Environmental Systems 1

Danielle Morrison Judith Shoucair Lisa Martinez

Rome, Italy

Latitude: 41° 54‘ 0” N Longitude: 12° 30‘ 0” E

Rome, Italy

Latitude: 41° 54‘ 0” N Longitude: 12° 30‘ 0” E

Kitchen

Sleeping

Bathroom

Living Area

NSITE PLANScale:14" = 1'-0"

3'-4"

4'-4"

4'-10"2'-6" 3'-4"

3'-4"

3'-4"

4'

4'-4"

2'-8"3'-4"2'-10"2'-4"

SITE SECTIONScale:14" = 1'-0"

Kitchen

Sleeping

Bathroom

PLANScale:14" = 1'-0"

Living Area

SECTION B1" = 1'-0"

SECTION A1

Kitchen

Sleeping

Bathroom

Living Area

B

A

Scale:1/4"= 1'-0"

E ELEVATION

N ELEVATIONS ELEVATION

W ELEVATION

Scale: 3/16"= 1'-0"

maltwick
Sticky Note
terrible image
maltwick
Sticky Note
What time of year? how are you using this?

SUN DIAGRAM (SUMMER SOLSTICE)

SUN DIAGRAM (WINTER SOLSTICE)

9:00 AM

2:00 PM

9:00 AM

2:00 PM

Scale: 3/16"= 1'-0"

N

maltwick
Sticky Note
wind diagram shows the wind from the other direction. which is it?

Marble StuccoConcrete Concrete Ceramic Tiles

Ceramic Tiles

2x4 Wood Asphalt Shingles

1" Foam Board Insulation

FLOOR DETAILFoam Board InsulationLinoleum TileConcrete

WALL DETAILConcreteMarble StoccoFoam Board Insulation

ROOF DETAILFoam Board Insulation

Asphalt Shingles

R-VALUE5.4.5.8

R-VALUE.8125.4

R-VALUE5.4

.5

.44

1" Foam Board Insulation

2 x 4 Wood Studs 4.38Linoleum Tile

Solid Core Flush 3.7DOOR DETAIL R-VALUE

Double Insulating Glass 2.04WINDOW DETAIL R-VALUE

(1/2") air space

Windows: [(6 x 3') x 2 ] + (2 x 3') + (3 x 3')AREAS

Doors: 3 x (7 x 3')51 ft.sq.63 ft.sq.

DETAILScale: 1/2" = 1'-0"

THICKNESS1"

1/2"1'

1'2"1"

1/2"

2 1/4"

THICKNESS

THICKNESS

THICKNESS

THICKNESS

1"

Walls: [(17'-3" x 10') x 2] + [(15'-2" x 10') x 2] - 51 ft. sq. 596.5 ft.sq.

18.2

35.72

6.7

Batt Insulation

Batt Insulation 8" 25

U-VALUE.1492

U-VALUE.0549

U-VALUE.0279

.2703U-VALUE

.4902U-VALUE

TOTAL

JANUARY Dry Bulb: 50o F Interior Temperature: 65o F Difference: 15o F q (Wall) (.0549) (596.5ft2) (15) = 491.22Btu/h q (Roof) (.0279) (224ft2) (15) = 93.74 Btu/h q (Window) (.4902) (51ft2) (15) = 375.00 Btu/h q (Doors) (.2703) (63ft2) (15) = 255.43 Btu/h q (Total above ground) = 1,215.39 Btu/h

APRIL Dry Bulb: 60o F Interior Temperature: 65o F Difference: 5o F q (Wall) (.0549) (596.5ft2) (5) = 163.74 Btu/h q (Roof) (.0279) (224ft2) (5) = 31.25 Btu/h q (Window) (.4902) (51ft2) (5) = 125.00 Btu/h q (Doors) (.2703) (63ft2) (5) = 85.14 Btu/h q (Total above ground) = 405.13 Btu/h AUGUST Dry Bulb: 82o F Interior Temperature: 65o F Difference: 17o F q (Wall) (.0549) (596.5ft2) (17) = 556.71Btu/h q (Roof) (.0279) (224ft2) (17) = 106.24 Btu/h q (Window) (.4902) (51ft2) (17) = 425.00 Btu/h q (Doors) (.2703) (63ft2) (17) = 289.49 Btu/h q (Total above ground) = 1,377.44 Btu/h

OCTOBER Dry Bulb: 70o F Interior Temperature: 65o F Difference: 5o F q (Wall) (.0549) (596.5ft2) (5) = 163.74 Btu/h q (Roof) (.0279) (224ft2) (5) = 31.25 Btu/h q (Window) (.4902) (51ft2) (5) = 125.00 Btu/h q (Doors) (.27033) (63ft2) (5) = 85.14 Btu/h q (Total above ground) = 405.13 Btu/h

JANUARY Dry Bulb: 50o F Interior Temperature: 65o F Difference: 15o F q (Wall) (.0549) (596.5ft2) (15) = 491.22Btu/h q (Roof) (.0279) (224ft2) (15) = 93.74 Btu/h q (Window) (.4902) (51ft2) (15) = 375.00 Btu/h q (Doors) (.2703) (63ft2) (15) = 255.43 Btu/h q (Total above ground) = 1,215.39 Btu/h

APRIL Dry Bulb: 60o F Interior Temperature: 65o F Difference: 5o F q (Wall) (.0549) (596.5ft2) (5) = 163.74 Btu/h q (Roof) (.0279) (224ft2) (5) = 31.25 Btu/h q (Window) (.4902) (51ft2) (5) = 125.00 Btu/h q (Doors) (.2703) (63ft2) (5) = 85.14 Btu/h q (Total above ground) = 405.13 Btu/h AUGUST Dry Bulb: 82o F Interior Temperature: 65o F Difference: 17o F q (Wall) (.0549) (596.5ft2) (17) = 556.71Btu/h q (Roof) (.0279) (224ft2) (17) = 106.24 Btu/h q (Window) (.4902) (51ft2) (17) = 425.00 Btu/h q (Doors) (.2703) (63ft2) (17) = 289.49 Btu/h q (Total above ground) = 1,377.44 Btu/h

OCTOBER Dry Bulb: 70o F Interior Temperature: 65o F Difference: 5o F q (Wall) (.0549) (596.5ft2) (5) = 163.74 Btu/h q (Roof) (.0279) (224ft2) (5) = 31.25 Btu/h q (Window) (.4902) (51ft2) (5) = 125.00 Btu/h q (Doors) (.27033) (63ft2) (5) = 85.14 Btu/h q (Total above ground) = 405.13 Btu/h

JANUARY Dry Bulb: 50o F Interior Temperature: 65o F Difference: 15o F q (Wall) (.0549) (596.5ft2) (15) = 491.22Btu/h q (Roof) (.0279) (224ft2) (15) = 93.74 Btu/h q (Window) (.4902) (51ft2) (15) = 375.00 Btu/h q (Doors) (.2703) (63ft2) (15) = 255.43 Btu/h q (Total above ground) = 1,215.39 Btu/h

APRIL Dry Bulb: 60o F Interior Temperature: 65o F Difference: 5o F q (Wall) (.0549) (596.5ft2) (5) = 163.74 Btu/h q (Roof) (.0279) (224ft2) (5) = 31.25 Btu/h q (Window) (.4902) (51ft2) (5) = 125.00 Btu/h q (Doors) (.2703) (63ft2) (5) = 85.14 Btu/h q (Total above ground) = 405.13 Btu/h AUGUST Dry Bulb: 82o F Interior Temperature: 65o F Difference: 17o F q (Wall) (.0549) (596.5ft2) (17) = 556.71Btu/h q (Roof) (.0279) (224ft2) (17) = 106.24 Btu/h q (Window) (.4902) (51ft2) (17) = 425.00 Btu/h q (Doors) (.2703) (63ft2) (17) = 289.49 Btu/h q (Total above ground) = 1,377.44 Btu/h

OCTOBER Dry Bulb: 70o F Interior Temperature: 65o F Difference: 5o F q (Wall) (.0549) (596.5ft2) (5) = 163.74 Btu/h q (Roof) (.0279) (224ft2) (5) = 31.25 Btu/h q (Window) (.4902) (51ft2) (5) = 125.00 Btu/h q (Doors) (.27033) (63ft2) (5) = 85.14 Btu/h q (Total above ground) = 405.13 Btu/h

JANUARY Dry Bulb: 50o F Interior Temperature: 65o F Difference: 15o F q (Wall) (.0549) (596.5ft2) (15) = 491.22Btu/h q (Roof) (.0279) (224ft2) (15) = 93.74 Btu/h q (Window) (.4902) (51ft2) (15) = 375.00 Btu/h q (Doors) (.2703) (63ft2) (15) = 255.43 Btu/h q (Total above ground) = 1,215.39 Btu/h

APRIL Dry Bulb: 60o F Interior Temperature: 65o F Difference: 5o F q (Wall) (.0549) (596.5ft2) (5) = 163.74 Btu/h q (Roof) (.0279) (224ft2) (5) = 31.25 Btu/h q (Window) (.4902) (51ft2) (5) = 125.00 Btu/h q (Doors) (.2703) (63ft2) (5) = 85.14 Btu/h q (Total above ground) = 405.13 Btu/h AUGUST Dry Bulb: 82o F Interior Temperature: 65o F Difference: 17o F q (Wall) (.0549) (596.5ft2) (17) = 556.71Btu/h q (Roof) (.0279) (224ft2) (17) = 106.24 Btu/h q (Window) (.4902) (51ft2) (17) = 425.00 Btu/h q (Doors) (.2703) (63ft2) (17) = 289.49 Btu/h q (Total above ground) = 1,377.44 Btu/h

OCTOBER Dry Bulb: 70o F Interior Temperature: 65o F Difference: 5o F q (Wall) (.0549) (596.5ft2) (5) = 163.74 Btu/h q (Roof) (.0279) (224ft2) (5) = 31.25 Btu/h q (Window) (.4902) (51ft2) (5) = 125.00 Btu/h q (Doors) (.27033) (63ft2) (5) = 85.14 Btu/h q (Total above ground) = 405.13 Btu/h

maltwick
Sticky Note
NO Mechanical system yet. NO calculation of heat gains (solar)

Recommended