FireFinder XLS System Basics (12!10!04)1

Preview:

Citation preview

Siemens Building Technologies Fire Products DivisionCompany Confidential

FireFinder XLSSystem Basics

Siemens Building Technologies Fire Products DivisionCompany Confidential

Fire Alarm System Basics

System & Processor

Inputs Outputs

An

nu

nc

iatio

n

& C

on

trol

Siemens Building Technologies Fire Products DivisionCompany Confidential

Inputs

Manual pull stations• HMS-S, HMS-D, HMS-SA, HMS-M, HMS-2S

Monitor points (Transmit-Receive Interface, or TRI)• HTRI-S, HTRI-D, HTRI-R, HTRI-M• Used for waterflow, tamper, security, damper• Relay output available

Conventional Zone Module – HZM Short circuit isolator – HLIM Intelligent LEDs

• ILED-HC, ILED-HW Detectors

• Bases – DB-11, DB-HR, ADBH-11, AD-11P, AD-HR• Detectors – HFP-11, HFPT-11

– FirePrint!

Inputs

Siemens Building Technologies Fire Products DivisionCompany Confidential

What is FirePrint?

A revolutionary fire detection method that distinguishes between a fire’s unique “fingerprint” and deceptive phenomena, and reports only real fires.

11 different selectable applications FirePrint is NOT a fancy form of “alarm

verification/confirmation”• Makes decisions based on obscuration/temperature/time

Siemens offers the No False Alarm Guarantee• If the system is designed and maintained properly, Siemens

will pay any fines associated with false alarms from FirePrint detectors

• No other manufacturer offers this guarantee

• Since 1997, total fines paid out equals $0!

Inputs

Siemens Building Technologies Fire Products DivisionCompany Confidential

DPU Device Programming Unit

Tests/addresses both MXL and FireFinder XLS devices• Not used for XL3 devices

Built in loop tester!• Have contractor test all loop wiring & devices before panel

gets there!• Indicates # & type of devices, and what device is at what

address• Finds multiple response addresses• Ground faults, activations indicated

Connection to label printer• Prints loop # & address• Multiple copies available

Inputs

Siemens Building Technologies Fire Products DivisionCompany Confidential

DLC – Device Loop Card

Plug-in card 252 devices on a loop! 1 or 2 loops per card

• T-tapped inside card• Total 252 total devices in any combination

50 cards/100 loops per system 2500 devices per system Non-twisted, non-shielded wire

• Great for retrofits! Wire is POLARITY INSENSITIVE (SureWire) Smart Degrade capability

• Loop accessories/outputs operate in Degrade

Inputs

Siemens Building Technologies Fire Products DivisionCompany Confidential

CDC-4 Conventional Detector Card

Plug-in card 4 conventional detection circuits Optional Alarm Verification Supports Siemens conventional detectors & circuit

closure devices Supports select COMPETITIVE conventional detectors

• Check the installation instruction in the Tech Support area of the website

Inputs

Siemens Building Technologies Fire Products DivisionCompany Confidential

PMI – Person/Machine Interface

Main operator interface & central processor Large graphics screen for events, details, icons &

bitmaps System event LEDs Large lighted buttons – prompts users through system

operation “More Info” button – users get to detail & map screens Touch screen for reports and maintenance

System Processor

An

nu

nc

iatio

n

& C

on

trol

Siemens Building Technologies Fire Products DivisionCompany Confidential

Lighted buttons to prompt user

Partial System Disable

Audible Status

-Large 6” display with touch screen

System Status LED’s

Menu Access

Navigation Controls

HELP

Siemens Building Technologies Fire Products DivisionCompany Confidential

ALARM SUPERVISORY SECURITY TROUBLE

POWER

ON

AUDIBLES

SILENCED

PARTIAL SYS

DISABLED

MORE

INFO

Siemens Building Technologies Fire Products DivisionCompany Confidential

ALARM SUPERVISORY SECURITY TROUBLE

POWER

ON

AUDIBLES

SILENCED

PARTIAL SYS

DISABLED

Siemens Building Technologies Fire Products DivisionCompany Confidential

ALARM SUPERVISORY SECURITY TROUBLE

POWER

ON

AUDIBLES

SILENCED

PARTIAL SYS

DISABLED

Siemens Building Technologies Fire Products DivisionCompany Confidential

Enclosures

CAB1• Supports 1 row (4 module spaces) with PTB & batteries

CAB2• Supports 2 rows (8 module spaces) with PTB & batteries

CAB3• Supports 3 rows (12 module spaces) with PTB & batteries

Transponder enclosures• Same as CAB enclosures w/ grill outer doors

REMBOX2• Supports 2 inner door rows• No card cages

REMBOX4• Supports 4 inner door rows• No card cages

CAB-BATT Battery Box• For 55 AH, 100 AH batteries

System Processor

CAB1Small enclosure (one row) Ships complete:

• back box• inner door• outer door• module mounting plate

(CAB-MP)• door lens (OD-LP)

Options:• CAB1R (red version)• Tamper switch (HTSW-1)• Semi-flush trim kit (CAB1-TK)

CAB2 Medium

Enclosure (2 row)

CAB2 Ships complete:

• CAB2-BB• CAB2-BD• (2) CAB-MP’s• (1) OD-LP

Requires either (1):• OD-LP (lens)• OD-BP (blank)• OD-GP (grill)

Options:CAB2R (red version)CAB-2TK (semi-flush trim kit)

CAB-3 Large Enclosure

(3 row) CAB3 Ship Complete

• CAB3-BB • CAB3-BD• (3) CAB-MP’s• (1) OD-LP

Requires either (2):• OD-LP (lens)• OD-BP (blank)

• OD-GP (grill)

Options:CAB3R (red version)CAB-3TK (semi-flush trim kit)

Siemens Building Technologies Fire Products DivisionCompany Confidential

Remote “Lobby” EnclosuresREMBOX2 and REMBOX4

REMBOX2• Space for (2) inner door

modules. • Typically LVM and up to

(4) SCM-8’s • Optional plate to mount

(4) OCM-16 or SIM-16• Local tamper switch

option (HTSW-1)• Semi-flush or surface

mounting. No trim kit needed.

REMBOX4• Space for (4) inner door

modules. Typically LVM and SCM-8’s.

• Optional plate to mount (8) OCM-16 or SIM-16

• Local tamper switch option (HTSW-1)

• Semi-flush or surface mounting. No trim kit needed.

System Processor

Siemens Building Technologies Fire Products DivisionCompany Confidential

CC-5/CC-2 Card cages

All wiring lands on removable terminal blocks All cards fit in the same card cage

• No separate Fire/Voice card cages Efficient card mounting

• 10 cards in 19”w x 14”h row– MXL – 6 cards in 19”w x 17”h row

• Less space required = less/smaller enclosures 60 pin bus between all cardcages

• Connected by 1 cable!

System Processor

Siemens Building Technologies Fire Products DivisionCompany Confidential

All cards same size and plug into CC-5/CC-2 cardcages

Thumb screws for handles & to keep cards in place

Power limited Field wiring (top)

Non-Power limited internal wiring

(bottom)

Power input to cards from PSC-12/PSX-12 or ZAC/ZAM

amplifiers

Out of enclosure to field devices or remote enclosures

60 pin bus - power, data, communications etc.

Removable terminal blocks (with covers)

Card guides removable for easy wiring access in enclosure - mounted with (2) captive screws each.

Labels to identify which card goes in which slot.

Siemens Building Technologies Fire Products DivisionCompany Confidential

PSC-12/PSX-12 Power Supplies

Filtered & Regulated 12 amp 24VDC supply• 5 amp continuous use

120 to 240 volt AC input, 50/60 Hz. PSC-12 – Battery charger for 100AH batteries

• New batteries – BTX-3 PSX-12 – Power only (no charger) to

extend power in cabinet Four 2-amp Form “C” relays built in

• Alarm, trouble, 2 programmable

System Processor

Siemens Building Technologies Fire Products DivisionCompany Confidential

ZIC-4A – Zone Indicating Card

Plug-in card Four Class A or B circuits Used as

• NAC – horn or strobe• Speaker circuit – 1 or 2 channel• Releasing circuit• Municipal Tie/Leased Line• Bell follower (NAC extender)

4 Amp capacity per circuit (96 Watts speaker)

Outputs

Siemens Building Technologies Fire Products DivisionCompany Confidential

CRC-6 Controllable Relay Card

Six independently controlled Form C relays 4 amps 30VDC/120VAC (resistive) 3.5 amps 120VAC (inductive @ 0.6 p.f.) Coils supervised Status and troubleshooting LEDs built in

Outputs

Siemens Building Technologies Fire Products DivisionCompany Confidential

SSD System Status Display

4 x 40 character LCD display Local sounder & scroll buttons Acknowledge/Silence/Reset capabilities on SSD-C

• Keyswitch activates control buttons Can be mounted in a larger enclosure

• Model SSD-C-REM Up to 32 on a system!

SSD-C

An

nu

nc

iatio

n

& C

on

trol

Siemens Building Technologies Fire Products DivisionCompany Confidential

RPM Remote Peripheral Module

Two serial ports & 1 parallel port Mounts in its own enclosure

• Can be mounted under desk Used for

• Printer connection (PAL-1)– No VDT connection available

• FSI connection• Apogee Insight Life Safety system connection

OutputsA

nn

un

cia

tion

& C

on

trol

Siemens Building Technologies Fire Products DivisionCompany Confidential

FireFinder XLS – Module review (vs. MXL)

FireFinder XLS MXL PMI MMB-2, MMB-3, MKB-4 DLC ALD-2I ZIC-4A CSM-4 PSC-12/PSX-12 MPS-6/12 CC-5/CC-2 MOM-4/MOM-2 CAB1, CAB2, CAB3 MSE-2, MME-3, MLE-6 CRC-6 CRM-4 SSD, SSD-C RCC-1, RCC-2 RPM PIM-1, PIM-2

Siemens Building Technologies Fire Products DivisionCompany Confidential

FireFinder XLSSystems Basics

Thank You!Mark Pavlica

Product Manager

Siemens Fire Safety

mark.pavlica@siemens.com