HVDC Projects and Activities

Joerg Dorn, joerg.dorn@siemens.comPower Transmission and Distribution

IEEE PES General MeetingTampa - June, 27th 2007

2 26.06.2007 Power Transmission and DistributionJ. Dorn, PTD H 1T6

Neptune, USA, 2007

105 kmTransmission

dist.

Long distance

Sea Cable

Type of plant

Direct-light-triggered 8 kVThyristor voltage

500 kV DC, 230/345 kV,60 Hz

Voltage levels

660 MW, monopolarPower rating

New Jersey/New York

Long Island

Location

NeptuneProject name

Neptune RTSCustomer

3 26.06.2007 Power Transmission and DistributionJ. Dorn, PTD H 1T6

Ballia - Bhiwadi, India, 2009

800 kmTransmission

distance

Long distance

transmission

Type of plant

3600Number of

thyristors

Direct-light-triggered, 8 kVThyristor voltage

500 kV DC, 400 kV, 50 HzVoltage levels

2500 MW, bipolarPower rating

Uttar Pradesh province to

Rajasthan province

Location

Ballia-BhiwadiProject name

Powergrid Corporation of India

Ltd.

Customer

Delhi

Ballia

Bhiwadi

Delhi

Ballia

Bhiwadi

4 26.06.2007 Power Transmission and DistributionJ. Dorn, PTD H 1T6

Storebælt, Denmark, 2010

56 kmTransmission

distance

Submarine cable

transmission

Type of plant

1440Number of

thyristors

Direct-light-triggered, 8 kVThyristor voltage

400 kV DC, 400 kV, 50 HzVoltage levels

600 MW, monopolarPower rating

The islands Funen (Fyn) and

Zealand (Sjælland) in Denmark

Location

StorebæltProject name

Energinet.dkCustomer

5 26.06.2007 Power Transmission and DistributionJ. Dorn, PTD H 1T6

BritNed, UK – Netherlands, 2010*

Approximately 200 kmTransmission

distance

Submarine cable transmissionType of plant

3360Number of thyristors

Direct-light-triggered, 8 kVThyristor voltage

450 kV DC, 400 kV, 50 HzVoltage levels

1000 MW, monopolarPower rating

Isle of Grain on the southern bank

of the Thames Estuary in UK and

Maasvlakte west of Rotterdam in

the Netherlands

Location

BritNedProject name

BritNed Development Ltd. Customer

*Subject noticed to proceed

6 26.06.2007 Power Transmission and DistributionJ. Dorn, PTD H 1T6

Yunnan - Guangdong, China, 2010

1418 kmTransmission

distance

Long distance transmissionType of plant

5760Number of

thyristors

Direct-light-triggered, 8 kVThyristor voltage

800 kV DC, 525 kV, 50 HzVoltage levels

5000 MW, bipolarPower rating

Province Yunnan to province

Guangdong

Location

Yunnan-Guangdong ±800kV

UHVDC Transmission Project

Project name

China Southern Power Grid Co.,

Ltd.

Customer

7 26.06.2007 Power Transmission and DistributionJ. Dorn, PTD H 1T6

UHVDC Bushing at Test Lab TU Graz – Austria

800 kV DC Bushing in Test Field

8 26.06.2007 Power Transmission and DistributionJ. Dorn, PTD H 1T6

DC Reactor Testing

800 kV DC3,125 A75 mH28 tons !

9 26.06.2007 Power Transmission and DistributionJ. Dorn, PTD H 1T6

“Snapshots” from DC Valve Tower Testing

Dielectric Testing of Valve-Support Structure

10 26.06.2007 Power Transmission and DistributionJ. Dorn, PTD H 1T6

Power Quality for AC & DC Systems

Power Transmission and Distribution10

HVDCHVDCwithwith VSCVSC --

HVDCHVDC PLUSPLUS

11 26.06.2007 Power Transmission and DistributionJ. Dorn, PTD H 1T6

HVDC PLUS DevelopmentThe Modular Multilevel Converter - MMC

Low generation of harmonics

Low HF noise

Low switching losses

12 26.06.2007 Power Transmission and DistributionJ. Dorn, PTD H 1T6

Submodule Control

Phase UnitSubmodule

PLUSCONTROL

13 26.06.2007 Power Transmission and DistributionJ. Dorn, PTD H 1T6

Voltage generation

AC and DC voltages controlled by converter leg voltages:

+Ud/2

-Ud/2

Uac

Uac

14 26.06.2007 Power Transmission and DistributionJ. Dorn, PTD H 1T6

Two-level and Multilevel-Technology

)

Desired voltage Realized voltage

- Vd /2

0

+Vd /2

High harmonic DistortionHigh Stresses resulting in HF Noise

Low Generation of Harmonics

Low HF Noise

Low Switching Losses

Two-level technology Multilevel technology

15 26.06.2007 Power Transmission and DistributionJ. Dorn, PTD H 1T6

Steady-state simulations of MMC

PLOTS : Graphs

1.000 1.010 1.020

-250 -200 -150 -100 -50

0 50

100 150 200 250

U [k

V]+Ud -Ud US1 US2 US3

-2.00

-1.50

-1.00

-0.50

0.00

0.50

1.00

1.50

2.00

I [kA

]

is1 is2 is3

-1.50

-1.25

-1.00

-0.75

-0.50

-0.25

0.00

0.25

0.50

0.75

I [kA

]

i1p i2p i3p i1n i2n i3n

AC and DC terminal voltages

AC currents

Converter Phase Leg currents

16 26.06.2007 Power Transmission and DistributionJ. Dorn, PTD H 1T6

HVDC PLUS – The Smart Way

Compact Modular Design

Less Space Requirements

Advanced VSC Technology

DC cable transmission

DC overhead line transmission

Back-to-Back systems

Multi-terminal systems

STATCOM operation

17 26.06.2007 Power Transmission and DistributionJ. Dorn, PTD H 1T6

Thank you very much for your attention