inverter/chargers are notprotected against DC reverse polarity.Be very careful to connect the negativeand positive cable correctly or damagewill result and the warranty will be void.
WARNING
Recommended Fuse: Littlefuse Class T JLLNThis fuse with fuse holder is available from yourdealer or Heart Interface.
For Fleet Power 1000200 Amp Fuse & Holder PN# 84-4158-00200 Amp Fuse Only PN# 84-4157-00
For Fleet Power 2000, 2500300 Amp Fuse & Holder PN#84-4154-00300 Amp Fuse Only PN#84-4151-00
28
+ (red)
The negative cable should be con-nected directly to the negative post of thebattery bank or the ground side of a currentshunt. Do not use the vehicle frame as thenegative conductor. Tighten securely.
The positive battery cable must befused and connected to the positive post ofthe battery bank, or through a selectorswitch to one or more battery banks.
A spark may be generated when thefinal battery connection is made. This isnormal and do not be alarmed, however, donot make the final connection in the pres-ence of flammable fumes.
Battery Cable FusingA fuse is required by the NEC to pro-
tect the battery and cables. The fuse mustbe installed in the positive battery cable,within 18 inches of the battery.
The remote control cable can be ex-tended up to 50 feet if required. Use stan-dard 4 or 6 conductor telephone cable. Usea single length cable with no connectors orin-line splices. If phone cable is left over,coil it up and store it in an area away fromAC equipment to prevent electrical interfer-ence.
Once the above steps have been com-pleted the unit can be bolted down.
DC WiringTwo battery cables are provided with
the unit. Both are black, the positive cablehas a piece of red heat shrink insulation onthe end. High current will pass through theDC wiring. All wires must be properly sizedand all connections clean and tight.
It is recommended that the batterycables not be lengthened, however, it ispossible to extend the cables if necessary.Extension cables must be 00 AWG or thesame type of wire supplied with the unit, andthe total length for each battery cable mustnot exceed 10 feet.
Make sure the connections to the ex-tension cables are tight and properly insu-lated. Do not attempt to open the case andreplace battery cables.
90-0115-0010/97 Fltman.pm65
INSTALLATION OPTION 1
29
15, 20 or 30 Amp Shore PowerInverter Runs Entire Panel
In this system, the shore power isthe only external AC power sourceavailable. The entire circuit breakerpanel is connected to the output ofthe inverter/charger. Take thesethings into consideration are:
1. When you unplug from shorepower, be sure to turn OFF any appli-ances or tools that you do not want on theinverter. This will prevent overloading theinverter or a rapid discharge of the batterybank.
2. Power Sharing should be set forthe same value as the input shore powerbreaker.
3. If a converter or battery chargerwas originally wired into the system, itshould be disconnected. Do not allow aconverter/charger to operate on the in-verter power. This type of power loop willonly discharge the batteries.
4. Fleet Power 1000 has 15 Amptransfer only.
5. Use the hardwire output for 30 Amptransfer on the Fleet Power 2000, and2500.
90-0115-0010/97 Fltman.pm65
INSTALLATION OPTION 2
30 Amp Shore Power and Generator.Inverter Runs Entire Panel.
This system has 2 sources of ACpower, shore power and generator. There isa transfer switch between these two ACsources. The output of this transfer switchis switched to the input of the inverter/charger where it is passed through to thecircuit breaker panel.
The same considerations for Installa-tion 1 apply to this installation.
30
90-0115-0010/97 Fltman.pm65
INSTALLATION OPTION 3
50 Amp Shore Power/GeneratorInverter Runs 30 Amp Sub-Panel.
In this system the main circuitbreaker panel contains many loadsthat will not operate from theinverter such as air conditioning,stove, water or space heater. TheAC receptacle circuits are removedfrom the main circuit breaker paneland a 30 Amp sub-panel is installed.A 30 Amp branch circuit breaker on themain panel feeds the AC input of theinverter/charger, and feeds the sub-panelthrough the inverter's internal transferswitch.
31
90-0115-0010/97 Fltman.pm65
32
INSTALLATION OPTION 4 (Dual AC Input)
Fleet Power 2500 Only
• 50 Amp 120 Volt Shore Power Service
• Generator
The transfer switch shown,switches, either manually or automati-cally, between generator and shorepower. This switch is unrelated to thetransfer switch inside the Fleet Power 2500.This AC panel has a single 120 volt leg.
The transfer AC input and the Charger ACinput are fed from separate 30 Amp circuitbreakers. Make sure the wiring between the ACpanel and the inverter will safely carry two 30Amp circuits. Typically, a minimum of 10 AWGwires would be used. 6 each (2 hot, 2 neutraland 2 ground).
Please note that the inverter AC outputbreakers are isolated from the main panel.Keeping the inverter loads isolated isimportant. Do not back feed the unit by supply-ing AC from shore or generator to the inverterAC output. Three inverter breakers are shownin the particular diagram. You are not limited tothree breakers.
90-0115-0010/97 Fltman.pm65
DC WIRING OPTIONS
DC Wiring #1 - Two Battery* SystemUsing Manual Battery Switch
This system is simple and effective,providing the user with the ability to choosebetween either battery for inverter use orcharging.
When charging, the battery switch istypically left in the "All" or "Both" position sothat both batteries are charged. Whenusing the inverter, the inverter batteryshould be selected with the battery switch.
The inverter/charger's negative batterycable should be connected directly to thebattery that will normally supply the inverter.A fuse should be installed in the positivecable within 18 inches of the battery. If thecables to the switch exceed 18 inches, eachcable will require a fuse.
DC Wiring #2 - Two Battery* SystemUsing an Isolator for Charging bothBatteries
This allows charging of both batteriesfrom an alternator, but the inverter can onlydraw power from the auxiliary battery. Thisprevents accidental discharge of the enginebattery by the inverter. A paralleling sole-noid can be used in place of the isolator.
33* Each battery shown can representa battery bank.
For Installations using BatterySwitches NOTE: No other DC loadsshould be connected to the common onthe battery switch. This will prevent theiroperation directly from charger powerwhen the battery switch is OFF.
WARNING
90-0115-0010/97 Fltman.pm65
DC WIRING OPTIONS
DC Wiring #3 - Two Auxiliary Batteries*with Battery Switch and One EngineBattery
This system allows the inverter to useeither auxiliary battery. The engine batterycan always be charged by the alternator, butcannot be discharged by the inverter. Theuser can select between the two auxiliarybatteries with the batteryswitch for charging or forinverter operation.
DC Wiring #4 - Three Batteries*Connected with Battery Switches
This allows any combination ofthree battery banks to be chargedby or selected to run the inverter.
If both switches are on "all",then all batteries are in parallel.Batteries can be independentlyadded to or removed from thesystem by selecting theappropriate switch position.
34
* Each battery shown canrepresent a battery bank.
90-0115-0010/97 Fltman.pm65
TROUBLESHOOTING
LEDNumber Indication
LED 1 Illuminates if the unit shuts down for any reason.
LED 2 Over-temperature. Allow to cool.
LED 3The unit detected a failure. Call Heart InterfaceTechnical Support.
LED 4Inverter overload caused by too large a load orshort circuit. Reset by cycling power switch orplugging in incoming AC power.
LED 5Battery overload caused by excessively dischargedbatteries. Refer to page 40.
LED 6Incoming AC backfeed. Potentially damaging to theunit. Disconnect incoming AC power and correctthe situation.
LED 7Triac thermal run away. Turn OFF and allow to cooldown.
LED 8High battery voltage shutdown during charge mode.Check all charging sources for proper voltage.Reset by cycling the power switch.
LED 9-10 Not used for troubleshooting.
35
90-0115-0010/97 Fltman.pm65
TROUBLESHOOTING
1. Digital clocks either employ an internal timebase or derive their time base from the incomingAC waveform. The frequency is usually wellregulated at 60 Hz. The clock either counts thenumber of peaks in the waveform or the numberof times the waveform crosses zero volts. Thecircuitry to count the zero crossing events is morepopular. The longer zero cross time of theinverter's modified sinewave may cause doubleclocking, resulting in a faster clock.
SlowDigitalClock
36
Problem Things to Check
No InverterOutput
1. Battery voltage under load.2. Battery connections and DC fuse.3. Circuit breaker on front panel.4. Thermal condition, high powered loads orinadequate ventilation may cause overheating.5. Overloads or short circuit, check for excessiveloads or bad wiring connections.6. Reset button oin GFCI outlet.
Low InverterOutput Voltage
Confirm that your volt meter is a true RMS meter.Standard volt meters will not accurately read thewaveform of the inverter and may read anywherefrom 90 to 120 volts. If a true RMS meter is notavailable, check the brightness of an incandescentlight bulb - if it appears normal, the output voltage isproperly regulated.
Little or NoOutput from
BatteryCharger
1. Wiring connections - check both the AC and DCconnections.2. AC input voltage - low voltage input will result inlow DC output current. Expect reduced chargeroutput from generators under 3,500 watts.3. AC reverse polarity - check for voltage betweenthe incoming white and green wires. If 120 volts ismeasured, this is reverse polarity.
MicrowaveOven Cooking
Slow
1. Microwave ovens will normally cook slow oninverters due to a slightly low peak AC voltage. 2.Cooking speed will be determined by batteryvoltage. Low voltage results in increased cookingtime. Support the battery bank with an alternator orother charging source for quicker cooking.
90-0115-0010/97 Fltman.pm65
GLOSSARY
Alternating Current (AC) An electric currentthat reverses direction at regular intervals.Sources of alternating current are shore power,generator power, inverter power or householdcurrent.
Ampere (Amp, A) The unit of measure ofelectron flow rate of current through a circuit.
Ampere-hour (Amp-Hr., AH) A unit of measurefor a battery's electrical storage capacity, ob-tained by multiplying the current in amperes bythe time in hours of discharge (Example: abattery which delivers 5 amperes for 20 hoursdelivers 5 amperes times 20 hours, or 100Amp-Hr. of capacity.)
AH Capacity The ability of a fully chargedbattery to deliver a specified quantity of electric-ity (Amp-Hr., AH) at a given rate (Amp, A) overa definite period of time (Hr.). The capacity of abattery depends upon a number of factors suchas: active material, weight, density, adhesion togrid, number, design and dimensions of plates,plate spacing design of separators, specificgravity and quantity of available electrolyte, gridalloys, final limiting voltage, discharge rate,temperature, internal and external resistance,age and life of the battery (bank).
AWG (American Wire Gauge) A standardused to measure the size of wire.
Circuit An electric circuit is the path of anelectric current. A closed circuit has a completepath. An open circuit has a broken or discon-nected path.
Circuit (Series) A circuit which has only onepath for the current to flow. Batteries arrangedin series are connected with the negative of the
first to the positive of the second, negative ofthe second to the positive of the third, etc. Iftwo 6 volt batteries of 50 ampere-hours capac-ity are connected in series, the circuit voltage isequal to the sum of the two battery voltages, or12 volts, and the ampere-hour capacity of thecombination is 50 ampere-hours.
Circuit (Parallel) A circuit which provides morethan one path for current flow. A parallel ar-rangement of batteries (of like voltage andcapacity) would have all positive terminalsconnected to a conductor and all negativeterminals connected to another conductor. Iftwo 12 volt batteries of 50 ampere-hour capac-ity each are connected in parallel, the circuitvoltage is 12 volts, and the ampere-hour capac-ity of the combination is 100 ampere-hours.
Current The rate of flow of electricity or themovement rate of electrons along a conductor.It is comparable to the flow of a stream of water.The unit of measure for current is ampere.
Cycle In a battery, one discharge plus onerecharge equals one cycle.
Dip Switch A series of small switches used forspecial programming of the Fleet Power in-verter/charger. These switches are located onthe back of the Fleet Power remote panel.
Direct Current (DC) Current that flows continu-ously in one direction such as that from batter-ies, photovoltaics, alternators, chargers and DCgenerators.
37
90-0115-0010/97 Fltman.pm65
Power Sharing The ability of the charger toreduce its output when the AC power beingconsumed by the charger and external ACloads connected to the output of the inverterare in excess of the input breaker rating.
Volt The unit of measure for electric potential.
Watt The unit for measuring electrical power,i.e., the rate of doing work, in moving electronsby or against an electric potential.
Watt-Hour (Watt-HR, WH) The unit for measur-ing electrical energy which equals Watts xHours.
Wet Cell Battery A type of battery that usesliquid as an electrolyte. The wet cell batteryrequires periodic maintenance; cleaning theconnections, checking the electrolyte level andperforming an equalization cycle.
Equalize Charge A controlled overcharge ofthe batteries which brings all cells up to thesame voltage potential, extends the battery life,restores capacity and mixes the electrolyte.
Gel Cell Battery A type of battery that uses agelled electrolyte solution. These batteries aresealed and are virtually maintenance-free. Notall sealed batteries are the gel cell type.
GFCI (Ground Fault Circuit Interrupter) Aprotective device that rapidly de-energizes acircuit when current to ground exceeds a prede-termined value.
Ground The reference potential of a circuit. Inautomotive use, the result of attaching onebattery cable to the body or frame which is usedas a path for completing a circuit in lieu of adirect wire from a component. This method isnot suitable for connecting the negative cableof the inverter to ground. Instead, route thecable directly to the negative terminal of thebattery.
LED (Light Emitting Diode) Indicator light.
Negative Designating or pertaining to electricalpotential. The negative terminal is the pointfrom which electrons flow during discharge.
Ohm A unit for measuring electrical resistance.
Ohm's Law Expresses the relationship be-tween Voltage (V), Current (I) in an electricalcircuit with resistance (R). It can be expressedas follows: V=IR. If any two of the threevalues are known, the third value can be calcu-lated by using the above formula.
Positive Designating or pertaining to electricalpotential; opposite of negative. The positivebattery terminal is the point where electronsreturn to the battery during discharge.
GLOSSARY
38
90-0115-0010/97 Fltman.pm65
SPECIFICATIONS
39
MODEL
Nominal Battery Voltage
Battery Voltage Range
Low Battery Cutout
AC Input Voltage Range
Frequency Regulation
Inverter Output Power (Continuous)
Inverter Voltage Regulation
Wave Shape
Surge Power (15 seconds)
Output AC Amps at rated load
Input DC Amps
Power Factors Allowed
Full Load Efficiency
Peak Efficiency
Protection
Transfer Switch
GFCI
Charging Rate
Bulk Charge Voltage
Float Charge Voltage
Equalizing Charge Voltage
Battery Cables
Hardwire
Status Panel
Weight
Dimensions
FP 2500-12
12 VDC
10.0 - 15.5 VDC
10 VDC
90-130 VAC
.05% @ 60 Hz
2500 VA
120V 5% True RMS
Modified Sine Wave
5200 VA
20.83
250
All
86%
94%
Circuit Breaker,Electronic, Thermal,High Battery, LowBattery
Yes
No
130 Amps
14.4 VDC*
13.5 VDC*
16.3 VDC*
Yes 3'
Yes
Optional Remote
56 lbs.
12" x 11.5" x 8.75"
-+
FP 2000-12
12 VDC
10.0 - 15.5 VDC
10 VDC
90-130 VAC
.05% @ 60 Hz
2000 VA
120V 5% True RMS
Modified Sine Wave
4500 VA
16.67
200
All
84%
93%
Circuit Breaker,Electronic, Thermal,High Battery, LowBattery, GFCI
Yes
Yes
100 Amps
14.4 VDC*
13.5 VDC*
16.3 VDC*
Yes 3'
Yes
Optional Remote
52 lbs.
12" x 11.5" x 8.75"
FP1000-12 and FP2000-12 models are certified by UL to comply with FED spec-KKK-A1822, SAE spec-SAE-JRR1, for emergency vehicleapplication. All models are UL and C-UL Listed for Canadian use. *Indicates adjustable setting with the optional remote control.
-+
FP 1000-12
12 VDC
10.0 - 15.5 VDC
10 VDC
90-130 VAC
.05% @ 60 Hz
1000 VA
120V 5% True RMS
Modified Sine Wave
3000 VA
8.33
100
All
85%
92%
Circuit Breaker,Electronic, Thermal,High Battery, LowBattery, GFCI
Yes
Yes
50 Amps
14.4 VDC*
13.5 VDC*
16.3 VDC*
Yes 3'
No
Optional Remote
31 lbs.
12" x 9.75" x 7"
-+
90-0115-0010/97 Fltman.pm65
WARRANTY
Your Heart Interface Fleet PowerInverter/Charger is under limited warrantyfor a period of 12 months from date ofpurchase.
Terms of the warranty are detailedon the warranty registration card. Pleasecomplete this card and return it to HeartInterface to register your warranty.
If the unit requires service, contactHeart Interface by telephone. The servicetechnician will ask for the serial number ofyour unit. Please have this informationready.
Phone numbers: (253) 872-7225 (800) 446-6180
A return authorization number will berequired on all returns. This number isissued by the service technician and shouldbe written on the shipping box.