View
6
Download
0
Category
Preview:
Citation preview
R410A refrigerant
Total versatility
Water fi lter installed standard
Hydronic unit incorporated
<
<
<
<
Air-cooled water chiller with helical fans
NECS_0152_0612_200907_GB
r HFC
R-410A
(The photo of the unit is indicative and may change depending on the model)
Climaveneta Technical Bulletin
0152 - 0612
33,8 - 341 kW
NECS
II NECS_0152_0612_200907_GB
NECS
HFC R410a
SUMMARYNECS
0152 - 0612
Liability disclaimer
This bulletin is not exhaustive about: installation, use, safety
precautions, handling and transport. Refer to “General Manual
for Installation” for further informations.
This bulletin refers to standard executions, in particular
for dimension, weight, electric, hydraulic, aeraulic and refriger-
ant connections (whereas applicable). Contact Climaveneta
Commercial Offi ce for further drawings and schemes.
Climaveneta declines any liability derived from the bulletin’s
use.
This bulletin is of exclusive property of Climaveneta, and all
forms of copy are prohibited.
The data contained herein are subject to variation without no-
tice.
Company quality system
certifi ed to UNI EN ISO 9001
This company parti-
cipates in the Eurovent
Certifi cation Programme.
The products are listed in the
Directory of certifi ed products.
Eurovent certifi cation ap-
plied to units with cooling
capacity up to 1500 kW for
air cooled water chillers and
water cooled liquid chillers.
1. Product presentation
1.1 Energy indices ESEER and IPLV
1.2 Using the energy indices
1.3 Control unit with LED display
1.4 Integrated Hydronic Unit (optional)
2. Unit description
2.1 NECS. State of the art system
2.2 Standard unit composition
2.3 Electronic controller
2.4 Accessories
3. Technical data
3.1 General technical data
3.2 Cooling capacity performance
3.3 Desuperheater capacity perfor.
4. Operating range
5. Hydraulic data
5.1 Water fl ow and pressure drop
6. Hydronic groups
7. Electrical data
8. Full load sound level
9. Dimensional drawings
10. Free spaces - lifting mode - symbols
11. Legend of pipe connections
pg. n° III
pg. n° III
pg. n° IV
pg. n° V
pg. n° VI
pg. n° 1
pg. n° 1
pg. n° 1
pg. n° 1
pg. n° 2
pg. n° 3
pg. n° 3
pg. n° 11
pg. n° 21
pg. n° 29
pg. n° 30
pg. n° 30
pg. n° 31
pg. n° 36
pg. n° 37
pg. n° A1
pg. n° A4
pg. n° A5
Company quality system
certifi ed to UNI EN ISO 9001
III NECS_0152_0612_200907_GB
NECS
HFC R410a
1. PRODUCT PRESENTATION
NECS, the CLIMAVENETA R410A range
Scroll compressors, featuring high effi ciency, low vibrations
and low noise emissions.
Range fl exibility. A good 11 size and up to 4 version are avail-
able in the 38 - 159 kW range.
Part load effi ciency with EER > 4,3
New controller with QuickMind
Idrorelax, in order to realize your ideas.
Climaveneta presents its new NECS (New Evolution Cli-
maveneta System) range of chillers (heat pumps) fi tted with
R410A rotary scroll compressors. Consistently with corporate
culture, the NECS series exploits cutting-edge technology to
achieve extremely high levels of quality, focusing on maximum
energy effi ciency and minimum noise emissions.
Why R410A?Though R410A is a blend, it behaves just like a pure gas and features a negligible temperature glide. Thanks to its outstand-ing heat conductivity, R410A contributes towards achieving el-evated system effi ciency. R410A is also an ecological gas, both because its elevated effi ciency reduces electricity consumption and, consequently, CO
2, emissions and because it does not
damage the ozone layer (ODP = 0). The scroll compressor has been expressly redesigned for use with the new gas and is now even more compact and silent than before.
Low-Noise VersionsTwo noise reduction versions are available for all sizes: low noise and super low noise. Low noise levels are achieved by reducing fan speed while the circuitry has been optimised and
the coils generously sized to ensure the unit works correctly.
The energy effi ciency (EER)The energy effi ciency (EER) of these Climaveneta units is fur-ther enhanced thanks the fact that the design of the heat ex-change surfaces, coils and plate exchangers was focused on minimising running costs.Well as achieving an EER close to 2.9, this design focus achieves very high levels reliability and lengthens the working life of the compressor.
1.1 Energy indices ESEER and IPLV
Increasingly closer attention is being paid towards the power
consumption of air-conditioning equipment, both in Europe and
elsewhere.
For many years in the United States, reference has not just
been made to effi ciency at rated conditions. A valuation index
is used which considers marginal operation of the unit at rated
conditions as well as the increased usage when the separation
stages of the cooling compressors are used.
The valuation index adopted in the United States is called IPLV
(Integrated Part Load Value) and is defi ned in the regulations
issued by ARI (American Refrigeration Institute).
ARI Standard
IPLVARI =(1*EER100%
+ 42*EER 75%
+ 45*EER50%
+ 12*EER25%
) /100
where EER100%
, EER75%
, EER50%
, EER25%
are the effi ciencies of
the chiller in the various load conditions (100% - 75% - 50% and
25% respectively), calculated in the external air temperature
conditions shown below.
The temperature of the water leaving the evaporator is consid-
ered constant at 6.7°C in all load conditions, with a delta of 5°C
in the full load condition.
The multipliers 1, 42, 45 e 12 are the cooling performance coef-
fi cients in various load conditions statistically calculated by ARI
an the basis of surveys conducted, for various types of build-
ings and operating conditions, in 29 American cities.
Evaporator temp. leaving 6,7°C costante
DeltaT full load 5°C
Load 100% 75% 50% 25%
External air temp. 35°C 26,7°C 18,3°C 12,8°C
In Europe there is a proposal for EECCAC (Energy Effi ciency
and Certifi cation of Central Air Conditioner)
Proposal EECCAC
ESEER = (3*EER100%
+33*EER75%
+ 41*EER50%
+ 23*EER25%
)/100
Evaporator temp. leaving 6,7°C
DeltaT full load 5°C
Load 100% 75% 50% 25%
External air temp. 35°C 30°C 25°C 20°C
IV NECS_0152_0612_200907_GB
NECS
HFC R410a
After establishing which index to use and estimating the total
power required by the system in the summer mode (in kWh),
we can calculate seasonal electricity consumption (in kWh) us-
ing the following formula:
Power absorbed = Power requested / Index of effi ciency
The real power calculation can be obtained more correctly in
a “dynamic” form, that is, considering the load performance
curve at different external temperatures, the location and the
reference number of operating hours.
These fi gures will allow plant consultants and designers to
make their evaluations depending on the type of building, the
place of installation and the type of heat load, etc...
They can also determine the energy index using the method
that best refl ects plant requirements and can make compari-
sons between similar or equivalent systems using the same
reference unit.
NECS IPLV ESEER
0152 B 4,53 4,05
0182 B 4,81 4,29
0202 B 4,77 4,22
0252 B 4,66 4,15
0302 B 4,59 4,15
0352 B 4,68 4,27
0412 B 4,69 4,17
0452 B 4,73 4,30
0512 B 4,71 4,25
0552 B 4,89 4,40
0612 B 4,67 4,20
0152 HT 4,69 4,28
0182 HT 4,65 4,18
0202 HT 4,84 4,41
0252 HT 4,44 4,09
0302 HT 4,61 3,86
0352 HT 4,46 4,18
0412 HT 4,69 4,28
0452 HT 4,70 4,31
0512 HT 4,84 4,39
NECS IPLV ESEER
0512 LN 4,65 4,03
0182 LN 4,80 4,20
0202 LN 4,80 4,25
0252 LN 4,73 4,22
0302 LN 4,57 4,11
0352 LN 4,36 3,99
0412 LN 4,50 4,02
0452 LN 4,58 4,15
0512 LN 4,56 4,06
0552 LN 4,69 4,19
0612 LN 4,44 3,96
0152 SL 4,40 3,77
0182 SL 4,51 3,93
0202 SL 4,58 4,01
0252 SL 4,38 3,89
0302 SL 4,38 3,86
0352 SL 4,21 3,87
0412 SL 4,36 3,91
0452 SL 4,34 3,91
0512 SL 4,42 3,90
Energy = percentage of total power produced in the various conditions
1.2 Using the energy indices
18 20 22 24 26 28 32 30 34 36 12 14 16 18 20 22 24 26 28 30 32 34 36
0
25
50
75
100
125
ESEER IPLV
External Air Temperature (°C)
Load-W
eig
hin
g c
oeff
icie
nts
(%
)
Load Air Temp. Weighing coefficients
100%
50%
75%
25%
35°C
25°C
30°C
20°C
3%
41%
33%
23%
35°C
18,3°C
26,7°C
12,8°C
1%
45%
42%
12%
Load
Weighing coefficients
Load
Weighing coefficients
Air Temp. Weighing coefficients
External Air Temperature (°C)
V NECS_0152_0612_200907_GB
NECS
HFC R410a
The new “W3000 Base” control unit is installed on all units.
The “W3000 Compact” control unit, featuring a “user friendly”
LCD interface, is available on all units as an accessory item.
This interface is also available in a version with a remote con-
trol
feature.
Main functions: QuickMind, local and
remote FWS supervision, dual setpoint
management, etc., confi rm Climaveneta’s
commitment to continually developing its
electronics technology. The heat pumps,
moreover, are fi tted with the original
Climaveneta defrosting control system
called “Autotuning Defrost” which con-
siderably reduces defrosting times, thus
improving the energy performance of the
unit. Interfaces with BMS systems:
METASYS®, MODBUS®, LONWORKS®,
SIEMENS®, TREND®.
Black Box logs data relative to 200 alarm events which can be
printed with of personal computer.
1.3 Control unit with LED display
QuickMind is a special control unit which monitors the main
operating parameters, predicts system behaviour and antici-
pates unit settings in order to constantly optimise perform-
ance; it allows both return and delivery water temperatures
to be chosen as adjustment parameters.
It can reduce outlet temperature fl uctua-
tions even with a small amount of water
in the system. When, for dualcompres-
sor chillers featuring a maximum of 12
start-ups per hour and using a traditional
adjustment system, the minimum recom-
mended water content is 5.5 l/kW, Quick-
Mind ensures the same chiller operates
correctly even with a water content of just
2.5 l/kW and considerably reduces out-
let temperature fl uctuations. The above
graph shows that outlet temperature
fl uctuations with QuickMind are limited
to 4.3°C as opposed to 7.54°C if the tra-
ditional adjustment system were used,
without even ensuring an acceptable
minimum compressor start time.
2
3
5
4
6
5.9
4.56
7.54
11.34
3 3
3.9
3.3 3.2 3.1
7
8
10
9
Ou
tpu
t te
mp
era
ture
(°C
)
Variation output temperature
11
12
0.5 1.5 2.5 3.5 4.5 5.5 6.5 7.5 8.5 9.5
4.3
3.5
3
11.510.5
3.52 3.52 3.52 3.52 3.523,68 3.52
Not acceptable minimum starting time compressors
Step-wise regulation
Quickmind
VI NECS_0152_0612_200907_GB
NECS
HFC R410a
1.4 Integrated Hydronic Unit (Optional).
Compact PLUG and PLAY units.
NECS has been designed to reduce installation work to a
minimum.
The integrated hydronic unit incorporates all the hydraulic com-
ponents, thus optimising installation space, time and costs.
The integrated hydronic unit can be composed give:
- Storage tank
- Horizontal one-piece centrifuge pump
- Pump inlet pressure gauge
- Flow switch
- Flow control valve
- Discharge valve
- Exchanger input water temperature probe
- Exchanger outlet water temperature probe
- Air vent
- 3 bar safety valve.
- One 8 or 12-litre expansion tanks, pre-pressurised to 1.5 bar
- Check valve (only if P2 is fi tted)
- Pre-mounted Y-shaped water fi lter with stainless steel mesch
Available confi gurations
Hydronic group 1 pump
Hydronic group 2 pumps
Hydronic group 1 pump with water tank
Hydronic group 2 pumps with water tank
For greater information, to see the section “Hydronic Groups”.
IDRORELAX
The NECS range of chillers with heat pump is available in
the IR confi guration; this allows units to be combined with
IDRORELAX, a centralised hydronic system for managing cool-
ing and heating requirements and producing hot running water
for residential, hotel and offi ce applications.
Further information on the IDRORELAX system can be ob-
tained by consulting the relative documentation.
1 NECS_0152_0612_200907_GB
NECS
HFC R410a
2.1 NECS. State of the art system
NECS is a new series of heat pumps and water chillers which
are ideal for low-to-medium power air-conditioning systems and
particularly suitable for installations with a limited water con-
tent.
NECS is a step beyond other systems thanks to its exclu-
sive QuickMind control system, specifi cally developed by Cli-
maveneta.
Thanks to the innovative QuickMind control, the NECS system
has been designed to work on plants with a low water content
where, unlike traditional controls, it minimises the variations in
inlet water temperature even in extremely variable load condi-
tions. It is a highly professional alternative to the installation of
storage tanks.
NECS assures a precise water temperature control even at just
2.5 litres/kW.
Technical start-up and operating times have been reduced.
During the start-up phase, just the temperature set point needs
setting.
The possibility integration of the hydronic-pump-group inside
the unit simplifi es the water and electrical power circuits of the
system.
QuickMind continuously adapts its system settings to the vari-
ous requirements of the plant.
Air-cooled water chillers
Air-cooled water chiller with axial fans for outdoor installation.
The unit is supplied with anti-freeze oil and refrigerant and has
been factory tested. Onsite installation therefore just involves
making connections to the mains power and water supplies.
Unit charged with R410A ecological refrigerant.
2.2 Standard unit composition
Supporting frame
Frame comprising a base in polyester-painted hot-galvanised
sheet steel and supporting panels in Peraluman. The self-sup-
porting structure containing the main components is designed
to ensure maximum ease of access during servicing and main-
tenance operations.
Compressors
Hermetic scroll compressors. All the compressors are fi tted with
an oil sump heater, electronic overheating protection with cen-
tralised manual reset and a two-pole electric motor.
Water-refrigerant heat exchanger
AISI 316 steel braze-welded plate exchanger. The heat ex-
changers are insulated with a closed-cell condensation proof
lining in neoprene. A thermostatically controlled electric heater
prevents ice from forming inside the evaporator when the unit is
not working. When the unit is working, it is protected by a differ-
ential pressure switch mounted on the water side. The unit can
work with antifreeze mixtures at exchanger outlet temperatures
as low as -8°C.
Water side fi lter
“Y” type fi lter designed and built to retain impurities in the hy-
draulic circuit. It features a stainless steel mesh cartridge with
0.9mm holes which can be replaced easily without removing
the valve from the piping.
Refrigerant-air heat exchanger
Finned coil exchanger made from copper tubes and aluminium
fi ns. The aluminium fi ns are correctly spaced to guarantee opti-
mum heat exchange effi ciency.
Fans
Axial electric fans, protected to IP 44, with external rotor and
plastic-coated aluminium blades. Housed in aerodynamic
hoods complete with safety grille.
6 - pole electric motor with built-in thermal protection. The fan
chamber is divided into two sections. This improves effi ciency
with partial loads as the fans of the idle circuit can be stopped.
Refrigerant circuit
Main components of the refrigerant circuit:
- dryer fi lter,
- refrigerant line sight glass with humidity indicator,
- externally equalised thermostatic valve,
- high pressure safety valve,
- high and low pressure switches,
Electric power and control panel
Electric power and control panel, built to EN 60204-1/EC 204-1
standards, complete with:
- control circuit transformer,
- general door lock isolator,
- automatic circuit breakers for compressors and fans,
- fuses and contactors for compressors and fans,
- terminals for cumulative alarm block (BCA),
- remote ON/OFF terminals,
- spring-type control circuit terminal board,
- electric panel with double door and seals for outdoor installa-
tion,
- electronic controller,
- control circuit numbered wires,
- pump control consent relay,
- fan speed continuous regulation
2.3 Electronic controller
W3000 is a special control which monitors the main operating
parameters of the system, predicts the behaviour of the plant
and anticipates the units settings in order to constantly optimise
its performance.
- optimises plant operation
- minimises discharge line temperature oscillations compared
with the set point
- allows either return or delivery water temperatures to be set as
adjustment parameters.
- optimises compressor operation in the event of reduced
loads
- stores 200 alarm events; these can be downloaded to any
personal computer.
- detects and reports a large series of events such as: insuf-
fi cient water content in the plant; low/high water fl ow in the
plant; low/high inlet water temperature; pump and compressor
maintenance times; refrigerant circuit integrity alarm.
W3000 is also suitable for: interface connection with BMS sys-
tems; interface connection with the Climaveneta Supervision
Software; remote control of the unit by modem (fi xed/GSM);
control from a remote keyboard.
Availabilities of kit a Remote Keyboard for unit already installed.
It only comprises n° 2 keyboard for unit assembled without pre-
disposition Remote Keyboard.
2. UNIT DESCRIPTION
2 NECS_0152_0612_200907_GB
NECS
HFC R410a
Basic model
Unit without heat recovery.
Model with partial heat recovery (D)
Air cooled chiller with partial heat recovery. Compared with the
basic confi guration, this version features an additional refriger-
ant/water heat exchanger on the gas delivery line. This heat
exchanger, fi tted in series before the traditional cooling circuit
condenser, is large enough to recover heat for the production of
medium-to-high temperature water for domestic hot water and
the like. The heating capacity of the heat recovery circuit is ap-
proximately equal to the power input of the compressor. Each
exchanger is fi tted standard with an antifreeze heater.
AVAILABLE VERSIONS
B (base)
Standard unit.
HT (High Temperature)
Version suitable for operation with high condenser input air
temperatures.
This version features an oversized condensing section in order
to ensure that heat is correctly exchanged even in particularly
tough environmental conditions. As a result, when working at
normal air temperatures, an increase in cooling capacity and
a decrease in power input is obtained, thereby improving the
cooling effi ciency ratio (E.E.R.).
LN (Low Noise)
Low noise version. This confi guration features special sound-
proofi ng for the compressor chamber and reduced fan speed.
Fan speed is automatically increased if environmental condi-
tions are particularly tough.
SL (Super Low Noise)
Super low noise version. This confi guration features special
soundproofi ng for the compressor chamber, reduced fan speed,
an oversized condensing section. Fan speed is automatically
increased if environmental conditions are particularly tough.
2.4 Accessories
- Increased noise insulation (std on SL units)
- Noise insulation (for B/HT units)
- Rubber isolators
- Compressor suction valve
- Compressor discharge valve
- Cu/Cu condensing coils
- Condensing coils with epoxy-coated fi ns
- Condensing coils with Fin Guard Silver treatment
- Coil protection with wire net.
- Evaporator water fl ow switch (supplied separately)
- Free voltage contacts for compr. operation signalling
- Remote control phase sequence
- HP and LP gauges
- W3000 Compact Keyboard
- Remote keyboard (only with keyboard W3000 Compact)
- Water pump kit with or without storage tank
- Storage tank auxsiliary GA
- Water tank anti-freeze heater (if fi tted)
5 6,5 6,5 6,5 8,3 8,8 9,4
11,5 13,6 13,1 12,6
5 6,5 6,5 6,5 8,3 8,8 9,4
11,5 13,6
5 6,5 6,5 6,5 8,3 8,8 9,4
11,5 13,6 13,1 12,6
5 6,5 6,5 6,5 8,3 8,8 9,4
11,5 13,6
BCOOLING CAPACITY PERFORMANCE
NECS
015230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
42,0 39,6 38,6 37,0 34,1 32,9 43,2 40,8 39,7 38,1 35,1 33,8 44,5 42,0 40,9 39,2 36,1 34,811,5 12,8 13,4 14,3 15,8 16,5 11,6 12,9 13,5 14,4 16,0 16,6 11,7 13,0 13,6 14,5 16,1 16,77,23 6,82 6,64 6,36 5,87 5,66 7,44 7,02 6,84 6,56 6,04 5,82 7,66 7,23 7,04 6,75 6,22 5,9970,3 62,5 59,3 54,5 46,3 43,0 74,5 66,4 63,0 57,8 49,1 45,6 78,9 70,3 66,7 61,3 52,0 48,3
Ta
Dpev 83,5 74,3 70,6 64,8 54,9 51,0 88,1 78,5 74,5 68,4 57,9 53,7 92,8 82,7 78,5 72,0 61,0 56,5Qev 7,88 7,43 7,24 6,94 6,39 6,16 8,09 7,64 7,44 7,13 6,56 6,32 8,31 7,84 7,64 7,32 6,73 6,48Pat 11,9 13,2 13,7 14,6 16,2 16,8 12,0 13,3 13,8 14,7 16,3 16,9 12,1 13,4 13,9 14,8 16,3 17,0Pf 45,7 43,2 42,0 40,3 37,1 35,7 47,0 44,3 43,2 41,4 38,1 36,7 48,2 45,5 44,3 42,5 39,1 37,6
9 10 11Tev
018230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
49,2 46,5 45,4 43,8 40,9 39,7 50,6 47,9 46,8 45,1 42,2 41,0 52,0 49,2 48,1 46,4 43,5 42,312,7 14,0 14,6 15,4 17,0 17,6 12,8 14,1 14,7 15,6 17,1 17,8 12,9 14,3 14,9 15,7 17,3 17,98,46 8,01 7,82 7,53 7,04 6,83 8,71 8,24 8,05 7,76 7,26 7,06 8,95 8,47 8,28 7,99 7,49 7,2862,2 55,7 53,1 49,3 43,0 40,5 65,8 59,0 56,3 52,3 45,8 43,2 69,5 62,4 59,6 55,4 48,7 46,1
Ta
Dpev 73,3 65,8 62,9 58,6 51,7 49,0 77,1 69,3 66,3 61,9 54,8 52,0 81,0 72,9 69,8 65,3 58,0 55,2Qev 9,19 8,71 8,51 8,22 7,71 7,51 9,42 8,94 8,74 8,44 7,94 7,74 9,66 9,16 8,97 8,67 8,17 7,97Pat 13,1 14,4 15,0 15,9 17,4 18,1 13,2 14,6 15,1 16,0 17,6 18,2 13,3 14,7 15,3 16,1 17,7 18,4Pf 53,3 50,5 49,4 47,7 44,8 43,6 54,7 51,9 50,7 49,0 46,1 44,9 56,1 53,2 52,0 50,3 47,4 46,3
9 10 11Tev
020230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
56,1 52,8 51,3 49,0 44,9 43,1 57,7 54,3 52,8 50,5 46,2 44,4 59,4 55,8 54,3 51,9 47,6 45,715,3 17,0 17,7 18,9 20,9 21,8 15,4 17,2 17,9 19,1 21,1 22,0 15,6 17,3 18,1 19,2 21,3 22,29,66 9,08 8,83 8,44 7,72 7,42 9,94 9,35 9,09 8,69 7,96 7,65 10,2 9,62 9,35 8,94 8,19 7,8757,3 50,7 47,9 43,7 36,7 33,8 60,7 53,7 50,8 46,4 38,9 35,9 64,2 56,8 53,8 49,1 41,2 38,1
Ta
Dpev 67,8 60,0 56,8 51,9 43,6 40,3 71,4 63,3 59,9 54,8 46,0 42,5 75,1 66,6 63,1 57,7 48,5 -Qev 10,5 9,88 9,61 9,19 8,42 8,10 10,8 10,1 9,87 9,44 8,66 8,32 11,1 10,4 10,1 9,69 8,89 -Pat 15,7 17,5 18,2 19,4 21,5 22,3 15,9 17,6 18,4 19,6 21,6 22,5 16,0 17,8 18,5 19,7 21,8 -Pf 61,0 57,4 55,8 53,4 48,9 47,0 62,6 58,9 57,3 54,8 50,2 48,3 64,2 60,4 58,8 56,2 51,6 -
9 10 11Tev
025230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
63,1 59,5 57,9 55,5 51,0 49,1 65,0 61,2 59,6 57,0 52,4 50,4 66,8 63,0 61,3 58,6 53,8 51,717,5 19,3 20,1 21,4 23,6 24,6 17,6 19,5 20,3 21,5 23,8 24,8 17,8 19,6 20,4 21,7 24,0 24,910,9 10,2 9,97 9,55 8,78 8,45 11,2 10,5 10,3 9,82 9,02 8,68 11,5 10,8 10,6 10,1 9,26 8,9050,2 44,6 42,3 38,8 32,8 30,4 53,3 47,3 44,8 41,0 34,6 32,1 56,3 50,0 47,4 43,3 36,5 33,7
Ta
Dpev 59,5 52,8 50,0 45,7 38,3 35,4 62,8 55,6 52,6 48,0 40,2 37,1 66,1 58,5 55,3 50,4 42,1 -Qev 11,8 11,1 10,8 10,4 9,49 9,12 12,1 11,4 11,1 10,6 9,72 9,33 12,5 11,7 11,4 10,9 9,95 -Pat 17,9 19,8 20,6 21,9 24,1 25,1 18,1 20,0 20,8 22,0 24,2 25,2 18,2 20,1 20,9 22,1 24,4 -Pf 68,7 64,7 62,9 60,1 55,1 53,0 70,5 66,4 64,6 61,7 56,4 54,2 72,3 68,1 66,2 63,2 57,7 -
9 10 11Tev
030230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
83,5 78,9 76,9 73,8 68,2 65,9 85,8 81,2 79,2 76,0 70,3 67,9 88,1 83,4 81,4 78,2 72,5 70,022,5 24,9 25,9 27,6 30,6 31,9 22,7 25,1 26,2 27,8 30,9 32,2 22,9 25,4 26,4 28,1 31,2 32,514,4 13,6 13,2 12,7 11,7 11,3 14,8 14,0 13,6 13,1 12,1 11,7 15,2 14,4 14,0 13,5 12,5 12,168,8 61,5 58,5 53,9 46,0 42,9 72,7 65,1 61,9 57,1 48,9 45,6 76,8 68,8 65,5 60,4 51,9 48,5
Ta
Dpev 80,9 72,5 69,1 63,8 55,0 51,5 85,1 76,4 72,8 67,4 58,3 54,6 89,4 80,3 76,6 71,0 61,7 -Qev 15,6 14,7 14,4 13,8 12,8 12,4 16,0 15,1 14,8 14,2 13,2 12,8 16,4 15,5 15,2 14,6 13,6 -Pat 23,2 25,6 26,7 28,4 31,5 32,8 23,4 25,8 26,9 28,6 31,7 33,1 23,6 26,1 27,1 28,9 32,0 -Pf 90,4 85,6 83,6 80,3 74,6 72,2 92,7 87,8 85,8 82,5 76,7 74,3 95,0 90,0 87,9 84,7 78,9 -
9 10 11Tev
Ta [°C] - Air temperatureTev [°C] - Plant (side) cooling exchanger output water temperature
Pat [kW] - Total power inputQev [m³/h] - Plant (side) heat exchanger water flowDpev [kPa] - Plant (side) cooling exchanger pressure drop
Pf [kW] - Cooling capacity
'-' Conditions outside the operating rangeWaterflow and pressure drop on heat exchangers calculated with 5°C of delta TNOTE: Data on grey background: unit switched to non-silenced operation
11ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
BCOOLING CAPACITY PERFORMANCE
NECS
035230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
95,6 90,1 87,9 84,3 78,0 75,4 98,3 92,8 90,4 86,8 80,4 77,8 101 95,4 93,0 89,3 82,9 80,225,9 28,6 29,7 31,5 34,9 36,3 26,2 28,9 30,0 31,9 35,3 36,7 26,5 29,2 30,4 32,2 35,6 37,116,5 15,5 15,1 14,5 13,4 13,0 16,9 16,0 15,6 14,9 13,8 13,4 17,4 16,4 16,0 15,4 14,3 13,870,5 62,7 59,6 54,8 47,0 43,9 74,6 66,4 63,1 58,2 50,0 46,7 78,8 70,3 66,8 61,6 53,1 49,7
Ta
Dpev 83,2 74,2 70,6 65,2 56,3 52,8 87,6 78,2 74,5 68,9 59,7 56,1 92,1 82,3 78,5 72,7 63,2 -Qev 17,9 16,9 16,5 15,8 14,7 14,2 18,3 17,3 16,9 16,3 15,1 14,7 18,8 17,8 17,4 16,7 15,6 -Pat 26,8 29,5 30,7 32,6 36,0 37,4 27,1 29,8 31,0 32,9 36,3 37,8 27,4 30,1 31,3 33,2 36,7 -Pf 104 98,0 95,6 91,9 85,4 82,7 106 101 98,1 94,4 87,9 85,2 109 103 101 96,9 90,4 -
9 10 11Tev
041230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
107 101 98,1 94,1 87,1 84,2 110 104 101 96,9 89,8 86,9 113 107 104 99,8 92,6 89,629,6 32,5 33,8 35,9 39,5 41,1 30,0 33,0 34,3 36,3 40,0 41,6 30,3 33,4 34,7 36,7 40,5 42,118,4 17,3 16,9 16,2 15,0 14,5 19,0 17,9 17,4 16,7 15,5 15,0 19,5 18,4 17,9 17,2 15,9 15,473,9 65,4 62,0 57,0 48,8 45,7 78,3 69,3 65,8 60,5 52,0 48,7 82,7 73,4 69,7 64,2 55,3 51,8
Ta
Dpev 87,3 77,5 73,7 68,0 58,7 55,1 92,0 81,8 77,8 71,8 62,3 - 96,8 86,2 82,0 75,9 66,0 -Qev 20,0 18,9 18,4 17,7 16,4 15,9 20,6 19,4 18,9 18,2 16,9 - 21,1 19,9 19,4 18,7 17,4 -Pat 30,7 33,7 35,1 37,2 40,9 42,5 31,0 34,1 35,5 37,6 41,4 - 31,4 34,5 35,9 38,0 41,8 -Pf 116 110 107 103 95,4 92,4 119 113 110 106 98,2 - 122 116 113 108 101 -
9 10 11Tev
045230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
123 116 114 109 101 98,0 127 120 117 112 104 101 131 123 120 116 107 10432,5 35,7 37,1 39,3 43,2 44,9 32,9 36,1 37,5 39,7 43,6 45,3 33,3 36,5 37,9 40,1 44,0 45,721,2 20,0 19,5 18,8 17,4 16,9 21,9 20,6 20,1 19,3 18,0 17,4 22,5 21,2 20,7 19,9 18,5 17,972,5 64,6 61,5 56,7 48,9 45,8 76,8 68,5 65,2 60,2 51,9 48,6 81,3 72,5 69,0 63,7 55,0 51,6
Ta
Dpev 85,8 76,6 72,9 67,3 58,2 54,6 90,4 80,7 76,8 71,0 61,4 - 95,2 85,0 80,9 74,8 64,8 -Qev 23,1 21,8 21,3 20,5 19,0 18,4 23,7 22,4 21,9 21,0 19,5 - 24,3 23,0 22,4 21,6 20,1 -Pat 33,6 36,9 38,3 40,5 44,4 46,1 34,0 37,2 38,6 40,8 44,8 - 34,3 37,6 39,0 41,2 45,2 -Pf 134 127 124 119 110 107 138 130 127 122 113 - 141 133 130 125 116 -
9 10 11Tev
051230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
139 131 128 123 114 111 143 135 132 127 118 114 147 139 135 130 121 11736,0 39,5 41,0 43,3 47,6 49,4 36,4 39,9 41,4 43,7 48,0 49,8 36,8 40,3 41,8 44,1 48,3 50,123,9 22,6 22,0 21,2 19,7 19,1 24,6 23,2 22,7 21,8 20,3 19,6 25,3 23,9 23,3 22,4 20,8 20,278,0 69,8 66,4 61,4 53,0 49,7 82,6 73,9 70,4 65,1 56,2 52,6 87,4 78,2 74,4 68,8 59,4 55,6
Ta
Dpev 92,2 82,5 78,6 72,6 62,7 58,7 97,2 87,0 82,8 76,5 66,0 61,9 102 91,6 87,2 80,5 69,5 65,1Qev 26,0 24,6 24,0 23,0 21,4 20,7 26,7 25,2 24,6 23,6 22,0 21,3 27,3 25,9 25,2 24,3 22,5 21,8Pat 37,1 40,6 42,1 44,5 48,7 50,5 37,5 41,0 42,5 44,9 49,1 50,8 37,8 41,4 42,9 45,2 49,4 51,1Pf 151 143 139 134 124 120 155 146 143 137 127 123 159 150 146 141 131 127
9 10 11Tev
055230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
159 150 146 141 131 127 163 155 151 145 135 130 168 159 155 149 138 13441,2 45,2 46,9 49,7 54,6 56,7 41,6 45,7 47,4 50,2 55,1 57,2 42,1 46,1 47,9 50,6 55,6 57,727,3 25,8 25,2 24,2 22,5 21,8 28,1 26,6 26,0 24,9 23,2 22,4 28,9 27,4 26,7 25,7 23,8 23,192,6 82,7 78,8 72,8 62,8 58,9 98,1 87,7 83,5 77,1 66,6 62,4 104 92,7 88,3 81,6 70,4 66,0
Ta
Dpev 110 97,9 93,2 86,1 74,3 69,6 116 103 98,3 90,8 78,3 73,4 122 109 103 95,6 82,5 -Qev 29,7 28,1 27,4 26,4 24,5 23,7 30,5 28,9 28,2 27,1 25,1 24,3 31,3 29,6 28,9 27,8 25,8 -Pat 42,5 46,6 48,4 51,1 56,0 58,1 42,9 47,0 48,8 51,6 56,5 58,6 43,4 47,5 49,2 52,0 56,9 -Pf 173 163 159 153 142 138 177 168 163 157 146 141 182 172 168 161 150 -
9 10 11Tev
Ta [°C] - Air temperatureTev [°C] - Plant (side) cooling exchanger output water temperature
Pat [kW] - Total power inputQev [m³/h] - Plant (side) heat exchanger water flowDpev [kPa] - Plant (side) cooling exchanger pressure drop
Pf [kW] - Cooling capacity
'-' Conditions outside the operating rangeWaterflow and pressure drop on heat exchangers calculated with 5°C of delta TNOTE: Data on grey background: unit switched to non-silenced operation
12ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
BCOOLING CAPACITY PERFORMANCE
NECS
061230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
175 165 161 154 143 138 180 170 165 159 147 142 185 174 170 163 151 14648,0 52,8 54,8 58,0 63,8 66,2 48,6 53,4 55,4 58,6 64,4 66,8 49,1 53,9 56,0 59,2 65,0 67,530,1 28,4 27,7 26,5 24,6 23,8 31,0 29,2 28,5 27,3 25,3 24,5 31,8 30,0 29,3 28,1 26,0 25,198,7 87,7 83,3 76,7 65,8 61,5 105 92,9 88,2 81,2 69,6 65,1 110 98,1 93,2 85,8 73,6 68,8
Ta
Dpev 117 104 98,3 90,5 77,6 72,5 123 109 104 95,3 81,7 76,4 129 115 109 100 85,9 -Qev 32,7 30,8 30,0 28,8 26,7 25,8 33,6 31,6 30,8 29,6 27,4 26,5 34,4 32,5 31,6 30,3 28,1 -Pat 49,7 54,5 56,6 59,9 65,7 68,1 50,2 55,1 57,2 60,4 66,3 68,7 50,8 55,7 57,8 61,0 66,9 -Pf 190 179 174 167 155 150 195 184 179 172 159 154 200 188 184 176 163 -
9 10 11Tev
Ta [°C] - Air temperatureTev [°C] - Plant (side) cooling exchanger output water temperature
Pat [kW] - Total power inputQev [m³/h] - Plant (side) heat exchanger water flowDpev [kPa] - Plant (side) cooling exchanger pressure drop
Pf [kW] - Cooling capacity
'-' Conditions outside the operating rangeWaterflow and pressure drop on heat exchangers calculated with 5°C of delta TNOTE: Data on grey background: unit switched to non-silenced operation
13ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
HTCOOLING CAPACITY PERFORMANCE
NECS
015230 35 40 43 4625 25 30 35 40 43 46 25 30 35 40 43 46
6 7 8Tev
PfPatQevDpev
43,3 41,0 38,5 35,7 33,9 32,1 44,6 42,3 39,7 36,8 35,0 33,1 45,9 43,5 40,9 37,9 36,0 34,010,8 12,0 13,4 14,9 15,9 17,0 10,9 12,1 13,5 15,0 16,0 17,0 11,0 12,2 13,6 15,1 16,1 17,17,45 7,06 6,62 6,15 5,84 5,52 7,68 7,28 6,83 6,34 6,02 5,69 7,90 7,50 7,04 6,53 6,20 5,8674,7 67,0 59,1 50,9 45,9 41,0 79,3 71,3 62,8 54,1 48,8 43,6 84,0 75,6 66,6 57,4 51,8 46,2
Ta
Dpev 88,9 80,1 70,6 60,8 54,8 48,9 93,9 84,6 74,7 64,3 57,9 - 99,1 89,3 78,8 67,8 61,1 -Qev 8,13 7,71 7,24 6,72 6,38 6,03 8,36 7,93 7,45 6,91 6,56 - 8,58 8,15 7,65 7,10 6,74 -Pat 11,1 12,3 13,7 15,2 16,2 17,2 11,2 12,4 13,8 15,3 16,3 - 11,3 12,5 13,9 15,4 16,3 -Pf 47,2 44,8 42,1 39,0 37,1 35,0 48,5 46,0 43,2 40,1 38,1 - 49,8 47,3 44,4 41,2 39,1 -
9 10 11Tev
018230 35 40 43 4625 25 30 35 40 43 46 25 30 35 40 43 46
6 7 8Tev
PfPatQevDpev
50,6 48,0 45,4 42,5 40,8 38,9 52,1 49,4 46,7 43,9 42,1 40,3 53,5 50,8 48,1 45,2 43,4 41,612,5 13,7 15,1 16,6 17,6 18,5 12,6 13,9 15,2 16,7 17,7 18,7 12,7 14,0 15,4 16,9 17,8 18,88,71 8,27 7,81 7,32 7,02 6,70 8,96 8,51 8,04 7,55 7,25 6,94 9,22 8,76 8,28 7,78 7,48 7,1765,9 59,4 52,9 46,5 42,7 39,0 69,8 62,9 56,2 49,5 45,6 41,8 73,8 66,6 59,5 52,6 48,6 44,6
Ta
Dpev 77,9 70,3 62,9 55,8 51,6 47,6 82,0 74,1 66,5 59,1 54,8 50,7 86,3 78,0 70,1 62,5 58,1 53,9Qev 9,47 9,00 8,51 8,02 7,71 7,40 9,72 9,24 8,75 8,25 7,95 7,64 9,97 9,48 8,98 8,48 8,18 7,88Pat 12,8 14,1 15,5 17,0 17,9 18,9 12,9 14,2 15,6 17,1 18,0 19,0 13,0 14,3 15,7 17,2 18,2 19,2Pf 55,0 52,2 49,4 46,5 44,8 43,0 56,4 53,6 50,8 47,9 46,1 44,3 57,8 55,0 52,1 49,2 47,5 45,7
9 10 11Tev
020230 35 40 43 4625 25 30 35 40 43 46 25 30 35 40 43 46
6 7 8Tev
PfPatQevDpev
59,6 56,7 53,3 49,6 47,2 44,6 61,4 58,4 55,0 51,2 48,7 46,0 63,1 60,1 56,6 52,7 50,2 47,514,0 15,5 17,2 19,1 20,3 21,6 14,1 15,6 17,3 19,2 20,4 21,7 14,2 15,7 17,4 19,3 20,6 21,810,3 9,75 9,18 8,54 8,12 7,68 10,6 10,0 9,46 8,81 8,38 7,93 10,9 10,3 9,75 9,08 8,64 8,1864,7 58,4 51,8 44,8 40,5 36,2 68,6 62,1 55,0 47,7 43,1 38,6 72,6 65,8 58,4 50,6 45,9 41,1
Ta
Dpev 76,8 69,6 61,9 53,7 48,7 43,6 81,0 73,5 65,4 56,9 51,6 46,3 85,4 77,6 69,1 60,1 54,6 49,0Qev 11,2 10,6 10,0 9,35 8,90 8,43 11,5 10,9 10,3 9,62 9,16 8,68 11,8 11,2 10,6 9,89 9,43 8,93Pat 14,3 15,8 17,6 19,5 20,7 22,0 14,4 16,0 17,7 19,6 20,8 22,1 14,5 16,1 17,8 19,7 20,9 22,2Pf 64,9 61,8 58,3 54,3 51,7 48,9 66,6 63,5 59,9 55,8 53,2 50,4 68,4 65,2 61,5 57,4 54,7 51,8
9 10 11Tev
025230 35 40 43 4625 25 30 35 40 43 46 25 30 35 40 43 46
6 7 8Tev
PfPatQevDpev
66,6 63,4 59,7 55,7 53,1 50,4 68,7 65,3 61,6 57,4 54,7 51,9 70,7 67,3 63,4 59,1 56,3 53,416,7 18,3 20,2 22,2 23,6 25,0 16,8 18,5 20,3 22,4 23,7 25,1 16,9 18,6 20,4 22,5 23,8 25,211,5 10,9 10,3 9,59 9,14 8,67 11,8 11,2 10,6 9,89 9,42 8,93 12,2 11,6 10,9 10,2 9,70 9,1956,0 50,6 45,0 39,1 35,6 32,0 59,4 53,8 47,8 41,6 37,8 33,9 63,0 57,1 50,7 44,1 40,0 35,9
Ta
Dpev 66,7 60,5 53,7 46,6 42,3 37,9 70,5 63,9 56,8 49,3 44,6 39,9 74,4 67,5 60,0 51,9 47,0 42,0Qev 12,5 11,9 11,2 10,5 9,97 9,44 12,9 12,3 11,6 10,8 10,2 9,69 13,2 12,6 11,9 11,0 10,5 9,93Pat 17,0 18,7 20,5 22,6 23,9 25,3 17,1 18,8 20,6 22,7 24,0 25,4 17,3 18,9 20,7 22,8 24,1 25,5Pf 72,7 69,2 65,2 60,8 57,9 54,8 74,7 71,2 67,1 62,5 59,4 56,2 76,7 73,1 68,9 64,1 61,0 57,6
9 10 11Tev
030230 35 40 43 4625 25 30 35 40 43 46 25 30 35 40 43 46
6 7 8Tev
PfPatQevDpev
87,0 82,9 78,3 73,1 69,8 66,2 89,5 85,3 80,6 75,4 72,0 68,4 92,0 87,7 82,9 77,6 74,2 70,521,1 23,2 25,7 28,5 30,3 32,2 21,3 23,4 25,9 28,7 30,5 32,5 21,5 23,6 26,1 28,9 30,7 32,715,0 14,3 13,5 12,6 12,0 11,4 15,4 14,7 13,9 13,0 12,4 11,8 15,8 15,1 14,3 13,4 12,8 12,174,8 67,9 60,6 52,8 48,1 43,3 79,2 72,0 64,2 56,2 51,2 46,2 83,7 76,1 68,0 59,6 54,4 49,2
Ta
Dpev 88,3 80,4 71,9 63,1 57,8 52,4 93,1 84,7 75,9 66,8 61,2 - 97,9 89,1 80,0 70,6 64,9 -Qev 16,3 15,5 14,7 13,8 13,2 12,5 16,7 15,9 15,1 14,2 13,6 - 17,1 16,3 15,5 14,5 13,9 -Pat 21,7 23,8 26,3 29,1 31,0 32,9 21,8 24,0 26,5 29,3 31,1 - 22,0 24,2 26,7 29,5 31,3 -Pf 94,5 90,1 85,3 79,9 76,4 72,8 97,0 92,5 87,6 82,1 78,7 - 99,4 94,9 89,9 84,4 80,9 -
9 10 11Tev
Ta [°C] - Air temperatureTev [°C] - Plant (side) cooling exchanger output water temperature
Pat [kW] - Total power inputQev [m³/h] - Plant (side) heat exchanger water flowDpev [kPa] - Plant (side) cooling exchanger pressure drop
Pf [kW] - Cooling capacity
'-' Conditions outside the operating rangeWaterflow and pressure drop on heat exchangers calculated with 5°C of delta TNOTE: Data on grey background: unit switched to non-silenced operation
14ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
HTCOOLING CAPACITY PERFORMANCE
NECS
035230 35 40 43 4625 25 30 35 40 43 46 25 30 35 40 43 46
6 7 8Tev
PfPatQevDpev
99,4 94,3 88,7 82,8 79,0 75,1 102 97,1 91,4 85,4 81,5 77,5 105 99,9 94,1 88,0 84,1 -25,1 27,5 30,3 33,3 35,4 37,5 25,4 27,8 30,5 33,6 35,7 37,8 25,6 28,0 30,8 33,9 36,0 -17,1 16,2 15,3 14,2 13,6 12,9 17,6 16,7 15,7 14,7 14,0 13,3 18,1 17,2 16,2 15,1 14,5 -76,2 68,6 60,8 52,9 48,2 43,5 80,8 72,7 64,5 56,3 51,3 46,4 85,5 77,0 68,4 59,8 54,6 -
Ta
Dpev 90,3 81,4 72,4 63,4 58,0 - 95,2 85,9 76,5 67,2 61,6 - 100 90,5 80,7 71,1 65,3 -Qev 18,6 17,7 16,7 15,6 14,9 - 19,1 18,2 17,1 16,1 15,4 - 19,6 18,6 17,6 16,5 15,8 -Pat 25,8 28,3 31,1 34,2 36,3 - 26,1 28,5 31,4 34,5 36,6 - 26,3 28,8 31,6 34,8 36,8 -Pf 108 103 96,8 90,6 86,7 - 111 105 99,5 93,2 89,3 - 114 108 102 95,8 91,9 -
9 10 11Tev
041230 35 40 43 4625 25 30 35 40 43 46 25 30 35 40 43 46
6 7 8Tev
PfPatQevDpev
113 107 101 94,5 90,3 86,1 117 111 104 97,5 93,3 88,9 120 114 107 101 96,2 91,827,8 30,4 33,3 36,7 38,8 41,1 28,1 30,7 33,7 37,0 39,2 41,5 28,4 31,0 34,0 37,4 39,5 41,919,5 18,5 17,4 16,3 15,5 14,8 20,1 19,1 18,0 16,8 16,1 15,3 20,7 19,6 18,5 17,3 16,6 15,883,0 74,4 65,9 57,5 52,6 47,7 88,1 79,1 70,1 61,3 56,1 51,0 93,3 83,8 74,4 65,1 59,7 54,4
Ta
Dpev 98,6 88,7 78,8 69,2 63,5 57,9 104 93,7 83,4 73,3 67,4 - 110 98,9 88,1 77,6 71,5 -Qev 21,3 20,2 19,0 17,8 17,1 16,3 21,9 20,8 19,6 18,4 17,6 - 22,5 21,3 20,1 18,9 18,1 -Pat 28,6 31,3 34,3 37,7 39,9 42,2 28,9 31,6 34,6 38,0 40,2 - 29,1 31,8 34,9 38,3 40,6 -Pf 124 117 111 104 99,2 94,7 127 120 114 107 102 - 130 124 117 110 105 -
9 10 11Tev
045230 35 40 43 4625 25 30 35 40 43 46 25 30 35 40 43 46
6 7 8Tev
PfPatQevDpev
126 119 112 105 99,9 94,9 130 123 116 108 103 97,8 134 127 119 111 106 -31,8 34,8 38,2 42,0 44,4 47,0 32,1 35,2 38,6 42,4 44,8 47,4 32,4 35,5 38,9 42,7 45,2 -21,7 20,6 19,3 18,0 17,2 16,3 22,4 21,2 19,9 18,6 17,7 16,8 23,0 21,8 20,5 19,1 18,3 -75,9 68,0 60,1 52,2 47,5 42,9 80,5 72,2 63,8 55,5 50,5 45,6 85,2 76,4 67,6 58,8 53,6 -
Ta
Dpev 90,0 80,8 71,5 62,3 56,8 - 95,0 85,3 75,5 65,8 60,1 - 100 89,9 79,6 69,5 63,5 -Qev 23,7 22,4 21,1 19,7 18,8 - 24,3 23,0 21,7 20,2 19,3 - 24,9 23,6 22,2 20,8 19,9 -Pat 32,8 35,8 39,3 43,1 45,5 - 33,1 36,2 39,6 43,4 45,9 - 33,4 36,5 40,0 43,8 46,2 -Pf 137 130 122 114 109 - 141 134 126 117 112 - 145 137 129 121 115 -
9 10 11Tev
051230 35 40 43 4625 25 30 35 40 43 46 25 30 35 40 43 46
6 7 8Tev
PfPatQevDpev
141 134 126 118 112 107 146 138 130 121 115 110 150 142 134 125 119 -34,8 38,1 41,8 46,0 48,7 51,5 35,1 38,5 42,2 46,4 49,0 51,8 35,5 38,8 42,6 46,7 49,4 -24,3 23,1 21,7 20,2 19,3 18,3 25,1 23,8 22,4 20,8 19,9 18,9 25,8 24,4 23,0 21,4 20,4 -81,1 72,9 64,5 56,1 51,0 46,0 86,0 77,3 68,4 59,5 54,1 48,8 91,0 81,8 72,4 62,9 57,3 -
Ta
Dpev 96,2 86,5 76,5 66,5 60,5 - 101 91,3 80,8 70,2 63,8 - 107 96,1 85,1 73,9 67,2 -Qev 26,5 25,1 23,6 22,0 21,0 - 27,2 25,8 24,3 22,6 21,6 - 27,9 26,5 24,9 23,2 22,2 -Pat 35,8 39,2 42,9 47,0 49,7 - 36,1 39,5 43,3 47,4 50,0 - 36,4 39,9 43,6 47,7 50,3 -Pf 154 146 137 128 122 - 158 150 141 131 125 - 162 154 145 135 129 -
9 10 11Tev
Ta [°C] - Air temperatureTev [°C] - Plant (side) cooling exchanger output water temperature
Pat [kW] - Total power inputQev [m³/h] - Plant (side) heat exchanger water flowDpev [kPa] - Plant (side) cooling exchanger pressure drop
Pf [kW] - Cooling capacity
'-' Conditions outside the operating rangeWaterflow and pressure drop on heat exchangers calculated with 5°C of delta TNOTE: Data on grey background: unit switched to non-silenced operation
15ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
LNCOOLING CAPACITY PERFORMANCE
NECS
015230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
40,4 37,9 36,8 35,1 32,0 - 41,6 39,0 37,9 36,1 32,9 - 42,8 40,1 38,9 37,1 33,8 -12,0 13,4 14,0 14,9 16,6 - 12,1 13,5 14,1 15,1 16,7 - 12,3 13,7 14,3 15,2 16,8 -6,96 6,52 6,34 6,04 5,52 - 7,16 6,71 6,52 6,22 5,67 - 7,37 6,90 6,70 6,39 5,82 -65,2 57,2 54,0 49,1 40,9 - 69,0 60,6 57,2 52,0 43,3 - 73,0 64,1 60,5 54,9 45,6 -
Ta
Dpev 77,1 67,7 63,8 57,9 - - 81,2 71,3 67,2 60,9 - - 85,5 75,0 70,6 64,0 - -Qev 7,57 7,09 6,89 6,56 - - 7,77 7,28 7,07 6,73 - - 7,97 7,46 7,24 6,90 - -Pat 12,4 13,8 14,4 15,3 - - 12,5 13,9 14,5 15,4 - - 12,6 14,0 14,6 15,5 - -Pf 43,9 41,2 40,0 38,1 - - 45,1 42,3 41,0 39,1 - - 46,3 43,3 42,0 40,0 - -
9 10 11Tev
018230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
47,1 44,4 43,3 41,5 38,6 - 48,5 45,7 44,5 42,8 39,8 - 49,8 46,9 45,8 44,0 41,1 -13,3 14,8 15,3 16,3 17,9 - 13,5 14,9 15,5 16,5 18,1 - 13,7 15,1 15,7 16,6 18,3 -8,11 7,64 7,45 7,15 6,64 - 8,34 7,86 7,66 7,37 6,86 - 8,57 8,08 7,88 7,58 7,08 -57,2 50,7 48,1 44,4 38,2 - 60,4 53,7 51,0 47,1 40,8 - 63,8 56,7 54,0 50,0 43,5 -
Ta
Dpev 67,1 59,8 57,0 52,9 - - 70,6 63,0 60,1 55,9 - - 74,1 66,3 63,3 59,0 - -Qev 8,79 8,30 8,10 7,80 - - 9,01 8,52 8,32 8,02 - - 9,23 8,74 8,54 8,24 - -Pat 13,8 15,3 15,9 16,8 - - 14,0 15,4 16,0 17,0 - - 14,1 15,6 16,2 17,1 - -Pf 51,0 48,2 47,0 45,3 - - 52,3 49,5 48,3 46,6 - - 53,6 50,7 49,6 47,8 - -
9 10 11Tev
020230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
56,3 52,9 51,5 49,2 45,1 43,3 57,9 54,5 53,0 50,7 46,4 44,6 59,5 56,0 54,5 52,1 47,8 45,915,2 16,9 17,6 18,7 20,8 21,7 15,3 17,0 17,8 18,9 21,0 21,9 15,5 17,2 17,9 19,1 21,2 22,09,68 9,11 8,86 8,47 7,76 7,45 9,97 9,38 9,12 8,72 7,99 7,68 10,2 9,65 9,39 8,97 8,23 7,9157,6 51,0 48,2 44,1 37,0 34,1 61,0 54,0 51,2 46,7 39,3 36,3 64,5 57,2 54,1 49,5 41,6 38,4
Ta
Dpev 68,1 60,4 57,2 52,3 44,0 - 71,8 63,7 60,3 55,2 46,5 - 75,5 67,0 63,5 58,1 49,0 -Qev 10,5 9,91 9,65 9,22 8,46 - 10,8 10,2 9,91 9,48 8,70 - 11,1 10,4 10,2 9,72 8,93 -Pat 15,6 17,4 18,1 19,3 21,3 - 15,8 17,5 18,3 19,4 21,5 - 15,9 17,7 18,4 19,6 21,6 -Pf 61,1 57,6 56,0 53,6 49,1 - 62,7 59,1 57,5 55,0 50,5 - 64,3 60,6 59,0 56,4 51,8 -
9 10 11Tev
025230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
63,6 60,0 58,4 56,0 51,6 49,7 65,5 61,8 60,1 57,6 53,0 51,1 67,3 63,5 61,8 59,2 54,4 52,417,2 19,0 19,8 21,1 23,3 24,3 17,3 19,2 20,0 21,2 23,5 24,4 17,5 19,3 20,1 21,4 23,6 24,610,9 10,3 10,1 9,64 8,88 8,56 11,3 10,6 10,4 9,92 9,13 8,79 11,6 10,9 10,6 10,2 9,37 9,0251,0 45,4 43,0 39,5 33,5 31,1 54,0 48,1 45,6 41,8 35,4 32,9 57,2 50,9 48,2 44,2 37,4 34,6
Ta
Dpev 60,4 53,7 50,9 46,6 39,3 36,4 63,8 56,7 53,7 49,1 41,3 38,1 67,2 59,6 56,5 51,6 43,2 -Qev 11,9 11,2 10,9 10,5 9,61 9,25 12,2 11,5 11,2 10,7 9,85 9,47 12,6 11,8 11,5 11,0 10,1 -Pat 17,6 19,5 20,3 21,5 23,8 24,7 17,8 19,6 20,4 21,7 23,9 24,8 17,9 19,8 20,6 21,8 24,0 -Pf 69,2 65,2 63,5 60,8 55,8 53,7 71,1 67,0 65,2 62,4 57,2 54,9 72,9 68,7 66,9 63,9 58,5 -
9 10 11Tev
030230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
82,0 77,3 75,3 72,1 66,3 - 84,3 79,5 77,4 74,2 68,4 - 86,6 81,7 79,6 76,3 70,5 -23,0 25,5 26,6 28,3 31,4 - 23,2 25,8 26,9 28,6 31,7 - 23,5 26,0 27,1 28,9 32,1 -14,1 13,3 13,0 12,4 11,4 - 14,5 13,7 13,3 12,8 11,8 - 14,9 14,1 13,7 13,1 12,1 -66,5 59,1 56,0 51,3 43,5 - 70,2 62,5 59,3 54,4 46,2 - 74,1 66,0 62,6 57,6 49,1 -
Ta
Dpev 78,0 69,5 66,1 60,8 - - 82,0 73,2 69,6 64,2 - - 86,1 77,0 73,3 67,7 - -Qev 15,3 14,4 14,1 13,5 - - 15,7 14,8 14,4 13,9 - - 16,1 15,2 14,8 14,2 - -Pat 23,8 26,3 27,4 29,2 - - 24,0 26,6 27,7 29,4 - - 24,2 26,8 27,9 29,7 - -Pf 88,8 83,8 81,7 78,4 - - 91,0 86,0 83,9 80,5 - - 93,3 88,2 86,0 82,7 - -
9 10 11Tev
Ta [°C] - Air temperatureTev [°C] - Plant (side) cooling exchanger output water temperature
Pat [kW] - Total power inputQev [m³/h] - Plant (side) heat exchanger water flowDpev [kPa] - Plant (side) cooling exchanger pressure drop
Pf [kW] - Cooling capacity
'-' Conditions outside the operating rangeWaterflow and pressure drop on heat exchangers calculated with 5°C of delta TNOTE: Data on grey background: unit switched to non-silenced operation
16ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
LNCOOLING CAPACITY PERFORMANCE
NECS
035230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
93,5 87,9 85,6 82,0 75,6 72,9 96,1 90,5 88,1 84,4 78,0 75,3 98,8 93,0 90,6 86,9 80,3 77,627,4 30,2 31,4 33,3 36,7 38,2 27,7 30,5 31,7 33,7 37,1 38,6 28,1 30,9 32,1 34,0 37,5 39,016,1 15,1 14,7 14,1 13,0 12,6 16,5 15,6 15,2 14,5 13,4 13,0 17,0 16,0 15,6 15,0 13,8 13,467,4 59,7 56,5 51,8 44,1 41,0 71,3 63,2 59,9 55,0 46,9 43,7 75,3 66,8 63,4 58,3 49,9 46,5
Ta
Dpev 79,4 70,5 66,9 61,6 52,9 - 83,6 74,3 70,6 65,1 56,1 - 87,8 78,2 74,4 68,7 59,5 -Qev 17,5 16,5 16,0 15,4 14,3 - 17,9 16,9 16,5 15,8 14,7 - 18,4 17,3 16,9 16,2 15,1 -Pat 28,4 31,2 32,5 34,4 37,9 - 28,7 31,6 32,8 34,8 38,3 - 29,0 31,9 33,2 35,1 38,7 -Pf 101 95,5 93,1 89,3 82,8 - 104 98,0 95,6 91,8 85,2 - 107 101 98,1 94,3 87,7 -
9 10 11Tev
041230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
107 100 97,6 93,5 86,6 83,7 110 103 100 96,4 89,3 86,4 113 106 103 99,2 92,1 89,130,3 33,3 34,6 36,6 40,3 41,9 30,7 33,7 35,0 37,1 40,8 42,4 31,1 34,1 35,4 37,5 41,3 42,818,3 17,2 16,8 16,1 14,9 14,4 18,9 17,8 17,3 16,6 15,4 14,9 19,4 18,3 17,8 17,1 15,9 15,373,1 64,7 61,3 56,4 48,3 45,1 77,5 68,6 65,1 59,9 51,4 48,1 81,9 72,6 68,9 63,5 54,7 51,2
Ta
Dpev 86,4 76,7 72,9 67,2 58,0 54,5 91,1 80,9 76,9 71,1 61,6 57,9 95,8 85,3 81,1 75,0 65,2 -Qev 19,9 18,8 18,3 17,6 16,3 15,8 20,5 19,3 18,8 18,1 16,8 16,3 21,0 19,8 19,3 18,6 17,3 -Pat 31,4 34,5 35,9 37,9 41,7 43,3 31,8 34,9 36,3 38,4 42,2 43,8 32,2 35,3 36,7 38,8 42,6 -Pf 116 109 106 102 94,8 91,9 119 112 109 105 97,7 94,7 122 115 112 108 101 -
9 10 11Tev
045230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
120 113 110 106 97,7 94,3 124 117 113 109 101 97,1 127 120 117 112 103 99,933,9 37,2 38,7 41,0 45,1 46,8 34,3 37,7 39,1 41,4 45,5 47,3 34,7 38,1 39,5 41,8 46,0 47,720,7 19,5 19,0 18,2 16,8 16,2 21,3 20,1 19,5 18,7 17,3 16,7 21,9 20,6 20,1 19,3 17,8 17,269,1 61,2 58,0 53,3 45,5 42,4 73,2 64,8 61,4 56,4 48,2 45,0 77,3 68,5 64,9 59,7 51,0 47,6
Ta
Dpev 81,5 72,2 68,5 63,0 53,9 50,4 85,9 76,1 72,2 66,4 56,9 53,2 90,3 80,1 76,0 69,9 60,0 56,1Qev 22,5 21,2 20,6 19,8 18,3 17,7 23,1 21,7 21,2 20,3 18,8 18,2 23,7 22,3 21,7 20,8 19,3 18,7Pat 35,1 38,5 40,0 42,3 46,4 48,1 35,5 38,9 40,4 42,7 46,8 48,6 35,8 39,3 40,8 43,1 47,2 49,0Pf 131 123 120 115 106 103 134 126 123 118 109 106 137 129 126 121 112 108
9 10 11Tev
051230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
135 127 124 119 110 106 139 131 127 122 113 109 142 134 131 125 116 11237,7 41,4 43,0 45,5 49,9 51,8 38,2 41,9 43,4 45,9 50,3 52,2 38,6 42,3 43,9 46,3 50,7 52,623,2 21,9 21,3 20,4 18,9 18,2 23,9 22,5 21,9 21,0 19,4 18,7 24,5 23,1 22,5 21,6 19,9 19,273,7 65,5 62,1 57,1 48,8 45,5 78,0 69,3 65,7 60,4 51,6 48,1 82,4 73,1 69,4 63,7 54,4 50,7
Ta
Dpev 86,9 77,1 73,1 67,2 57,3 53,4 91,5 81,1 77,0 70,7 60,3 56,1 96,2 85,3 80,9 74,2 63,3 -Qev 25,2 23,7 23,1 22,2 20,5 19,8 25,9 24,3 23,7 22,7 21,0 20,3 26,5 25,0 24,3 23,3 21,5 -Pat 39,0 42,7 44,3 46,7 51,1 53,0 39,4 43,1 44,7 47,1 51,5 53,3 39,8 43,5 45,1 47,5 51,9 -Pf 146 138 134 129 119 115 150 141 138 132 122 118 154 145 141 135 125 -
9 10 11Tev
055230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
154 145 141 135 125 120 158 149 145 139 128 124 162 153 149 143 132 12743,5 47,8 49,6 52,5 57,7 59,9 44,0 48,3 50,2 53,1 58,3 60,5 44,5 48,9 50,7 53,6 58,8 61,026,5 24,9 24,2 23,2 21,5 20,7 27,2 25,6 24,9 23,9 22,1 21,3 28,0 26,3 25,6 24,5 22,7 21,986,8 76,8 72,9 66,9 57,0 53,1 91,8 81,3 77,1 70,7 60,3 56,2 97,0 85,9 81,4 74,7 63,6 59,3
Ta
Dpev 102 90,5 85,8 78,7 67,0 62,4 108 95,3 90,3 82,8 70,5 65,6 113 100 94,9 87,0 74,0 68,9Qev 28,7 27,0 26,3 25,2 23,3 22,4 29,5 27,7 27,0 25,9 23,9 23,0 30,2 28,4 27,7 26,5 24,4 23,6Pat 45,0 49,4 51,2 54,2 59,3 61,5 45,5 49,9 51,8 54,7 59,8 62,0 46,0 50,4 52,3 55,2 60,3 62,5Pf 167 157 153 146 135 130 171 161 157 150 138 134 175 165 161 154 142 137
9 10 11Tev
Ta [°C] - Air temperatureTev [°C] - Plant (side) cooling exchanger output water temperature
Pat [kW] - Total power inputQev [m³/h] - Plant (side) heat exchanger water flowDpev [kPa] - Plant (side) cooling exchanger pressure drop
Pf [kW] - Cooling capacity
'-' Conditions outside the operating rangeWaterflow and pressure drop on heat exchangers calculated with 5°C of delta TNOTE: Data on grey background: unit switched to non-silenced operation
17ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
LNCOOLING CAPACITY PERFORMANCE
NECS
061230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
168 158 154 147 135 130 173 162 158 151 139 - 178 167 162 155 142 -51,1 56,2 58,3 61,7 67,8 70,3 51,7 56,8 59,0 62,4 68,5 - 52,4 57,5 59,7 63,1 69,2 -29,0 27,2 26,4 25,3 23,2 22,4 29,8 27,9 27,2 26,0 23,9 - 30,6 28,7 27,9 26,7 24,5 -91,5 80,5 76,1 69,5 58,8 54,6 96,7 85,0 80,4 73,5 62,1 - 102 89,7 84,8 77,4 65,4 -
Ta
Dpev 107 94,5 89,3 81,5 68,9 - 113 99,3 93,8 85,7 72,3 - 119 104 98,5 89,9 75,9 -Qev 31,4 29,5 28,6 27,4 25,1 - 32,2 30,2 29,4 28,0 25,8 - 33,0 30,9 30,1 28,7 26,4 -Pat 53,0 58,2 60,4 63,8 69,9 - 53,6 58,8 61,1 64,5 70,6 - 54,3 59,5 61,7 65,2 71,3 -Pf 182 171 166 159 146 - 187 175 170 163 150 - 192 180 175 167 153 -
9 10 11Tev
Ta [°C] - Air temperatureTev [°C] - Plant (side) cooling exchanger output water temperature
Pat [kW] - Total power inputQev [m³/h] - Plant (side) heat exchanger water flowDpev [kPa] - Plant (side) cooling exchanger pressure drop
Pf [kW] - Cooling capacity
'-' Conditions outside the operating rangeWaterflow and pressure drop on heat exchangers calculated with 5°C of delta TNOTE: Data on grey background: unit switched to non-silenced operation
18ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
SLCOOLING CAPACITY PERFORMANCE
NECS
015230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
38,6 35,9 34,7 32,9 35,7 34,5 39,7 36,9 35,7 33,8 36,8 35,6 40,8 37,9 36,6 40,9 37,9 36,713,0 14,5 15,1 16,1 14,9 15,6 13,1 14,7 15,3 16,3 15,0 15,7 13,3 14,8 15,4 13,6 15,1 15,86,65 6,18 5,98 5,66 6,15 5,95 6,84 6,35 6,14 5,81 6,34 6,13 7,02 6,52 6,30 7,04 6,53 6,3259,5 51,3 48,0 43,1 50,9 47,6 62,9 54,2 50,7 45,4 54,1 50,6 66,4 57,2 53,4 66,6 57,4 53,7
Ta
Dpev 69,9 60,1 56,2 70,6 60,8 56,8 73,5 63,1 58,9 74,7 64,3 60,1 77,2 66,2 61,7 78,8 67,8 63,4Qev 7,21 6,69 6,46 7,24 6,72 6,50 7,39 6,85 6,62 7,45 6,91 6,68 7,57 7,01 6,77 7,65 7,10 6,86Pat 13,4 14,9 15,6 13,7 15,2 15,9 13,6 15,1 15,7 13,8 15,3 15,9 13,7 15,2 15,9 13,9 15,4 16,0Pf 41,9 38,8 37,5 42,1 39,0 37,7 42,9 39,8 38,4 43,2 40,1 38,8 43,9 40,7 39,3 44,4 41,2 39,8
9 10 11Tev
018230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
46,7 44,0 42,8 41,1 42,5 41,4 48,0 45,2 44,1 42,3 43,9 42,7 49,3 46,5 45,3 43,6 45,2 44,013,9 15,3 15,9 16,8 16,6 17,2 14,0 15,5 16,1 17,0 16,7 17,4 14,2 15,6 16,3 17,2 16,9 17,58,04 7,57 7,37 7,07 7,32 7,12 8,27 7,79 7,59 7,29 7,55 7,35 8,49 8,00 7,81 7,51 7,78 7,5856,2 49,7 47,2 43,4 46,5 44,0 59,4 52,6 50,0 46,2 49,5 46,9 62,6 55,6 52,9 48,9 52,6 49,9
Ta
Dpev 65,9 58,7 55,9 62,9 55,8 53,0 69,3 61,8 59,0 66,5 59,1 56,2 72,7 65,0 62,1 70,1 62,5 59,5Qev 8,71 8,22 8,02 8,51 8,02 7,81 8,93 8,44 8,24 8,75 8,25 8,05 9,15 8,65 8,46 8,98 8,48 8,28Pat 14,4 15,8 16,4 15,5 17,0 17,6 14,5 16,0 16,6 15,6 17,1 17,7 14,7 16,2 16,8 15,7 17,2 17,8Pf 50,6 47,7 46,6 49,4 46,5 45,4 51,8 49,0 47,8 50,8 47,9 46,7 53,1 50,2 49,1 52,1 49,2 48,1
9 10 11Tev
020230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
54,1 50,5 48,9 46,5 49,6 48,0 55,6 51,9 50,3 47,8 51,2 49,5 57,2 53,4 51,7 56,6 52,7 51,016,3 18,1 18,9 20,1 19,1 19,9 16,5 18,3 19,1 20,3 19,2 20,0 16,6 18,5 19,3 17,4 19,3 20,19,31 8,69 8,42 8,00 8,54 8,26 9,58 8,94 8,66 8,23 8,81 8,52 9,84 9,19 8,90 9,75 9,08 8,7953,3 46,4 43,6 39,3 44,8 41,9 56,4 49,1 46,1 41,6 47,7 44,7 59,5 51,9 48,7 58,4 50,6 47,5
Ta
Dpev 62,8 54,7 51,4 61,9 53,7 50,4 66,0 57,6 54,1 65,4 56,9 53,4 69,4 60,5 56,9 69,1 60,1 56,5Qev 10,1 9,43 9,14 10,0 9,35 9,05 10,4 9,68 9,38 10,3 9,62 9,32 10,6 9,92 9,62 10,6 9,89 9,58Pat 16,8 18,7 19,5 17,6 19,5 20,3 17,0 18,9 19,7 17,7 19,6 20,4 17,2 19,1 19,8 17,8 19,7 20,5Pf 58,7 54,8 53,1 58,3 54,3 52,6 60,2 56,2 54,5 59,9 55,8 54,1 61,7 57,6 55,8 61,5 57,4 55,6
9 10 11Tev
025230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
61,9 58,1 56,5 54,0 55,7 54,0 63,7 59,8 58,1 55,5 57,4 55,6 65,4 61,4 59,7 56,9 59,1 57,318,4 20,3 21,1 22,4 22,2 23,1 18,5 20,5 21,3 22,6 22,4 23,2 18,7 20,7 21,5 22,8 22,5 23,410,7 10,0 9,73 9,29 9,59 9,30 11,0 10,3 10,0 9,55 9,89 9,58 11,3 10,6 10,3 9,80 10,2 9,8648,3 42,6 40,3 36,7 39,1 36,8 51,1 45,1 42,6 38,8 41,6 39,0 54,0 47,6 44,9 40,9 44,1 41,4
Ta
Dpev 57,0 50,2 47,3 43,0 46,6 43,7 60,1 52,8 49,8 45,1 49,3 46,2 63,2 55,4 52,2 60,0 51,9 48,6Qev 11,6 10,9 10,5 10,1 10,5 10,1 11,9 11,1 10,8 10,3 10,8 10,4 12,2 11,4 11,1 11,9 11,0 10,7Pat 18,9 20,8 21,7 22,9 22,6 23,5 19,1 21,0 21,8 23,1 22,7 23,6 19,2 21,1 22,0 20,7 22,8 23,6Pf 67,2 63,0 61,2 58,4 60,8 58,9 69,0 64,6 62,8 59,8 62,5 60,5 70,7 66,2 64,3 68,9 64,1 62,0
9 10 11Tev
030230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
78,8 73,6 71,4 68,0 73,1 70,9 80,9 75,7 73,4 69,9 75,4 73,1 83,0 77,7 75,5 82,9 77,6 75,324,7 27,5 28,6 30,5 28,5 29,7 25,0 27,8 29,0 30,9 28,7 29,9 25,3 28,1 29,3 26,1 28,9 30,113,6 12,7 12,3 11,7 12,6 12,2 13,9 13,0 12,6 12,0 13,0 12,6 14,3 13,4 13,0 14,3 13,4 13,061,3 53,5 50,4 45,6 52,8 49,7 64,7 56,6 53,3 48,4 56,2 52,9 68,2 59,7 56,3 68,0 59,6 56,1
Ta
Dpev 71,8 63,0 59,4 71,9 63,1 59,6 75,4 66,3 62,6 75,9 66,8 63,1 79,1 69,7 65,9 80,0 70,6 66,8Qev 14,7 13,7 13,3 14,7 13,8 13,4 15,0 14,1 13,7 15,1 14,2 13,8 15,4 14,5 14,1 15,5 14,5 14,1Pat 25,6 28,4 29,7 26,3 29,1 30,3 25,9 28,8 30,0 26,5 29,3 30,5 26,2 29,1 30,3 26,7 29,5 30,7Pf 85,2 79,8 77,5 85,3 79,9 77,6 87,3 81,8 79,5 87,6 82,1 79,8 89,4 83,9 81,6 89,9 84,4 82,1
9 10 11Tev
Ta [°C] - Air temperatureTev [°C] - Plant (side) cooling exchanger output water temperature
Pat [kW] - Total power inputQev [m³/h] - Plant (side) heat exchanger water flowDpev [kPa] - Plant (side) cooling exchanger pressure drop
Pf [kW] - Cooling capacity
'-' Conditions outside the operating rangeWaterflow and pressure drop on heat exchangers calculated with 5°C of delta TNOTE: Data on grey background: unit switched to non-silenced operation
19ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
SLCOOLING CAPACITY PERFORMANCE
NECS
035230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
94,4 88,8 86,5 82,9 82,8 80,3 97,0 91,4 89,0 85,4 85,4 82,8 99,7 94,0 91,6 87,9 88,0 85,427,5 30,2 31,4 33,3 33,3 34,7 27,8 30,6 31,7 33,6 33,6 35,0 28,1 30,9 32,1 34,0 33,9 35,316,2 15,3 14,9 14,3 14,2 13,8 16,7 15,7 15,3 14,7 14,7 14,3 17,2 16,2 15,8 15,1 15,1 14,768,7 60,9 57,8 53,1 52,9 49,7 72,7 64,5 61,2 56,3 56,3 53,0 76,8 68,2 64,8 59,6 59,8 56,3
Ta
Dpev 81,0 72,0 68,4 63,1 63,4 59,8 85,2 75,9 72,2 66,6 67,2 63,4 89,6 79,9 76,0 80,7 71,1 67,2Qev 17,6 16,6 16,2 15,6 15,6 15,2 18,1 17,1 16,6 16,0 16,1 15,6 18,5 17,5 17,1 17,6 16,5 16,1Pat 28,4 31,2 32,4 34,4 34,2 35,6 28,7 31,6 32,8 34,7 34,5 35,9 29,0 31,9 33,1 31,6 34,8 36,1Pf 102 96,5 94,1 90,4 90,6 88,0 105 99,1 96,6 92,8 93,2 90,6 108 102 99,1 102 95,8 93,2
9 10 11Tev
041230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
107 101 98,0 94,0 94,5 91,7 110 104 101 96,8 97,5 94,7 113 107 104 99,7 101 97,730,6 33,6 34,9 36,9 36,7 38,1 31,0 34,0 35,3 37,3 37,0 38,4 31,4 34,4 35,7 37,8 37,4 38,818,4 17,3 16,9 16,2 16,3 15,8 19,0 17,8 17,4 16,7 16,8 16,3 19,5 18,4 17,9 17,2 17,3 16,873,8 65,3 61,9 56,9 57,5 54,2 78,1 69,2 65,7 60,4 61,3 57,8 82,6 73,2 69,5 64,1 65,1 61,5
Ta
Dpev 87,2 77,4 73,5 67,8 69,2 65,4 91,9 81,7 77,7 71,7 73,3 69,4 96,7 86,0 81,9 75,7 77,6 73,5Qev 20,0 18,9 18,4 17,7 17,8 17,3 20,6 19,4 18,9 18,2 18,4 17,9 21,1 19,9 19,4 18,7 18,9 18,4Pat 31,7 34,8 36,1 38,2 37,7 39,1 32,1 35,2 36,5 38,6 38,0 39,5 32,4 35,6 36,9 39,0 38,3 39,8Pf 116 110 107 103 104 101 119 112 110 105 107 104 122 115 113 108 110 107
9 10 11Tev
045230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
118 111 108 103 105 101 121 114 111 106 108 105 125 117 114 119 111 10835,4 38,9 40,4 42,7 42,0 43,6 35,9 39,4 40,9 43,2 42,4 44,0 36,3 39,8 41,3 38,9 42,7 44,320,3 19,1 18,6 17,8 18,0 17,5 20,9 19,6 19,1 18,3 18,6 18,0 21,5 20,2 19,6 20,5 19,1 18,566,5 58,6 55,4 50,7 52,2 49,1 70,3 62,0 58,6 53,7 55,5 52,2 74,2 65,4 62,0 67,6 58,8 55,3
Ta
Dpev 78,2 69,0 65,3 71,5 62,3 58,6 82,3 72,7 68,8 75,5 65,8 62,0 86,5 76,4 72,3 79,6 69,5 65,5Qev 22,1 20,7 20,2 21,1 19,7 19,1 22,6 21,2 20,7 21,7 20,2 19,6 23,2 21,8 21,2 22,2 20,8 20,2Pat 36,7 40,3 41,8 39,3 43,1 44,7 37,2 40,7 42,2 39,6 43,4 45,1 37,6 41,1 42,7 40,0 43,8 45,4Pf 128 120 117 122 114 111 131 123 120 126 117 114 135 126 123 129 121 117
9 10 11Tev
051230 32 35 40 4225 25 30 32 35 40 42 25 30 32 35 40 42
6 7 8Tev
PfPatQevDpev
131 123 120 114 118 114 135 127 123 117 121 117 139 130 126 134 125 12139,4 43,3 45,0 47,6 46,0 47,7 39,9 43,8 45,5 48,1 46,4 48,1 40,3 44,3 45,9 42,6 46,7 48,522,6 21,2 20,6 19,7 20,2 19,6 23,2 21,8 21,2 20,2 20,8 20,2 23,9 22,4 21,7 23,0 21,4 20,869,9 61,5 58,1 53,0 56,1 52,7 73,9 64,9 61,3 56,0 59,5 55,9 77,9 68,5 64,7 72,4 62,9 59,1
Ta
Dpev 82,1 72,1 68,0 76,5 66,5 62,5 86,3 75,7 71,5 80,8 70,2 65,9 90,6 79,5 75,0 85,1 73,9 69,4Qev 24,5 22,9 22,3 23,6 22,0 21,4 25,1 23,5 22,9 24,3 22,6 21,9 25,7 24,1 23,4 24,9 23,2 22,5Pat 40,8 44,7 46,4 42,9 47,0 48,8 41,2 45,2 46,8 43,3 47,4 49,1 41,7 45,6 47,2 43,6 47,7 49,4Pf 142 133 129 137 128 124 146 137 133 141 131 127 149 140 136 145 135 131
9 10 11Tev
Ta [°C] - Air temperatureTev [°C] - Plant (side) cooling exchanger output water temperature
Pat [kW] - Total power inputQev [m³/h] - Plant (side) heat exchanger water flowDpev [kPa] - Plant (side) cooling exchanger pressure drop
Pf [kW] - Cooling capacity
'-' Conditions outside the operating rangeWaterflow and pressure drop on heat exchangers calculated with 5°C of delta TNOTE: Data on grey background: unit switched to non-silenced operation
20ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
BDESUPERHEATER CAPACITY PERFOR.
NECS - D
0152
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
44,9 44,9 44,9 42,3 42,3 42,3 41,2 41,2 41,2 39,5 39,5 39,5 36,4 36,4 36,4 35,1 35,1 35,1
11,3 11,3 11,3 12,5 12,5 12,5 13,1 13,1 13,1 13,9 13,9 13,9 15,4 15,4 15,4 16,1 16,1 16,1
10,3 9,49 8,98 11,5 10,9 10,4 12,1 11,6 11,0 12,9 12,6 11,9 14,4 14,4 13,7 15,1 15,2 14,5
1,78 1,65 1,56 1,99 1,90 1,80 2,09 2,01 1,91 2,23 2,18 2,07 2,50 2,50 2,38 2,61 2,64 2,52
5,58 4,79 4,30 7,03 6,36 5,73 7,70 7,12 6,42 8,82 8,41 7,60 11,0 11,1 10,0 12,0 12,3 11,2
Tde
Ta
0182
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
52,5 52,5 52,5 49,7 49,7 49,7 48,5 48,5 48,5 46,8 46,8 46,8 43,8 43,8 43,8 42,5 42,5 42,5
12,4 12,4 12,4 13,7 13,7 13,7 14,2 14,2 14,2 15,1 15,1 15,1 16,6 16,6 16,6 17,2 17,2 17,2
11,4 10,5 9,97 12,7 12,1 11,4 13,2 12,7 12,0 14,1 13,7 13,0 15,6 15,6 14,8 16,2 16,4 15,6
1,97 1,83 1,73 2,20 2,09 1,98 2,29 2,20 2,09 2,44 2,38 2,26 2,70 2,70 2,57 2,81 2,84 2,70
6,88 5,91 5,31 8,53 7,72 6,96 9,28 8,58 7,74 10,5 10,0 9,05 12,9 12,9 11,7 13,9 14,2 12,9
Tde
Ta
0202
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
59,9 59,9 59,9 56,3 56,3 56,3 54,8 54,8 54,8 52,4 52,4 52,4 48,0 48,0 48,0 46,1 46,1 46,1
14,9 14,9 14,9 16,6 16,6 16,6 17,3 17,3 17,3 18,4 18,4 18,4 20,4 20,4 20,4 21,3 21,3 21,3
13,9 12,9 12,2 15,6 14,8 14,0 16,3 15,7 14,8 17,4 17,0 16,1 19,4 19,4 18,4 20,3 20,5 19,4
2,41 2,24 2,12 2,70 2,57 2,44 2,82 2,72 2,58 3,02 2,95 2,80 3,36 3,37 3,20 3,51 3,55 3,38
10,3 8,83 7,93 12,9 11,7 10,5 14,1 13,0 11,7 16,1 15,3 13,9 20,0 20,0 18,1 21,8 22,3 20,2
Tde
Ta
0252
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
67,4 67,4 67,4 63,5 63,5 63,5 61,8 61,8 61,8 59,2 59,2 59,2 54,4 54,4 54,4 52,3 52,3 52,3
17,0 17,0 17,0 18,8 18,8 18,8 19,6 19,6 19,6 20,8 20,8 20,8 23,0 23,0 23,0 23,9 23,9 23,9
16,0 14,8 14,0 17,8 16,9 16,1 18,6 17,9 16,9 19,8 19,3 18,3 22,0 22,0 20,9 22,9 23,1 22,0
2,78 2,57 2,44 3,09 2,94 2,79 3,22 3,10 2,94 3,43 3,35 3,19 3,81 3,82 3,63 3,97 4,02 3,82
13,6 11,7 10,5 16,9 15,3 13,8 18,4 17,0 15,3 20,8 19,9 17,9 25,7 25,7 23,3 27,8 28,5 25,8
Tde
Ta
0302
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
89,0 89,0 89,0 84,2 84,2 84,2 82,1 82,1 82,1 78,9 78,9 78,9 73,0 73,0 73,0 70,5 70,5 70,5
22,0 22,0 22,0 24,3 24,3 24,3 25,3 25,3 25,3 26,9 26,9 26,9 29,9 29,9 29,9 31,1 31,1 31,1
20,5 18,9 17,9 22,8 21,6 20,5 23,8 22,9 21,7 25,4 24,8 23,5 28,4 28,4 27,0 29,6 29,9 28,5
3,54 3,28 3,11 3,95 3,76 3,56 4,12 3,96 3,76 4,40 4,30 4,09 4,91 4,92 4,68 5,13 5,19 4,94
10,9 9,38 8,43 13,6 12,3 11,1 14,8 13,7 12,3 16,9 16,1 14,5 21,0 21,1 19,1 22,9 23,5 21,3
Tde
Ta
0352
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
102 102 102 96,2 96,2 96,2 93,8 93,8 93,8 90,1 90,1 90,1 83,5 83,5 83,5 80,7 80,7 80,7
25,3 25,3 25,3 27,9 27,9 27,9 29,0 29,0 29,0 30,8 30,8 30,8 34,1 34,1 34,1 35,5 35,5 35,5
23,8 22,0 20,9 26,4 25,1 23,8 27,5 26,4 25,1 29,3 28,6 27,1 32,6 32,6 30,9 34,0 34,3 32,6
4,13 3,82 3,62 4,58 4,35 4,13 4,77 4,59 4,36 5,08 4,96 4,72 5,64 5,65 5,38 5,88 5,95 5,67
14,8 12,7 11,4 18,2 16,5 14,9 19,8 18,3 16,5 22,5 21,4 19,4 27,7 27,8 25,2 30,1 30,8 28,0
Tde
Ta
Ta [°C] - Source (side) cooling exchanger air temperaturePf (kW) - Cooling capacity (Plant side cooling exchanger water in/out 12/7 °C)Pat (kW) - Total power inputPtde (kW) - Heat recovery thermal capacityQde (m3/h) - Plant (side) cooling exchanger recovery water flowDpde (kPa) - Plant side heating exchanger recovery pressure drop'-' - Conditions outside the operating range
NOTE: Data on grey background: unit switched to non-silenced operationWaterflow and pressure drop on heat exchangers calculated with 5°C of delta T
Tde (°C) - Plant (side) heat exchanger recovery output water temperature
21ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
BDESUPERHEATER CAPACITY PERFOR.
NECS - D
0412
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
114 114 114 108 108 108 105 105 105 101 101 101 93,2 93,2 93,2 90,1 90,1 90,1
29,0 29,0 29,0 31,9 31,9 31,9 33,1 33,1 33,1 35,1 35,1 35,1 38,7 38,7 38,7 40,2 40,2 40,2
27,5 25,4 24,0 30,4 28,8 27,3 31,6 30,3 28,8 33,6 32,7 31,1 37,2 37,2 35,3 38,7 39,1 37,1
4,76 4,41 4,17 5,26 5,00 4,75 5,47 5,26 5,00 5,82 5,68 5,40 6,44 6,45 6,14 6,70 6,78 6,46
19,7 16,9 15,2 24,1 21,8 19,6 26,1 24,1 21,8 29,5 28,1 25,4 36,1 36,2 32,8 39,1 40,0 36,3
Tde
Ta
0452
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
132 132 132 124 124 124 121 121 121 117 117 117 108 108 108 105 105 105
31,8 31,8 31,8 34,9 34,9 34,9 36,2 36,2 36,2 38,4 38,4 38,4 42,1 42,1 42,1 43,8 43,8 43,8
29,8 27,6 26,1 32,9 31,3 29,6 34,2 32,9 31,2 36,4 35,4 33,6 40,1 40,1 38,1 41,8 42,2 40,1
5,16 4,79 4,53 5,70 5,42 5,15 5,93 5,70 5,42 6,30 6,15 5,84 6,95 6,96 6,63 7,23 7,32 6,97
16,4 14,0 12,6 19,9 18,0 16,2 21,6 19,9 18,0 24,3 23,2 20,9 29,6 29,7 26,9 32,1 32,8 29,8
Tde
Ta
0512
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
148 148 148 140 140 140 137 137 137 131 131 131 122 122 122 118 118 118
35,2 35,2 35,2 38,6 38,6 38,6 40,0 40,0 40,0 42,3 42,3 42,3 46,4 46,4 46,4 48,1 48,1 48,1
32,7 30,2 28,6 36,1 34,3 32,4 37,5 36,0 34,1 39,8 38,8 36,8 43,9 43,9 41,7 45,6 46,1 43,8
5,66 5,25 4,97 6,24 5,94 5,64 6,50 6,25 5,93 6,89 6,73 6,39 7,60 7,61 7,24 7,90 7,99 7,61
19,6 16,9 15,1 23,9 21,6 19,5 25,9 23,9 21,6 29,1 27,8 25,1 35,4 35,5 32,2 38,2 39,1 35,5
Tde
Ta
0552
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
170 170 170 160 160 160 156 156 156 150 150 150 140 140 140 135 135 135
40,2 40,2 40,2 44,2 44,2 44,2 45,8 45,8 45,8 48,5 48,5 48,5 53,3 53,3 53,3 55,3 55,3 55,3
37,7 34,9 33,0 41,7 39,6 37,5 43,3 41,6 39,4 46,0 44,9 42,6 50,8 50,8 48,2 52,8 53,3 50,7
6,54 6,06 5,74 7,22 6,87 6,52 7,51 7,22 6,85 7,97 7,78 7,39 8,79 8,81 8,38 9,14 9,25 8,80
17,6 15,1 13,6 21,5 19,4 17,5 23,2 21,5 19,4 26,2 24,9 22,5 31,8 31,9 28,9 34,4 35,2 31,9
Tde
Ta
0612
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
187 187 187 176 176 176 171 171 171 165 165 165 152 152 152 147 147 147
47,0 47,0 47,0 51,6 51,6 51,6 53,6 53,6 53,6 56,7 56,7 56,7 62,2 62,2 62,2 64,6 64,6 64,6
44,5 41,1 38,9 49,1 46,6 44,2 51,1 49,0 46,5 54,2 52,8 50,1 59,7 59,7 56,7 62,1 62,7 59,6
7,70 7,13 6,76 8,50 8,09 7,68 8,84 8,50 8,07 9,38 9,16 8,71 10,3 10,4 9,86 10,8 10,9 10,4
24,4 21,0 18,8 29,8 27,0 24,3 32,2 29,8 26,9 36,3 34,6 31,2 44,1 44,2 40,1 47,6 48,7 44,2
Tde
Ta
Ta [°C] - Source (side) cooling exchanger air temperaturePf (kW) - Cooling capacity (Plant side cooling exchanger water in/out 12/7 °C)Pat (kW) - Total power inputPtde (kW) - Heat recovery thermal capacityQde (m3/h) - Plant (side) cooling exchanger recovery water flowDpde (kPa) - Plant side heating exchanger recovery pressure drop'-' - Conditions outside the operating range
NOTE: Data on grey background: unit switched to non-silenced operationWaterflow and pressure drop on heat exchangers calculated with 5°C of delta T
Tde (°C) - Plant (side) heat exchanger recovery output water temperature
22ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
HTDESUPERHEATER CAPACITY PERFOR.
NECS - D
0152
25 30 35 40 43 46
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
46,3 46,3 46,3 43,9 43,9 43,9 41,2 41,2 41,2 38,2 38,2 38,2 36,3 36,3 36,3 34,3 34,3 34,3
10,6 10,6 10,6 11,8 11,8 11,8 13,1 13,1 13,1 14,5 14,5 14,5 15,5 15,5 15,5 16,5 16,5 16,5
9,58 8,86 8,38 10,8 10,2 9,68 12,1 11,8 11,2 13,5 13,5 12,9 14,5 14,7 14,0 15,5 16,0 15,2
1,66 1,54 1,46 1,86 1,77 1,68 2,09 2,04 1,94 2,35 2,35 2,24 2,51 2,55 2,43 2,68 2,77 2,64
4,86 4,17 3,75 6,13 5,55 5,00 7,73 7,37 6,66 9,72 9,75 8,83 11,1 11,5 10,4 12,7 13,5 12,3
Tde
Ta
0182
25 30 35 40 43 46
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
54,0 54,0 54,0 51,3 51,3 51,3 48,5 48,5 48,5 45,5 45,5 45,5 43,7 43,7 43,7 41,8 41,8 41,8
12,2 12,2 12,2 13,4 13,4 13,4 14,8 14,8 14,8 16,2 16,2 16,2 17,1 17,1 17,1 18,1 18,1 18,1
10,7 9,90 9,36 11,9 11,3 10,7 13,3 12,9 12,3 14,7 14,7 14,0 15,6 15,8 15,1 16,6 17,1 16,2
1,85 1,72 1,63 2,07 1,97 1,87 2,30 2,24 2,13 2,55 2,55 2,43 2,70 2,75 2,62 2,87 2,96 2,82
6,07 5,21 4,68 7,54 6,83 6,15 9,32 8,89 8,03 11,5 11,5 10,4 12,9 13,4 12,1 14,5 15,5 14,1
Tde
Ta
0202
25 30 35 40 43 46
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
63,7 63,7 63,7 60,6 60,6 60,6 57,0 57,0 57,0 53,1 53,1 53,1 50,5 50,5 50,5 47,8 47,8 47,8
13,7 13,7 13,7 15,1 15,1 15,1 16,8 16,8 16,8 18,6 18,6 18,6 19,8 19,8 19,8 21,0 21,0 21,0
12,2 11,2 10,6 13,6 12,9 12,3 15,3 14,9 14,1 17,1 17,1 16,2 18,3 18,5 17,6 19,5 20,1 19,1
2,11 1,95 1,85 2,36 2,25 2,13 2,65 2,58 2,46 2,96 2,97 2,82 3,17 3,22 3,06 3,38 3,49 3,32
7,83 6,72 6,04 9,84 8,91 8,03 12,4 11,8 10,7 15,5 15,5 14,1 17,7 18,3 16,6 20,2 21,5 19,5
Tde
Ta
0252
25 30 35 40 43 46
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
71,2 71,2 71,2 67,8 67,8 67,8 63,9 63,9 63,9 59,6 59,6 59,6 56,8 56,8 56,8 53,8 53,8 53,8
16,3 16,3 16,3 17,9 17,9 17,9 19,7 19,7 19,7 21,6 21,6 21,6 22,9 22,9 22,9 24,3 24,3 24,3
14,3 13,2 12,5 15,9 15,1 14,3 17,7 17,2 16,3 19,6 19,6 18,7 20,9 21,2 20,2 22,3 22,9 21,8
2,47 2,29 2,17 2,75 2,62 2,48 3,06 2,99 2,84 3,40 3,41 3,24 3,62 3,68 3,51 3,86 3,98 3,79
10,8 9,28 8,33 13,4 12,1 10,9 16,5 15,8 14,2 20,5 20,5 18,6 23,2 24,0 21,8 26,3 28,0 25,4
Tde
Ta
0302
25 30 35 40 43 46
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
92,9 92,9 92,9 88,5 88,5 88,5 83,6 83,6 83,6 78,2 78,2 78,2 74,7 74,7 74,7 70,9 70,9 70,9
20,6 20,6 20,6 22,7 22,7 22,7 25,1 25,1 25,1 27,7 27,7 27,7 29,5 29,5 29,5 31,4 31,4 31,4
18,6 17,2 16,3 20,7 19,6 18,6 23,1 22,5 21,3 25,7 25,7 24,5 27,5 27,9 26,6 29,4 30,3 28,8
3,22 2,99 2,83 3,58 3,41 3,23 3,99 3,90 3,71 4,46 4,47 4,25 4,77 4,84 4,61 5,09 5,25 5,01
9,05 7,77 6,98 11,2 10,1 9,11 13,9 13,2 12,0 17,3 17,4 15,7 19,8 20,4 18,5 22,6 24,0 21,8
Tde
Ta
0352
25 30 35 40 43 46
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
106 106 106 101 101 101 94,9 94,9 94,9 88,6 88,6 88,6 84,6 84,6 84,6 80,5 80,5 80,5
24,6 24,6 24,6 26,9 26,9 26,9 29,6 29,6 29,6 32,6 32,6 32,6 34,5 34,5 34,5 36,6 36,6 36,6
22,1 20,4 19,3 24,4 23,2 22,0 27,1 26,4 25,0 30,1 30,1 28,6 32,0 32,5 30,9 34,1 35,1 33,4
3,82 3,54 3,35 4,23 4,02 3,82 4,69 4,58 4,35 5,21 5,21 4,96 5,54 5,64 5,37 5,90 6,09 5,80
12,7 10,9 9,80 15,6 14,1 12,7 19,1 18,2 16,5 23,6 23,7 21,4 26,8 27,7 25,1 30,4 32,3 29,3
Tde
Ta
Ta [°C] - Source (side) cooling exchanger air temperaturePf (kW) - Cooling capacity (Plant side cooling exchanger water in/out 12/7 °C)Pat (kW) - Total power inputPtde (kW) - Heat recovery thermal capacityQde (m3/h) - Plant (side) cooling exchanger recovery water flowDpde (kPa) - Plant side heating exchanger recovery pressure drop'-' - Conditions outside the operating range
NOTE: Data on grey background: unit switched to non-silenced operationWaterflow and pressure drop on heat exchangers calculated with 5°C of delta T
Tde (°C) - Plant (side) heat exchanger recovery output water temperature
23ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
HTDESUPERHEATER CAPACITY PERFOR.
NECS - D
0412
25 30 35 40 43 46
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
121 121 121 115 115 115 108 108 108 101 101 101 96,8 96,8 96,8 92,2 92,2 92,2
27,2 27,2 27,2 29,7 29,7 29,7 32,6 32,6 32,6 35,8 35,8 35,8 37,9 37,9 37,9 40,1 40,1 40,1
24,7 22,9 21,6 27,2 25,9 24,5 30,1 29,3 27,8 33,3 33,3 31,6 35,4 35,9 34,2 37,6 38,8 36,9
4,28 3,97 3,76 4,71 4,49 4,26 5,21 5,09 4,84 5,77 5,78 5,50 6,13 6,23 5,94 6,52 6,72 6,41
16,0 13,7 12,3 19,4 17,5 15,8 23,6 22,5 20,4 29,0 29,1 26,3 32,7 33,8 30,7 37,0 39,4 35,8
Tde
Ta
0452
25 30 35 40 43 46
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
135 135 135 128 128 128 120 120 120 112 112 112 107 107 107 102 102 102
31,1 31,1 31,1 34,0 34,0 34,0 37,3 37,3 37,3 41,0 41,0 41,0 43,3 43,3 43,3 45,8 45,8 45,8
28,6 26,4 25,0 31,5 29,9 28,4 34,8 33,9 32,2 38,5 38,5 36,5 40,8 41,4 39,4 43,3 44,6 42,5
4,95 4,59 4,35 5,46 5,19 4,93 6,03 5,89 5,60 6,66 6,67 6,35 7,07 7,19 6,85 7,50 7,74 7,38
15,0 12,9 11,6 18,3 16,5 14,9 22,3 21,2 19,2 27,2 27,3 24,7 30,7 31,7 28,7 34,5 36,7 33,4
Tde
Ta
0512
25 30 35 40 43 46
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
151 151 151 143 143 143 135 135 135 126 126 126 120 120 120 114 114 114
34,0 34,0 34,0 37,2 37,2 37,2 40,8 40,8 40,8 44,8 44,8 44,8 47,4 47,4 47,4 50,1 50,1 50,1
31,5 29,1 27,5 34,7 33,0 31,2 38,3 37,4 35,5 42,3 42,3 40,2 44,9 45,6 43,3 47,6 49,0 46,6
5,45 5,05 4,78 6,01 5,72 5,43 6,64 6,48 6,16 7,33 7,34 6,99 7,78 7,90 7,53 8,24 8,51 8,11
18,2 15,6 14,0 22,2 20,1 18,1 27,0 25,8 23,3 32,9 33,0 29,9 37,1 38,3 34,7 41,7 44,3 40,3
Tde
Ta
Ta [°C] - Source (side) cooling exchanger air temperaturePf (kW) - Cooling capacity (Plant side cooling exchanger water in/out 12/7 °C)Pat (kW) - Total power inputPtde (kW) - Heat recovery thermal capacityQde (m3/h) - Plant (side) cooling exchanger recovery water flowDpde (kPa) - Plant side heating exchanger recovery pressure drop'-' - Conditions outside the operating range
NOTE: Data on grey background: unit switched to non-silenced operationWaterflow and pressure drop on heat exchangers calculated with 5°C of delta T
Tde (°C) - Plant (side) heat exchanger recovery output water temperature
24ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
LNDESUPERHEATER CAPACITY PERFOR.
NECS - D
0152
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
43,2 43,2 43,2 40,5 40,5 40,5 39,3 39,3 39,3 37,5 37,5 37,5 34,2 34,2 34,2 - - -
11,7 11,7 11,7 13,1 13,1 13,1 13,6 13,6 13,6 14,6 14,6 14,6 16,2 16,2 16,2 - - -
11,1 10,3 9,70 12,4 11,8 11,2 13,0 12,5 11,8 13,9 13,6 12,9 15,5 15,5 14,7 - - -
1,92 1,78 1,69 2,15 2,05 1,94 2,25 2,17 2,06 2,41 2,35 2,24 2,69 2,69 2,56 - - -
6,52 5,60 5,02 8,20 7,42 6,68 8,97 8,29 7,48 10,3 9,78 8,84 12,8 12,8 11,6 - - -
Tde
Ta
0182
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
50,3 50,3 50,3 47,4 47,4 47,4 46,2 46,2 46,2 44,4 44,4 44,4 41,3 41,3 41,3 - - -
13,0 13,0 13,0 14,4 14,4 14,4 15,0 15,0 15,0 15,9 15,9 15,9 17,5 17,5 17,5 - - -
12,4 11,5 10,9 13,8 13,1 12,4 14,4 13,8 13,1 15,3 14,9 14,1 16,8 16,8 16,0 - - -
2,15 1,99 1,89 2,39 2,27 2,16 2,49 2,39 2,27 2,64 2,58 2,45 2,91 2,92 2,78 - - -
8,16 7,01 6,29 10,1 9,12 8,21 10,9 10,1 9,11 12,3 11,8 10,6 15,0 15,1 13,6 - - -
Tde
Ta
0202
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
60,1 60,1 60,1 56,5 56,5 56,5 55,0 55,0 55,0 52,6 52,6 52,6 48,2 48,2 48,2 46,3 46,3 46,3
14,8 14,8 14,8 16,5 16,5 16,5 17,2 17,2 17,2 18,3 18,3 18,3 20,3 20,3 20,3 21,1 21,1 21,1
13,9 12,8 12,1 15,5 14,7 14,0 16,2 15,6 14,8 17,3 16,9 16,0 19,3 19,3 18,4 20,2 20,4 19,4
2,40 2,22 2,11 2,69 2,56 2,43 2,81 2,70 2,57 3,00 2,93 2,79 3,35 3,35 3,19 3,49 3,53 3,36
10,2 8,74 7,85 12,8 11,6 10,4 14,0 12,9 11,6 15,9 15,2 13,7 19,8 19,8 18,0 21,5 22,0 20,0
Tde
Ta
0252
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
67,9 67,9 67,9 64,1 64,1 64,1 62,4 62,4 62,4 59,8 59,8 59,8 55,0 55,0 55,0 53,0 53,0 53,0
16,8 16,8 16,8 18,6 18,6 18,6 19,3 19,3 19,3 20,5 20,5 20,5 22,7 22,7 22,7 23,6 23,6 23,6
15,8 14,6 13,8 17,6 16,7 15,8 18,4 17,6 16,7 19,6 19,1 18,1 21,7 21,7 20,6 22,6 22,9 21,7
2,74 2,54 2,40 3,05 2,90 2,75 3,18 3,06 2,90 3,39 3,31 3,14 3,76 3,77 3,58 3,92 3,97 3,78
13,2 11,4 10,2 16,4 14,8 13,4 17,9 16,5 14,9 20,3 19,3 17,5 25,0 25,1 22,7 27,1 27,8 25,2
Tde
Ta
0302
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
87,5 87,5 87,5 82,5 82,5 82,5 80,3 80,3 80,3 77,0 77,0 77,0 71,0 71,0 71,0 - - -
22,5 22,5 22,5 24,9 24,9 24,9 26,0 26,0 26,0 27,6 27,6 27,6 30,7 30,7 30,7 - - -
21,2 19,6 18,6 23,6 22,4 21,3 24,7 23,7 22,5 26,4 25,7 24,4 29,4 29,4 27,9 - - -
3,67 3,40 3,22 4,09 3,89 3,70 4,28 4,11 3,90 4,57 4,46 4,24 5,09 5,10 4,85 - - -
11,7 10,1 9,05 14,6 13,2 11,9 15,9 14,7 13,3 18,2 17,3 15,6 22,6 22,7 20,5 - - -
Tde
Ta
0352
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
99,7 99,7 99,7 93,9 93,9 93,9 91,4 91,4 91,4 87,6 87,6 87,6 80,9 80,9 80,9 78,1 78,1 78,1
26,8 26,8 26,8 29,5 29,5 29,5 30,7 30,7 30,7 32,5 32,5 32,5 35,9 35,9 35,9 37,3 37,3 37,3
24,8 23,0 21,7 27,5 26,2 24,8 28,7 27,6 26,1 30,5 29,8 28,3 33,9 33,9 32,2 35,3 35,7 33,9
4,30 3,98 3,78 4,77 4,54 4,31 4,97 4,78 4,54 5,29 5,17 4,91 5,87 5,88 5,59 6,11 6,19 5,89
16,1 13,8 12,4 19,8 17,9 16,1 21,5 19,9 17,9 24,4 23,3 21,0 30,0 30,1 27,3 32,6 33,3 30,2
Tde
Ta
Ta [°C] - Source (side) cooling exchanger air temperaturePf (kW) - Cooling capacity (Plant side cooling exchanger water in/out 12/7 °C)Pat (kW) - Total power inputPtde (kW) - Heat recovery thermal capacityQde (m3/h) - Plant (side) cooling exchanger recovery water flowDpde (kPa) - Plant side heating exchanger recovery pressure drop'-' - Conditions outside the operating range
NOTE: Data on grey background: unit switched to non-silenced operationWaterflow and pressure drop on heat exchangers calculated with 5°C of delta T
Tde (°C) - Plant (side) heat exchanger recovery output water temperature
25ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
LNDESUPERHEATER CAPACITY PERFOR.
NECS - D
0412
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
114 114 114 107 107 107 104 104 104 100,0 100,0 100,0 92,7 92,7 92,7 89,6 89,6 89,6
29,7 29,7 29,7 32,6 32,6 32,6 33,9 33,9 33,9 35,8 35,8 35,8 39,4 39,4 39,4 41,0 41,0 41,0
27,7 25,6 24,2 30,6 29,1 27,5 31,9 30,6 29,0 33,8 33,0 31,3 37,4 37,4 35,6 39,0 39,3 37,4
4,80 4,44 4,21 5,30 5,04 4,79 5,52 5,31 5,04 5,86 5,72 5,44 6,48 6,49 6,18 6,75 6,83 6,50
20,0 17,2 15,4 24,5 22,2 20,0 26,5 24,5 22,1 29,9 28,5 25,8 36,6 36,7 33,3 39,7 40,6 36,8
Tde
Ta
0452
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
129 129 129 121 121 121 118 118 118 113 113 113 104 104 104 101 101 101
33,1 33,1 33,1 36,4 36,4 36,4 37,8 37,8 37,8 40,0 40,0 40,0 44,0 44,0 44,0 45,7 45,7 45,7
31,1 28,8 27,3 34,4 32,7 31,0 35,8 34,4 32,6 38,0 37,1 35,2 42,0 42,0 39,9 43,7 44,1 41,9
5,39 5,00 4,74 5,96 5,67 5,38 6,20 5,96 5,66 6,59 6,43 6,11 7,27 7,28 6,93 7,56 7,65 7,29
17,8 15,3 13,7 21,8 19,7 17,8 23,6 21,8 19,7 26,6 25,4 22,9 32,4 32,5 29,5 35,1 35,9 32,5
Tde
Ta
0512
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
144 144 144 136 136 136 132 132 132 127 127 127 117 117 117 113 113 113
36,9 36,9 36,9 40,5 40,5 40,5 42,0 42,0 42,0 44,4 44,4 44,4 48,6 48,6 48,6 50,4 50,4 50,4
34,4 31,8 30,1 38,0 36,1 34,2 39,5 37,9 35,9 41,9 40,8 38,7 46,1 46,1 43,8 47,9 48,4 46,0
5,96 5,52 5,23 6,58 6,26 5,94 6,84 6,58 6,25 7,26 7,08 6,73 7,99 8,00 7,62 8,30 8,40 8,00
21,8 18,7 16,8 26,5 24,0 21,6 28,7 26,5 23,9 32,3 30,8 27,8 39,2 39,3 35,6 42,3 43,3 39,2
Tde
Ta
0552
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
164 164 164 154 154 154 150 150 150 144 144 144 133 133 133 128 128 128
42,6 42,6 42,6 46,7 46,7 46,7 48,5 48,5 48,5 51,3 51,3 51,3 56,3 56,3 56,3 58,4 58,4 58,4
40,1 37,1 35,0 44,2 42,0 39,8 46,0 44,2 41,9 48,8 47,6 45,2 53,8 53,8 51,1 55,9 56,5 53,7
6,94 6,43 6,09 7,66 7,29 6,92 7,97 7,66 7,28 8,46 8,26 7,85 9,32 9,34 8,88 9,69 9,80 9,33
19,8 17,0 15,3 24,2 21,9 19,7 26,2 24,2 21,8 29,5 28,1 25,4 35,8 35,9 32,5 38,7 39,6 35,9
Tde
Ta
0612
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
180 180 180 168 168 168 164 164 164 157 157 157 144 144 144 - - -
50,0 50,0 50,0 54,9 54,9 54,9 57,0 57,0 57,0 60,3 60,3 60,3 66,2 66,2 66,2 - - -
47,5 43,9 41,6 52,4 49,8 47,2 54,5 52,4 49,6 57,8 56,4 53,5 63,7 63,7 60,5 - - -
8,23 7,62 7,22 9,08 8,64 8,20 9,45 9,08 8,63 10,0 9,78 9,30 11,0 11,0 10,5 - - -
27,9 23,9 21,5 34,0 30,8 27,7 36,8 34,0 30,7 41,3 39,4 35,6 50,1 50,3 45,5 - - -
Tde
Ta
Ta [°C] - Source (side) cooling exchanger air temperaturePf (kW) - Cooling capacity (Plant side cooling exchanger water in/out 12/7 °C)Pat (kW) - Total power inputPtde (kW) - Heat recovery thermal capacityQde (m3/h) - Plant (side) cooling exchanger recovery water flowDpde (kPa) - Plant side heating exchanger recovery pressure drop'-' - Conditions outside the operating range
NOTE: Data on grey background: unit switched to non-silenced operationWaterflow and pressure drop on heat exchangers calculated with 5°C of delta T
Tde (°C) - Plant (side) heat exchanger recovery output water temperature
26ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
SLDESUPERHEATER CAPACITY PERFOR.
NECS - D
0152
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
41,2 41,2 41,2 38,3 38,3 38,3 37,0 37,0 37,0 35,0 35,0 35,0 38,2 38,2 38,2 36,9 36,9 36,9
12,7 12,7 12,7 14,2 14,2 14,2 14,8 14,8 14,8 15,8 15,8 15,8 14,5 14,5 14,5 15,2 15,2 15,2
12,1 11,2 10,6 13,5 12,8 12,2 14,1 13,6 12,9 15,1 14,7 14,0 13,5 13,5 12,9 14,2 14,3 13,6
2,09 1,94 1,83 2,34 2,23 2,11 2,45 2,36 2,24 2,62 2,56 2,43 2,35 2,35 2,24 2,45 2,48 2,36
7,71 6,62 5,94 9,69 8,78 7,90 10,6 9,80 8,84 12,1 11,5 10,4 9,72 9,75 8,83 10,6 10,9 9,87
Tde
Ta
0182
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
49,8 49,8 49,8 46,9 46,9 46,9 45,7 45,7 45,7 43,9 43,9 43,9 45,5 45,5 45,5 44,3 44,3 44,3
13,6 13,6 13,6 15,0 15,0 15,0 15,5 15,5 15,5 16,4 16,4 16,4 16,2 16,2 16,2 16,8 16,8 16,8
12,6 11,7 11,0 14,0 13,3 12,6 14,6 14,0 13,3 15,5 15,1 14,3 14,7 14,7 14,0 15,3 15,5 14,7
2,19 2,03 1,92 2,43 2,31 2,19 2,53 2,43 2,31 2,68 2,62 2,49 2,55 2,55 2,43 2,65 2,68 2,55
8,44 7,25 6,51 10,4 9,41 8,48 11,3 10,4 9,40 12,7 12,1 11,0 11,5 11,5 10,4 12,4 12,7 11,5
Tde
Ta
0202
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
57,7 57,7 57,7 53,9 53,9 53,9 52,2 52,2 52,2 49,6 49,6 49,6 53,1 53,1 53,1 51,4 51,4 51,4
15,9 15,9 15,9 17,7 17,7 17,7 18,5 18,5 18,5 19,6 19,6 19,6 18,6 18,6 18,6 19,4 19,4 19,4
15,0 13,8 13,1 16,7 15,9 15,1 17,5 16,8 15,9 18,7 18,2 17,3 17,1 17,1 16,2 17,9 18,1 17,2
2,59 2,40 2,27 2,90 2,76 2,62 3,03 2,91 2,77 3,24 3,16 3,00 2,96 2,97 2,82 3,10 3,13 2,98
11,8 10,2 9,13 14,8 13,4 12,1 16,2 15,0 13,5 18,5 17,6 15,9 15,5 15,5 14,1 16,9 17,3 15,7
Tde
Ta
0252
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
66,1 66,1 66,1 62,0 62,0 62,0 60,3 60,3 60,3 57,5 57,5 57,5 59,6 59,6 59,6 57,7 57,7 57,7
17,9 17,9 17,9 19,8 19,8 19,8 20,6 20,6 20,6 21,9 21,9 21,9 21,6 21,6 21,6 22,5 22,5 22,5
16,7 15,4 14,6 18,5 17,6 16,7 19,3 18,6 17,6 20,6 20,1 19,0 19,6 19,6 18,7 20,5 20,7 19,7
2,89 2,67 2,53 3,21 3,05 2,90 3,35 3,22 3,06 3,56 3,48 3,31 3,40 3,41 3,24 3,55 3,59 3,42
14,7 12,6 11,3 18,2 16,5 14,8 19,8 18,3 16,5 22,4 21,4 19,3 20,5 20,5 18,6 22,3 22,8 20,6
Tde
Ta
0302
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
83,9 83,9 83,9 78,5 78,5 78,5 76,2 76,2 76,2 72,6 72,6 72,6 78,2 78,2 78,2 75,9 75,9 75,9
24,2 24,2 24,2 26,9 26,9 26,9 28,0 28,0 28,0 29,9 29,9 29,9 27,7 27,7 27,7 28,9 28,9 28,9
22,9 21,2 20,0 25,6 24,3 23,0 26,7 25,7 24,3 28,6 27,9 26,4 25,7 25,7 24,5 26,9 27,2 25,8
3,97 3,68 3,48 4,43 4,22 4,00 4,63 4,45 4,23 4,95 4,83 4,59 4,46 4,47 4,25 4,66 4,72 4,49
13,7 11,8 10,6 17,1 15,5 13,9 18,7 17,3 15,6 21,3 20,3 18,4 17,3 17,4 15,7 18,9 19,4 17,6
Tde
Ta
0352
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
101 101 101 94,8 94,8 94,8 92,4 92,4 92,4 88,6 88,6 88,6 88,6 88,6 88,6 85,9 85,9 85,9
26,9 26,9 26,9 29,6 29,6 29,6 30,7 30,7 30,7 32,5 32,5 32,5 32,6 32,6 32,6 33,8 33,8 33,8
24,4 22,6 21,4 27,1 25,7 24,4 28,2 27,1 25,7 30,0 29,3 27,8 30,1 30,1 28,6 31,3 31,7 30,1
4,23 3,92 3,71 4,69 4,46 4,23 4,89 4,70 4,46 5,20 5,08 4,83 5,21 5,21 4,96 5,43 5,49 5,23
15,6 13,4 12,0 19,1 17,3 15,6 20,8 19,2 17,3 23,6 22,5 20,3 23,6 23,7 21,4 25,7 26,3 23,8
Tde
Ta
Ta [°C] - Source (side) cooling exchanger air temperaturePf (kW) - Cooling capacity (Plant side cooling exchanger water in/out 12/7 °C)Pat (kW) - Total power inputPtde (kW) - Heat recovery thermal capacityQde (m3/h) - Plant (side) cooling exchanger recovery water flowDpde (kPa) - Plant side heating exchanger recovery pressure drop'-' - Conditions outside the operating range
NOTE: Data on grey background: unit switched to non-silenced operationWaterflow and pressure drop on heat exchangers calculated with 5°C of delta T
Tde (°C) - Plant (side) heat exchanger recovery output water temperature
27ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
SLDESUPERHEATER CAPACITY PERFOR.
NECS - D
0412
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
114 114 114 107 107 107 105 105 105 100 100 100 101 101 101 98,2 98,2 98,2
30,0 30,0 30,0 32,9 32,9 32,9 34,1 34,1 34,1 36,1 36,1 36,1 35,8 35,8 35,8 37,2 37,2 37,2
27,5 25,4 24,1 30,4 28,9 27,4 31,6 30,4 28,8 33,6 32,8 31,1 33,3 33,3 31,6 34,7 35,0 33,3
4,76 4,41 4,18 5,26 5,01 4,75 5,48 5,27 5,00 5,82 5,69 5,41 5,77 5,78 5,50 6,01 6,08 5,79
19,8 17,0 15,2 24,1 21,8 19,7 26,2 24,2 21,8 29,5 28,2 25,4 29,0 29,1 26,3 31,4 32,2 29,2
Tde
Ta
0452
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
126 126 126 118 118 118 115 115 115 110 110 110 112 112 112 109 109 109
34,7 34,7 34,7 38,1 38,1 38,1 39,5 39,5 39,5 41,8 41,8 41,8 41,0 41,0 41,0 42,5 42,5 42,5
32,2 29,8 28,2 35,6 33,8 32,0 37,0 35,5 33,7 39,3 38,3 36,3 38,5 38,5 36,5 40,0 40,4 38,4
5,58 5,17 4,90 6,16 5,86 5,57 6,41 6,17 5,86 6,81 6,65 6,32 6,66 6,67 6,35 6,93 7,01 6,68
19,1 16,4 14,7 23,3 21,1 19,0 25,2 23,3 21,0 28,4 27,1 24,5 27,2 27,3 24,7 29,5 30,2 27,3
Tde
Ta
0512
25 30 32 35 40 42
35 40 45 35 40 45 35 40 45 35 40 45 35 40 45 35 40 45
Pf
Pat
Ptde
Qde
Dpde
140 140 140 131 131 131 128 128 128 122 122 122 126 126 126 122 122 122
38,6 38,6 38,6 42,3 42,3 42,3 44,0 44,0 44,0 46,5 46,5 46,5 44,8 44,8 44,8 46,5 46,5 46,5
36,1 33,4 31,6 39,8 37,9 35,9 41,5 39,8 37,7 44,0 42,9 40,7 42,3 42,3 40,2 44,0 44,5 42,3
6,25 5,79 5,48 6,90 6,57 6,23 7,18 6,90 6,56 7,62 7,44 7,07 7,33 7,34 6,99 7,62 7,71 7,34
23,9 20,5 18,4 29,2 26,4 23,8 31,6 29,2 26,3 35,5 33,9 30,6 32,9 33,0 29,9 35,6 36,5 33,1
Tde
Ta
Ta [°C] - Source (side) cooling exchanger air temperaturePf (kW) - Cooling capacity (Plant side cooling exchanger water in/out 12/7 °C)Pat (kW) - Total power inputPtde (kW) - Heat recovery thermal capacityQde (m3/h) - Plant (side) cooling exchanger recovery water flowDpde (kPa) - Plant side heating exchanger recovery pressure drop'-' - Conditions outside the operating range
NOTE: Data on grey background: unit switched to non-silenced operationWaterflow and pressure drop on heat exchangers calculated with 5°C of delta T
Tde (°C) - Plant (side) heat exchanger recovery output water temperature
28ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
4. OPERATING RANGE
NECS NECS-D -
Evaporator Desuperheater Heat recovery
min max min max min max
Exch. water (in) (°C) 8 (1) 23 (1) 18 (1) (2) --- - -
Exch. water (out) (°C) 5 (1) (6) 15 (1) 26 (1) (2) --- - -
Thermal difference (°C) 3 8 4 --- - -
(*) According to unit size
(1) Condenser air (in) 35 °C
(2) Evaporator water (in/out) 12/7 °C
(3) With low ambient temperature control (STD/OPT)
(4) Condenser air-fl ow rate in low-noise operating mode
(5) Condenser air-fl ow rate in standard operating mode
(6) With temperatures down to -8°C use anti-freeze mixtures. In case of
lower temperatures, please contact our Sales Department.
ETHYLENE GLYCOL MIXTURE
Ethylene glycol and water mixtures, used as a heat-conveying fl uid,
cause a variation in unit performance. For correct data, use the factors
indicated in the following table.
Freezing point (°C)
0 -5 -10 -15 -20 -25 -30 -35
Ethylene glycol percentage by weight
0 12% 20% 30% 35% 40% 45% 50%
cPf 1 0,985 0,98 0,974 0,97 0,965 0,964 0,96
cQ 1 1,02 1,04 1,075 1,11 1,14 1,17 1,2
cdp 1 1,07 1,11 1,18 1,22 1,24 1,27 1,3
cPf: cooling capacity correction factor
cQ: fl ow correction factor
cdp: pressure drop correction factor
For data concerning other kind of anti-freeze solutions (e.g. propylene
glycol) please contact our Sales Department.
Fouling factorsEvaporator Heat recovery Desuperheater
f1 fk1 fx1 f2 fk2 fx2 f3 fk3 fx3
(m2°C/W) 4,4 x 10-5 1 1 1 0,99 1,03 1,03 0,99 1,03 1,03
(m2 °C/W) 0,86 x 10-4 0,96 0,99 0,99 0,98 1,04 1,04 0,98 1,04 1,04
(m2 °C/W) 1,72 x 10-4 0,93 0,98 0,98 0,95 1,06 1,06 0,95 1,06 1,06
FOULING FACTORS
Performances are based on clean condition of tubes (fouling factor =1).
For different fouling values, performance should be adjusted using the
correction factors shown in the following table.
f1 - f2 - f3: capacity correction factors
fk1 - fk2 - fk3: compressor power input correction factors
fx1 - fx2 - fx3: total power input correction factors
Vers. Min Min Max (*) Max (*)
Ambient air temp. (in) (°C) SL -10 (2) -10 (2)(3) 35 - 37 (2)(4) 46 (5)
Ambient air temp. (in) (°C) LN -10 (2) -10 (2)(3) 40 - 43 (2)(4) ---
Ambient air temp. (in) (°C) HT -10 (2) -10 (2)(3) 46 (2)(4) ---
Ambient air temp. (in) (°C) HL -10 (2) -10 (2)(3) 43 - 44 (2)(4) ---
Limits to exchanger water temperature are valid within the minimum -
maximum water fl ow range indicated in the Hydraulic Data section.
29 NECS_0152_0612_200907_GB
NECS
HFC R410A
5. HYDRAULIC DATA
SIZE Evaporator Rec (1) - Cond (2) Desuperheater
KQ min
m3/h
Q max
m3/h
W.c.
min m3 KQ min
m3/h
Q max
m3/hK
Q min
m3/h
Q max
m3/h
0152 1.346 4,1 11,0 0,3 - - - 1767 --- 2,6
0182 869 4,9 13,0 0,4 - - - 1767 --- 2,8
0202 615 5,4 14,5 0,4 - - - 1767 --- 3,5
0252 426 6,1 16,3 0,5 - - - 1767 --- 4,0
0302 334 8,2 21,8 0,7 - - - 871 --- 5,1
0352 261 9,3 24,8 0,8 - - - 871 --- 5,8
0412 218 10,4 27,8 0,8 - - - 871 --- 6,7
0452 161 12,1 32,2 1,0 - - - 613 --- 7,2
0512 137 13,6 36,3 1,1 - - - 613 --- 8,0
0552 124 15,6 41,5 1,3 - - - 412 --- 9,2
0612 109 17,1 45,5 1,4 - - - 412 --- 10,8
Water fl ow in the heat exchangers is given by:
Q=Px0,86/Dt
Q: water fl ow (m3/h)
Dt: difference between inlet and outlet water temp. (°C)
P: heat exchanger capacity (kW)
Pressure drop is given by:
Dp= K x Q2/1000
Q: water fl ow (m3/h)
Dp: pressure drop (kPa)
K: unit size ratio
K evap : standard mains fi lter included
Q min: minimum water fl ow admitted to the heat exchanger.
Q max: maximum water fl ow admitted to the heat exchanger.
C.a. min: minimum water content admitted in the plant, using
traditional control logic
(1) Rec. = Heat Recovery. For units with total heat recovery.
(2) Cond.= Condenser. For water to water type units. In units
with heat recovery, this data is valid for both the
condensing and the heat recovery exchangers.
5.1 Water fl ow and pressure drop
30 NECS_0152_0612_200907_GB
NECS
HFC R410A
Available confi gurations
Hydronic group 1 pump
Hydronic group 2 pumps
Hydronic group 1 pump with water tank
Hydronic group 2 pumps with water tank
Compact units PLUG and PLAY
The units in the NECS system are fi tted standard with a hy-
dronic group. This houses all the main hydraulic components,
thereby optimising hydraulic and electric installation space,
time and cost.
The innovative QuickMind control fi tted to the units in the NECS
system, has been designed to work on systems with a low wa-
ter content, offering highly professional alternatives to the in-
stallation of systems featuring storage units.
For special applications, a tank to install inside the unit is avail-
able on request.
2-pole low head pump
Horizontal one-piece centrifuge pump with one impeller, axial
suction and radial delivery, AISI 304L stainless steel pump body
impeller. The section of shaft in contact with the liquid is made
from stainless steel. Mechanical seal made from components
in ceramics/carbon/NBR/AISI304. Three-phase electric motor
protected to IP55, insulation class F, suitable for continuous
service.
Second pump
A second stand-by pump for high or low pressures is available
on request. The pumps are automatically exchanged on the
basis of a rotation programme and the stand-by pump cuts in
automatically if the primary pump fails. The two-pump hydron-
ic assembly is also fi tted with check valves to ensure the unit
works correctly.
Special pumps
For pumps with different confi gurations, please contact our
sales department.
Water Tank
All units can be fi tted with an internal storage tank holding 85 or
250 litres, depending on the version.
This is made from sheet steel, welded using leading-edge tech-
nologies and protected from corrosion with a coat of paint.
Each tank is tested to 7.5 bar to ensure an operating pressure
of 5 bar.
The condensation-proof lagging is made from a 20 mm layer of
foamed cross-linked polyethylene bonded to an external em-
bossed metallic scratchproof fi lm.
Water-side mechanical fi lter (standard)
Y-fi lter designed and built to capture the impurities in the hy-
draulic circuit. It is fi tted with a 0.9 mm stainless steel mesh car-
tridge which can be replaced without removing the valve body
from the piping.
The supply does not include the following accessories though
these are recommended to ensure correct system operation:
- Pressure gauges upline and downline from the unit
- Flexible joints on piping
- On-off valves
- Outlet control thermometer
6. HYDRONIC GROUPS
31 NECS_0152_0612_200907_GB
NECS
HFC R410A
Confi guration Hydronic group 1 pump
The hydronic group comprises:
- P Horizontal one-piece centrifuge pump.
- MA Hydraulic circuit pressure gauge
- F Flow switch
- RT Flow control valve
- SC Discharge valve
- S1 Exchanger input water temperature probe
- S2 Exchanger outlet water temperature probe
- SF Air vent
- VA 3 bar safety valve
- VE 8-litre expansion tanks, pre-pressurised to 1.5 bar
- FI Mains fi lter. Standard.
Confi guration Hydronic group 2 pumps
The hydronic group comprises:
- P Horizontal one-piece centrifuge pump.
- MA Hydraulic circuit pressure gauge
- F Flow switch
- RT Flow control valve
- SC Discharge valve
- S1 Exchanger input water temperature probe
- S2 Exchanger outlet water temperature probe
- SF Air vent
- VA 3 bar safety valve
- VE 8-litre expansion tanks, pre-pressurised to 1.5 bar
- VR Check valve (only if P2 is fi tted)
- FI Mains fi lter. Standard.
The electrical panel of the unit is protected with Automatic
circuit breakers.
32 NECS_0152_0612_200907_GB
NECS
HFC R410A
Confi guration Hydronic group 1 pump with water tank
The hydronic group comprises:
- P Horizontal one-piece centrifuge pump
- AC Storage tank
- MA Hydraulic circuit pressure gauge
- F Flow switch
- RT Flow control valve
- SC Discharge valve
- S1 Exchanger input water temperature probe
- S2 Exchanger outlet water temperature probe
- SF Air vent
- VA 3 bar safety valve
- VE 8-litre expansion tanks, pre-pressurised to 1.5 bar, with
storage tank 85 and 150 lt.
12-litre expansion tanks, pre-pressurised to 1.5 bar, with
storage tank 190 and 250 lt.
- FI Mains fi lter. Standard.
Confi guration Hydronic group 2 pumps with water tank
The hydronic group comprises:
- P Horizontal one-piece centrifuge pump
- A Storage tank
- MA Hydraulic circuit pressure gauge
- F Flow switch
- RT Flow control valve
- SC Discharge valve
- S1 Exchanger input water temperature probe
- S2 Exchanger outlet water temperature probe
- SF Air vent
- VA 3 bar safety valve
- VE 8-litre expansion tanks, pre-pressurised to 1.5 bar, with
storage tank 85 and 150 lt.
12-litre expansion tanks, pre-pressurised to 1.5 bar,
with storage tank 190 and 250 lt.
- VR Check valve (only if P2 is fi tted)
- FI Mains fi lter. Standard.
The electrical panel of the unit is protected with Automatic
circuit breakers.
33 NECS_0152_0612_200907_GB
NECS
HFC R410A
SizePf (1)
[kW]
Q (1)
[m3/h]
Pump
ref.
F.L.I.
[kW]
F.L.A.
[A]
Hp
[kPa]
0152 38,0 6,5 A 1,1 2,5 137
0182 45,0 7,7 A 1,1 2,5 134
0202 50,0 8,6 B 1,1 2,5 180
0252 57,0 9,8 B 1,1 2,5 174
0302 76,0 13,1 C 1,5 3,2 166
0352 87,0 15,0 C 1,5 3,2 162
0412 97,0 16,7 D 2,2 4,8 215
0452 112,0 19,3 E 3,0 5,6 234
0512 127,0 21,8 E 3,0 5,6 228
0552 145,0 24,9 E 3,0 5,6 221
0612 159,0 27,3 E 3,0 5,6 214
2-pole low head pump
Size
Unit without tank Unit with tank
1 Pump 2 Pumps 1 Pump 2 Pumps
KP1Dpu
[kPa]
Hu
[kPa]KP2
Dpu
[kPa]
Hu
[kPa]KAC1
Dpu
[kPa]
Hu
[kPa]KAC2
Dpu
[kPa]
Hu
[kPa]
0152 1404 60 77 1437 62 75 1437 62 75 1437 62 75
0182 916 55 78 947 57 76 947 57 76 947 57 76
0202 653 49 130 684 52 127 684 52 127 684 52 127
0252 461 44 130 486 47 127 486 47 127 486 47 127
0302 366 62 129 396 68 123 396 68 123 396 68 123
0352 289 64 118 319 71 111 319 71 111 319 71 111
0412 250 69 146 280 78 137 280 78 137 280 78 137
0452 174 65 165 185 69 161 185 69 161 185 69 161
0512 150 71 152 161 77 146 161 77 146 161 77 146
0552 130 81 133 140 87 127 140 87 127 140 87 127
0612 122 91 116 132 99 108 132 99 108 132 99 108
(1) Values refer to rated operating conditions
Pf Cooling capacity of unit
Q Flow of water to evaporator
F.L.I. Power absorbed by pump
F.L.A. Current absorbed by pump
Hp Head of pump
Dpu Total pressure drop of hydronic group
Hu Working head
ACC Water Tank capacity
KG1 Extra weight with only pumps
KG2 Extra weight witht pumps and empty water tank
Coeffi cients for calculating pressure drops comprise standard
mains fi lter:
K P1 Unit with Hydronic group and one pump
K P2 Unit with Hydronic group and two pumps
K AC1 Unit with 1 Pump and Storage tank
K AC2 Unit with 2 Pumps and Storage tank
60
80
100
120
140
160
180
200
220
240
260
280
300
320
340
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85
Q [m3/h]
H [
kP
a]
A
B
C
D
E
Storage tank
B LN HT-SL
85 85 85
85 85 85
85 150 150
85 150 150
150 190 150
150 190 190
190 190 190
190 190 190
250 250 250
250 250 250
250 250 250
34 NECS_0152_0612_200907_GB
NECS
HFC R410A
1 PUMP 2 PUMPS
B LN HT SL B LN HT SL
0152 35 35 30 30 70 70 60 60
0182 35 35 35 35 70 70 70 70
0202 35 30 35 35 70 60 70 70
0252 35 30 35 35 70 60 70 70
0302 35 30 35 35 70 60 70 70
0352 35 35 35 35 70 70 70 70
0412 35 35 40 40 70 70 80 80
0452 35 35 45 45 70 70 90 90
0512 50 50 45 45 100 100 90 90
0552 50 50 45 45 100 100 90 90
0612 50 50 45 45 100 100 90 90
1 PUMP 2 PUMPS
B LN HT SL B LN HT SL
0152 145 145 150 150 180 180 180 180
0182 145 145 135 135 180 180 170 170
0202 145 220 225 225 180 250 260 260
0252 145 220 215 215 180 250 250 250
0302 225 270 275 275 260 300 310 310
0352 225 275 265 265 260 310 300 300
0412 275 275 270 270 310 310 310 310
0452 275 275 245 245 310 310 290 290
0512 350 350 345 345 400 400 390 390
0552 350 350 345 345 400 400 390 390
0612 350 350 345 345 400 400 390 390
WEIGHT DIFFERENCES
Weight differences, in Kg, compared with the Standard Unit.
The weight of the Standard Unit is indicated on page A2.
There is no difference in weight between the low head and
high head versions.
Without WATER TANK
With WATER TANK FULL (working)
1 PUMP 2 PUMPS
B LN HT SL B LN HT SL
0152 60 60 65 65 95 95 95 95
0182 60 60 50 50 95 95 85 85
0202 60 70 75 75 95 100 110 110
0252 60 70 65 65 95 100 100 100
0302 75 80 85 85 110 110 120 120
0352 75 85 75 75 110 120 110 110
0412 85 85 80 80 120 120 120 120
0452 85 85 55 55 120 120 100 100
0512 100 100 95 95 150 150 140 140
0552 100 100 95 95 150 150 140 140
0612 100 100 95 95 150 150 140 140
With WATER TANK EMPTY (Transport)
35 NECS_0152_0612_200907_GB
NECS
HFC R410A
BNECS8. FULL LOAD SOUND LEVEL
SIZE Octave band [Hz]
2000100050025012563 80004000
Total sound
level
Sound power level dB(A)
SOUND POWER
83 81 85 82 78 76 69 68 840152
83 81 85 82 78 76 69 68 840182
83 81 85 82 78 76 69 68 840202
83 81 85 82 78 76 69 68 840252
84 82 86 83 79 77 70 69 850302
85 83 87 84 80 78 71 70 860352
85 83 87 84 80 78 71 70 860412
85 83 87 84 80 78 71 70 860452
86 84 88 85 81 79 72 71 870512
86 84 88 85 81 79 72 71 870552
86 84 88 85 81 79 72 71 870612
Plant (side) cooling exchanger water (in/out) 12/7 °C
Source (side) heat exchanger air (in) 35 °C
Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units;
in compliance with ISO 3744 for non-certified units
Such certification refers specifically to the sound Power Level in dB(A). This is therefore the only acoustic data to be considered as binding.
Working conditions
SIZE Octave band [Hz] at 10 m
2000100050025012563 80004000
Total sound
level
Sound pressure level dB(A)
SOUND PRESSURE LEVEL
51 49 53 50 46 44 37 36 520152
51 49 53 50 46 44 37 36 520182
51 49 53 50 46 44 37 36 520202
51 49 53 50 46 44 37 36 520252
52 50 54 51 47 45 38 37 530302
53 51 55 52 48 46 39 38 540352
53 51 55 52 48 46 39 38 540412
53 51 55 52 48 46 39 38 540452
54 52 56 53 49 47 40 39 550512
54 52 56 53 49 47 40 39 550552
54 52 56 53 49 47 40 39 550612
Plant (side) cooling exchanger water (in/out) 12/7 °C
Source (side) heat exchanger air (in) 35 °C
Average sound pressure level, at 10 (m.) distance, unit in a free field on a reflective surface; non-binding value obtained
from the sound power level
Working conditions
37ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
HTNECS
FULL LOAD SOUND LEVEL
SIZE Octave band [Hz]
2000100050025012563 80004000
Total sound
level
Sound power level dB(A)
SOUND POWER
83 81 85 82 78 76 69 68 840152
84 82 86 83 79 77 70 69 850182
84 82 86 83 79 77 70 69 850202
85 83 87 84 80 78 71 70 860252
85 83 87 84 80 78 71 70 860302
86 84 88 85 81 79 72 71 870352
86 84 88 85 81 79 72 71 870412
86 84 88 85 81 79 72 71 870452
86 84 88 85 81 79 72 71 870512
Plant (side) cooling exchanger water (in/out) 12/7 °C
Source (side) heat exchanger air (in) 35 °C
Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units;
in compliance with ISO 3744 for non-certified units
Such certification refers specifically to the sound Power Level in dB(A). This is therefore the only acoustic data to be considered as binding.
Working conditions
SIZE Octave band [Hz] at 10 m
2000100050025012563 80004000
Total sound
level
Sound pressure level dB(A)
SOUND PRESSURE LEVEL
51 49 53 50 46 44 37 36 520152
52 50 54 51 47 45 38 37 530182
52 50 54 51 47 45 38 37 530202
53 51 55 52 48 46 39 38 540252
53 51 55 52 48 46 39 38 540302
54 52 56 53 49 47 40 39 550352
54 52 56 53 49 47 40 39 550412
54 52 56 53 49 47 40 39 550452
54 52 56 53 49 47 40 39 550512
Plant (side) cooling exchanger water (in/out) 12/7 °C
Source (side) heat exchanger air (in) 35 °C
Average sound pressure level, at 10 (m.) distance, unit in a free field on a reflective surface; non-binding value obtained
from the sound power level
Working conditions
38ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
LNNECS
FULL LOAD SOUND LEVEL
SIZE Octave band [Hz]
2000100050025012563 80004000
Total sound
level
Sound power level dB(A)
SOUND POWER
80 78 81 78 73 69 61 59 790152
80 78 81 78 73 69 61 59 790182
81 79 82 79 74 70 62 60 800202
81 79 82 79 74 70 62 60 800252
82 80 83 80 75 71 63 61 810302
82 80 84 81 77 75 68 67 830352
82 80 84 81 77 75 68 67 830412
82 80 84 81 77 75 68 67 830452
83 81 85 82 78 76 69 68 840512
83 81 85 82 78 76 69 68 840552
83 81 85 82 78 76 69 68 840612
Plant (side) cooling exchanger water (in/out) 12/7 °C
Source (side) heat exchanger air (in) 35 °C
Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units;
in compliance with ISO 3744 for non-certified units
Such certification refers specifically to the sound Power Level in dB(A). This is therefore the only acoustic data to be considered as binding.
Working conditions
SIZE Octave band [Hz] at 10 m
2000100050025012563 80004000
Total sound
level
Sound pressure level dB(A)
SOUND PRESSURE LEVEL
48 46 49 46 41 37 29 27 470152
48 46 49 46 41 37 29 27 470182
49 47 50 47 42 38 30 28 480202
49 47 50 47 42 38 30 28 480252
50 48 51 48 43 39 31 29 490302
50 48 52 49 45 43 36 35 510352
50 48 52 49 45 43 36 35 510412
50 48 52 49 45 43 36 35 510452
51 49 53 50 46 44 37 36 520512
51 49 53 50 46 44 37 36 520552
51 49 53 50 46 44 37 36 520612
Plant (side) cooling exchanger water (in/out) 12/7 °C
Source (side) heat exchanger air (in) 35 °C
Average sound pressure level, at 10 (m.) distance, unit in a free field on a reflective surface; non-binding value obtained
from the sound power level
Working conditions
39ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
SLNECS
FULL LOAD SOUND LEVEL
SIZE Octave band [Hz]
2000100050025012563 80004000
Total sound
level
Sound power level dB(A)
SOUND POWER
80 75 73 75 72 66 60 57 760152
81 76 74 76 73 67 61 58 770182
81 76 74 76 73 67 61 58 770202
83 77 75 77 74 68 62 59 780252
83 77 75 77 74 68 62 59 780302
81 79 81 79 76 72 67 64 810352
81 79 81 79 76 72 67 64 810412
81 79 81 79 76 72 67 64 810452
82 80 82 80 77 73 68 65 820512
Plant (side) cooling exchanger water (in/out) 12/7 °C
Source (side) heat exchanger air (in) 35 °C
Sound power on the basis of measurements made in compliance with ISO 9614 and Eurovent 8/1 for Eurovent certified units;
in compliance with ISO 3744 for non-certified units
Such certification refers specifically to the sound Power Level in dB(A). This is therefore the only acoustic data to be considered as binding.
Working conditions
SIZE Octave band [Hz] at 10 m
2000100050025012563 80004000
Total sound
level
Sound pressure level dB(A)
SOUND PRESSURE LEVEL
48 43 41 43 40 34 28 25 440152
49 44 42 44 41 35 29 26 450182
49 44 42 44 41 35 29 26 450202
51 45 43 45 42 36 30 27 460252
51 45 43 45 42 36 30 27 460302
49 47 49 47 44 40 35 32 490352
49 47 49 47 44 40 35 32 490412
49 47 49 47 44 40 35 32 490452
50 48 50 48 45 41 36 33 500512
Plant (side) cooling exchanger water (in/out) 12/7 °C
Source (side) heat exchanger air (in) 35 °C
Average sound pressure level, at 10 (m.) distance, unit in a free field on a reflective surface; non-binding value obtained
from the sound power level
Working conditions
40ELCADOC - Ver. 0.9.9.10 NECS_0152_0612_200909_EN Ref.: R410A
NECS
B - HL - HT - LN - SL
A 1 NECS_0152_0612_200907_GB HFC R410A
9. DIMENSIONAL DRAWINGS
REMARKS:
For installation purposes, please refer to the documentation sent after the pur-
chase-contract. This technical data should be considered as indicative.
CLIMAVENETA may modify them at any moment.
Rif 0152 0182 0202 0252 0302 0352 0412 0452 0512 0552 0612
1 - 2 Evaporator
UNI ISO RP2” 2” 2” 2” 2” 2” 2” 2 1/2” 2 1/2” 2 1/2” 2 1/2”
4 - 5Desuperheater
UNI ISO RP1 1/2” 1 1/2” 1 1/2” 1 1/2” 1 1/2” 1 1/2” 1 1/2” 1 1/2” 1 1/2” 1 1/2” 1 1/2”
AB
H
1 EVAPORATOR WATER OUTLET
2 EVAPORATOR WATER INLET
3 POWER INLET
4 DESUPERHEATER WATER OUTLET
5 DESUPERHEATER WATER INLET
AIR INLET
AIR OUTLET
NECS
A2 NECS_0152_0612_200907_GBELCAdoc 16/04/2008 HFC R410A
DIMENSIONAL DRAWINGS
Size
DIMENSIONS AND WEIGHTSFREE SPACES (See fol. page)
NECS NECS-D
A [mm] B [mm] H [mm] P [kg] A [mm] B [mm] H [mm] P [kg] R1 [mm] R2 [mm] R3 [mm] R4 [mm]
0152 B 1695 1120 1420 370 1695 1120 1420 380 1000 1000 600 600
0152 HT 1695 1120 1420 390 1695 1120 1420 400 1000 1000 600 600
0152 LN 1695 1120 1420 370 1695 1120 1420 380 1000 1000 600 600
0152 SL 1695 1120 1420 390 1695 1120 1420 400 1000 1000 600 600
0182 B 1695 1120 1420 410 1695 1120 1420 410 1000 1000 600 600
0182 HT 2195 1120 1420 450 2195 1120 1420 460 1000 1000 600 600
0182 LN 1695 1120 1420 410 1695 1120 1420 410 1000 1000 600 600
0182 SL 2195 1120 1420 450 2195 1120 1420 460 1000 1000 600 600
0202 B 1695 1120 1420 410 1695 1120 1420 420 1000 1000 600 600
0202 HT 2195 1120 1420 480 2195 1120 1420 490 1000 1000 600 600
0202 LN 2195 1120 1420 460 2195 1120 1420 470 1000 1000 600 600
0202 SL 2195 1120 1420 480 2195 1120 1420 490 1000 1000 600 600
0252 B 1695 1120 1420 420 1695 1120 1420 430 1000 1000 600 600
0252 HT 2745 1120 1420 540 2745 1120 1420 550 1000 1000 600 600
0252 LN 2195 1120 1420 490 2195 1120 1420 510 1000 1000 600 600
0252 SL 2745 1120 1420 540 2745 1120 1420 550 1000 1000 600 600
0302 B 2195 1120 1420 620 2195 1120 1420 630 1000 1000 600 600
0302 HT 2745 1120 1420 700 2745 1120 1420 710 1000 1000 600 600
0302 LN 2745 1120 1420 660 2745 1120 1420 680 1000 1000 600 600
0302 SL 2745 1120 1420 700 2745 1120 1420 710 1000 1000 600 600
0352 B 2195 1120 1420 650 2195 1120 1420 660 1000 1000 600 600
0352 HT 3245 1120 1620 780 3245 1120 1620 800 1000 1000 600 600
0352 LN 2745 1120 1620 720 2745 1120 1620 730 1000 1000 600 600
0352 SL 3245 1120 1620 780 3245 1120 1620 800 1000 1000 600 600
0412 B 2745 1120 1420 730 2745 1120 1420 740 1000 1000 600 600
0412 HT 3245 1120 1620 860 3245 1120 1620 880 1000 1000 600 600
0412 LN 2745 1120 1620 790 2745 1120 1620 800 1000 1000 600 600
0412 SL 3245 1120 1620 860 3245 1120 1620 880 1000 1000 600 600
0452 B 2745 1120 1420 780 2745 1120 1420 800 1000 1000 600 600
0452 HT 3245 1120 1620 910 3245 1120 1620 930 1000 1000 600 600
B - HT - LN - SL
NECS
A3 NECS_0152_0612_200907_GBELCAdoc 16/04/2008 HFC R410A
DIMENSIONAL DRAWINGS
Size
DIMENSIONS AND WEIGHTSFREE SPACES (See fol. page)
NECS NECS-D
A [mm] B [mm] H [mm] P [kg] A [mm] B [mm] H [mm] P [kg] R1 [mm] R2 [mm] R3 [mm] R4 [mm]
0452 LN 2745 1120 1620 820 2745 1120 1620 840 1000 1000 600 600
0452 SL 3245 1120 1620 910 3245 1120 1620 930 1000 1000 600 600
0512 B 3245 1120 1620 930 3245 1120 1620 950 1000 1000 600 600
0512 HT 3245 1120 1620 940 3245 1120 1620 960 1000 1000 600 600
0512 LN 3245 1120 1620 930 3245 1120 1620 950 1000 1000 600 600
0512 SL 3245 1120 1620 940 3245 1120 1620 960 1000 1000 600 600
0552 B 3245 1120 1620 950 3245 1120 1620 970 1000 1000 600 600
0552 LN 3245 1120 1620 950 3245 1120 1620 970 1000 1000 600 600
0612 B 3245 1120 1620 960 3245 1120 1620 980 1000 1000 600 600
0612 LN 3245 1120 1620 960 3245 1120 1620 980 1000 1000 600 600
NECS
A4 NECS_0152_0612_200907_GBELCAdoc 16/04/2008 HFC R410A
10. FREE SPACES - LIFTING MODE - SYMBOLS
INSTRUCTIONS:
- Make sure that all the panels are fi rmly fi xed in place before moving the unit.
- Before lifting it, check the weight on the CE label.
- Use all, and only, the lifting points provided,
- Use slings of equal length,
- Use a spread-bar (not included)
- Move the unit carefully and avoid abrupt movements.
Warning: Electrical power!
Warning: Sharp edges!
Warning: Fans!
11. LEGEND OF PIPE CONNECTIONS
UNI ISO 228/1
Pipe threads where pressure-tight joints are not made on the
threads - Designation, dimensions and tolerances
Used terminology:
G: Pipe threads where pressure-tight joints are not made on
the threads
A: Close tolerance class for external pipe threads where pres-
sure-tight joints are not made on the threads
B: Wider tolerance class for external pipe threads where pres-
sure-tight joints are not made on the threads
Internal threads: G letter followed by thread mark (only toler-
ance class)
External threads: G letter followed by thread mark and by A
letter for A class external threads or by B
letter for B class external threads.
UNI ISO 7/1
Pipe threads where pressure-tight joints are made on the
threads - Designation, dimensions and tolerances
Used terminology:
Rp: Internal cylindrical threads where pressure-tight joints are
made on the threads
Rc: Internal conical threads where pressure-tight joints are
made on the threads
R: External conical threads where pressure-tight joints are
made on the threads
Internal cylindrical threads: R letter followed by P letter
Internal conical threads: R letter followed by C letter
External conical threads: R letter
Designation Description
UNI ISO 7/1 - Rp 1 1/2
Internal cylindrical threads where pressure-tight joints are made on the threads, defi ned by stand-
ard UNI ISO 7/1
Conventional ø: 1 1/2”
UNI ISO 7/1 - Rp 2 1/2
Internal cylindrical threads where pressure-tight joints are made on the threads, defi ned by stand-
ard UNI ISO 7/1
Conventional ø: 2 1/2”
UNI ISO 7/1 - Rp 3
Internal cylindrical threads where pressure-tight joints are made on the threads, defi ned by stand-
ard UNI ISO 7/1
Conventional ø: 3”
UNI ISO 7/1 - R 3
External conical threads where pressure-tight joints are made on the threads, defi ned by standard
UNI ISO 7/1
Conventional ø: 3”
UNI ISO 228/1 - G 4 B
Internal cylindrical threads where pressure-tight joints are not made on the threads, defi ned by
standard UNI ISO 228/1
Tolerance class B for external thread
Conventional ø: 4”
DN 80 PN 16Flange Nominal Diameter: 80 mm
Nominal Pressure: 16 bar
Notes:
Conventional diameter value [in inches] identifi es short thread
designation, based upon the relative standard.
All relative values are defi ned by standards.
As example, here below some values:
UNI ISO 7/1 UNI ISO 228/1
Conventional ø 1” 1”
Pitch 2.309 mm 2.309 mm
External ø 33.249 mm 33.249 mm
Core ø 30.291 mm 30.291 mm
Thread height 1.479 mm 1.479 mm
A5 NECS_0152_0612_200907_GB
NECS
HFC R134a
www.climaveneta.com
Climaveneta S.p.A.Via Sarson 57/c
36061 Bassano del Grappa (VI)
Italy
Tel +39 0424 509 500
Fax +39 0424 509 509
info@climaveneta.com
www.climaveneta.com
Climaveneta Home System Via Duca d’Aosta 121
31030 Mignagola (TV)
Italy
Tel +39 0422 4131
Fax +39 0422 413659
info.cvhs@climaveneta.com
www.climaveneta.com
Climaveneta France3, Village d’Entreprises
ZA de la Couronne des Prés
Avenue de la Mauldre
78680 Epône
France
Tel +33 (0)1 30 95 19 19
Fax +33 (0)1 30 95 18 18
info@climaveneta.fr
www.climaveneta.fr
Climaveneta DeutschlandRhenus Platz 2
59439 Holzwickede
Germany
Tel +49 2301 91222-0
Fax +49 2301 91222-99
info@climaveneta.de
www.climaveneta.de
Climaveneta
España - Top ClimaLondres 67, 1 4
08036 Barcelona
Spain
Tel +34 934 195 600
Fax +34 934 195 602
topclima@topclima.com
www.climaveneta.com
Climaveneta Chat Union
Refrig. Equipment Co Ltd88 Bai Yun Rd, Pudong Xinghuo
New dev. zone 201419 Shanghai
China
Tel 008 621 575 055 66
Fax 008 621 575 057 97
Climaveneta Polska Sp. z o.o.Ul. Sienkiewicza 13A,
05-120 Legionowo,
Poland
Tel +48 22 766 34 55-57
Fax +48 22 784 39 09
info@climaveneta.pl
www.climaveneta.pl
Recommended