Copyright © Hawaiian Electric Company, HELCO, and SEL 2016

Integrating Synchrophasors and Oscillography for Wide-Area

Power System AnalysisDora Nakafuji

Hawaiian Electric Company

Laura Rogers Hawaii Electric Light Company

Jared Bestebreur, Michael Rourke, and Greg ZweigleSchweitzer Engineering Laboratories, Inc.

Hawaii Electric Light Company (HELCO)

Map data ©2016 Google

50% Renewable Power Regularly Integrated

Challenges With Islanded SystemsSignificant Voltage, Frequency, and Power Swings

PMU Frequency

59.647 Hz

60.014 Hz

60.564 Hz

12:40:00 AM 12:53:20 AM 1:10:00 AM

Renewables Introduce Faster Dynamics

SCADA Misses Information

91.90 kW

62.31 kW

32.72 kW

4:27:00 PM 4:27:20 PM 4:27:40 PM

PMU Real PowerSCADA Real Power

• Post-fault event report is saved to IED’s nonvolatile memory

• Voltage and current measurements are sent to SCADA from IED or remote terminal unit (RTU) every few seconds

Traditional Monitoring and Analysis

IED

What Is an Event Report?

Prefault Data Post-Fault Data

• Currents• Voltages• Digitals

Fault DataIED

Report Analysis Before Software Tools

What Is a Synchrophasor?

Architecture for Data Synchronization

Correlation of Time-Stamped Data Types

• Remote download via communications processor• Local download at substation

Traditional Event Report Collection Systems

Clock

IRIG-BSCADA

Engineering

Communications Processor

Protective Relays

Defense-in-Depth Security Approach

Substation Perimeter

Serial Encryption, User Access Proxy

Switch

WAN

Zone 0

Zone 1

Zone 2

Zone 3

Protective Relays

Communications Processor or PDC

Local Collection for Simplicity

Protective Relays

Managed Ethernet Switch

Protective Relays

Report Collection

Communications Processor

Wide-Area Collection for High-Speed Networks

Substation IED Network

Substation IED Network

Substation IED Network

WAN

Report Collection

Hybrid Collection for Performance and Security

Protective Relays

Protective Relays

Report Collection

WAN

Communications Processor Communications Processor

Substation Substation

Architecture for Streaming Synchrophasors

Substation PMU/PDC Network

Substation PMU/PDC Network

Substation PMU/PDC Network

Web Client

WAN

Central PDC Synchrophasor Archive

Collection Architecture Implemented at HELCO

Control Center

Substation

Event Report DataSynchrophasor Data

WAN

Central PDC Synchrophasor Archive

Event Report Collection and Archive

Protective Relays

Switch

PDC

Communications Processor

Web Client

HELCO Lightning StrikePMU Frequency

59.647 Hz

60.014 Hz

60.564 Hz

12:40:00 AM 12:53:20 AM 1:10:00 AM

IED 1

IED 2

IED 3

59.647 Hz

60.014 Hz

60.564 Hz

12:40:00 AM 12:53:20 AM 1:10:00 AM

IED 1

IED 2

IED 3

Synchrophasors

IED Event Reports

Data Correlation for Added Context

59.647 Hz

60.014 Hz

60.564 Hz

12:40:00 AM 12:53:20 AM 1:10:00 AM

IED 1

IED 2

IED 3

Event Summary Data for Operations

IED Event Report Summary

Event Reports for Detailed Analysis

• Faster analysis of system events• Better understanding of renewable impact on system

during disturbances• Situational awareness for operations

HELCO Benefits

Questions?