View
5
Download
0
Category
Preview:
Citation preview
• Hardwiredoutputviaintegraljunctionbox
• Availablewithcordedorflexinput
• PureSineWavetechnologywithAutomaticVoltageRegulation toimprovethequalityofpowerprovidedtotheA/Vsystem
• Expansionbatteryoptionextendsruntimeintheeventof sustainedpoweroutages
• Surgesuppressionutilizesacleanline-to-neutraldesignthat doesnotpassnoisecontaminationtoground
• Internetenabledwithoptionalexpansioncord,whichincludes:
• RealtimeUPSmonitoringviatheWeb
• RemotemanagementandconfigurationofUPSviaWeb BrowserorNMS(NetworkManagementSystem)
• Auto-shutdowntoprotectservers/workstationsfromdata lossduetopowerfailure
• Scheduleshutdown/start-up/rebootoftheUPS
• EventloggingtotraceUPSoperationalhistory
• Dataloggingforanalyzingpowerconditions
• EventnotificationviaemailandSNMPtraps
• SupportsTCP/IP,SNMP/HTTP,NTP,DNS,SMTPprotocol
• MIB(ManagementInformationBase)provided
• Quickinstallationanduserfriendlyinterface
• UserupgradeablefirmwareviaFTP
• Securitymanagementprovided
• ControlsystemintegrationviaRS-232andUSBandanalogI/O
• Loadsheddingallowsextendedruntimeforsystem-critical componentsbydisconnectingpowertoless-criticalcomponents
• LineInteractiveTechnology
• PowerManagersoftwareallowsextensiveconfiguration andeventnotificationcapabilities
• EnergySaverdesignreducespowerconsumptionby upto75%whencomparedwithtraditionalUPSdesigns
• ULListedintheUSandCanada
HardwiredUninterruptible Power Supply
96-01160/rev.1/08-15-11
Hardwired Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems
96-01160/rev.1/08-15-11/HardwiredUninterruptiblePowerSupply
UPS-2200R-HH(front)
UPS-2200R-HH(Rear)
UPS-EBPR
EXCEPTIONAL SUPPORT & PROTECTION™
Features
c u s t o m i z a b l e s p e c i f i c at i o n c l i p s a v a i l a b l e at m i d d l e at l a n t i c . c o m
US: New Jersey • California • Illinois • Voice: 973-839-1011 Fax: 973-839-1976 • middleatlantic.comCanada: Ontario • British Columbia • Voice: 613-836-2501 Fax: 613-836-2690 • middleatlantic.ca
RackmountUninterruptiblePowerSupply(UPS)shallbeMiddleAtlanticProductsmodel#UPS-2200R-__(corded,flexinput,refertochart).UPSshallbelineinteractivewithAVR.Unitshallmeasure19.00”Wx3.50”Hx19.00”Dandoccupy2rackspaces.UPSshallhavearearmountingrangeof19”to32”andnotrequiremorethanonepersontomount.Unitshalloperateon120VAC/60Hzcurrent.Unitshallhaveanominaloutputof120V.Unitshallhaveacapacityof2,150VAand1,650W.Unitshallhave(2)NEMA5-20Rreceptaclesontherearoftheunit.UPS-2200R-CH/HHshallhaveahardwiredJ-Boxoutputandoneeachcritical/non-criticalloadNEMA5-20Rreceptacle.UnitshallbeIPenabledwhenusedwithoptionalIPExpansioncard,model#UPS-IPCARD.RackmountUPSshallincludea(36”flexcable,9’SignalSafe™powercordwithNEMA5-20Pplug,refertochart.UPSshallhavesurgesuppressionthatutilizesacleanline-to-neutraldesignthatdoesnotpassnoisecontaminationtoground.RackmountUPSshallhaveahotswappablebatterythatallowsfora8minuteruntimeathalfloadanda16minuteruntimeatfullload.Rearofunitshallhaveinputsthatallowfortheinstallationofupto10additionalhotswappablebatteries.RackmountUPSshallbeRoHSEUDirective2002/95/ECcompliant.RackmountUPSshallutilizeMiddleAtlanticPowerManager™software.RackmountUPSshallbewarrantiedtobefreefromdefectsinmaterialsandworkmanshipundernormaluseandconditionsforaperiodof3years;batteryshallbewarrantiedforaperiodof2years.RackmountUPSshallbeULlistedinUSandCanada.
UPS-IPCARDWebbasedcontrolshallbeenabledonnon-internetenabledMiddleAtlanticProductsUPSbyUPS-IPCARD,whichshallbeinstalledintotheExpansionPortontherearoftheUPS.ThisshallbecompatiblewithUPSfirmwarev1.65orgreater,andprovidefullfunctionalitywhenusedonmodelswithfirmwarev1.75orgreater.
ExpansionBatteryRackmountexpansionbatterypackshallbeMiddleAtlanticProductsmodel#UPS-EBPR.ExpansionbatterypackshallbesuitableforusewithUPS-2200R-HH/CH.UPS-EBPRshallmeasure19.00”Wx3.50”Hx19.29”Dandoccupy2rackspaces.With__hotswappablebatteriesconnectedtotheunit,thereisa__minuteruntimeathalfloadanda__minuteruntimeatfullload(refertochart).Rackmountexpansionbatterypackshallbewarrantiedforaperiodof2years.
ReplacementBatteryReplacementBatteryPackfortheUPSshallbeMiddleAtlanticProductsmodel#UPS-RBP.ReplacementbatterypackshallbesuitableforusewithUPS-2200R-HH/CH.Replacementbatteryshallbewarrantiedtobefreefromdefectsinmaterialsandworkmanshipundernormaluseandconditionsforaperiodof2years.
Architects and Engineers’ Specifications
US: New Jersey • California • Illinois • Voice: 973-839-1011 Fax: 973-839-1976 • middleatlantic.comCanada: Ontario • British Columbia • Voice: 613-836-2501 Fax: 613-836-2690 • middleatlantic.ca
TOP VIEW BOTTOM VIEW
FRONT VIEW (UPS-EBPR) REAR VIEW (UPS-EBPR)
UPS basic dimensionsAll dimensions in inches unless otherwise noted [All dimensions in brackets are in millimeters]
SIDE VIEW SIDE VIEW
FRONT VIEW REAR VIEW
EXPANSION BATTERY CONNECTOR
HARDWIRED OUTPUTACCESS PANEL
SERIALCONTROL PORTS
20A CIRCUIT BREAKER
ETHERNET SURGEPROTECTION
CATV SURGE PROTECTION
CORD/FLEXCABLE
IP CARD EXPANSION PORT(ORDER P/N UPS-IPCARD)2X NEMA5-20R (UPS-2200R-HH)
2X NEMA5-20R (UPS-2200R-CH)(1X CRITICAL LOAD/1X NON CRITICAL LOAD)
POWER SWITCH
FUNCTION SELECT
LCD DISPLAY
3.465[88]
AC INPUT
19.29 [490]
REAR MOUNTING
RANGE19” [483]
TO 32” [813]
17.829[452.9]
19.00 [483]
19.00 [483]
17.047 [433]
48V DC BATTERY OUTPUT
48V DC BATTERY INPUT
POWER SWITCH
AC OUTPUT NEMA5-15R
US: New Jersey • California • Illinois • Voice: 973-839-1011 Fax: 973-839-1976 • middleatlantic.comCanada: Ontario • British Columbia • Voice: 613-836-2501 Fax: 613-836-2690 • middleatlantic.ca
GeneralInformation
ModelNo. UPS-2200R-CHSeries UPS-2200R-HHSeries
Input
NominalInputVoltage 120V 120V
InputVoltageRange 80VAC–145VAC 80VAC–145VAC
InputFrequency 60Hz+/-3Hz(autosensing) 60Hz+/-3Hz(autosensing)
InputProtectionType Resettablethermalfuse Resettablethermalfuse
CordLength/CordType/PlugType 9ft./12/3/NEMA5-20P 36”flexinput
Output
GreenModeConsumption Lessthan9Watfullbatterycapacity Lessthan9Watfullbatterycapacity
NominalOutputVoltage 120V 120V
Capacity(VA) 2150VA 2150VA
Capacity(Watts) 1650W 1650W
Waveform PureSineWave PureSineWave
OnLineOutputFrequency 57-63Hzfor60Hznominal 57-63Hzfor60Hznominal
OnBatteryOutputFrequency 60Hz+/-.1Hz 60Hz+/-.1Hz
TransferTime(Typical) 4mstypicallinetobattery/batterytoline 4mstypicallinetobattery/batterytoline
OverloadProtection(onlinemode) 100%≤Load<110%warning,120secshutdown110%≤Load<125%warning,40secshutdown125%≤Loadwarning,10secshutdown
100%≤Load<110%warning,120secshutdown110%≤Load<125%warning,40secshutdown125%≤Loadwarning,10secshutdown
OverloadProtection(onbatterymode) 100%≤Load<110%warning,30secshutdown110%≤Load<125%warning,10secshutdown125%≤Loadwarning,3secshutdown
100%≤Load<110%warning,30secshutdown110%≤Load<125%warning,10secshutdown125%≤Loadwarning,3secshutdown
SurgeProtectionandFiltering UPS-2200R-CHSeries UPS-2200R-HHSeries
Lightning/SurgeProtection L-N=>381J(127Jx3)Clampvoltage270V(Maxenergy10/1000µs)
L-N=>381J(127Jx3)Clampvoltage270V(Maxenergy10/1000µs)
RJ11/RJ45Protection Sidactorx1ClampVoltage275VFuse(.75A/250V)x2
Sidactorx1ClampVoltage275VFuse(.75A/250V)x2
Physical
OutputReceptacles (2)NEMA5-20RReceptacles,J-Box (2)NEMA5-20RReceptacles,J-Box
Dimensions(in.) 19.00”[423]Wx3.50”[89]Hx19.29”[490]D 19.00”[423]Wx3.50”[89]Hx19.29”[490]D
Weight(lb.) 77lbs. 77lbs.
Battery
Rating 12V/9.0AHx4 12V/9.0AHx4
AutoCharger 1A 1A
HotSwappableExternalBattery Yes Yes
RunTimeatHalfLoad 13minutes 13minutes
RunTimeatFullLoad 6.4minutes 6.4minutes
WarningDiagnostics
ControlPanel LCDDisplayIndicators,PowerOn LCDDisplayIndicators,PowerOn
AudibleAlarms OnBattery,LowBattery OnBattery,LowBattery
Environmental
OperatingTemperature 32°Fto104°F(0°Cto40°C) 32°Fto104°F(0°Cto40°C)
OperatingRelativeHumidity 0to95%Non-Condensing 0to95%Non-Condensing
TotalHarmonicDistortion(THD)
TotalSystemLoad 0% 20% 60% 100%
UtilityMains*THD 2.0% 2.0% 2.0% 2.0%
BatteryBackupTHD 1.9% 1.3% 1.5% 5.2%*typical120Vpowerwith2%-4%THD
US: New Jersey • California • Illinois • Voice: 973-839-1011 Fax: 973-839-1976 • middleatlantic.comCanada: Ontario • British Columbia • Voice: 613-836-2501 Fax: 613-836-2690 • middleatlantic.ca
Communication UPS-2200R-CHSeries UPS-2200R-HHSeries
Software MiddleAtlanticPowerManager™ MiddleAtlanticPowerManager™
Management
Self-Test ManualSelf-Testviafrontpanel ManualSelf-Testviafrontpanel
Auto-Charger/Auto-Restart Yes Yes
COMInterface Primary: -RS232Communication+Control -AnalogStatusNotification+Control
Secondary: -Analogstatusnotificationonly
Primary: -RS232Communication+Control -AnalogStatusNotification+Control
Secondary: -Analogstatusnotificationonly
Built-inUSBInterface Yes Yes
UPS-2200RSeries
Load(VA) 120 240 360 480 600 720 840 960 1080 1200 1320 1440 1560 1680 1800 1920
Load(W)* 90 180 270 360 450 540 630 720 810 900 990 1080 1170 1260 1350 1440
Load(A) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Numberofexpansionbatteries
ESTIMATEDRUNTIME(Minutes)
UPSonly 102 51 34 26 20 17 15 13 11 10 9 9 8 7 7 6
1 561 283 190 143 114 94 80 69 60 53 47 42 37 33 29 26
2 1020 515 345 260 207 171 145 125 109 96 84 75 66 58 51 45
3 1479 747 501 377 300 249 211 181 158 139 122 108 95 84 74 64
4 1938 979 657 494 394 326 276 238 207 181 160 141 124 109 96 84
5 2397 1211 813 611 487 403 341 294 256 224 197 174 153 135 118 103
6 2856 1443 968 728 580 480 407 350 305 267 235 207 182 161 141 122
7 3315 1676 1124 845 674 557 472 406 353 310 272 240 212 186 163 142
8 3774 1908 1280 962 767 635 537 463 402 352 310 273 241 212 185 161
9 4233 2140 1435 1079 860 712 603 519 451 395 348 306 270 237 208 181
10 4692 2372 1591 1196 954 789 668 575 500 438 385 339 299 263 230 200
*AssumingaPowerFactorof.75
US: New Jersey • California • Illinois • Voice: 973-839-1011 Fax: 973-839-1976 • middleatlantic.comCanada: Ontario • British Columbia • Voice: 613-836-2501 Fax: 613-836-2690 • middleatlantic.ca
UtilityVoltage(AC) ≤80 81-105 106-133 133-147 >147
FansEngaged Front&Rear Rearonly None RearOnly Front&Rear
dBAaboveAmbient 27dBA 14dBA 0 14dBA 27dBA
Recommended