20
08/2
011
Design1. Dual wall tube.2. Stress control tube.3. Stress control mastic.4. Non-tracking tube (only for
36GTS1).5. Overall protection tube.6. Sealing mastic.7. Screen continuity (copper
mesh).8. Conductor connector
(supplied on request).9. Ferrule for screen wires.
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV19/33 (36) kV
Specifications and standardsMeets the requirements of CENELEC HD 629.2 andIEC 60502-4.
Up to 36 kV
GTS1HEAT-SHRINKABLE
SINGLE CORE XLPESTRAIGHT JOINT
ApplicationFor jointing polymeric cable to be laid in air or directly buried. The product is fully screened and fully submersible.
Straight Jointtype
VoltageUm(kV)
Length“L”
(mm)
Conductor sizes(mm2)
min max17GTS1
24GTS1
36GTS1
12 & 17.5
24
36
600 - 750
600 - 750
750 - 1000
25
25
35
630
630
800
6
2
9
7
3
4
8
1
5
L
21
Kit contentsThe complete GTS1 joint kit comprises the following components:
Ordering instructionsSelect the part number corresponding to both system voltage and conductor size.
Example:The copper wire screened cable is 12 kV, 150 mm² stranded aluminium.Order: 17GTS1.240w.
Orderingpart
number
VoltageU0/U(kV)
Conductor size range(mm2)
min max
17GTS1.50w17GTS1.95w
17GTS1.240w17GTS1.630w
17GTS1.1000w
24GTS1.50w24GTS1.240w24GTS1.400w24GTS1.630w
24GTS1.1000w
36GTS1.95i36GTS1.240i36GTS1.500i36GTS1.800i
36GTS1.1200i
6/10 & 6.35/11 & 8.7/156/10 & 6.35/11 & 8.7/156/10 & 6.35/11 & 8.7/156/10 & 6.35/11 & 8.7/156/10 & 6.35/11 & 8.7/15
12/20 & 12.7/2212/20 & 12.7/2212/20 & 12.7/2212/20 & 12.7/2212/20 & 12.7/22
18/30 & 19/3318/30 & 19/3318/30 & 19/3318/30 & 19/3318/30 & 19/33
255095240630
2535150300630
3570185500630
50952406301000
502404006301000
952405008001200
The kit also comprises installation instructions, semi-conductive tape, adhesive tape, a copper braid and a ferrule for the screen wire connection.
+
Sealing mastic
“NGAF”
Black stress control tube
“GT1”
Anti-tracking tube “GT2”
(only for36GTS1)
Stress control mastic
“MNAC”
=+ + XXGTS1straightjoint kit
++
Overallprotection
tube“GT4”
Roll of tinned copper mesh
tape
+
Dualwalltube
“GT25”
For use with copper wire screened cables.No further earthing device is necessary.
For use with coppertape screened cables.
Order: -Aw/-Aiinstead of -w/-i
(e.g. 17GTS1.240Aw).
For use with other cable types.
Please contact our representative.
For use with three-core cables:
see GTS3.
When jointing cables of different sizes,
please contact our representative.
Can be supplied with all common types of
conductor connectors.
22
08/2
011
GTS3HEAT-SHRINKABLE THREE CORE XLPE
STRAIGHT JOINT
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV19/33 (36) kV
Specifications and standardsMeets the requirements of CENELEC HD 629.2 andIEC 60502-4.
Up to 36 kVApplicationFor jointing three core polymeric cable to be directly buried. The product is fully screened and fully submersible.
Straight Jointtype
VoltageUm(kV)
Length“L”
(mm)
Conductor sizes(mm2)
min max17GTS324GTS336GTS3
12 & 17.52436
1200 - 16001200 - 16001400 - 1800
252535
400400400
Design1. Dual wall tube.2. Stress control tube.3. Screen continuity (copper
mesh).4. Stress control mastic.5. Overall protection tube.6. Sealing mastic.7. Canister. 8. Conductor connector
(supplied on request).9. Non-tracking tube (only for 36GTS3 - not shown).
5
6
6
8
3
1
2
7
4
L
23
Ordering instructionsSelect the part number corresponding to both system voltage and cable dimensions.
Example:The cable is 24 kV, 3 x 120 mm2 stranded aluminium with an individual copper tape screen and a steel wire armour.Order: 24GTS3.240k.
Orderingpart
number
VoltageU0/U(kV)
Conductor size range(mm2)
min max
17GTS3.50k
17GTS3.95k
17GTS3.240k
17GTS3.400k
24GTS3.50k
24GTS3.240k
24GTS3.400k
36GTS3.95k
36GTS3.240k
36GTS3.400k
6/10 & 6.35/11 & 8.7/15
6/10 & 6.35/11 & 8.7/15
6/10 & 6.35/11 & 8.7/15
6/10 & 6.35/11 & 8.7/15
12/20 & 12.7/22
12/20 & 12.7/22
12/20 & 12.7/22
18/30 & 19/33
18/30 & 19/33
18/30 & 19/33
16
50
95
185
25
50
150
35
70
150
50
95
240
400
50
240
400
95
240
400
Different types of screen continuity kits can be supplied.
Please contact our representative.
Kit contentsThe complete GTS3 joint kit comprises the following components:
The kit also comprises installation instructions, semi-conductive tape, adhesive tape, a copper braid, tinned copper mesh tape, armour continuity roll springs and a ferrule for the screen wire connection.
+
Sealing mastic
“NGAF”
Black stress control tube
“GT1”
Stress control mastic
“MNAC”
=+ + XXGTS3straightjoint kit
++
Dual walltube
“GT25”
Overallprotection
tube“GT8”
Canister
+
Protection tube
“GT3”
When jointing cablesof different sizes,
please contact our representative.
For use with single core cables:
see GTS1.
Can be supplied with all common types of
conductor connectors.
For use with copper wire screened cables.No further earthing device is necessary.
For use with other cable types.
Please contact our representative.
24
08/2
011
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV19/33 (36) kV
Up to 36 kV
GTM3HEAT-SHRINKABLE
THREE CORE TRANSITION JOINT
ApplicationFor jointing three-core paper cables (draining and non-draining) to three core polymeric cables. For use with belted or screened (Höchstädter) cables with a common lead sheath. This transition joint is fully screened, submersible and suitable to be directly buried.
Straight Jointtype
VoltageUm(kV)
Length“L”
(mm)
Conductor sizes(mm2)
min max17GTM3
24GTM3
36GTM3
12 - 17.5
24
36
1200 - 1400
1600 - 1800
1800 - 2100
25
25
35
400
400
400
Specifications and standardsMeets the requirements of CENELEC HD 629.2 andIEC 60502-4.
Design 1. Dual wall tube. 2. Stress control tube. 3. Screen continuity (copper mesh). 4. Stress control mastic. 5. Overall protection tube. 6. Sealing mastic. 7. Canister. 8. Conductor connector (supplied on request). 9. Non-tracking tube (only for 36GTM3 - not shown). 10. Barrier tube. 11. Semi-conductive break-out. 12. Semi-conductive tubes. 13. Stress control mastic. 14. Semi-conductive tape.
5
13
6
14
11
12
10
7
2
1
4
8
3
6
L
25
+ +
Black stress control tube
“GT1”
=+ +
Dual walltube
“GT25”
Overallprotection
tube“GT8”
Canister
+
Protection tube
“GT3”
Ordering instructionsSelect the part number corresponding to both system voltage and cable dimensions.
Example:The three core belted cable is12 kV, 3 x 150 mm², non-draining, armoured and must be jointed to a three core 12 kV, 150 mm² XLPE cable.Order: 17GTM3.240K.
Orderingpart
number
VoltageU0/U(kV)
Conductor size range(mm2)
min max
17GTM3.50K
17GTM3.95K
17GTM3.240K
17GTM3.400K
24GTM3.50K
24GTM3.240K
24GTM3.400K
36GTM3.95K
36GTM3.240K
36GTM3.400K
6/10 and 8.7/15
6/10 and 8.7/15
6/10 and 8.7/15
6/10 and 8.7/15
12/20
12/20
12/20
18/30
18/30
18/30
16
50
95
240
25
50
150
35
70
150
50
95
240
400
50
240
400
95
240
400
For transition to threesingle core
XLPE cables: see GTM.3.1.
Different armour connections are
available. Please contact our
representative.
Kit contentsThe complete GTM3 joint kit comprises the following components:
The kit also comprises installation instructions, semi-conductive tape, Hi-K mastic, sealing mastic “NGAF”, adhesive tape, copper braid, tinned copper mesh tape, armour continuity and roll springs.
XXGTM3transition joint kit
For use with other cable types.
Please contact our representative.
+ +
Barriertube
“GT10”
Can be supplied with all common types of
conductor connectors.
For use withPICAS cables.
Please contact our representative.
When jointing cables of different sizes,
please contact our representative.
Semi-conductive break-out“36TTS”
Semi-conductive
tube“GT5”
26
08/2
011
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV19/33 (36) kV
Specifications and standardsMeets the requirements of CENELEC HD 629.2 andIEC 60502-4.
Up to 36 kV
GTM3.1HEAT-SHRINKABLE
THREE CORE TRANSITION JOINT
ApplicationFor jointing three-core paper cables (draining and non-draining) to three single core polymeric cables. For use with belted or screened (Höchstädter) cables with a common lead sheath. This transition joint is fully screened, submersible and suitable to be directly buried.
Straight Jointtype
VoltageUm(kV)
Length“L”
(mm)
Conductor sizes(mm2)
min max17GTM3.1
24GTM3.1
36GTM3.1
12 - 17.5
24
36
1800
1800
1800 - 2300
25
25
35
400
400
400
Design 1. Dual wall tube. 2. Stress control tube. 3. Protection tube. 4. Hi-K mastic. 5. Sealing mastic. 6. Screen continuity (copper braid and mesh). 7. Conductor connector (supplied on request). 8. Semi-conductive break-out. 9. Semi-conductive tubes. 10. Barrier tube. 11. Break-out.
3
3
8
10
5
4
6
9
7
1
2
4
5
11
L
27
Ordering instructionsSelect the part number corresponding to both system voltage and cable dimensions.
Example:The three core belted cable is 12 kV, 3 x 150 mm², non-draining, armoured and must be jointed to a three single core12 kV, 150 mm² XLPE cables.Order: 17GTM3.1.240i.
Orderingpart
number
VoltageU0/U(kV)
Conductor size range(mm2)
min max
17GTM3.1.50W
17GTM3.1.95W
17GTM3.1.240W
17GTM3.1.400W
24GTM3.1.50W
24GTM3.1.240W
24GTM3.1.400W
36GTM3.1.95i
36GTM3.1.240i
36GTM3.1.400i
6/10 and 8.7/15
6/10 and 8.7/15
6/10 and 8.7/15
6/10 and 8.7/15
12/20
12/20
12/20
18/30
18/30
18/30
25
50
95
240
25
50
150
35
70
150
50
95
240
400
50
240
400
95
240
400
When jointing cables of different sizes,
please contact our representative.
For use withPICAS cables.
Please contact our representative.
For use with other cable types,
please contact our representative.
For transition to three core XLPE cables:
see GTM3.
Can be supplied with all common types of
conductor connectors.
Different armour connections are
available. Please contact our
representative.
Kit contentsThe complete GTM3.1 joint kit comprises the following components:
The kit also comprises installation instructions, semi-conductive tape, Hi-K mastic, stress control mastic, sealing mastic “NGAF”, adhesive tape, copper braid, tinned copper mesh tape, armour continuity and roll springs.
+
Semi-conductive tube “GT5”
Protection tube
“GT3”
=+ XXGTM3.1transitionjoint kit
+
Dual walltube
“GT25”
Barriertube
“GT10”
+
Break-out“36TTE”
Black stress control
tube “GT1”
++
Semi-conductive break-out“36TTS”
28
08/2
011
Design 1. Dual wall tube. 2. Hi-K mastic. 3. Stress control tube. 4. Conductor connector (supplied on request). 5. Semi-conductive break- out. 6. Barrier tube. 7. Semi-conductive tubes. 8. Canister. 9. Screen continuity (copper braid and mesh). 10. Overall protection tubes.
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV19/33 (36) kV
Specifications and standardsMeets the requirements of CENELEC HD 629.2 andIEC 60502-4.
Up to 36 kV
GTC3HEAT-SHRINKABLE THREE CORE PILCSTRAIGHT JOINT
Straight Jointtype
VoltageUm(kV)
Length“L”
(mm)
Conductor sizes(mm2)
min max
17GTC3
24GTC3
36GTC3
12 - 17.5
24
36
1800
1600 - 1800
1800 - 2100
25
25
35
240
400
400
ApplicationFor jointing three-core paper cables (draining and non-draining). For use with belted or screened (Höchstädter) cables with a common lead sheath. This joint is fully screened, submersible and suitable to be directly buried.
4
2
1
3
8
7
6
5
9
2
10
L
29
Ordering instructionsSelect the part number corresponding to both system voltage and conductor size.
Example:The cable is 24 kV, 3 x 120 mm2 stranded aluminium, with non-draining paper insulation.It has an individual tape screen and a steel wire armour.Order: 24GTC3.240k.
Orderingpart
number
VoltageU0/U(kV)
Conductor size range(mm2)
min max
17GTC3.50k
17GTC3.95k
17GTC3.240k
17GTC3.400k
24GTC3.50k
24GTC3.240k
24GTC3.400k
36GTC3.95k
36GTC3.240k
36GTC3.400k
6/10 and 8.7/15
6/10 and 8.7/15
6/10 and 8.7/15
6/10 and 8.7/15
12/20
12/20
12/20
18/30
18/30
18/30
16
50
95
240
25
50
150
35
70
150
50
95
240
400
50
240
400
95
240
400
Kit contentsThe complete GTC3 joint kit comprises the following components:
= XXGTC3straightjoint kit
+
Protection tube
“GT8”
+
Canister
The kit also comprises installation instructions, semi-conductive tape, Hi-K and stress control mastic, sealing mastic “NGAF”, adhesive tape, copper braid, tinned copper mesh tape, armour continuity and roll springs.
When jointing cables of different sizes,
please contact our representative.
For use withPICAS cables.
Please contact our representative.
For use with individual lead screened cables,please contact our
representative.
Can be supplied with all common types of
conductor connectors.
For use withXLPE cables: see GTS3.
For use with single core cables,
please contact our representative.
Semi-conductive tube “GT5”
+
2 x Protection tube
“GT3”
Dual walltube
“GT25”
Barriertube
“GT10”
+++
2 x Semi-conductive break-out“36TTS”
Recommended