W O R L D L E A D E R O F I N N O VAT I V E S O LU T I O N S I N F I R E D E T E C T I O N A N D A L A R M S YS T E M S
AUS / PAGE 1 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
W O R L D L E A D E R O F I N N O VAT I V E S O LU T I O N S I N F I R E D E T E C T I O N A N D A L A R M S YS T E M S
eCATALOGUEAUSTRALIA
AUS / PAGE 2 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
AMPAC TECHNOLOGIES
Ampac Technologies is the largest independent and privately owned manufacturer and supplier of fire detection and alarm systems in Australia.
Ampac specialises in the research & development, design, manufacturing, marketing and distribution for a complete range of system solutions. We supply systems for a vast variety of applications including commercial and industrial buildings, mines, prisons, hospitals, hotels and multi-residential complexes.
Ampac operates Australia-wide through a network of branch offices. These offices provide sales and technical support for fire installation & EWIS contractors as well as fire discipline and electrical consulting engineers. We also work with building owners and maintenance engineers to make recommendations for future planning or budgeting.
Since its inception in 1974, Ampac has grown to become a thriving global operation with a focus on quality and exceptional customer service and support. Our passion for growing our business through the relationships we have with our customers is one that energises us. It fuels our desire to make better products, implement more efficient systems, grow our network of operations and develop our people.
Ampac Technologies is ISO 9001 accredited locally and also holds overseas approvals with LPCB & UL for other key global markets.
Ampac’s comprehensive range of products enables us to deliver complete solutions for fire detection and alarm systems of any size for any customer. Indeed, developing unparalleled customer partnerships drives our desire to be ‘World leaders of Innovatiove Solutions in Fire Detection and Alarm Systems’.
CONTROL PANELS 3
ZoneSense DH4 Conventional 3ZoneSense PLUS Conventional 6 LoopSense Intelligent 17 FireFinder Conventional/Intelligent 28 EMERGENCY WARNING SYSTEMS 45
EV3000 Emergency Warning System 45Speakers 53
SmartGraphicsHD 58
DETECTORS 60
Orbis Conventional 60XP95 Intelligent 65Discovery Intelligent 70
INTERFACES 77
Ampac I/O Devices 78Apollo I/O Devices 82
AUDIO VISUAL SIGNALLING 85
XP95/Discovery Sounders, Beacons & Sounder Beacons inc Bases 86Ampac Bells, Strobes & Remote Indicators 91Klaxon Sounder Beacon 98Electronic Sounders 99
ANCILLARIES 101
Power Supplies 102Manual Call Points 104Occupant Warning Systems Amplified Sound Systems 109Electro-Magnetic Door Holders 111Document Cabinets 115Test Equipment 116Batteries 118
NEW
GRAPHICS SYSTEM 58
NEW
AUS / PAGE 3 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
ZoneSense DH4 Conventional Control Panel
The ZoneSense DH4 Control Panel is a simple and low cost 4 zone panel. It is a local alarm panel which means that it is not suitable to be directly connected to fire brigade monitoring equipment. It is an ideal fire panel for any small residential applications (not requiring brigade monitoring) or can also be used as a door holder control panel. Each of the 4 zones can be connected up to 40 x high quality commercial grade conventional fire detectors to deliver a high quality detection & alarm system. It is possible to use the ZoneSense panel in ‘Mains only’ option mode which eliminates the need to connect back up batteries. Both ABS and Metal versions are available.
• Dual Door Holder Outputs
• Mains Only Mode
• Low Quiescent Current
• Single PCB architecture
• Walk Test Facility
• Class Change Input
• Alert Input
• Up to 40 Conventional detectors per Zone
• Available in ABS (BX1) and Metal (BX10) cabinet versions
CONTROL PANELS
AUS / PAGE 4 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
ZoneSense DH4 – Metal Cabinet ZoneSense DH4 – ABS Cabinet
CONTROL PANELS ZONESENSE DH4 Conventional
Power SupplyMains Supply voltage 204 – 264 VAC @ 47 – 63HzNom. Operating voltage 27 VDCPower Supply Current 1.6 A (max)Quiescent Current 20 mA (without Door Holder)Operating Temperature -5° to +55° C (no icing)Relative Humidity 25% - 75% (non condensing)
Zone Detection CircuitNo of Zones Four (4) x 2-wire systemZone Monitoring Open and Short circuitZone Quiescent Current 4mA, 10uF EOLNo of Detectors/Circuits 40 (max)End Of Line (EOL) 10uF EOLMax Cable Length 3km (Based on cable resistive and capacitive values of 50Ω and 1uF respectively)
Outputs AvailableAlarm Outputs (monitored) Open Collector, 250mA (2 O/P’s available) 10KΩ EOLDoor Holder outputs (monitored) Open Collector, 250mA (2 O/P’s available) 10KΩ EOLFire Output Relay (voltage free) NO, C, NC Contact rating: 1A @ 30VDCFault Output Relay (voltage free) NO, C, NC Contact rating: 1A @ 30VDCAuxiliary DC Output 150mA @ 24VDC
Miscellaneous FeaturesClass Change Input Non-Latching, switched -veAlert Input Non-Latching, switched -veBattery Monitoring 4 Way DIP switch array (factory set to “OFF”)
AUS / PAGE 5 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
ZoneSense DH4 ABS (BX1) excl Batteries 2250-4200 ZoneSense DH4 METAL (BX10) excl Batteries 2250-4250 Metal BX10 Surround ENC3016-A
CONTROL PANELS ZONESENSE DH4 Conventional
MechanicalMaterialABS Cabinet ABS/Blend High ImpactMetal Cabinet 1.2mm Mild SteelFinishABS Cabinet ABS Light GreyMetal Cabinet Metal Oyster Matt RippleABS (BX1) Cabinet H 300mm x W 360mm x D 100mmMetal Cabinet (BX10) H 300mm x W 360mm x D 100mmPacked H 310mm x W 500mm x D 110mmWeight Packed excluding batteriesABS 3kgMetal 5.2kg
Note:Gyprock fixing (toggle brackets) are available to flush fit any Ampac ABS enclosure into a wall cavity Item No (4210-0002 & 4210-0003 )
ZoneSense DH4 – Metal Cabinet ZoneSense DH4 – ABS Cabinet
AUS / PAGE 6 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
ZoneSense PLUS Conventional Control Panel
CONTROL PANELS
The Ampac ZoneSense PLUS Fire Alarm Control Panel is a versatile four or eight zone conventional panel. The user friendly navigation system provides simple operation during an emergency while also enabling complex cause and effect programming to be undertaken.
A range of modular panel add-on kits allows the panel to be professionally tailored to the requirements of each installation. This means small conventional panels can now be used in a wider range of applications.
ZoneSense PLUS offers you complete control. The panel can be easily upgraded and programmed on site. ZoneSense PLUS is approved to AS4428 and is available in ABS (BX1) or metal cabinets (BX20) with either four (4) or eight (8) zone conventional detection circuits.
• Available in 4 Zone or 8 Zone Panels
• Up to 40 Conventional detectors per zone
• RS485 port supports a range of Add-on modules
• Available in ABS (BX1) and Metal (BX20) cabinet versions
• Complies with AS4428
AUS / PAGE 7 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
ZoneSense PLUS – ABS Cabinet
CONTROL PANELS ZONESENSE PLUS Conventional
ZoneSense PLUS – ABS and Metal
Power SupplyMains Supply voltage 204 – 264 VAC @ 47 – 63HzNom. Operating voltage 27 VDCPower Supply Current 2 A (max)Quiescent Current 40.5 mA (min)
Zone Detection CircuitNo of Zones Four (4) or Eight (8) x 2-wire systemZone Monitoring Open and Short circuitZone Quiescent Current 4mA, 10uF EOLNo of Detectors/Circuits 40 (max)Eon Of Line Value (EOL) 3K3Ω (default), 4K7Ω, 6K8Ω, 10KΩ and 10uF (Optional)Max Cable Length 3km (Based on cable resistive and capacitive values of 50Ω and 1uF respectively)
OutputsComms Output RS485 (4 and 8 zone only)EXT Bell Output (monitored) 1A (max) 10KΩ EOLWarning Sys Output (monitored) 1A (max) 10KΩ EOLACF Output (monitored) 1A (max) 10KΩ EOLASE Output (monitored) 1A (max) 10KΩ EOLReset/Buzzer Output Open Collector, 40mA 15sec pulseFire Alarm Output Relay (voltage free) NO, C, NC. Contact rating: 1A @ 30VDCFault Output Relay (voltage free) NO, C, NC. Contact rating: 1A @ 30VDCAuxiliary DC Output (monitored) 500mA @ 24VDC10KΩ EOL
MiscellaneousMCP input Non-Latching, switched –veFault input Non-Latching, switched –veDoor Switch Non-Latching, switched –ve
EnvironmentalOperating Temperature -5° to +55° C (no icing)Relative Humidity 25% - 75% (non condensing)
ZoneSense PLUS – Metal Cabinet
AUS / PAGE 8 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
ZoneSense PLUS – ABS Cabinet
CONTROL PANELS ZONESENSE PLUS Conventional
ZoneSense PLUS – ABS Ancillary Cabinet
ZoneSense PLUS – ABS Cabinetwith Windows
ZoneSense PLUS Control Panel4 Zone ABS (BX1) 2550-1100 8 Zone ABS (BX1) 2550-1200 4 Zone ABS (BX1) with windows 2550-2100 8 Zone ABS (BX1) with windows 2550-2200ABS Joiner Moulding ENC1851-AAncillary Cabinet ABS (BX1) 2510-9001
ZoneSense PLUS – ABS
Certain ABS versions also come optionally with the provision of extra window space. These windows are to allow for space to add ZoneSense Plus Add on Modules into the panel fascia.
MechanicalMaterial ABS/Blend High ImpactFinish ABS Light GreyDimensions 300mm (H) x 360mm (W) x 100mm (D)Weight packed excluding Batteries 3kg
Note:Gyprock fixing (toggle brackets) are available to flush fit any Ampac ABS enclosure into a wall cavity Item No (4210-0002 & 4210-0003 )
AUS / PAGE 9 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
ZoneSense PLUS – Metal Cabinet
CONTROL PANELS ZONESENSE PLUS Conventional
ZoneSense PLUS – Metal
A diverse range of factory pre assembled ZoneSense Plus products are made available for the installers convenience. These include a range with occupant warning system pre fitted and or Agent Release (Gas) module fitted.
It is also possible to fit ZoneSense Plus “add on modules” after purchasing a standard ZoneSense Plus panel as long as there is space provision on the enclosure to fit the module.
MechanicalMaterial 1.2mm Mild SteelFinish Metal Oyster Matt RippleDimensions ZoneSense Plus Metal: 500(H) x 405(W) x 145(D) mm Metal Ancillary Cabinet: 250(H) x 405(W) x 145(D) mmWeight packed excluding Batteries ZoneSense Plus Metal: 8.5kg Metal Ancillary Cabinet: 2kg
ZoneSense PLUS Control Panel4 Zone Metal (BX20) with MCP 2550-0100 8 Zone Metal (BX20) with MCP 2550-0200 4 Zone Metal (BX20) with Agent Release 2550-01518 Zone Metal (BX20) with Agent Release 2550-02524 Zone EV20 OWS Fitted 2550-01208 Zone EV20 OWS Fitted 2550-02204 Zone EV40 OWS Fitted 2550-01408 Zone EV40 OWS Fitted 2550-0240Ancillary Cabinet Metal (BX20) 8510-9001 Surround for Metal Cabinet only ENC1798-ASurround for Metal & Ancillary Cabinet ENC1797-A
ZoneSense PLUS – Rack Mount
For added flexibility ZoneSense Plus Rack versions are now available. This allows a ZoneSense Plus Fire indicator panel to be easily integrated in a rack arrangement with other larger models of Ampac warning systems
ZoneSense PLUS Control Panel4 Zone Combo Rack Mount 2553-04008 Zone Combo Rack Mount 2553-0800
AUS / PAGE 10 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Input Board
• Provides inputs for sprinkler pumps, tanks, valves, shutdowns, etc• 16 inputs per board• Inputs map to relays or indicators• Programmed via the ZoneSense PLUS front panel• Max 1 per ZoneSense PLUS
Input Board 4310-0040
Relay Board
• Provides volt free change over contacts• 8 relay outputs per board• Programmed via the ZoneSense PLUS front panel• Max 1 per ZoneSense PLUS system• Remote version available – DIN Mount chassis• Remote version communication via RS485 serial link
Relay Board 4310-0050Relay Board (Remote) 4310-0055
CONTROL PANELS ZONESENSE PLUS Conventional – Add Ons
Voltage 24 VDCQuiescent current 2.6 mAMax current 45 mAOutput rating 0.5 amp at 24 VDCOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 120 grams
Voltage 24 VDCQuiescent current 2.4 mAMax current 80 mARelay contact rating 1 amp at 24 VDCOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 130 grams
AUS / PAGE 11 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Fire Brigade Board
• Provides common outputs for connection to fire brigade signalling equipment
• 5 outputs – Alarm, Fault, Isolate, Battery Fail and 2nd Alarm• Programmed via the ZoneSense PLUS front panel• Max 1 per ZoneSense PLUS
Fire Brigade Board 4310-0070
Sounder Board
• Provides 8 monitored switched 24 VDC outputs per board• Programmed via the ZoneSense PLUS front panel• Max 1 per ZoneSense PLUS
Sounder Board 4310-0060
CONTROL PANELS ZONESENSE PLUS Conventional – Add Ons
Voltage 24 VDCQuiescent current 5.6 mAMax current 26 mAOutput rating (ea) 500 mA at 24 VDCOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 100 grams
Voltage 24 VDCQuiescent current 9 mAMax current 52 mAOutput rating 1 amp at 24 VDCOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 110 grams
AUS / PAGE 12 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
CONTROL PANELS ZONESENSE PLUS Conventional – Add Ons
Fire Fan Module
• Controls and monitors fire fans, dampers, sprinkler pumps etc.• 4 controls per module• Separate start and stop output per control• 3 status inputs per control• Labels can be modified on site• Programmed via the FACP front panel• Max 1 per ZoneSense PLUS• Location or title descriptor label
Fire Fan Module 4310-0021
Voltage 24 VDCQuiescent current 13.5 mAMax current 50 mARelay contact rating 3 amp at 24 VDCOperating temperature -5°C to 55°C (no icing)Relative Humidity 0 to 95% (non condensing)Weight 230 grams
Switch/Indicator Card
• Controls and monitors solenoid test switches, manual shutdowns etc• Eight (8) push on / push off switches per card• Switches map to relays – requires relay board (Order Code: 4310-0050)• One (1) status indicator per switch – requires input board (Order Code:
4310-0040)• Labels can be modified on site• Programmed via the FACP front panel• Max 1 per ZoneSense PLUS• Location or title descriptor label
Switch/Indicator Card 4310-0030
Voltage 24 VDCQuiescent current 3.6 mAMax current 8 mAOperating temperature -5°C to 55°C (no icing)Relative Humidity 0 to 95% (non condensing)Weight 100 grams
AUS / PAGE 13 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
CONTROL PANELS ZONESENSE PLUS Conventional – Add Ons
Agent Release Module
• Compliance with AS4214• Controls & Monitors Agent release system• Outputs for warning signs & activation devices• Inputs for signals from pressure switches & valves• Serial connection to Agent release (LCS) Local control Station • Programmed via the FACP front panel• Maximum is 1 per ZoneSense PLUS• Location or title descriptor label
Agent Release Module 4310-0011
Voltage 24 VDCQuiescent current 28.5 mAMax current 1.5 ARelay contact rating 1 amp at 24 VDCOperating temperature -5°C to 55°C (no icing)Relative Humidity 0 to 95% (non condensing)Weight 250 grams
Agent Release – Local Control Station
• Remote Agent release LCS• Complies with AS4214• For Use only with Agent release Module 4310-0011• Double Action manual Agent release facility• Toggle between initial & reserve agent• Can install up to 8 x LCSs per panel
Local Control Station 4310-0019
Material 1.2mm steel for Back BoxFinish Oyster matt rippleDimension 233H x 186W x 47D mmWeight 860 gramsOperating Voltage 27VDCQuiescent Current 40.5mAMonitored Inputs Pressure Switch; Low Pressure Switch; InterlockManual Release 2A @ 27VDC (Current Limited)Stage 1 & 2 Switched 1A @ 27VDCSystem Inoperative 1A @ 27VDCGas Fired 1A @ 27VDCComms Output RS485
AUS / PAGE 14 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
ZoneSense PLUS AR Agent Release Panel
The ZoneSense PLUS AR (Agent Release) Panel is a dedicated panel for agent release systems. Housed in a metal cabinet, the ZoneSense PLUS AR is available in either four (4) or eight (8) zones. Based on a ZoneSense PLUS Fire Alarm Control Panel (FACP), the AR version is fitted with an Agent Release Panel Add-on (control card and termination board) and a dual action yellow manual call point as standard. The Agent Release panel add-on option is factory set.
CONTROL PANELS
• Dedicated Agent Release system - purpose built with a host of ancillary products to suit
• Comprehensive system status – the AR panel includes a number of system status indicators that facilitates ease of operation and maintenance
• Local Control Station with control and indication – mimics full status of the Agent Release panel. An outdoor version of this product is available
• User interface and operation based around Industry Fire Emergency procedures – ensures that the system installed is intuitive and easy to use
• Dual action Manual Call Point – the yellow MCP is a break glass type and requires a dual action to be activated i.e. lift the protective transparent cover and break the glass
• Agent Release Panel is compliant with AS4214
AUS / PAGE 15 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
CONTROL PANELS ZoneSense PLUS AR
ZoneSense PLUS AR
Fire Alarm Control PanelOperating Voltage 23 to 28 VDCQuiescent Current 37 mA (minimum)Power Supply 27VDC (nominal) @ 2AmpsExt Bell Output 1A (max) – monitoredWarning Sys Output 1A (max) – monitoredACF Output 1A (max) – monitoredASE Output 1A (max) – monitoredFire Alarm Output Volt free 1A @ 24 VDC Open Collector OutputFault Output Volt free 1A @ 24 VDC Open Collector OutputAux DC Output 500mA @ 24 VDC – monitoredReset/Buzzer Open Collector OutputCommunications Output RS485End-Of-Line Values 3k3 (fitted as standard), 4k7, 6k8, or 10k ohms, 10μ FaradMaterial 1.2 mm mild steelFinish Oyster matt rippleDimension Metal Cabinet: 500H x 405W x 145D mm Metal ancillary cabinet: 250H x 405W x 145D mmWeight (excluding batteries) 8kg
Agent Release SystemPressure Switch Input Monitored InputLow Pressure Switch Input Monitored InputInterlock Input Monitored InputGas Fired Output Volt Free Changeover 1A@24VDCSystem Inoperative Output Volt Free Changeover 1A@24VDCStage 1 Output MonitoredStage 2 Output MonitoredRelease Initial Agent Output Monitored current limited 2A maxRelease Reserve Agent Output Monitored current limited 2A max
ZoneSense PLUS AR 4 Zone 2550-0151ZoneSense PLUS AR 8 Zone 2550-0252
AUS / PAGE 16 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Agent Release Warning Signs
The AR panel supports a 2-wire connection to warning signs. The 2-wire connection supports both single or dual stage signs. The latter is possible because of the voltage reverse technology adopted by the AR panel. Multiple warning signs may be connected to the AR panel. The connection will be in a ‘daisy chain’ configuration with the last warning sign fitted with an End-Of-Line (EOL) resistor. The EOL resistor facilitates the monitoring of the warning sign circuit. A maximum of 6 warning signs may be fittedto an AR panel.
An on-board buzzer fitted to every sign provides audible warning. However in the event AS1670.4 audible warning tones are required, external electronic sounders may be connected directly to each warning sign. An external switch may be connected to the sign to mute audiblewarning.
ACP-04 Manual Call Point Yellow 213-0061 ACP-04 Manual Call Point Hinged Cover 213-0057
IP50 SIGNS Warning sign back box (IP50) no fascia 207-0050“Extinguishing System Inoperative” complete IP50 207-0051Special wording fascia only 207-0052“Fire Alarm, Do Not Enter” fascia only 207-0053 “Fire Alarm, Evacuate Area” fascia only 207-0054 “Do Not Enter, Gas Discharged” fascia only 207-0055“Fire Door CLosing” fascia only 207-0056“Do Not Enter” fascia only 207-0057 IP65 SIGNS Warning sign back box (IP65) no fascia 207-0060 “Extinguishing System Inoperative” complete IP65 207-0061 Special wording fascia only 207-0062 “Fire Alarm, Do Not Enter” fascia only 207-0063“Fire Alarm, Evacuate Area” fascia only 207-0064 “Do Not Enter, Gas Discharged” fascia only 207-0065“Fire Door Closing” fascia only 207-0066“Do Not Enter” fascia only 207-0067 SOUNDERS Vantage Sounder (Red/White) 205-0062/63Vantage Combi (Red/White) 205-0066/67
CONTROL PANELS ZoneSense PLUS AR – Ancillary Products
IP50 Model
IP65 Model
AUS / PAGE 17 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
CONTROL PANELS
NEW
LoopSenseIntelligent Control Panel
LoopSense is an Intelligent Analogue Addressable Fire Alarm Control Panel. Available in one or two loops, the LoopSense comes packed with options and features that facilitate flexibility, ease of installation and commissioning.
• Clear back-lit 240 x64 graphic LCD
• 500mA loop current
• Advanced balanced loop design for noise rejection
• Auto learn facility
• Supports extensive range of Add Ons, including the SmartTerminal Repeater
• User friendly Loopmaster programming software tool
• Laptop connection using USB2.0 or RS232 serial port
• Complies to AS7240-2:2004, AS7240-4:2004, and AS4428-3:2010 -ActivFire ® listed
AUS / PAGE 18 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
CONTROL PANELS LOOPSENSE Intelligent
NEW LoopSense – SP1X Cabinet NEW LoopSense – SP8X Cabinet
SP1X SP8XPower Supply (General)Output Voltage 27.5VDC +/- 0.1VDC 27.5VDC +/- 0.1VDCBattery Type (maximum) 26Ah 40.0AhBattery Discharged Cut Off Voltage 21VDC 21VDC
Base PanelQuiescent Current 1 Loop Panel 115mA 115mA2 Loop Panel 135mA 135mA
LoopLoop current 500mA max 500mA maxDetectors/Devices per Loop 126 max 126 maxCabling Requirements 2 core 1.5 to 2.5mm 2 core 1.5 to 2.5mmFault supervision O/C, S/C, overcurrent O/C, S/C, overcurrentProtocol XP95, Discovery XP95, Discovery
OutputsAlarm Sounder Outputs 4 x supervised/programmable 4 x supervised/programmable 24VDC @ 500mA max 24VDC @ 500mA maxRelay outputs 3 x programmable 3 x programmable Voltage free 24VDC @ 1A Voltage free 24VDC @ 1AOpen Collector Output 2 x programmable – 30mA 2 x programmable – 30mAAuxiliary VDC 2 x protected/programmable 2 x protected/programmable 24VDC @ 500mA 24VDC @ 500mA
InputsSupervised 4 x O/C, S/C, 10K EOL 4 x O/C, S/C, 10K EOL
Communications PortInternal to LoopSense RS485 RS485External to LoopSense RS485 RS485Printer port RS232 or Parallel RS232 or ParallelPC Interfacing RS232 or USB 2.0 RS232 or USB 2.0
AUS / PAGE 19 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
CONTROL PANELS LOOPSENSE Intelligent
NEW LoopSense – SP1X Cabinet NEW LoopSense –SP8X Cabinet
SP1X SP8XElectricalPower Supply 3A PSU version 6A PSU versionInput Voltage 204 - 264VAC 204 - 264VACProtection 3Amp M205 5Amp M205Output Current 3Amps 4AmpsCharger Current 600mA 1000mA
EnvironmentalOperating temperature -5°C to +55°C (no icing) -5°C to +55°C (no icing)Relative humidity 25% to 75% (non condensing) 25% to 75% (non condensing)IP rating IP30 IP30
MechanicalMaterial 1.2mm steel 1.2mm steelFinish Surf Mist Ripple Surf Mist RippleDimensions 505H x 405W x 150Dmm 845H x 515W x 175DmmWeight 9kg 15kg
NEW LoopSense Intelligent Control Panel LoopSense, 1 Loop. 3A SP1X Enclose 8251-0110LoopSense, 2 Loop. 3A SP1X Enclosure 8251-0210LoopSense, 1 Loop. 6A SP8X Enclosure 8251-0113LoopSense, 2 Loop. 6A SP8X Enclosure 8251-0213
Flush Mount Surround for SP1X 4210-0042Flush Mount Surround for SP8X 4210-00442nd Loop Activation Key 8210-0001
*Approvals: AS7240-2:2004, AS7240-4:2004, AS4428-3:2010
AUS / PAGE 20 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Dot Matrix Panel Printer
• The dot matrix printer provides hardcopy activity report• Alarms, faults, isolates and system logs may be printed• 3 colour status LED• Self test mode• Easy maintenance for replaceable ribbon cassette and paper roll
Dot Matrix Panel Printer 159-0110Paper – 10 rolls MIS1981Ribbon MIS1982
CONTROL PANELS LOOPSENSE Intelligent
Voltage 5 VDCQuiescent current 1A @ 5 VDCCharacter size 5 x 7 dotsOperating temperature -5°C to +55°C (no icing)Relative humidity 25 to 95% (non condensing)Weight 380 grams
SmartTerminal Repeater
The SmartTerminal Repeater is an LCD annunciator designed to remotely display the status and provide control of the LoopSense Fire Alarm Control Panel.
• Connects to a Communication Driver Board inside the LoopSense Control Panel
• 4 line by 40 character LCD with backlight and navigation keys UP/DOWN keys allow the SmartTerminal to be used for FACP operation and interrogation
• Buzzer and system Reset• Flush or surface mountable enclosure• Controls have tactile and audible feedback of operation• All terminals cater for 2.5mm cables• Stand alone power supply capabilities• Flush mount kit available (Gyprock toggel fixings)• Max 30 Per LoopSense
NEW LoopSense SmartTerminal RepeatersSmartTerminal wthout PSU 4350-0004SmartTerminal Repeater with 2 Amp PSU 4350-0005SmartTerminal Slim Line Repeater without PSU 4350-0006
Mounting Kit (Flush Mount) 4210-0002
Voltage 24 VDCQuiescent current (backlight/buzzer off ) 12.4 mAMax current (backlight/buzzer on) 44 mAMax distance from main panel 1.2 kmAuxiliary output (monitored) 27 VDC 500 mAOperating temperature -5°C to +55°C (no icing)Relative humidity 25 to 95% (non condensing)Size SmartTerminal Repeater 300H x 360W x 100Dmm SmartTerminal Slimline Repeater 195H x 324W x 52DmmWeight SmartTerminal Repeater 2.5 kg SmartTerminal Slimline Repeater 1 kg
AUS / PAGE 21 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
CONTROL PANELS LOOPSENSE Intelligent- Add Ons
Relay Board
• Provides volt free change over contacts• 8 relay outputs per board• Remote version available – DIN Mount chassis• Remote version communication via RS485 serial link
Voltage 24 VDCQuiescent current 2.4 mAMax current 80 mARelay contact rating 1 amp at 24 VDCOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 130 grams System Capacity: LoopSense 15 Maximum ZoneSense Plus 1 Maximum
Relay Board 4310-0050Relay Board (Remote) 4310-0055
Sounder Board
• Provides 8 monitored switched 24 VDC outputs per boardVoltage 24 VDCQuiescent current 5.6 mAOutput rating (ea) 500 mA at 24 VDCOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 100 grams System Capacity: LoopSense 15 Maximum ZoneSense Plus 1 Maximum
Sounder Board 4310-0060
AUS / PAGE 22 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
CONTROL PANELS LOOPSENSE Intelligent- Add Ons
Fire Brigade Board
• Provides common outputs for connection to fire brigade signalling equipment
• 5 outputs – Alarm, Fault, Isolate, Battery Fail and 2nd Alarm
Voltage 24 VDCQuiescent current 9 mAMax current 52 mAOutput rating 1 amp at 24 VDCOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 110 grams System Capacity: LoopSense 1 Maximum ZoneSense Plus 1 Maximum
Fire Brigade Board 4310-0070
Voltage 24 VDCQuiescent current 2.6 mAMax current 45 mAOutput rating 0.5 amp at 24 VDCOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing) Weight 120 grams System Capacity LoopSense 15 Maximum ZoneSense Plus 1 Maximum
Input Board 4310-0040
Input Board
• Provides inputs for sprinkler pumps, tanks, valves, shutdowns, etc• 16 inputs per board• Inputs map to relays or indicators• Programmed via the LoopMaster
AUS / PAGE 23 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
CONTROL PANELS LOOPSENSE Intelligent- Add Ons
8 Zone Conventional Board
• Supports up to eight conventional zones• Selectable end of line device 3K3, 4K7, 6K8, 10K or 10µF capacitor• Supports head removal requirement on each zone• Supports up to 40 conventional devices per zone circuit (ORBIS)• Programmable latching and non-latching (self-resetting) input on each zone circuit
Voltage 24 VDCQuiescent current 15mA (including capacitive EOL current) plus device currentAlarm current 43mA (one circuit in alarm)Operating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Size 72.5 x 155mmWeight 120 grams System Capacity: LoopSense 15 Maximum
8 Zone Conventional Board 4310-0082
32 Zone Indicator Card
• Provides 32 Zone LED’s capable of indicating zone Fire, Disabled, Fault and Dependency B.• Suitable for use with the FireFinder range of FACP’s• Suitable for use with LoopSense FACP• Customisable zone identification label• Fully programmable via LoopMaster
Voltage 27 VDCQuiescent current 3.6 mAMax current 8mAOutput rating 0.5 amp at 24 VDCOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 100 grams System Capacity: LoopSense 15 Maximum
32 Zone Indicator Card 4310-0086Slip In Label LAB 3001
NEW
NEW
AUS / PAGE 24 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
CONTROL PANELS LOOPSENSE Intelligent- Add Ons
Switch/Indicator Card
Voltage 24 VDCQuiescent current 3.6 mAMax current 8 mAOperating temperature -5°C to 55°C (no icing)Relative Humidity 0 to 95% (non condensing)Weight 100 grams System Capacity: FireFinder 15 Maximum LoopSense 15 Maximum ZoneSense Plus 1 Maximum
Switch/Indicator Card 4310-0030Slip in Label LAB 1483
• 8 x Push Button On / Off switches• 8 x LED display of the On / Off condition• Controls and Monitors solenoid test switches, manual shutdowns and
etc• Programmable via the ZoneSense PLUS front panel• Programmable via ConfigManager for the FireFinder range of panels• Programmable via LoopMaster for the LoopSense range of panels
AUS / PAGE 25 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Fire Fan Module
Each Fire Fan Module houses the control and indication of up to four (4) fire fans and a single control/indication for plant trip reset.
A hard-wired version of a fire fan module consists of a Fire Fan Control Card and Termination Board. Field wiring is terminated to the termination board at the FACP.
A loop-driven version is also available and in this configuration only the Fire Fan Control Card would be required. Field wiring will terminate to address input/output devices that operate on the addressable loop.
• Four (4) Controls per Module• Status indication for Run / Fault / Stop• Controls for ON / Auto / Off• Audible and visual feedback of button press• Built in Plant Trip Reset• Supports 3, 4 and 5 Wire Connections• Available in Hardware or loop driven versions• Communicates with FACP via RS485 communication port• Where applicable all terminals cater for 2.5mm² cables
Hard Wired 4310-0021Loop Driven 4310-0071Slip in Label Template LAB1486
Operating Voltage 27VDCDimensions:Controller Card Fits standard Panel Cut-OutTermination Board 155mm x 72mmContact Rating 1 amp @ 24VDCApproval AS1668System Capacity:FireFinder 15 MaximumLoopSense 15 MaximumZoneSense Plus 1 Maximum
CONTROL PANELS LOOPSENSE Intelligent- Add Ons
AUS / PAGE 26 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
CONTROL PANELS LOOPSENSE Intelligent- Add Ons
Agent Release Module
• Compliance with AS4214• Controls & Monitors Agent release system• Outputs for warning signs & activation devices• Inputs for signals from pressure switches & valves• Serial connection to Agent release (LCS) Local control Station • Programmed via the FACP front panel• Maximum is 1 per FACP• Location or title descriptor label
Voltage 24 VDCQuiescent current 28.5 mAMax current 1.5 ARelay contact rating 1 amp at 24 VDCOperating temperature -5°C to 55°C (no icing)Relative Humidity 0 to 95% (non condensing)Weight 250 grams
System Capacity FireFinder 8 Max LoopSense 8 Max ZoneSense PLUS 1 Max
Agent Release Module 4310-0011
Agent Release – Local Control Station
• Remote Agent release LCS• Complies with AS4214• For Use only with Agent release Module 4310-0011• Double Action manual Agent release facility• Toggle between initial & reserve agent• Can install up to 8 x LCSs per panel
Material 1.2mm steel for Back BoxFinish Oyster matt rippleDimension 233H x 186W x 47D mmWeight 860 gramsOperating Voltage 27VDCQuiescent Current 40.5mAMonitored Inputs Pressure Switch; Low Pressure Switch; InterlockManual Release 2A @ 27VDC (Current Limited)Stage 1 & 2 Switched 1A @ 27VDCSystem Inoperative 1A @ 27VDCGas Fired 1A @ 27VDCComms Output RS485
Local Control Station 4310-0019
AUS / PAGE 27 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
CONTROL PANELS LoopSense Intelligent – Ancillary Products
Agent Release Warning Signs
The AR panel supports a 2-wire connection to warning signs. The 2-wire connection supports both single or dual stage signs. The latter is possible because of the voltage reverse technology adopted by the AR panel. Multiple warning signs may be connected to the AR panel. The connection will be in a ‘daisy chain’ configuration with the last warning sign fitted with an End-Of-Line (EOL) resistor. The EOL resistor facilitates the monitoring of the warning sign circuit. A maximum of 6 warning signs may be fittedto an AR panel.
An on-board buzzer fitted to every sign provides audible warning. However in the event AS1670.4 audible warning tones are required, external electronic sounders may be connected directly to each warning sign. An external switch may be connected to the sign to mute audiblewarning.
ACP-04 Manual Call Point Yellow 213-0061 ACP-04 Manual Call Point Hinged Cover 213-0057
IP50 SIGNS Warning sign back box (IP50) no fascia 207-0050“Extinguishing System Inoperative” complete IP50 207-0051Special wording fascia only 207-0052“Fire Alarm, Do Not Enter” fascia only 207-0053 “Fire Alarm, Evacuate Area” fascia only 207-0054 “Do Not Enter, Gas Discharged” fascia only 207-0055“Fire Door CLosing” fascia only 207-0056“Do Not Enter” fascia only 207-0057 IP65 SIGNS Warning sign back box (IP65) no fascia 207-0060 “Extinguishing System Inoperative” complete IP65 207-0061 Special wording fascia only 207-0062 “Fire Alarm, Do Not Enter” fascia only 207-0063“Fire Alarm, Evacuate Area” fascia only 207-0064 “Do Not Enter, Gas Discharged” fascia only 207-0065“Fire Door Closing” fascia only 207-0066“Do Not Enter” fascia only 207-0067 SOUNDERS Vantage Sounder (Red/White) 205-0062/63Vantage Combi (Red/White) 205-0066/67
AUS / PAGE 28 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
FireFinder Conventional / IntelligentFire Alarm Control Panel
FireFinder is a state of the art multi microprocessor controlled Intelligent Fire Alarm Control Panel. Modular in design, the FireFinder provides flexibility and versatility that can be configured to operate with both intelligent analogue addressable and conventional devices in the one system.
Available in single loop or multiple loop configurations, the FireFinder supports the leading Apollo XP95 and Discovery detector protocols. The Ampac ConfigManager software tools provide a powerful combination with the FireFinder to configure the system operational and functional characteristics of an installation. Enhanced networking capabilities offer the user extended applications with FireFinder incorporating a Master/ Slave Fire control panel arrangement, true Peer to Peer systems, data gathering panels and SmartGraphics a PC based application for the supervision, monitoring and control of larger fire management systems. • Clear back-lit 40 character 8 line LCD display• Programming options via the front panel or laptop computer• Remote system interrogation and diagnostics• Extensive Alarm Management resources• Self Auto Learn capabilities• Day Night sensitivity settings• Versatile multi processor architecture• Event log and printer options• SPOT – Single Person Operation Test• Flexible modular expansion and panel Add Ons• Optional 32, 64, 96 & 128 zone indicators• SmartTerminal repeater options
CONTROL PANELS
AUS / PAGE 29 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
CONTROL PANELS FIREFINDER Conventional / Intelligent AS4428
FireFinder SP1XConventional / Intelligent Control Panel
FireFinder SP8XConventional / Intelligent Control Panel
ElectricalPower Supply 85 to 264 VACOutput Voltage 27 VDCQuiescent Current 450mA (min)Battery Capacity 12 Ah (min)
OutputsBell 1 (monitored) Switched 24 VDC 2ABell 2 (monitored) Switched 24 VDC 2AAuxiliary (monitored) Switched 24 VDC 2AAuxiliary (unmonitored) Volt free 1A @ 24 VDCEWS (monitored) Switched 24 VDC 2AEWS (unmonitored) Volt free 1A @ 24 VDCFault Volt free 1A @ 24 VDCIsolate Volt free 1A @ 24 VDCAlarm Volt free 1A @ 24 VDCValve Monitor Volt free 1A @ 24 VDCBattery Fail Volt free 1A @ 24 VDC
MechanicalMaterials / Finish 1.2mm steel / Arch White powder coatConstruction ModularDimensions SP1X 500H x 405W x 145D mm SP8X 840H x 515W x 170D mm SP16X 1200H x 625W x 240D mm 10U 700H x 625W x 240D mm 16U 1200H x 700W x 350D mm 29U 1800H x 700W x 350D mm SP1X Anc Cab 250H x 405W x 145D mm SP8X Anc Cab 418H x 515W x 170D mmWeight SP1X 10 kg SP8X 20 kg SP16X 35 kg 10U 40 kg 16U 90 kg 29U 130 kg SP1X Anc Cab 3 kg SP8X Anc Cab 5 kg
AUS / PAGE 30 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
FireFinder Conventional Control PanelSP1X 16 Zone 8550-1150 SP1X 16 Zone EV20+Mic 5.6A 8550-1450 SP1X 16 Zone EV40+Mic 5.6A 8550-1430 SP8X 16 Zone 5.6A 8550-4150 SP8X 16 Zone EV40+Mic 5.6A 8550-4450 SP8X 16 Zone EV60+Mic 5.6A 8550-4460 SP8X 16 Zone EV120+Mic 18A 8550-4480 SP16X 16 Zone 5.6A 8550-5150 10U 16 Zone 5.6A 8550-6150 16U 16 Zone 5.6A 8550-6250 29U 16 Zone 5.6A 8550-6350 SP1X Ancillary Cabinet 8510-9003 SP8X Ancillary Cabinet 8510-9010 SP1X Surround ENC1798-F SP8X Surround 158-0033 SP16X Surround ENC2844-F SP1X+Ancillary Cabinet Surround ENC1797-F SP8X+Ancillary Cabinet Surround 158-0027
CONTROL PANELS FIREFINDER Conventional AS4428
FireFinder SP1XConventional Control Panel
FireFinder SP8XConventional Control Panel
Note:All panels have glazed outer doorsAdditional 16 Zone and Loop Add-On Kits can be fitted
AUS / PAGE 31 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
FireFinder Intelligent Control PanelSP1X 1 Loop 8550-1100SP1X 1 Loop EV20+Mic 5.6A 8550-1400SP1X 1 Loop EV40+Mic 5.6A 8550-1440SP8X 1 Loop 5.6A 8550-4100SP8X 1 Loop EV40+Mic 5.6A 8550-4400SP8X 1 Loop EV60+Mic 5.6A 8550-4470SP8X 1 Loop EV120+Mic 18A 8550-4490SP16X 1 Loop 5.6A 8550-510010U 1 Loop 5.6A 8550-610016U 1 Loop 5.6A 8550-620029U 1 Loop 5.6A 8550-6300SP1X Ancillary Cabinet 8510-9003SP8X Ancillary Cabinet 8510-9010SP1X Surround ENC1798-FSP8X Surround 158-0033SP16X Surround ENC2844-FSP1X+Ancillary Cabinet Surround ENC1797-FSP8X+Ancillary Cabinet Surround 158-0027
CONTROL PANELS FIREFINDER Intelligent AS4428
FireFinder SP1XIntelligent Control Panel
FireFinder SP8XIntelligent Control Panel
Note:All panels have glazed outer doorsAdditional 16 Zone and Loop Add-On Kits can be fitted
AUS / PAGE 32 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
High Level Interface Expander or Port Expander Board
The High Level Interface Expander provides the ability for the FireFinder Fire Alarm Control Panels (FACP’s) to support a range of high level interface options. The physical interface between the FACP and equipmentcan be RS232 or RS485.
Typical applications where the HLI Expander is used are:
• Building Management• Paging system• Nurse Call Systems• EV3000• SmartGraphics• MODBUS
FireFinder High Level Interface Expander – Factory Fitted Inside Panel 159-0268FireFinder High Level Interface Expander – Add-On Kit 4310-0080
Network Interface Card (NIC) – 2 Wire Network
• The NIC gives the FireFinder network capabilities via the RS422 communications port
• Provides an additional RS232 communications port when connected to Controller Interface Card (CIC)
• High level interface for Building Management or ModBus protocol for SmartGraphics and PLCs
• The NIC can be isolated from other network devices• Loop In/Loop Out for easy installation
Network Interface Card – NIC (2 wire) NZ4512SP1X 159-0258SP8X 159-0259SP16X/Rack 159-0260Add-On Kit 4310-0079
CONTROL PANELS FIREFINDER Conventional / Intelligent
Voltage 24 VDCQuiescent Current 65 mAAvailable Ports RS422 – network RS232 – serial commsMax distance (between NICs) 1.2kmCable requirements RS422 – 2 pair twisted/screened RS232 – 1 pair twisted/screenedOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 225 grams
Supply Voltage 27VDCQuiescent current 7.5maMax No. HLIE per FACP controller 3Size 155 L x 72.5 W x 20 D mmPorts RS232 RS485Max Distance 15m 1.2kmsCabling Multi-core 1 twisted pair + cable+shield shield
NEW
AUS / PAGE 33 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Module Expansion Kit for Modules (5–8)
• Expands the capacity of the FireFinder to accommodate a further four loops, 64 conventional zones, four I/O modules or any combination of the above
• Requires a main controller board
Note: Other expansion module kits are available with 16AZF/Loop/or I/O modules pre-fitted to suit. Consult your Customer Service office for more details.
SP8X Loop Module Expansion Kit 159-0112SP16X/Rack Loop Module Expansion Kit 159-0022
Analogue Loop Upgrade Kit
• This kit adds an intelligent analogue loop to the FireFinder Control Panel• For an odd numbered loop upgrade the kit consists of an I/O CPU
module, cable and termination card• An even numbered loop upgrade consists of an I/O CPU module and cable
1 Loop Upgrade Kit – even numbered loop SP1X 159-00011 Loop Upgrade Kit and processor – odd numbered loop SP1X 159-0003Even No. Loop SP16X/Rack 159-0002Even No. Loop SP8 159-0046Odd No. Loop SP16X/Rack 159-0004
CONTROL PANELS FIREFINDER Conventional / Intelligent
Voltage 24 VDCQuiescent current 40 mALoop current 250 mA max.Operating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 200 grams
Voltage 24 VDCQuiescent current 5 mAOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 110 grams
AUS / PAGE 34 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
8 Way Serial Relay Output Board
• Each serial relay output board offers 8 voltage free relay outputs, each rated at 5 amps, 24 VDC
• Each relay has a single normally open/close volt-free contact extended to a wire-protected screw terminal
• The serial 8-way relay is driven directly from the main controller board
Rack 8 Way Serial Relay Output Board 159-0072SPX 8 Way Serial Relay Output Board 159-0079
CONTROL PANELS FIREFINDER Conventional / Intelligent
Voltage 24 VDCQuiescent current 5 mARelay output current 5 Amps at 24 VDCOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 190 grams
4 Plus 4 Bell Monitor Board
• The 4 Plus 4 Bell Monitor has screw terminals for 4 voltage free contacts and 4 switched 24V DC sounder outputs
• The outputs are programmable and monitored for open or short circuit• The board connects directly to the main controller board
4 Plus 4 Bell Monitor Board 159-0069
Voltage 24 VDCQuiescent current 20 mARelay output current 1 Amp at 24 VDCSounder output current 1 Amp eachCapacity 8 boards per main controllerOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 250 grams
AUS / PAGE 35 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Fire Fan Module
Each Fire Fan Module houses the control and indication of up to four (4) fire fans and a single control/indication for plant trip reset.
A hard-wired version of a fire fan module consists of a Fire Fan Control Card and Termination Board. Field wiring is terminated to the termination board at the FACP.
A loop-driven version is also available and in this configuration only the Fire Fan Control Card would be required. Field wiring will terminate to address input/output devices that operate on the addressable loop.
• Four (4) Controls per Module• Status indication for Run / Fault / Stop• Controls for ON / Auto / Off• Audible and visual feedback of button press• Built in Plant Trip Reset• Supports 3, 4 and 5 Wire Connections• Available in Hardware or loop driven versions• Communicates with FACP via RS485 communication port• Where applicable all terminals cater for 2.5mm² cables
Hard Wired 4310-0021Loop Driven 4310-0071Slip in Label Template LAB1486
Operating Voltage 27VDCDimensions:Controller Card Fits standard Panel Cut-OutTermination Board 155mm x 72mmContact Rating 1 @ 24VDCApproval AS1668System Capacity:FireFinder 15 MaximumLoopSense 15 MaximumZoneSense Plus 1 Maximum
CONTROL PANELS FIREFINDER Conventional / Intelligent- Add Ons
AUS / PAGE 36 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
8-Way 5A Relay
• Each upgrade panel add-on offers 8 voltage free relay outputs. E ach output is rated at 5 amps, 24 VDC
• Each relay has a single normally open/close volt-free contact extended to a wire-protected screw terminal
• The standard 8-way relay upgrade requires spare capacity available on a 128/128 I/O and 16/16 I/O module
SPX 8-Way 5A O/P Relay 159-0013 Rack 8-Way 5A O/P Relay 159-0015
CONTROL PANELS FIREFINDER Conventional / Intelligent
Voltage 24 VDCQuiescent current 5 mA (Serial Relay Board)Operating temperature -5°C to 55°C (no icing)Relative Humidity 0 to 95% (non condensing)Weight 190 grams
AUS / PAGE 37 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
8 Way Bell Monitor Board
• The 8-Way Bell Monitor has 8 switched 24V DC sounder outputs• The outputs are programmable and monitored for open or short circuit• The board connects directly to the main controller board
8 Way Bell Monitor Board 159-0071
16 Way Conventional Zone Card
• Adds 16 conventional Alarm Zone Circuits• Kit consists of an I/O CPU module, cable and 16 zone termination card• Supports up to 40 conventional detectors (Series 60, Series 65 or Orbis)
per zone• Fixed 3K3 End-Of-Line device• Supports Ampac NZ detector models
SP8X/SP16X 16 Way Conventional Zone Card 159-0005Rack 16 Way Conventional Zone Card 159-0006
CONTROL PANELS FIREFINDER Conventional / Intelligent
Voltage 24 VDCQuiescent current 20 mAMax sounder output current 1 Amp eachMax output current 4 Amps per boardOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 250 grams
Voltage 24 VDCQuiescent current 145 mAOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 185 grams
AUS / PAGE 38 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
16 Opto Inputs
• The Opto Input panel add-on provides 16 programmable electrically isolated inputs to the FACP
• The input from a third party source should be a volt-free contact• This upgrade requires spare capacity available on a 128/128 I/O and
16/16 I/O Interconnect Module
SP 16 Opto Input 159-0010 Rack 16 Opto Input 159-0011
Voltage 24 VDCQuiescent current 5 mAOperating temperature -5°C to 55°C (no icing)Relative Humidity 0 to 95% (non condensing)Weight 185 grams
Modem
• The modem allows a remote access to FireFinder• Configuration and application software can be uploaded or
downloaded via the modem• Wireless Modem requires available signal from appropriate network• All modems are AUSTEL approved• Great tool to provide remote support
SPX Modem 159-0033Rack Modem 159-0065Wireless Modem 159-0068
Voltage 27 VDCData transfer rate 9600 baud maxComms to FACP RS 232Operating temperature -5°C to 55°C (no icing)Relative Humidity 0 to 95% (non condensing)Weight SP & Rack: 1kg Wireless: 5kg
CONTROL PANELS FIREFINDER Conventional / Intelligent
AUS / PAGE 39 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
8 Way Switch and Indicator Card
• 8 x Push Button On / Off switches• 8 x LED display of the On / Off condition• Controls and Monitors solenoid test switches, manual shutdowns and
etc• Programmable via the ZoneSense PLUS front panel• Programmable via ConfigManager for the FireFinder range of panels• Programmable via LoopMaster for the LoopSense range of panels
Switch and Indicator Card 4310-0030 Slip In Label LAB 1483
Voltage 24VDCQuiescent Current 3.6mAMax Current 8mAOperating Temperature -5°C - 55°C (no icing)Relative Humidity 0 to 95% (non condensing)Weight 100gramsSystem Capacity FireFinder 15 Maximum LoopSense 15 Maximum ZoneSense Plus 1 Maximum
CONTROL PANELS FIREFINDER Conventional / Intelligent- Add Ons
AUS / PAGE 40 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Agent Release System AS4214
The Agent Release System comprises of the Main Control Card, Termination Board and Local Control Stations. In addition a yellow Manual Call Point can be supplied to fit to the main Fire Alarm Control Panel (FACP) (This is a requirement of AS4214 Agent Release Systems)
The Agent Release System can be configured to operatein a single group or dual group mode.
• Controls and Monitors Agent Release System• Outputs for Warning Signs and activation devices• Inputs for signals from pressure switches & valves• Serial connection to Agent Release Local Control Station (LCS)• Programmable via the ZoneSense PLUS front panel• Programmable via ConfigManager for the FireFinder range of panels• Programmable via LoopMaster for the LoopSense range of panels
Agent Release Kit 4310-0011
Pressure Switch Input Monitored InputLow Pressure Switch Input Monitored InputInterlock Input Monitored InputGas Fired Output Volt Free Changeover 1A@24VDCSystem Inoperative Output Volt Free Changeover 1A@24VDCStage 1 Output MonitoredStage 2 Output MonitoredRelease Initial Agent Output Monitored current limited 2A maxRelease Reserve Agent Output Monitored current limited 2A max System Capacity FireFinder 8 Maximum LoopSense 8 Maximum ZoneSense Plus 1 Maximum
CONTROL PANELS FIREFINDER Conventional / Intelligent- Add Ons
Local Control Station AS4214
A maximum of 8 LCS's can be connected remote to the panel. An operator may manually release or inhibit release from any of these LCS's.
• RS485 serial connection from the FireFinder FACP to the Agent Release Local Control Station (LCS)
• A 20mm knock out is provided in the top and bottom of the LCS metal enclosure
Local Control Station 4310-0019
Inhibit Agent Release Push button hinged coverManual release MCP with hinged cover
AUS / PAGE 41 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
CONTROL PANELS FIREFINDER Conventional / Intelligent – Ancillary Products
Agent Release Warning Signs
The AR panel supports a 2-wire connection to warning signs. The 2-wire connection supports both single or dual stage signs. The latter is possible because of the voltage reverse technology adopted by the AR panel. Multiple warning signs may be connected to the AR panel. The connection will be in a ‘daisy chain’ configuration with the last warning sign fitted with an End-Of-Line (EOL) resistor. The EOL resistor facilitates the monitoring of the warning sign circuit. A maximum of 6 warning signs may be fittedto an AR panel.
An on-board buzzer fitted to every sign provides audible warning. However in the event AS1670.4 audible warning tones are required, external electronic sounders may be connected directly to each warning sign. An external switch may be connected to the sign to mute audiblewarning.
ACP-04 Manual Call Point Yellow 213-0061 ACP-04 Manual Call Point Hinged Cover 213-0057
IP50 SIGNS Warning sign back box (IP50) no fascia 207-0050“Extinguishing System Inoperative” complete IP50 207-0051Special wording fascia only 207-0052“Fire Alarm, Do Not Enter” fascia only 207-0053 “Fire Alarm, Evacuate Area” fascia only 207-0054 “Do Not Enter, Gas Discharged” fascia only 207-0055“Fire Door CLosing” fascia only 207-0056“Do Not Enter” fascia only 207-0057 IP65 SIGNS Warning sign back box (IP65) no fascia 207-0060 “Extinguishing System Inoperative” complete IP65 207-0061 Special wording fascia only 207-0062 “Fire Alarm, Do Not Enter” fascia only 207-0063“Fire Alarm, Evacuate Area” fascia only 207-0064 “Do Not Enter, Gas Discharged” fascia only 207-0065“Fire Door Closing” fascia only 207-0066“Do Not Enter” fascia only 207-0067 SOUNDERS Vantage Sounder (Red/White) 205-0062/63Vantage Combi (Red/White) 205-0066/67
AUS / PAGE 42 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Panel Mounted LED Indicators
• Provide flexibility to include additional LED indicators to the FireFinder SP1X and SP8X
• Available in three versions: – 32 zone alarm only indication (red) – 16 zone alarm/fault indication (red/amber) – 32 zone general indication (amber)• Serial connection to the FireFinder panel• Simple clip installation• Indicators remain illuminated until reset by the panel• Indicators are tested by the FireFinder panel’s lamp test control
FireFinder SP1X 32 Zone Alarm Only Indication (Red) 159-0106FireFinder SP8X 32 Zone Alarm Only Indication (Red) 159-0089
FireFinder SP1X 16 Zone Alarm/Fault Indication (Red/Amber) 159-0107FireFinder SP8X 16 Zone Alarm/Fault Indication (Red/Amber) 159-0108
FireFinder SP1X 32 Zone General Indication (Amber) 159-0123FireFinder SP8X 32 Zone General Indication (Amber) 159-0124
Voltage 27 VDCQuiescent current 30 mAMax current 40 mAOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 100 grams
CONTROL PANELS FIREFINDER Conventional / Intelligent
AUS / PAGE 43 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Remote Mounted LED Indicators
• The remote LED indicator boards provide facilities to mimic the FireFinder zone LEDs and switches
• Connects to the RS485 communications bus via the controller interface card
• Allows the custom design of geographic site layout mimics• Each termination board connects up to 32 zone LEDs – 31 boards
maximum – total 992 zone indications
FireFinder LED Mimic Driver 32 Way 159-0145Mimic Output Termination Board 159-0152FireFinder 16 Zone LED Display Board 159-0218
CONTROL PANELS FIREFINDER Conventional / Intelligent
Voltage 27 VDCQuiescent current 8 mA maxMax current 100 mACommunication mode RS485Baud rate 19200 maxCommunication cable 1 x pair twisted and screenedNo. of boards 31 maxNo. of zones 992 zones maxBuzzer external max current 20 mAOn board status indication Power on – green Normal – green Fault – yellowCommon inputs Reset Lamp test Buzzer mute Bell isolate Manual evacuateOperating temperature -5°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)
FireFinder LED Mimic Driver
Mimic Output Termination Board
Remote Expansion LED Board
AUS / PAGE 44 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Fibre Optic Network Interface
The fibre optic network interface kit offers the user a method of interconnecting two (2) or more networked FireFinder Fire Alarm Control Panels (FACP) using fibre optic cable as an alternative to copper wire. Each FACP will require a kit. Each kit comprises of 2 modem interfaces plus cables.
• 4 versions available to suit your cabling scheme on site• Redundant loop integrity (same as copper)• A network interface card is still required at each FACP node• Maximum distance using ‘Multimode’ (between nodes) up to 5km;
using Single Mode 50km Item Max Distance Code between NodesFireFinder Fibre Optic Multimode 2 core 5km max 159-0251 FireFinder Fibre Optic Multimode 1 core 5km max 159-0252 FireFinder Fibre Optic Single mode 2 core 50km max 159-0253 FireFinder Fibre Optic Single mode 1 core 50km max 159-0254
Supply Voltage 24 VDCQuiescent Current 80 mA @ 24 VDCOptical Connector ST standardPorts Available RS422/RS485Size (mm) 104D x 104W x 25HWeight 280gOperating Temperature -20°C to +75°CHumidity 0 to 95% relative, non-condensing
CONTROL PANELS FIREFINDER Conventional / Intelligent
AUS / PAGE 45 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Emergency Warning Systems
The Ampac EV3000 Occupant Warning and Intercom System is designed for the purpose of enabling the orderly evacuation of occupants, from a building or structure, in the event of an emergency.
The system comprises of two (2) sub-systems. The first being the Occupant Warning System (OWS) and the other the Occupant Intercom System (OIS). While the Warning and Intercom System have separate controls, they coexist in a panel that is logically presented and aesthetically pleasing.
The Occupant Warning System makes use of speakers strategically placed around the site, to broadcast ALERT, and/or EVACUATION signals or public address announcements. The OWS may be automatically initiated or manually operated. When not used in an emergency situation, the EV3000 can broadcast background music and/or general paging announcements.
The Occupant Intercom System (OIS) consists of front panel control at the Emergency Control Panel (ECP) and Warden Intercom Phones (WIP) that are strategically placed throughout the building. Communication is only possible between the WIP and ECP.
For larger sites, multiple control panels may be networked.
EMERGENCY WARNING SYSTEMS
AUS / PAGE 46 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Emergency Warning Systems
• Modular system design – can be easily customised to meet special requirements• Discrete front panel control – ‘natural’ style layout easy to locate zones• Amplifiers available: 40, 120, 240 & 480-watts – choice of amplifiers to suit your need• Visual output for hearing impaired or noisy environments• Common or individual fire alarm inputs – an “all call” or staged evacuation may be
configured• 2-wire Warden Intercom Phones (WIP) – monitored for open and short circuit• Common or zoned background music inputs – non-emergency input gives EV3000
the flexibility to fit most applications including shopping centres, hospitals, etc• Monitoring of speaker circuits – monitoring for short or open circuit• Monitoring of Visual Warning indicators – monitoring for short or open circuit• Automatic volume control incorporating ambient noise sensing microphone – ideal
for applications where the ambient noise levels are different at various times of day• Fail safe volume override output – used as a control to shutdown all non-emergency
facilities offered by the EV3000 and to override attenuated volume controls located in the field
• Stand-by signal generators – provides 100% backup of emergency tones for greater reliability
• Stand-by microphone amplifiers – provides 100% backup of emergency public address for greater reliability
• Automatic changeover to stand-by amplifier – may be configured in the event an active amplifier is faulty
• Digital paging console – attractive remote paging console with seven (7) segment digital display and keypad gives operator quick and easy access to paging zones
• Networked system – expands EV3000 features to include master / sub panel configuration, and remote paging console
• Optic Fibre Interface – the optional Optic Fibre interface allows the EV3000 to be networked over optic fibre cables
EMERGENCY WARNING SYSTEMS
AUS / PAGE 47 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
EV3000 12U
EV3000 29U
EV3000 16U
EV3000 29U Double Rack
EMERGENCY WARNING SYSTEMS EV3000 Emergency Control Panel
MechanicalMaterial 1.6mm Mild SteelFinish Powder Coated Arch WhiteDimensions 10U 700H x 625W x 240D mm (SEC P only) 12U 900H x 650W x 290D mm 16U 1200H x 700W x 375D mm 29U 1800H x 700W x 375D mmApprovals SSL – AS2220.89Signals Compliant with AS1670.4:2004
ElectricalPower Supply 7.5, 13, 19.5 or 26 A mps @ 24 VDCCommunication RS485 @ 9600 bpsEWS Zones 144 maxEIS Zones 288 maxPaging Console 8 max (recommended)ECP’s 12 max (recommended)Visual Warning Option 1 EV3000 Visual Outputs Maximum of 8 pairs per visual circuit
(for Xenon 208-0011). Not T3 compliantOption 2 EV3000 Visual Outputs Maximum of 40 pairs per visual circuit
(for LED 208-0063). T3 compliant Note: The LED visual pairs require the Ampac 4210-0031 Visual
Driver Kit fitted
EV3000 Emergency Control Panel12U MECP 105-000116U MECP 105-000229U MECP 105-000329U Double Cabinet MECP 105-000710U SECP 105-000412U SECP 105-000516U SECP 105-000629U SECP 105-0009
AUS / PAGE 48 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
40 Watt Power Amplifier
• A modular power amplifier that is rated at 40 watts• Multi-channel audio input supports Alert tone, Evacuation tone, Public
Address, and background music• Continuous monitoring of amplifier and 100 volt speaker circuit• Overload protection with Automatic• Easily plugs into an Ampac EV3000 amplifier frame• Can fit up to 8 amplifiers per frame
40 Watt Power Amplifier 154-0075
EMERGENCY WARNING SYSTEMS EV3000 Emergency Control Panel – Add Ons
Voltage 24 VDCQuiescent current 58mAMax current 3400mAMax output power 40 WattsOutput voltage 100 VAC RMSFreq. Response 150Hz to 12kHz (±1dB)Distortion Max 1% at full load (typical 0.5%)Sensitivity +5dB <200Kohm balanced) (1.4VRMS)Overload 100 VRMS + 10%Weight 675 grams
120 Watt Power Amplifier
• A modular power amplifier that is rated at 120 watts• Multi-channel audio input supports Alert tone, Evacuation tone, Public
Address, and background music• Continuous monitoring of amplifier and 100 volt speaker circuit• Overload protection with Automatic• Easily plugs into an Ampac EV3000 amplifier frame• Can fit up to 4 amplifiers per frame
120 Watt Power Amplifier 154-0077
Voltage 24 VDCQuiescent current 175mAMax current 8100mAMax output power 120 WattsOutput voltage 100 VAC RMSFreq. Response 210Hz to 14.5kHz (±1dB)Distortion < 0.2% at full loadSignal to Noise 77 dBOverload 100 VRMS + 10%Weight 1160 grams
AUS / PAGE 49 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
240 Watt Power Amplifier
• 24v DC supply• Mother board address strapping (120 address positions)• Continuous fault monitoring• Volume override output• Test tone input• Data selectable 4 channel input (balanced)• Tone generator synchronisation input• Indication (power on - green, power shutdown - yellow, amp or line
fault - red, overload - red)• Minimum cable size 2.5mm²
240 Watt Power Amplifier 154-0001
EMERGENCY WARNING SYSTEMS EV3000 Emergency Control Panel – Add Ons
Voltage 24 VDCQuiescent current 350mAMax current 16200mAMax output power 240 WattsOutput voltage 100 VAC RMSFreq. Response 210Hz to 14.5kHz (±1dB)Distortion < 0.2% at full loadSignal to Noise 77 dBOverload 100 VRMS + 10%Weight 2320 grams
480 Watt Power Amplifier
• 24v DC supply• Mother board address strapping (120 address positions)• Continuous fault monitoring• Volume override output• Test tone input• Data selectable 4 channel input (balanced)• Tone generator• Indication (power on - green, power shutdown - yellow, amp or line
fault - red, overload - red)• Minimum cable size 4mm²
480 Watt Power Amplifier 154-0002
Voltage 24 VDCQuiescent current 700mAMax current 32400mAMax output power 480 WattsOutput voltage 100 VAC RMSFreq. Response 210Hz to 14.5kHz (±1dB)Distortion < 0.2% at full loadSignal to Noise 77 dBOverload 100 VRMS + 10%Weight 4640 grams
AUS / PAGE 50 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Emergency Alarm Initiating Device (EAID)
• Connects to S004 WIP• 2 wires for WIP & EAID• Compatible with 219-0015
Emergency Alarm Initiating Device (EAID) 213-0068
EMERGENCY WARNING SYSTEMS EV3000 Emergency Control Panel – Add Ons
Warden Intercom Phone – 2 Wire (S0004)
• 2 Wire WIP/EAID wiring• High quality WIP audio• Complies with AS4428.4• Suitable for models manufactured after July 2010
Warden Intercom Phone – 2 Wire (S0004) 219-0015WIP Enclosure Metal Surface Mounted 291-0054
Operating Voltage 27 VDC (line driven)Line Voltage On hook - 25 VDC max Off hook - 14 VDC maxCurrent draw On hook - 5 mA max Off hook - 35 mA maxLine Impedance 360 ohm balancedLine Level 0 dB (± 3dB)Cabling 2 wire - 2.5mm² max.Dimensions 215H x 85W x 62D mmWeight 380 grams
AUS / PAGE 51 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
EMERGENCY WARNING SYSTEMS EV3000 Emergency Control Panel – Add Ons
Remote Paging Console
• Provides a point to initiate a non-emergency voice announcement via the EV3000
• Provides a pre-announcement tone• Easy keypad operation to broadcast voice announcements to selected
zones, or group of zones• Connects to EV3000 via RS485• Derives power from the EV3000 panel Remote Paging Console 154-0005
Size 80H x 300W x 220D mmSupply voltage 12 VDCCurrent 400 mACommunication RS 485Weight 1160 grams
Warden Intercom Phone – 3 Wire
• The WIP is installed remote to the ECP• Provides intercommunication between users at the WIP and
Emergency Control Panel• This feature is only available when the Emergency Warning Intercom
facility has been incorporated in the control panel• Made of high impact red ABS plastic• Compatible with most EV3000 systems manufactured before July 2010
Warden Intercom Phone – 3 Wire 219-0007WIP Enclosure Metal Surface Mounted 291-0054
Operating Voltage 27 VDC (line driven)Line Voltage On hook - 25 VDC max Off hook - 14 VDC maxCurrent draw On hook - 5 mA max Off hook - 35 mA maxLine Impedance 360 ohm balancedLine Level 0 dB (± 3dB)Cabling 3 wire - 2.5mm² max.Dimensions 215H x 85W x 62D mmWeight 380 grams
AUS / PAGE 52 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Fibre Optic Network Interface for EV3000
The fibre modem network interface kit offers the user a method of interconnecting two (2) or more EV3000 Emergency Warning and Intercom System (EWIS) using fibre optic cable as an alternative to copper. The modems convert hardwired data and audio, to a common fibre opticcompatible output.
The fibre optic modems are full duplex and have 4-channels to carry both data and two (2) audio signals. Two (2) channels are required – emergency public address and warden intercom audio signals.
Fibre Optic Network Interface for EV3000 154-0005
EMERGENCY WARNING SYSTEMS EV3000 Emergency Control Panel – Add Ons
Supply Voltage 12 VDCQuiescent Current 300 mAInput Ports Available RS422 Emergency P.A. Warden Intercom Phone AudioMax. Distance 5 kmCabling 2-core multimode fibreFibre Connector ST StandardOptical DataWavelength 850nmMode MultimodeEmitter type LEDOperating Temperature 0°C to +55°CRelative Humidity 0 to 95% (no icing) (non condensing)Size L104 x W144 x D25 mm
Combined Strobe for EV3000 (Surface Mount)
Item pictured is 208-0066 Indoor. The IP65 model uses the deep base to achieve an outdoor solution where required.
Combined Strobe for EV3000 (Flush) 208-0066Combined Strobe for EV3000 (IP65 ) 208-0065Combined Strobe for EV3000 (Surface ) 208-0066
AUS / PAGE 53 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Ceiling Speaker – 100mm Recessed
• 100 mm recessed ceiling speaker• Operates with 100 volt speaker line• Capacitor fitted for line monitoring• Five (5) power output settings• Safety cover to protect terminals• Facility to secure field cabling to speaker housing• Optional low profile grill available
Ceiling Speaker – 100mm Recessed 218-0008Low Profile Grill 218-0003
EMERGENCY WARNING SYSTEMS Speakers
Rated Power 5 wattsLine Voltage 100 VoltFrequency R esponse 100 Hz to 20 kHzSPL 96 dB (1 watt @ 0.5m)Speaker Tap (watt) 0.33, 0.66, 1.25, 2.5, 5Cut-out size 85 mm DiameterDimensions 100 x 105 HmmWeight 800 grams
Ceiling Speaker – 200mm Recessed
• 200 mm recessed ceiling speaker• Operates with 100 volt speaker line• Capacitor fitted for line monitoring• Five (5) power output settings• Safety cover to protect terminals• Facility to secure field cabling to speaker housing• Optional low profile grill available
Ceiling Speaker – 200mm Recessed 218-0009Low Profile Grill 218-0021
Rated Power 5 wattsLine Voltage 100 VoltFrequency R esponse 100 Hz to 20 kHzSPL 96 dB (1 watt @ 0.5m)Speaker Tap (watt) 0.33, 0.66, 1.25, 2.5, 5Cut-out size 190 mm DiameterDimensions 200 x 75 HmmWeight 1 kg
AUS / PAGE 54 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Ceiling Speaker – 100mm One-Shot
• 100 mm quick-fit recessed ceiling speaker• Operates with 100 volt speaker line• Capacitor fitted for line monitoring• Five (5) power output settings• Safety cover to protect terminals• Facility to secure field cabling to speaker housing• Speaker grill incorporated with speaker
Ceiling Speaker – 100mm One-Shot (White) 218-0026Ceiling Speaker – 100mm One-Shot (Black) 218-0031Ceiling Speaker – 200mm One-Shot (White) 218-0032
EMERGENCY WARNING SYSTEMS Speakers
Rated Power 5 wattsLine Voltage 100 VoltFrequency R esponse 100 Hz to 15 kHzSPL 98 dB (1 watt @ 0.5m)Speaker Tap (watt) 0.33, 0.66, 1.25, 2.5, 5Cut-out size 140 mm DiameterDimensions 155 x 110 HmmWeight 850 grams
Surface Speaker – 100mm
• Custom designed speaker and transformer assembly engineered to meet Australian Fire Evacuation Standards
• High degree of speech intelligibility
Surface Speaker – 100mm 218-0022
Driver 100mm (4”) dual conePower taps 0.33, 0.66, 1.25, 2.5, 5WSPL 1W @ 1m 90dB @ 1kHz (+/- 2dB)Frequency response 100Hz-15kHzConnection 4 way terminal block + 22uF bipolar capacitor
AUS / PAGE 55 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
EMERGENCY WARNING SYSTEMS High Efficiency Speakers
EasyFit Ceiling Speakers
• In four useful sizes: 4”, 5”, 6.5”, 8”• Choice of power rating: 5W, 10W, 15W, & 30W• Wide bandwidth for music reproduction• Wide dispersion for speech intelligibility• Simple output-level selection• Easily flush-mounted in ceilings or bulkheads• Dependable rota-clamp fixing system• Blends in with virtually all interiors
Ceiling Speaker, Easyfit 5w 4” - EVAC 218-0041 Ceiling Speaker, Easyfit 5w 5” - Brilliant White 218-0042 Ceiling Speaker, Easyfit 5w 5” White 218-0043 Ceiling Speaker, Easyfit 10w 6.5” 218-0044 Ceiling Speaker, Easyfit 15w 8” White 218-0045 Ceiling Speaker, Easyfit 30w 8” White 218-0046
4 Inch 5 Watt 5 Inch 5 Watt 6 Inch 10 Watt 8 Inch 15 Watt 8 Inch 30 WattDriver 4” 5” 6.5” 8” 8”Maximum/rated power 8W/5W 8W/5W 15W/10W 22W/15W 45W/30W Power taps 5, 2.5, 1.25, 0.66, 0.33W 5, 2.5, 1, 0,5, 0.33W 10, 5, 2.5, 1.25W 15, 10, 5, 2.5, 1.25W 30, 15, 7.5, 3.75WFrequency Range 100Hz - 15kHz 50Hz - 17kHz 60Hz - 20kHz 50Hz - 17kHz 50Hz - 17kHzAxial sensitivity 1W/1m/1kHz 94dB SPL 97dB SPL 91dB SPL 93dB SPL 93dB SPLOpening Angle( -6dB) 144° / 93° at 1kHz / 4kHz 170° at 1kHz 170° at 1kHz 165° at 1kHz 100° at 1kHzCeiling cutout diameter 140mm 170mm 195mm 238mm 238mmOverall dimensions 170mm x 110mm 202mm x 90mm 220mm x 115mm 273mm x 103mm 273mm x 115mmSafety acc to EN 60065 acc to EN 60065 acc to EN 60065 acc to EN 60065 acc to EN 60065
AUS / PAGE 56 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
EMERGENCY WARNING SYSTEMS Speakers
Horn Speaker – 20 Watt
• 20 watt Flared horn speaker• Operates with 100 volt speaker line• Capacitor fitted for line monitoring• Five (5) power output settings• High SPL performance• Weatherproof construction• Mounting bracket supplied
Horn Speaker – 20 Watt 218-0007
Rated Power 20 wattsLine Voltage 100 VoltFrequency R esponse 270 Hz to13 kHzSPL 108 dB (1 watt @ 1m)Speaker Tap (watt) 2.5, 5, 7.5, 10, 15, 20Dispersion angle 110°Material UV stabilised plasticIP Rating IP65Dimensions 200 Dia x 290 DmmWeight 1.5 kg
Horn Speaker – 10 Watt
• 10 watt Flared horn speaker• Operates with 100 volt speaker line• Capacitor fitted for line monitoring• Five (5) power output settings• High SPL performance• Weatherproof construction• Mounting bracket supplied
Horn Speaker – 10 Watt 218-0028
Rated Power 10 wattsLine Voltage 100 VoltFrequency R esponse 250 Hz to 13 kHzSPL 105 dB (1 watt @ 1m)Speaker Tap (watt) 1.25, 2.5, 5, 7.5, 10Dispersion angle 110°Material UV stabilised plasticIP Rating IP65Dimensions 150 Dia x 190 DmmWeight 1.4 kg
AUS / PAGE 57 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
EMERGENCY WARNING SYSTEMS High Efficiency Speakers
Horn Speaker – 10 Watt / 20 Watt
• 10W & 20W Models available• IP66 Rated• Emergency Evacuation System ready• Wide dispersion for speech intelligibility• Screwdriver adjustable power tapping• Loop in / Loop out wiring
Horn Speaker – 10 Watt 218-0047Horn Speaker – 20 Watt 218-0048
10 Watt 20 WattRated input 100V 100VPower handling 10W 20WPower taps 10, 7.5, 5, 2.5, 20, 15. 10, 1.25 7.5, 5WSPL at Rated Power (10W @ 1m) 119 dB 124 dBSPL at Rated Power (1W @ 1m) 108 dB 110 dBFrequency Range (-10dB) 300Hz - 13kHz 9kHzDispersion Angle(-6dB) 140°@1kHz 90°@1kHzWeight 1.3KG 2.1KG
Speaker Attenuator
• Operates in conjunction with an Emergency Warning System (EWS)• Attenuates the sound level of speakers in the circuit during normal
operation of the EWS• 7-step attenuator setting including ‘OFF’ position• Switched 24 VDC (fail-safe operation) enables attenuation control• Screw driver terrminals for easy wiring
Speaker Attenuator – 40 Watt 100V 225-0002Speaker Attenuator – 100 Watt 100V 225-0003
Rated Power 40 or 100 wattsSpeaker L ine Voltage 100 VoltAttentuation 0, 5.7, 9.8, 16, 20, 26.3dB, ∞Override Relay Operating Voltage 24 VDCMaterial White UV stabilised plasticDimensions Suits single gang wall box (Australian)Weight 300 g
AUS / PAGE 58 CONTACT AMPAC HOME CONTENTS SEARCH ZOOM PRINT EXIT
GRAPHICS PACKAGE
SmartGraphicsHD A FireFinder FACP compatible product
AMPAC’s SmartGraphicsHD System unleashes the full power of FireFinder (fire detection) and the EV3000 (alarm and intercom) by creating a robust and versatile hub for controlling your fire detection, alarm and intercom systems with one fully integrated package. Flexible and intuitive in its design, SmartGraphicsHD puts the command of your systems at your fingertips.
• Interfaces to the FireFinder fire detection panel and the EV3000 emergency warning and intercom system
• Clearly shows on the building floor plan the start and spread of the fire and the status of the emergency warning and intercom system
• Has capabilities of e-mailing maps to emergency service organisations and key stakeholders
• Supports the latest 1920x1080 HD computer technology
• Able to operate over existing IT infrastructure
• Can be expanded to incorporate multi-site facilities into one central monitoring package
• Historic data log on the activity of the fire detection system and alarm system
• Three level password protection
• Detailed Egress Pathways
• Building Information (like hazardous materials) and mustering point displayed on maps
AUS / PAGE 59 CONTACT AMPAC HOME CONTENTS SEARCH ZOOM PRINT EXIT
GRAPHICS PACKAGE
Graphics PackageComputer (Rec Min) Intel Core Processor 2Ghz, 2GB RAM, 500 GB Hard Drive, CDROM, 6 USB Ports Serial Comms port for connection to FACP (RS232 or RS485 as required) Windows XP Professional (32bit) , or Windows 7 Professionl (32bit)Monitor 20” min (resolution 1920 x 1080)RS232 Comms 1 pair twisted & screened 15m maximum from FireFinder Baud rate- 9600 to 38400RS485 Comms 1 pair twisted & screened 1200m maximum from FireFinderEthernet 8 pin RGRJ45 Connector 10/100 Mbps IEEE 802.3. IEEE 802.38
SmartGraphicsHD
Licence Package Only 4100-0002Licence Package and computer - including a colour laser printer 4100-0003Licence Package and embedded computer with touch screen 4100-0004 - including a colour laser printer Licence Package and computer with touch screen monitor 4100-0005- including a colour laser printer Ethernet 159-0613 * Graphical Engineering available- please contact your local CSO Office.
AUS / PAGE 60 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Orbis Conventional Detectors
• Automatic drift compensation with DirtAlert® warning
• Patented FasTest® which reduces the time taken to test detectors
• SensAlert® uses a flashing LED to indicate that the sensor is not operating correctly
• StartUp™ for fast commissioning
• Attractive and compact design
• Electrically compatible with Series 60 and Series 65
• Wide voltage and operating temperature ranges
• Algorithms for transient rejection
• Flashing LED option
• 360° visibility of LEDs
• Insect resistant
Orbis is a range of conventional detectors which has been developed with sophisticated technology previously only found in intelligent detectors. Orbis is a range with modern styling and incorporates a mounting base wihich saves installation time.
DETECTORS
AUS / PAGE 61 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Orbis Optical Smoke Detector (AS)
The Orbis Optical Smoke Detector works using the well established light scatter principle, however, the sensing technology is radically different in design from previous optical detectors and significantly reduces false alarms.
• Responds well to slow-burning, smouldering fires • Performs well in black and white smoke • Extra confirmation of smoke before alarm signal is given • Reduced incidence of false alarms • Sensing chamber keeps out dust and other airborne contaminants • Operates over a broad range of voltages at extremes of temperature
Approvals: AS7240.7/CSIRO
Orbis Multisensor Detector (AS)
The Orbis Multisensor Detector benefits from the same false alarm reduction technology as the optical detector. It is a thermally enhanced smoke detector and so will not give an alarm from heat alone.
• Responds well to fast-burning, flaming fires • Reduced incidence of false alarms • Increased reliability of detection • Sensing chamber keeps out dust and other airborne contaminants • Operates over a broad range of voltages at extremes of temperature
Approvals: AS7240.7/CSIRO
DETECTORS ORBIS Conventional
Operating voltage 8.5 to 33 VDCQuiescent current 65μA at 24 VDCAlarm current 40mA at 24 VDCRemote output 1.2kΩ to -ve supplySize 97Dia x 31H mmOperating temperature -40°C to +70°C (no icing)Relative humidity 0 to 98% (non condensing)IP rating IP23D (EN60529)Weight 75 grams
Orbis Optical Smoke Detector (AS) 201-0512
Operating voltage 8.5 to 33 VDCQuiescent current 65μA at 24 VDCAlarm current 40mA at 24 VDCRemote output 1.2kΩ to -ve supplySize 97Dia x 42H mmOperating temperature -40°C to +70°C (no icing)Relative humidity 0 to 98% (non condensing)IP rating IP23D (EN60529)Weight 80 grams
Orbis Multisensor Detector (AS) 201-0514
AUS / PAGE 62 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Orbis Heat Detector
The Orbis Heat Detector monitors temperature by using a single thermistor network which provides a voltage output proportional to the external air temperature. There are seven classes of heat detectors in the Orbis range designed to suit a wide variety of operating conditions.
• Can be used for applications where smoke detectors are unsuitable• Ideal in environments that are dirty or smoky under normal conditions• Reduced incidence of false alarms• Increased reliability of detection
Approvals: AS7240.5/CSIRO
Orbis TimeSaver Base
The TimeSaver Base is a completely new design that provides installers with an open working area with fixing holes shaped to allow a simple mounting procedure.
• Grouped terminals to make wiring easy • Two fixing centres • LED alignment mark • Cable stripping guide • Detector locking mechanism• Continuity link for voltage testing prior to testing
Diode version available, which has a diode fitted for systems that house active EOL monitoring for head removal.
Simplified (LX version) available without the continuit link fitted.
Orbis TimeSaver Standard Base 201-0540 Orbis Time Saver LX Base 201-0541Orbis TimeSaver Diode Base 201-0542
Operating voltage 8.5 to 33 VDCQuiescent current 65μA at 24 VDCAlarm current 40mA at 24 VDCRemote output 1.2kΩ to -ve supplySize 97Dia x 36H mmOperating temperature -40°C to +70°C (no icing)Relative humidity 0 to 98% (non condensing)IP rating IP23D (EN60529)Weight 70 grams
Orbis Heat DetectorOrbis BR (65°C) Heat Detector (Type A) Rate of Rise (AS) 201-0500 Orbis A2S (50°C) Heat Detector (Type B) Static (AS) 201-0504 Orbis CR (80°C) Heat Detector (Type C) Rate of Rise (AS) 201-0508 Orbis CS (80°C) Heat Detector (Type D) Static (AS) 201-0510
Size 100Dia x 8H mmIP rating IP23D (EN60529)Weight 60 grams
DETECTORS ORBIS Conventional
AUS / PAGE 63 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Orbis LX Base
The Orbis LX Base has two slots for fixing screws at a spacing of 51mm to 69mm. Detectors fit into the base one way only and require clockwise rotation without force to be plugged in. • One way fit • Detector locking mechanism
Orbis LX Base 201-0545
DETECTORS ORBIS Conventional
Size 100Dia x 8H mmOperating temperature -40°C to +70°CHumidity 0 to 98%IP rating IP23D (EN60529)Weight 60 grams
Orbis TimeSaver Relay Base
The TimeSaver Relay Base incorporates a single pole voltage-free change-over contact for switching external equipment. When the detector changes to the alarm state, the relay is energised, causing the contact to change state. The contact will remain in this condition until the detector is reset.
• Grouped terminals to make wiring easy • Two fixing centres • LED alignment mark • Cable stripping guide • Continuity link for voltage testing of zone wiring prior to commissioning • Detector locking mechanism • Capable of switching up to 30V at 1A
Approvals: AS7240/CSIRO
Orbis TimeSaver Relay Base 201-0543
Size 100Dia x 8H mmOperating temperature -40°C to +70°CHumidity 0 to 98%IP rating IP23D (EN60529)Weight 60 grams
AUS / PAGE 64 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Ampac Duct Sampling Unit
The Ampac Duct Sampling Unit is designed to monitor levels of smoke in air ducts operating in air speeds of 0.5 to 20 meters per second.
The duct smoke detector can be fitted to any wall of a ventilation duct and has two tubes that extend into the duct through punched holes. The perforated sampling tube is placed in the airflow upstream of the exhaust tube which causes a pressure differential in the duct detector. Air is sucked up the sampling tube, across the detector and exhausted back into the air duct.
Using the 360mm sampling pipe supplied, an air duct of up to 560mm can be monitored. For duct widths greater than 560mm, three other lengths of sampling pipe are available:
1. For duct width 300 to 750mm2. For duct width 750 to 1500mm3. For duct width 1500 to 3000mm
• Volt free normally opened or closed non-latching relay contact. Relay energises when detector is in alarm (Available only with Ampac Orbis option)
• Both sampling and exhaust pipes are fitted to the back box without the need for tools making installation easier
Orbis Duct Sampling Unit inc Detector Base 214-0052 Duct Probe 300 to 750mm Sampling Pipe 214-0060 Duct Probe 750 to 1500mm Sampling Pipe 214-0061 Duct Probe 1500 to 3000mm Sampling Pipe 214-0062 Orbis Photo Optical Head 201-0512
DETECTORS ORBIS Conventional
Housing Grey - ABSCover Transparent - ABSDimension 115H x 340W x 60D mmTemperature Range 0 to +60°CHumidity Up to 85%, no condensationWeight 5.5 kg
• The cover of the duct smoke detector is monitored to ensure working integrity and if removed, causes a fault to appear at the fire alarm control panel
• Easily accessible wire clamping terminals ensure secure and fast termination
• Clear cover hence the alarm LED on the detector is visible at all times• Unique self-sealing test port allows the dispensing of test smoke via a
needle into the duct smoke detector to be tested without the need to remove the cover
• Sampling pipes available in 4 lengths• Weather resistant enclosure
Approvals: C-tick, AS1603-13
Note: The detector head is sold separately to the duct sampling unit
AUS / PAGE 65 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
XP95 Intelligent Detectors
• Alarm Flag for fast alarm reporting
• Alarm Address for fast location of alarm
• XPERT card addressing
• Electronics-free base
• Easy installation
• Elegant design
• Insect Resistant
Features
The XP95 range of intelligent fire detectors is advanced in design, improved in performance and has unique features that benefit the installer and end user. The range features smoke detectors (ionisation and optical), standard and high temperature heat detectors and a multisensor. Beam detectors, flame detectors, manual call points, audio visual signalling devices, interface units and isolators complete the range. XP95 has a ‘central intelligence’ system where all the decisions are made by the control panel.
DETECTORS
AUS / PAGE 66 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
XP95 Ionisation Smoke Detector
The XP95 Ionisation Smoke Detector uses a low activity radioactive foil to detect fires by irradiating the air in the smoke chambers and causing a current flow. If smoke enters the chamber, the current flow is reduced leading to an alarm.
• Responds well to fast-burning, flaming fires • Designed to operate in a variety of environments • Minimal effects from temperature, humidity, atmospheric pressure • Well protected against electromagnetic interference over a wide frequency range
Approvals: AS1603.2XP95 Ionisation Smoke Detector 201-0002
XP95 Optical Smoke Detector
The XP95 Optical Smoke Detector works using the light scatter principle and is ideal for applications where slow-burning or smouldering fires are likely.
• Responds well to slow-burning, smouldering fires • Well suited for bedrooms and escape routes• Unaffected by wind or atmospheric pressure
Approvals: AS1603.2
XP95 Optical Smoke Detector 201-0003XP95 Optical Smoke (Black) Detector 201-0092
Voltage 17-28 VDCQuiescent current 280μA at 24 VDCAlarm current 2.0mA at 24 VDCSize inc base 100Dia x 50H mmOperating temperature -20°C to +60°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP23DWeight inc base 161 grams
DETECTORS XP95 Intelligent
Voltage 17-28 VDCQuiescent current 340μA at 24 VDCAlarm current 4mA at 24 VDCSize inc base 100Dia x 50H mmOperating temperature -20°C to +60°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP23DWeight inc base 157 gramsSensitivity 0.12db/m
AUS / PAGE 67 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
XP95 Heat Detector
The XP95 Heat Detector monitors temperature by using a single thermistor network which provides a count output proportional to the external air temperature. The XP95 range features two Heat Detectors, standard and high emperature. The standard heat detector is classified as an A2S device and will report an alarm at 55°C. The high temperature detector, classified as a CS device, will report an alarm at 90°C.
• Ideal in environments that are dirty or smokey under normal conditions • Well suited for warehouses, loading bays and car parks • Unaffected by wind or atmospheric pressure
Approvals: AS1603.1XP95 Heat DetectorXP95 Heat Detector (Type A & B) A2S (55°C) 201-0001
Voltage 17-28 VDCQuiescent current 250-270μA at 24 VDCAlarm current 2mA at 24 VDCSize inc base 100Dia x 50H mmOperating temperature A2S: -20°C to +70°C (no icing) CS: -20°C to +120°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP53Weight inc base 157 grams
DETECTORS XP95 Intelligent
XP95 Intelligent Detector Base
All detectors in the XP95 range fit the Intelligent Detector Base. It is a low insertion force base with stainless steel contacts for the detector terminals.
• XPERT addressing • One way fit of detector• Locking feature to prevent unauthorised removal
Approvals: AS1603:Pt1&2
XP95/ Discovery Detector Base with Xpert Card 201-0004XP95 Detector Base (Black) with Xpert Card 201-0093
Size 100Dia x 8H mmOperating temperature -20°C to +60°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 55 grams
AUS / PAGE 68 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
DETECTORS XP95 Intelligent
XP95 Isolating Base
The new style Isolating Base senses and detects short-circuit faults on XP95 loops and spurs.
• Up to 20 devices may be installed between isolating bases• High brightness LED
XP95/ Discovery Isolating Base with Xpert Card 201-0125
Voltage 17-28 VDCQuiescent current 47μA (non isolating) 4mA (isolating)Size 100Dia x 24H mmOperating temperature -20°C to +60°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 100 grams
Blank XPERT Card
A universal address card supplied with all bases. Using a coding guide, pips are removed to set the address of the inserted detector.
• Simplifies and speeds up installation and commissioning• Uses patented, proven technology• Address remains the same, no matter how often detectors are replaced• Flexibility to create any address
Blank XPERT Card 38531-771Pre-addressed (1-126) Xpert Cards 201-0013
Pre-addressed XPERT Card
Pre-addressed XPERT cards are supplied with pips already removed.
• Saves time and increases accuracy during commissioning• Pre-numbered 1-126
AUS / PAGE 69 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Ampac Duct Sampling Unit
The Ampac Duct Sampling Unit is designed to monitor levels of smoke in air ducts operating in air speeds of 0.5 to 20 meters per second.
The duct smoke detector can be fitted to any wall of a ventilation duct and has two tubes that extend into the duct through punched holes. The perforated sampling tube is placed in the airflow upstream of the exhaust tube which causes a pressure differential in the duct detector. Air is sucked up the sampling tube, across the detector and exhausted back into the air duct.
Using the 360mm sampling pipe supplied, an air duct of up to 560mm can be monitored. For duct widths greater than 560mm, three other lengths of sampling pipe are available:
1. For duct width 300mm to 750mm2. For duct width 750mm to 1500mm3. For duct width 1500mm to 3000mm
• Both sampling and exhaust pipes are fitted to the back box without the need for tools making installation easier
• The cover of the duct smoke detector is monitored to ensure working integrity and if removed, causes a fault to appear at the fire alarm control panel
Duct Sampling Unit inc XP95 Detector Base 214-0051 Duct Probe 300mm to 750mm Sampling Pipe 214-0060 Duct Probe 750mm to 1500mm Sampling Pipe 214-0061 Duct Probe 1500mm to 3000mm Sampling Pipe 214-0062 XP95 Optical Smoke Detector 201-0003Discovery Multisensor Detector 201-0094
DETECTORS XP95 Intelligent
Housing Grey - ABSCover Transparent - ABSDimension 115H x 340W x 60D mmTemperature Range 0 to +60°CHumidity Up to 85%, no condensationWeight 5.5 kg
• Easily accessible wire clamping terminals ensure secure and fast termination
• Clear cover hence the alarm LED on the detector is visible at all times• Unique self-sealing test port allows the dispensing of test smoke via a
needle into the duct smoke detector to be tested without the need to remove the cover
• Sampling pipes available in 4 lengths• Weather resistant enclosure
Approvals: C-tick, AS1603-13
Note: The detector is sold separately to the duct sampling unit
AUS / PAGE 70 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Discovery Intelligent Detectors
• Rejection of transient signals
• Flashing LED option
• Five response modes for ease of optimisation to changing environments
• Drift compensation to ensure constant sensitivity
• Four bytes of non-volatile memory for user data
• Alarm flag for fast alarm reporting
• Conventional alarm facility during control panel processor fault
• 360° visibility in alarm
• Compatible with XP95 systems
• Insect resistant
Discovery is a range of high-specification, intelligent fire detectors developed to meet the requirements of sophisticated systems while providing engineers with an additional dimension in fire protection capability. Discovery has a ‘distributed intelligence system’ where decisions are made in the detector head as well as at the control panel. Drift compensation is also incorporated into the detector, allowing it to adapt to dirty or dusty environments reducing false alarms.
DETECTORS
AUS / PAGE 71 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Discovery Heat Detector
The Discovery Heat Detector, distinguishable by the low airflow resistant case, uses a single thermistor to sense the air temperature around the detector.
• Ideal in environments that are dirty or smokey under normal conditions• Well suited for warehouses, loading bays and car parks• Unaffected by wind or atmospheric pressure• Remote test feature
Approvals: AS1603.1 Discovery Heat DetectorDiscovery Heat Detector Type D 201-0090Discovery Heat Detector Type C 201-0089
Voltage 17-28 VDCQuiescent current 500μA at 24 VDCAlarm current 3.4mA at 24 VDCSize inc base 100Dia x 50H mmOperating temperature 0°C to +80°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP53Weight inc base 160 grams
DETECTORS APOLLO DISCOVERY Intelligent
AUS / PAGE 72 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Discovery Multisensor Detector
The Discovery Multisensor Detector comprises optical smoke and thermistor temperature sensors whose respective outputs can be split to deliver specific smoke or thermal actions respectively. This capability can aid early Alarm warning routines and other advanced detection techniques.
• Ideal for a wide range of applications• Highly immune to false alarms • Well suited for environments such as hotel bedrooms • Unaffected by wind or atmospheric pressure • Well suited for sensitive environments • Heat only, optical only options • Remote test feature
Approvals: AS1603.1
Discovery Multisensor Detector 201-0094
Voltage 17-28 VDCQuiescent current 500μA at 24 VDCAlarm current 3.5mA at 24 VDCSize inc base 100Dia x 58H mmOperating temperature -20°C to +60°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP43Weight inc base 160 grams
DETECTORS APOLLO DISCOVERY Intelligent
Mode Smoke Sensitivity Temperature Sensitivity Response Type Minimum Time to (grey smoke) (relative) Alarm (seconds)
% per m % per ft 1 1.1 0.35 High Multisensor 20 2 2.1 0.7 No response to heat Optical 30 3 2.8 0.9 Low Multisensor 20 4 4.2 1.4 High Multisensor 20 5 No response to smoke See text Heat A1 30
MultisensorDetector
OperatingModes
AUS / PAGE 73 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Discovery Carbon Monoxide Detector
The Discovery Carbon Monoxide (CO) Detector is good at detecting deep-seated fires. Please note that CO detectors do not detect smoke particles or heat and are not universal replacements for smoke detectors.
• Enhanced detection capability • Early response to hot fires • Ideal for smouldering fires • Less susceptible to false alarms caused by steam than smoke alarms • Five response modes
Approvals: AS1603.14 Discovery Carbon Monoxide Detector 201-0102
DETECTORS APOLLO DISCOVERY Intelligent
Voltage 17-28 VDCQuiescent current 500μA at 24 VDCAlarm current 3.5mA at 24 VDCSize inc base 100Dia x 50H mmOperating temperature 0°C to +50°C (no icing)Relative humidity 15 to 95% (non condensing)IP rating IP43Weight inc base 160 gramsCell life (max) 7 years
Mode Alarm Threshold Minimum Time to Alarm Typical Application (ppm) (seconds)
1 30 60 Sleeping with no ambient CO
2 45 30 General use fast response such as supplementary protection in atria
3 45 60 General use and sleeping risk with some low-level CO (such as from light smoking or an unventilated gas fire)
4 60 30 General smoking area and supplementary detection of deep seated fires such as laundry rooms
5 75 30 Supplementary use in kitchen or boiler room
Relative Performance of
Detectors inTest Fires
AUS / PAGE 74 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
DETECTORS APOLLO DISCOVERY Intelligent
Discovery Intelligent Detector BaseAll detectors in the Discovery range fit the Intelligent Detector Base. It is a low insertion force base with stainless steel contacts for the detector terminals. XPERT cards are supplied with all bases.
• XPERT addressing • One way fit • Locking feature to prevent unauthorised removal
Approvals: AS1603.1&2
Size 100Dia x 8H mmOperating temperature -20°C to +60°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 55 grams
XP95/Discovery Detector Base with Xpert Card 201-0004
Discovery Isolating BaseThe new style Isolating Base senses and detects short-circuit faults on loops and spurs.
• Up to 20 devices may be installed between isolating bases• High brightness LED
XP95/Discovery Isolating Base with Xpert Card 201-0125
Voltage 17-28 VDCQuiescent current 47μA (non isolating) 4mA (isolating)Size 100Dia x 24H mmOperating temperature -20°C to +60°C (no icing)Relative humidity 0 to 95% (non condensing)Weight 100 grams
Blank XPERT Card
A universal address card supplied with all bases. Using a coding guide, pips are removed to set the address of the inserted detector.
• Simplifies and speeds up installation and commissioning• Uses patented, proven technology• Address remains the same, no matter how often detectors are replaced• Flexibility to create any address
Pre-addressed XPERT Card
Pre-addressed XPERT cards are supplied with PIPs already removed.
• Saves time and increases accuracy during commissioning• Pre-numbered 1-126
Blank XPERT Card 38531-771Pre-addressed (1-126) Xpert Cards 201-0013
AUS / PAGE 75 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
DETECTORS BEAM DETECTORS Conventional
FIRERAY 2000 Optical Beam Smoke Detector
The FIRERAY 2000 is a conventional infrared optical beam smoke detector. It is an End to End type beam detector and is thus less susceptible to stray reflections since any reflection goes back towards the transmitter. As a result projected Optical Beams can operate within narrower gaps than reflective types.
• Separate transmitter and receiver• Range 10 to 100 metres• Low current consumption• Automatic drift compemsation• 3 x selectable sensitivity threshold levels• Low level control unit• Optional electronic alignment tool
Approvals: AS1603-7, EN54-12 and UL268
FIRERAY 2000 Beam Detector 220-0004
Operating range 10-100 metres Operating voltage 10.2VDC to 30VDC Fire relay contacts Norm open volt free 2A @ 30VDC
Resistive Fault relay contacts Norm closed volt free 2A @ 30VDC
ResistiveCondition Alarm condition: fire relay closing
May be latching or non-latching Operating temperature -20°C to +55°C (no icing) Relative humidity 0-90% (non condensing)IP rating IP50
AUS / PAGE 76 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
DETECTORS BEAM DETECTORS Conventional
FIRERAY 5000 Motorised Beam System
The FIRERAY 5000 Optical Beam Smoke Detectors can be used to provide ‘wide area’ smoke detection. They are usually used in situations where it is impractical, inappropriate or not cost effective (installation, wiring and maintenance) to use traditional point-type detectors. It also enables coverage of a large area, at minimal cost. Optical beam smoke detectors are also ideally suited for situations that might include high ceilings, dusty and dirty environments, or environments that experience temperature extremes.
• Up to 4 optical beam detectors per system controller• Easy fit system• Ground level control• Laser assisted alignment• Auto-optimise beam alignment• Contamination compensation• Building shift compensation
Approvals: AS7240-12, EN54-12 and UL268
Operating distance (separation) 8-100 metresCable length – system controller to detector(2 core screened fire resistant) 100 metresOperating voltage (to system controller) 14VDC to 28VDC Operating temperature -10°C to +55°C (no icing) Relative humidity 93% (non condensing)IP rating IP54
Accessories for FIRERAY 50R/100R AWD 5000
An extensive range of accessories are available to compliment the FIRERAY product.
Accessories for FIRERAY 50R/ 100R AWD 5000Single Reflector <50m 220-00073 x Reflector Long Range 100m Kit 220-0010Universal Bracket 220-00111 Prism Plate 220-00124 Prism Plate 220-0013Universal Ceiling Mount 220-0014
FIRERAY 5000 Motorised Beam SystemSystem Controller, Detector and Reflector 220-0008Additional Detector and Reflector 220-0009
AUS / PAGE 77 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
XP95/DiscoveryIntelligent Interfaces
• Easy to install
• Well protected
• Modular design
• A neat solution
Apollo manufactures a comprehensive range of interfaces for intelligent systems which enable fire protection systems to be engineered simply and effectively without the need for custom-designed equipment. There are a variety of interfaces available to suit a number of individual applications.
Standard Interfaces with Isolators are fitted with bi-directional short-circuit isolators so that they are unaffected by a single short circuit on either loop input or output. However, the Input/Output Unit and Output Unit with isolator are exceptions to this. The removal of loop power to these interfaces will cause a ‘set’ relay to ‘reset’.
DIN-Rail Interfaces feature enclosures that clip to standard 35mm DIN-Rails or are screwed to the base of a larger enclosure. They enable fire system designers to determine the functions required and create multi-purpose interfaces for individual sites.
Optimum protection can be provided when using the built-in isolator models.
INTERFACES
AUS / PAGE 78 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Single Input Device (SID)
The Single Input Device is an addressable loop device for use on the Apollo XP95 or Discovery protocol and provides a single monitored input.
• Interfaces a switch input to an Apollo addressable loop• Loop powered• One monitored input• Only one address used• Enclosure or DIN-Rail chassis mount• Status indicators can be switched on and off
Single Input Device (SID) – Boxed 201-0300Single Input Device (SID) – DIN mount 201-0350
INTERFACES AMPAC INPUT/OUTPUT DEVICES Intelligent
Single Input/Output Device (SIOD)
The Single Input/Output Device is an addressable loop device for use on the Apollo XP95 or Discovery protocol and provides a single monitored input and a voltage free relay output.
• Interfaces a switch input and a relay output to addressable loop• Loop powered• One monitored input• Single relay with clean changeover contact• Only one address used• Enclosure or DIN-Rail chassis mount• Status indicators can be switched on and off
Single Input/Output Device (SIOD) – Boxed 201-0301Single Input/Output Device (SIOD) – DIN mount 201-0351
Voltage 17-28 VDCQuiescent current 1.82mA at 24 VDCMax current 2.37mA at 24 VDCMonitored input 20k normal 500 - 15k closedSize – enclosure 132H x 82W x 55D mmSize – DIN chassis 77H x 57W x 40D mmOperating temperature -20°C to +60°C (no icing)Humidity 0 to 95% relative humidityIP rating – enclosure IP55Weight – enclosure 155 gramsWeight – DIN chassis 75 grams
Voltage 17-28 VDCQuiescent current 1.74mA at 24 VDCMax current 6.84mA at 24 VDCRelay contact rating 1A at 24 VDC clean changeoverMonitored input 20k normal 500 - 15k closedSize – enclosure 132H x 82W x 55D mmSize – DIN chassis 77H x 57W x 40D mmOperating temperature -20°C to +60°C (no icing)Humidity 0 to 95% relative humidityIP rating – enclosure IP55Weight – enclosure 155 gramsWeight – DIN chassis 75 grams
AUS / PAGE 79 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
INTERFACES AMPAC INPUT/OUTPUT DEVICES Intelligent
Three Input Device (3ID)
The Three Input Device is a versatile loop-powered three monitored input unit device for use on the Apollo XP95 or Discovery protocol.
• Interfaces three switch inputs to addressable loop• Loop powered• Three monitored inputs• Only one address used• Enclosure or DIN-Rail chassis mount• Status indicators can be switched on and off
Three Input Device (3ID) – Boxed 201-0308Three Input Device (3ID) – DIN mount 201-0358
Voltage 17-28 VDCQuiescent current 1.45mA at 24 VDCMax current 3.54mA at 24 VDCMonitored input 20k normal 500 - 15k closedSize – enclosure 200H x 150W x 60D mmSize – DIN chassis 98H x 72W x 40D mmOperating temperature -20°C to +60°C (no icing)Humidity 0 to 95% relative humidityIP rating – enclosure IP41Weight – enclosure 500 gramsWeight – DIN chassis 125 grams
Three Input/Output Device (3IOD)
The Three Input/Output Device is a versatile loop-powered unit for use on the Apollo XP95 or Discovery protocol. It provides three monitored inputs and three voltage free relay outputs.
• Interfaces three switch inputs and three relay outputs to addressable loop• Loop powered• Three fault monitored input• Three relays with clean changeover contact• Only one address used• Enclosure or DIN-Rail chassis mount• Status indicators can be switched on and off
Three Input/Output Device (3IOD) – Boxed 201-0309Three Input/Output Device (3IOD) – DIN mount 201-0359
Voltage 17-28 VDCQuiescent current 2.06mA at 24 VDCMax current 19.23mA at 24 VDCRelay contact rating 1A at 24 VDC clean changeoverMonitored input 20k normal 500 - 15k closedSize – enclosure 200H x 150W x 60D mmSize – DIN chassis 98H x 72W x 40D mmOperating temperature -20°C to +60°C (no icing)Humidity 0 to 95% relative humidityIP rating – enclosure IP41Weight – enclosure 500 gramsWeight – DIN chassis 125 grams
AUS / PAGE 80 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Three Input/Output Device (3IOD) EP – Externally Powered
The Three Input/Output Device EP is an externally powered unit device for use on the Apollo XP95 or Discovery protocol. Using an external 24VDC power supply, each device draws a minimum amount of loop current and provides three monitored inputs and three voltage free relay outputs.
• Interfaces three switch inputs and three relay outputs to addressable loop• Externally powered• Three fault monitored input• Three relays with clean changeover contact• Only one address used• Enclosure or DIN-Rail chassis mount• Status indicators can be switched on or off
Three Input/Output Device (3IOD) EP – Boxed 201-0310Three Input/Output Device (3IOD) EP – DIN mount 201-0360
INTERFACES AMPAC INPUT/OUTPUT DEVICES Intelligent
Voltage 17-28 VDCQuiescent current – loop 1.51mA at 24 VDCQuiescent current – external 5.08mA at 24 VDCMax current – loop 7.20mA at 24 VDCMax current – external 19.55mA at 24 VDCRelay contact rating 1A at 24 VDC clean changeoverMonitored input 20k normal 500 - 15k closedSize – enclosure 200H x 150W x 60D mmSize – DIN chassis 98H x 72W x 40D mmOperating temperature -20°C to +60°C (no icing)Humidity 0 to 95% relative humidityIP rating – enclosure IP41Weight – enclosure 500 gramsWeight – DIN chassis 125 grams
Alarm Acknowledgement Facility
The Alarm Acknowledgment Facility (AAF) is a loop powered addressable device that helps reduce the costly consequence of an unwanted alarm.
• Loop Powered Addressable Device• Built in Short Circuit Isolator• Easy configuration of Acknowledge and Investigate periods• Event logging of AAF sequence• Allows a group of detectors to be assigned to a nominated AAF• Aesthetically pleasing single gang Clipsal 2000 wall plate• Investigate status displayed at FACP and all associated LCDA’s• Audible warning is 75dB @ 1m from the built in buzzer• On board visual indication for “polling”, Fire and Fault status• Remote ‘Hush’ button input terminals available
Approvals: AS7240 and AS4428
Operating Voltage 21 to 28 VDC (loop powered)Quiescent Current 900μA at 24VDCAlarm Current <8mA at 24VDCAddress Setting 1 to 126Dimension Single gang Clipsal plateMaterial High impact ABS (white)Weight 45 grams
Alarm Acknowledgement Facility – Vertical 226-0002 Alarm Acknowledgement Facility – Horizontal 226-0004
AUS / PAGE 81 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Loop Powered Zone Interface Device (LZID)
AMPAC’s Loop Powered Zone Interface Device (LZID) is designed to connect to the analogue loops in any of AMPAC’s addressable range of fire alarm control panels (FACP’s).
• Single Conventional Zone Input• Apollo XP95 & Discovery protocol• Supports up to 40 conventional detectors• Remote LED Output• Short Circuit Isolation• Programmable EOL (3K3Ω, 6K2Ω or 10uF)
Loop Powered ZID (DIN Mount) 4210-0004Loop Powered ZID (Enclosed) 4210-0005
Operating Voltage 16Vdc – 27VdcZone Voltage (Loop Voltage ≥21V) 17 – 22VdcEnd Of Line Values 3K3Ω 6K2Ω 10uFQuiescent Current (EOL Fitted, Zone oltage = 22V and no detector load 12mA 9mA 6mAAlarm Current (remote LED not fitted) 28.5mA 28.5mA 28.5mAAlarm Current (remote LED fitted) 32mA 32mA 32mANo LZID’s / Loop 12 x 250mA Loop 24 x 500mA LoopNo. Detectors / Zone 40 MaxOperating temperature 0°C to +70°CDimensionsDIN Mount 98 (L) x 72.5 (W) x 40mm (D)Enclosed / Boxed 200 (L) x 150 (W) x 60mm (D)WeightDIN Mount 140gEnclosed / Boxed 460g
INTERFACES AMPAC INPUT/OUTPUT DEVICES Intelligent
AUS / PAGE 82 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Input/Output Unit with Isolator
The Input/Output unit with Isolator provides a voltage free, single, pole, change-over relay output, a single, monitored switch input and an unmonitored, non-polarised opto-coupled input.
• It can report fault, switch open and switch closed levels• Three visible LEDs• Loop powered• Voltage free• Capable of switching up to 1A at 30V• Built-in short circuit isolator (fitted on 55000-847)
Approvals: AS4428.1Input Unit with Isolator 201-0151Input Unit (no Isolator) 201-0007 Output Unit with Isolator 201-0152Output Unit (no Isolator) 201-0008
INTERFACES XP95/DISCOVERY Intelligent
Voltage 17-28vdcQuiescent current 1.2mA at 24vdcMax current 3.5mA at 24vdcRelay contact 1A at 30vdcOpto input 35vdc maxMonitored input voltage 9-11vdcOperating temperature -20°C to +70°C (no icing)Relative humidity 0 to 95% (non condensing)IP Rating IP54Size 150W x 90H x 48D mmWeight 240 grams
The Zone Monitor with Isolator powers and controls the operation of a zone of up to 20 Apollo Series 65 or Orbis fire detectors from a Discovery or XP95 Loop.
• Loop powered • Visible LED• Built-in short circuit isolator (fitted on 55000-845)
Approvals: AS4428.1
Zone Monitor with Isolator
Discovery/XP95 Zone Monitor with Isolator 201-0126Discovery/XP95 Zone Monitor (no Isolator) 201-0012
Voltage 17-28vdcQuiescent current 4mA + detector loadAlarm current 11mA at 24vdcEOL resistor value 5.1k ¹⁄₃ wattMaximum capacitor on zone terminals 50µFZone voltage 19V ± 1VOperating temperature -20°C to +70°C (no icing)Relative humidity 0 to 95% (non condensing)IP Rating IP54Size 150W x 90H x 48D mmWeight 230 grams
AUS / PAGE 83 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Sounder Control Unit with Isolator
The XP95 Sounder Control Unit with Isolator is used to control the operation of a zone of conventional sounders and report their status to the control panel. • Allows sounders to be operated continuously or be pulsed, 1 second on 1 second off• May be synchronized when in pulsed operation
Approvals: AS4428.1
Sounder Control Unit with Isolator 201-0127Sounder Control Unit (no Isolator) 201-0010
Voltage 17-28vdcQuiescent current 1.95mA at 24vdcLoop current max 4.5mAExternal supply 9-32vdc 1.25AExternal quiescent current 3mA at 32vdcExternal current max 47mA + loadSounder circuit load max 1A at 30vdcOperating temperature -20°C to +70°C (no icing)Relative humidity 0 to 95% (non condensing)IP Rating IP54Size 150W x 90H x 48D mmWeight 240 grams
INTERFACES XP95/DISCOVERY Intelligent
The Three Channel Input/Output unit with Isolator provides three voltage free, single pole, change-over relay outputs, and three monitored switch inputs.
• Supervises one or more normally-open switches on each of the three inputs• Loop powered• Capable of switching up to 30V at 1A on each of the three outputs• Built-in short circuit isolator
Approvals: AS4428.1
Three Channel Input/Output Unit with Isolator
Three Channel Input/Output Unit with Isolator 201-0175Three Channel Input/Output Unit (no Isolator) 201-0115
Voltage 17-28vdcQuiescent current 3mA at 24vdcMax current 7.5mA at 24vdcRelay contact 1A at 30vdcMonitored input voltage 9-11vdcOperating temperature -20°C to +70°C (no icing)Relative humidity 0 to 95% (non condensing)IP Rating IP54Size 250W x 175H x 75D mmWeight 621 grams
AUS / PAGE 84 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Mains Switching Input/Output Unit
The XP95 Loop Powered Mains Switching Input/ Output Unit provides a voltage free, single pole charge- over relay output and a monitored switch input. • Voltage free single pole charge-over relay• Monitored switch input• Fault LED• Input active LED• Relay on LED
Mains Switching Input/Output Unit 201-0180
Voltage 17-28vdcQuiescent current 1.2mA at 24vdcMax current 2.5mA at 24vdcRelay contact Switching capacity 1.25kVAMonitored input voltage 9-11vdcOperating temperature -20°C to +70°C (no icing)Relative humidity 0 to 95% (non condensing)IP Rating IP54Size 150W x 90H x 48D mmWeight 240 grams
INTERFACES XP95/DISCOVERY Intelligent
AUS / PAGE 85 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Audio Visual Signalling
Ampac offers a wide range of Intelligent Audio Visual (AV) signalling devices for use in conjunction with its range of intelligent and conventional detectors and control panels. A versatile and functional range offering a huge choice for any application.
• Sounder Bases combine an alarm sounder and detector base
• Beacon Bases combine an alarm beacon and detector base
• Sounder Beacon Bases combine an alarm sounder, beacon and detector base
• Sounders are used to provide an audible indication of an alarm
• Beacons are used to provide an visual flashing indication of an alarm
• Sounder/Beacons are used to provide an audible and flashing indication of an alarm
AUDIO VISUAL SIGNALLING
AUS / PAGE 86 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Integrated Sounder Base
The Integrated Sounder Base comprises a base sounder with integral mounting base and is for use with Discovery or XP95 ranges. It is designed for indoor use.
• Two volume ranges – via DIP switch setting• Synchronisation of ‘alert’ and ‘evacuate’ tones • Individual and group addressing • Unique acoustic self-test • Integrated base • Built-In short circuit isolator
Approvals: AS1670.4Integrated Base Sounder 201-0110White Cap 201-0114
AUDIO VISUAL SIGNALLING XP95/DISCOVERY INTELLIGENT SOUNDER BASES
Voltage (polarity sensitive) 17-28 VDCQuiescent current 1.2mAMax current (sounder operated) 5mAMax sounder output 92dB(A)Operating temperature -20°C to +60°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP21DSize 115Dia x 38H mmWeight 140 grams
AUS / PAGE 87 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Sounder Beacon Base
The Sounder Beacon Base is a loop-powered sounder and beacon combined with a standard Intelligent Mounting Base. It is used to signal a fire alarm in enclosed areas. The Sounder Beacon Base can be used either with a detector fitted or with a cap for operation as a stand-alone alarm device.
• Two volume ranges via DIP switch• Beacon flash rate as per AS1670.4• Synchronisation of ‘alert’ and ‘evacuate’ tones• Synchronisation of beacon flash• Individual and group addressing• Unique acoustic and beacon self test• Enables DDA compliance• Built-In short circuit isolator• Beacon only variant available
Approvals: AS1670.4
Sounder Beacon Base 201-0116Beacon Base 201-0120White Cap 201-0114
AUDIO VISUAL SIGNALLING XP95/DISCOVERY INTELLIGENT SOUNDER BEACON BASES
Voltage (polarity sensitive) 17-28 VDCQuiescent current + Beacon 300µAMax current (sounder operated) 8mAMax current (beacon only) 3.1 mAMax sounder output 91dB(A)Operating temperature -20°C to +60°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP21DSize 115Dia x 38H mmWeight 160 grams
AUS / PAGE 88 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Intelligent Open-Area Sounder (Sonos)
The Intelligent Open-Area Sounder has been designed for use in open areas and can be connected to any Discovery or XP95 system.
• Self-test fault monitoring• Choice of tones• Group addressing and synchronisation of alarm• Weatherproof IP65• Comes with Isolating Base as standard• Loop powered
Approvals: LPCB EN54-3/LPCB Intelligent Open Area Sounder (Red) Sonos 205-0100Intelligent Open Area Sounder (White) Sonos 205-0101
NEW
AUDIO VISUAL SIGNALLING XP95/DISCOVERY INTELLIGENT SOUNDERS
Voltage (polarity sensitive) 17-28 VDCQuiescent current 333µAMax current (sounder operated) 5mAMax sounder output 88-96dB(A) ±3dB(A)Operating temperature -10°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP65Size 104Dia x 95.5H mmWeight 225 grams
AUS / PAGE 89 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Loop-Powered Beacon
The Loop-Powered Beacon is a local-area beacon designed for indoor use. The beacon has been developed as a supplement to sounders for use in situations where there is a risk that sounders will not be heard.
• High intensity LED – more reliable than xenon beacons• Automatic LED check• Lockable• Wide angle of visibility• Enables DDA compliance• Synchronised flash• Can be used with Discovery or XP95
Approvals: AS1670.4
Loop-Powered Beacon (Red) 201-0118Loop-Powered Beacon (Clear Lens/Red Flash) Standard Flash 55000-878Loop-Powered Beacon (Amber) Standard Flash 55000-879
Intelligent Open-Area Beacon (Sonos)
The Intelligent Open-Area Beacon has been developed for use in situations where there is a risk that sounders will not be heard. It is weatherproof and can be used outside.
• Self-test fault monitoring• Weatherproof IP65• Group addressing• Synchronisation of alarm• Comes with Isolating Base as standard• Loop powered
Approvals: AS1670.4Intelligent Open Area Beacon (Red) Sonos 208-0100Intelligent Open Area Beacon (Clear) Sonos 208-0101
NEW
AUDIO VISUAL SIGNALLING XP95/DISCOVERY INTELLIGENT BEACONS
Voltage (polarity sensitive) 17-28 VDCQuiescent current 150µAMax current (beacon operated) 3mAFlash rate 1HzOperating temperature -20°C to +60°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP23DSize 115Dia x 38H mmWeight 140 grams
Voltage (polarity sensitive) 17-28 VDCQuiescent current 333µAMax current (beacon operated) 3.1mAFlash rate 1HzOperating temperature -10°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP65Size 104Dia x 97.5H mmWeight 205 grams
AUS / PAGE 90 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Intelligent Open-Area Sounder Beacon
The Intelligent Open-Area Sounder Beacon has been designed for use in open areas and can be connected to any Discovery or XP95 system.
• Gives two functions at one point• Self-test fault monitoring• Choice of tones• Group addressing and synchronisation of alarm• Comes with Isolating Base as standard• Loop powered
Approvals: AS1670.4Intelligent Open Area Sounder Beacon (Red) Sonos 205-0102Intelligent Open Area Sounder Beacon (Clear) Sonos 205-0103
NEW
AUDIO VISUAL SIGNALLING XP95/DISCOVERY INTELLIGENT SOUNDER/BEACONS
Voltage (polarity sensitive) 17-28 VDCQuiescent current 333µAMax current (sounder/beacon operated) 8mAMax sounder output 100dB(A)Flash rate 1HzOperating temperature -10°C to +55°C (no icing)Relative humidity 0 to 95% (non condensing)IP rating IP65Size 104Dia x 97.5H mmWeight 260 grams
AUS / PAGE 91 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
AUDIO VISUAL SIGNALLING AMPAC STROBES
ASL-86 Strobe
• Red or Amber Lens• High intensity output• ABS / Polycarbonate / Acrylic construction• Combined Red & Amber surface mount unit available
ASL-86 Strobe (Red) 208-0007ASL-86 Strobe (Amber) 208-0008ASL-86 Strobe (Red & Amber) Combined Unit 208-0011
Voltage 24 VDCCurrent 140mARating 10 WattsSize inc base 100Dia x 88H mmFlash rate 75 per minuteOperating temperature -20°C to + 60°CIP rating IP65Weight – strobe 182 gramsWeight – combined unit 719 grams
AUS / PAGE 92 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Sonos Low Current Visual Warning Device
The SONOS Low Current Visual Warning strobes are general purpose LED strobes for fire, security and industrial applications. The strobes come with the flexibility of individual Red, Amber and Clear strobes or combined Red/Amber strobe units complete with either a flush or surface mounting plate. The strobes utilises a full faced, translucent case which provides a much larger lens area and a greater spread of light. The strobes are suitable for use with AMPAC’s EV3000 system (both single and combined) and AMPAC’s fire panels (Single only). Simple ‘twist and click’ insertion avoids wiring and connection problems.
• Low current consumption• Simple ‘twist and click’ insertion• Red, Amber and Clear options• Quick connect/disconnect• IP65 weather proof options (deep base units) for indoor and outdoor use
Sonos Low Current Visual Warning Device (Red) 208-0060Sonos Low Current Visual Warning Device (Amber) 208-0061Sonos Low Current Visual Warning Device (Clear) 208-0062Sonos Low Current Visual Warning Device (Deep Base Only) 208-0064
AUDIO VISUAL SIGNALLING AMPAC STROBES (Conventional)
Operating voltage 17 – 60 VDCCurrent drain 5mAOperating Temperature -25°C to +70°CIP Rating Shallow IP21IP Rating Deep IP65Colour Base WhiteColour Lens Red, Amber, ClearApprovals C-tick
Combined Strobe for EV3000
Due to its low current draw the Sonos strokes can be connected in larger volumes onto the EV3000 visual output circuits.
Combined Strobe for EV3000 (Flush Mount) 208-0063Combined Strobe for EV3000 IP65 (Flush Mount) 208-0065Combined Strobe for EV3000 (Surface Mount) 208-0066
AUS / PAGE 93 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Strobe Sign Plate
Mounts directly behind the Single Red Sonos Strobe. Used outside the main building entrance which leads fire fighters to the fire indicator panel location. Outdoor strobes should always use the deep base.
AUDIO VISUAL SIGNALLING AMPAC STROBES (Conventional)
Strobe Sign Plate 207-0042
Fixing Directly behind the Sonos Model Strobe / Beacons Material Painted metal 1mmSize 120mm W X 160mm H
AUS / PAGE 94 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Fire Alarm Bell 150mm
• Motorised mechanism• Low current consumption• Red finish with FIRE lettering• Suitable for indoor use• Back box available – 206-0006
Bell 150mm 206-0012
Fire Alarm Bell 200mm
• Red finish with FIRE lettering• Solenoid actuating mechanism• Suitable for indoor use• Back box available – 206-0006
Bell 200mm 24Vdc 206-0001
AUDIO VISUAL SIGNALLING AMPAC BELLS
Voltage 24 VDCOperating current 25mASize (without back box) 150Dia x 56D mmSound Level 92 dB @ 3mOperating temperature -10°C to +55°C (no icing)Weight 764 grams
Voltage 19-27 VDCOperating current 100mASize (without back box) 200Dia x 70D mmSound Level 85 dB @ 3mOperating temperature -20°C to +70°C (no icing)Weight 1.25kg
Bell Back Box
• Allows surface mounting of bell• Screw thread conduit entry and protection for wiring terminals• Red finish• Weather seal
Bell Back Box for 206-0012 and 206-0001 206-0006
Material Aluminium castFinish RedDepth 40 mmWeight 270 grams
AUS / PAGE 95 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Key Holder – D2
• Provides a visible place to locate a key used for emergency access• Red finish• Instructions on glass• Break glass operation similar to a manual call point• Suitable for indoor use Key Holder – D2 215-0003
Spare Glass – D2 215-0004
AUDIO VISUAL SIGNALLING AMPAC KEY HOLDERS
Size 100Dia x 32D mmFinish RedWeight 130 grams
AUS / PAGE 96 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Fire Alarm Remote Indicator – Round
• Detector activation indicator• 5mm Red LED• Compact size• Modern styling• For conventional or analogue detectors• Choice of legend Remote Indicator – Blank 209-0001
Remote Indicator – Fire Alarm in Concealed Space 209-0004Remote Indicator – Fire Alarm in Roof Space 209-0005Remote Indicator – Fire Alarm in Room 209-0006Remote Indicator – Fire Alarm in Duct 209-0007Remote Indicator – Fire Alarm in Cupboard 209-0008Remote Indicator – Fire Alarm Under Floor 209-0009Remote Indicator – Fire Alarm in Return Air 209-0010Remote Indicator – Fire Alarm in Exhaust Duct 209-0011Remote Indicator – Fire Alarm in Supply Air Duct 209-0012Remote Indicator – Fire Alarm in Ceiling 209-0013Remote Indicator – Fire Alarm Above 209-0014Remote Indicator – Fire Alarm 209-0020Remote Indicator – Detector Activated 209-0023
AUDIO VISUAL SIGNALLING AMPAC REMOTE INDICATORS
Voltage 24 VDCCurrent at 24v 1.5mASize 74Dia x 16H mmWeight 26 grams
AUS / PAGE 97 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Indicator / Buzzer & Indicator / Buzzer with Mute
• Alarm activation indicator and buzzer• 10mm red flashing LED• Buzzer (with mute facility)• Modern styling
Flashing Indicator / Buzzer 209-0017Flashing Indicator / Buzzer with Mute Switch 209-0016
Indicator / BuzzerVoltage 24 VDCCurrent at 24v 27mALED flash rate 45 per minuteBuzzer 3.8kHz @ 114dBASize 70H x 110W x 10D mmWeight 64g Indicator / Buzzer with MuteVoltage 24 VDCCurrent at 24v 43mALED flash rate 45 per minuteBuzzer 3.8kHz @ 114dBASize 70H x 110W x 10D mmWeight 89g
AUDIO VISUAL SIGNALLING AMPAC REMOTE INDICATORS
AUS / PAGE 98 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Sonos Sounder Beacon
A general purpose electronic sounder beacon for fire, security and industrial applications. Deep base units have weatherproof protection to IP65 and can be used in all locations both indoors and outdoors. A full faced, translucent sounder case rather than a separate add-on beacon gives a much larger lens area and a greater spread of light.
• Simple `First Fix` installation – TimeSaver base• Quick connect/disconnect• Tone and volume can be preset or adjusted off-base• Weatherproof to IP65 (deep base units)• Low current LED beacon• Sounder and beacon can be controlled separately
Approvals: EN54-3/LPCB
Red Lens Sonos LED Beacon, shallow base 205-0105Deep Base (IP65) 208-0067Other Colour Combinations Available on Request.
AUDIO VISUAL SIGNALLING KLAXON SONOS SOUNDER BEACON
Audibility at 1m (tone dependent) Up to 106dB (A)Tones 32Voltage 17-60V DCCurrent 4-45mA (sounder) 5mA (beacon)IP Rating IP65 (deep base)Operating temperature -25°C to +70°CWeight 215 grams (shallow base) 250 grams (deep base)
AUS / PAGE 99 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Vector Sounder
• AS1670.4 – signal only• Externally powered - low current consumption• Volume control adjustment• Built-in synchronising circuitry with sounders on the same circuit• Can be installed as a sounder base for Apollo detectors or a surface
mount sounder when used in conjunction with the optional lid• Low profile• Available as standard with an XP95 universal base fitted (complete with
opto - interface board) so the sounder can be controlled via the remote LED output of the XP95 detector
Approvals: AS1670.4Vector Sounder 205-0077Vector Sounder Lid 205-0017
Vantage Sounder
• Selectable signals to AS1670.4• High output level – up to 100 dB• 3 selectable output levels• Low current consumption for rated output• 2 or 3 wire configuration• Automatic signal changeover facility• Excellent lateral sound dispersion• Built-in synchronising circuitry• Surface mounted• Quick-fit deep base option• Head to base locking
Approvals: AS1670.4Vantage Sounder Red with Shallow Base 205-0062 Vantage Sounder White with Shallow Base 205-0063 Deep Base Only Red 205-0064Deep Base Only White 205-0065
AUDIO VISUAL SIGNALLING ELECTRONIC SOUNDERS
Operating voltage 8 to 35 VDCSupply current Evac 15mA @ 24VDCSupply current Alert 8 mA @ 24VDCSignal output AS1670.4 – signal onlyMax. Output level 91 dBA @ 1 metre with detectorEvac 93 dBA @ 1 metre with lidVolume control -30dBAIP rating IP42Temperature range -20 to + 70°CConstruction ABSDimension (mm) 106Ø x 35h (Sounder & lid only)
Voltage 12 to 35 VDCVolume setting Low Med HighCurrent (mA @ 27VDC ) 7 12 19Sound Output (dB @ 1m) 85 95 100Signals AS1670.4Size (shallow base) 94 Dia x 85 H mmSize (deep base) 93 Dia x 102 H mmTemperature range -20°C to +70°CHumidity 0 to 95%IP Rating (shallow) IP43IP Rating (deep) IP65Weight 193 grams (deep base +5g)
AUS / PAGE 100 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Vantage Combi
• Signals to AS1670.4• High brightness LED strobe• High output level – up to 100dB• 3-level selectable sound output levels• Low current consumption less than 70mA• 2 or 3-wire configuration• Automatic signal changeover facility• ABS plastic – available in red or white• Excellent lateral sound dispersion• Built-in synchronising circuitry• Surface mounted• Quick-fit lockable base (both shallow and deep base)
Approvals: AS1670.4 Vantage Combi Red with Shallow Base 205-0066 Vantage Combi White with Shallow Base 205-0067 Deep Base Only Red 205-0064Deep Base Only White 205-0065
AUDIO VISUAL SIGNALLING ELECTRONIC SOUNDER/BEACONS
Voltage 18 to 35 VDCVolume setting Low Med HighCurrent (mA @ 27VDC ) 11 18 30Sound Output (dB @ 1m) 85 95 100Signal AS1670.4Flash rate 1 per secSize (shallow) 93 Dia x 90 H mmSize (deep) 93 Dia x 107 H m Temperature range -20°C to +70°CHumidity 0 to 95%IP Rating (shallow) IP43Weight 221 grams (deep base +5g)
AUS / PAGE 101 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
ANCILLARIES
AncillariesAmpac offers a wide range of Intelligent Ancillary devices for use in conjunction with its range of intelligent and conventional detectors and control panels. A versatile and functional range offering a huge choice for any application.
• Power Supplies
• Manual Call Points
• Fittings
• Occupant Warning Systems- Amplified Sound Systems
• Electro Magnetic Door Holders
• Document Cabinets
• Test Equipment
• Sealed Rechargeable Lead Acid Batteries
AUS / PAGE 102 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
MultiAmp PSU
The MultiAmp PSU is a general purpose regulated power supply unit.
• Available in 2A and 3A versions• Fault Relay Output• Fault indicator and Resettable Buzzer• Earth monitoring• Available in ABS (BX1)• Available in Metal cabinets (BX10) shallow and deep versions• 2.5mm² cable terminals
A set of two 7Ahr batteries may be housed in the BX1 and BX10 standard cabinet and a set of two 12Ahr batteries in the BX10 deep cabinet. (Maximum size based on Ampac battery specifications)
The unit incorporates temperature sensing and compensation whereby a change in ambient temperature adjusts the battery charging voltage.
The power supply will signal a Low Batt fault at 21.3 VDC.
Approvals: Complies with AS4428/AS7240
MultiAmp PSU 2A AS/EN Version (ABS BX1) 4510-2110 MultiAmp PSU 3A AS/EN Version (ABS BX1) 4510-2120 MultiAmp PSU 2A AS/EN Version (Metal BX10) 4510-2210 MultiAmp PSU 3A AS/EN Version (Metal BX10) 4510-2220 MultiAmp PSU 2A AS/EN Version (Metal BX10 Deep Cabinet) 4510-2310 MultiAmp PSU 3A AS/EN Version (Metal BX10 Deep Cabinet) 4510-2320 BX10 Surround ENC3016-A
MultiAmp PSU ABS
MultiAmp PSU Metal
Mains Supply 190 – 264 VACOperating Voltage 27.5 VDC ± 0.2 VDCSupply Current 2A Current limited (2Amp Version) 3A Current limited (3Amp Version)Operating Temperature 0°C to +40°CRelative Humidity 25% - 75%Battery Capacity:BX1 and BX10 2 x 7Ahr 12V Sealed Lead AcidBX10 Deep Cabinet 2 x 12Ahr 12V Sealed Lead AcidMaximum Charge Current 400mA (2A) 600mA (3A)Fault Relay NO,C,NC Contact rating: 1A @ 30VDCDimensions:ABS Cabinet (BX1) 300mm (H) x 360mm (W) x 100mm (D)Metal Cabinet (BX10) 300mm (H) x 360mm (W) x 100mm (D)Metal Cabinet (BX10 DEEP) 300mm (H) x 360mm (W) x 200mm (D)
ANCILLARIES POWER SUPPLIES
AUS / PAGE 103 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
ANCILLARIES POWER SUPPLIES
FastSense Power Supply Unit
• 2A power supply (incorporating battery charger)• Status indication – “POWER ON”, “BATTERY HIGH”, “BATTERY LOW”,
“BATTERY FAIL”• Battery test facility• Termination for power supply output – Clearly labelled and adequate
amount of room to terminate• Panel knockouts – top, side and rear of cabinet• Optional 6A power supply / battery charger may be fitted to the
FastSense PLUS version
FastSense PSU – FastSense 25 & FastSense 100 versions 216-0065FastSense PSU – FastSense PLUS version 216-0066
Operating voltage 240 VACOutput voltage 27 VDCMax output current 2 Amps @ 27.6 VDCBattery capacity: FastSense 25 & FastSense 100 versions 7 AhFastSense PLUS version 12 AhDimensions:FastSense 25 & FastSense 100 versions 300 H x 350 W x 130 D mmFastSense PLUS version 320 H x 500 W x 160 D mmMaterial 1.6 mm Mild steelFinish Powder coated Oyster Grey
AUS / PAGE 104 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Manual Call Point – ACP-04
• Double terminal, wire protected connectors for independent input and output connections when looping to other devices
• Protective film prevents glass from splintering when broken• Open or close circuit operation• 20 mm conduit entries• Testing and resetting the unit with key supplied• High reliability micro-switch operation• Manufactured from high impact plastic and resistant to heat• 470Ω in-line resistor
Manual Call Point – ACP-04 Red 213-0060Manual Call Point – ACP-04 Yellow 213-0061Manual Call Point – ACP-04 White 213-0062Manual Call Point – ACP-04 Green 213-0063Manual Call Point – ACP-04 Protective Cover 213-0057Manual Call Point – ACP-04 Glass 213-0058
ANCILLARIES Manual Call Points – Conventional
Current Rating 3A @ 12/24 VDC 1.5A @ 48 VDCSize H 88 x W 88 mm D 59 mm – surface mounted D 27 mm – flush mountedSwitch Type Single pole microCable termination 6 x 2.5mm2 screwIn-Line Resistor 470Ω (N/O operation only)Material High impact ABSOperating Temperature -5°C to +70°CHumidity 0 – 95% non-condensingIP rating IP 24DWeight 153 grams
AUS / PAGE 105 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Manual Call Point – Conventional FP2
• Re-setable operation• No broken glass or frangible element to replace• Tested by actual operation• Fluorescent band indicates call point has been operated• Open or closed circuit operation• Surface and Flush mountable• Transparent lift up cover available
FP2 Red 213-0021 FP2 White 213-0022 FP2 Protective Cover 213-0023
ANCILLARIES Manual Call Points
Contact rating 5A @ 30 VDC 10A @ 250 VACSize (surface mount) 87H x 87 W x 54 D mmSize (flush mount) 87H x 87 W x 16 D mmSwitch type Single poleMaterial High impact ABSOperating Temperature -10°C to +70°CIP rating IP44Weight 200 grams
Manual Call Point – Conventional Weatherproof
• Suitable for outdoor use• Hermetically sealed switches• Back box supplied
Manual Call Point – Conventional Weatherproof 213-0045
Contact rating 5A @ 24 VDCSize 110H x 110W x 65DmmSwitch type Single PoleMaterial High Impact ABSTemperature range -10°C to +70°CIP rating IP67Weight 200 g
AUS / PAGE 106 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
XP95 Manual Call Point
The XP95 Manual Call Point is compliant with EN54-11. The address of each call point is set at the commissioning stage by means of a seven segment DIL switch. The device features plug and play terminal connections and a resettable element.
• Plug-and-play terminal connectors for fast wiring• Allows wiring continuity testing before fitting• Isolated version available• Reports an alarm in under 0.2 seconds• Resettable element
Approvals: AS1670.1 and EN54-11XP95 Manual Call Point (Surface) 213-0050XP95 Manual Call Point with Isolator (Surface) 213-0051XP95 Manual Call Point Protective Cover 213-0064
Voltage 17-28 VDCQuiescent current 100μA at 24VDCAlarm current 4mAAddress method 7 segment DIL switchSize (surface mount) 93H x 89W x 59.5D mmOperating temperature -20°C to +60°C (no icing)Relative humidity 0-95% (non condensing)IP rating IP45Weight 190 grams
ANCILLARIES Manual Call Points
Intelligent Waterproof Manual Call Point
The Intelligent Waterproof Manual Call Point has been designed for use outdoors and in places where moisture can occur.
• Plug and play terminal connections for fast wiring • Allow wiring continuity testing before fitting • Isolated version available • Resettable element
Approvals: AS1670.1 and EN54-11
Intelligent Waterproof Manual Call Point 213-0066Intelligent Waterproof Manual Call Point with Isolator 213-0067
Voltage 17-28 VDCQuiescent current 230μAAlarm current 2mAAddress method 7 segment DIL switchSize (surface mount) 87H x 87W x 54D mmOperating temperature -20°C to +70°C (no icing)Relative humidity 0-95% (non condensing)IP rating IP67Weight 400 grams
AUS / PAGE 107 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
XP95 Intrinsically Safe Manual Call Point
The XP95 IS Manual Call Point is based on the standard weatherproof model. It features an ‘interrupt’ facility to provide fast response to an alarm.
• Reports an alarm in under 0.2 seconds• Waterproof• IP67
Approvals: AS1670.1 and EN54-11
XP95 Intrinsically Safe Manual Call Point 55100-940
Voltage 14 to 22 VDCQuiescent current 230uAAlarm current 2mAAddress method 7 segment DIL switchSize 124H x 124W x 60D mmOperating temperature -20°C to +60°C (no icing)Humidity 0 to 95%IP rating IP67Weight 400 gramsClassification E Ex ia IIc T5
ANCILLARIES Manual Call Points
AUS / PAGE 108 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Wall Boxes
• Used for flush mounting devices such as manual call points and sounders• Suitable for MCP models ACP-01 & FP2• Suitable for ‘Vara’ sounder
Wall Box Metal 268-0002 Wall Box Plastic 268-0009
ANCILLARIES Fittings
Size Metal 72H x 72W x 47D mm Plastic 72H x 72W x 35D mmWeight Metal 153 gramsPlastic 47 grams
AUS / PAGE 109 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Amplified Sound System – EV20
ANCILLARIES Occupant Warning Systems
Amplified Sound System – EV40
• Single zone amplified sound system for occupant warning• Signals to AS1670.4• Open and short circuit speaker line monitoring and protection• Manual control / isolation facility• Volt free Fire Alarm Control Panel input (latching)• Adjustable volume control• Automatic changeover between tones• Fault output• P.A. microphone input (optional)• Verbal messaging (optional)
Approvals: AS1670.4Amplified Sound System – EV20 222-0020Verbal Message 222-0026EV20/60/120 Microphone Upgrade Kit 222-0007
Voltage 27 VDCQuiescent current 41mAMax current 650mAMax output power 20 WattsOutput voltage 100 VAC RMSSignals AS1670.4Size - main board 180L x 82W x 55H mmSize - controls 90L x 35W x 40H mmTone timeout 0, 30, 60, 120, 180, 240 or 300 secsWeight 690 grams
• Single zone amplified sound system for occupant warning• Signals to AS1670.4• Open and short circuit speaker line monitoring and protection• Manual control / isolation facility• Volt free Fire Alarm Control Panel input (latching)• Adjustable volume control• Automatic changeover between tones• Fault output• P.A. microphone input (optional)• Verbal messaging (optional)
Approvals: AS1670.4
Amplified Sound System – EV40 222-0021Verbal Message 222-0013EV40 Microphone Upgrade 294-0001
Voltage 27 VDCQuiescent current 140mAMax current 2.8AMax output power 40 WattsOutput voltage 100 VAC RMSSignals AS1670.4Size - main board 170L x 90W x 60H mmSize - control card 90L x 35W x 40H mmTone timeout 0, 30, 60, 120, 150, 180, 210, 240, 270, 300, 360, 420, 480 or 540 secsWeight 900 grams
AUS / PAGE 110 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Amplified Sound System – EV60
• Single zone amplified sound system for occupant warning• Signals to AS1670.4• Open and short circuit speaker line monitoring and protection• Manual control / isolation facility• Volt free Fire Alarm Control Panel input (latching)• Adjustable volume control• Automatic changeover between tones• Fault output• P.A. microphone input (optional)• Verbal messaging (optional)
Approvals: AS1670.4Amplified Sound System – EV60 222-0022Verbal Message 222-0013EV20/60/120 Microphone Upgrade Kit 222-0007
ANCILLARIES Occupant Warning Systems
Voltage 27 VDCQuiescent current 140mAMax current 3.9AMax output power 60 WattsOutput voltage 100 VAC RMSSignals AS1670.4Size - main board 180L x 82W x 55H mmSize - controls 90L x 35W x 40H mmTone timeout 0, 30, 60, 120, 180, 240 or 300 secsWeight 2.75 kg
Amplified Sound System – EV120
• Single zone amplified sound system for occupant warning• Signals to AS1670.4• Open and short circuit speaker line monitoring and protection• Manual control / isolation facility• Volt free Fire Alarm Control Panel input (latching)• Adjustable volume control• Automatic changeover between tones• Fault output• P.A. microphone input (optional)• Verbal messaging (optional)
Approvals: AS1670.4Amplified Sound System – EV120 222-0023Verbal Message 222-0013EV20/60/120 Microphone Upgrade Kit 222-0007
Voltage 27 VDCQuiescent current 260mAMax current 8AMax output power 120 WattsOutput voltage 100 VAC RMSSignals AS1670.4Size - main board 170L x 210W x 85H mmSize - controls 90L x 35W x 40H mmTone timeout 0, 30, 60, 120, 180, 240 or 300 secsWeight 3.7 kg
AUS / PAGE 111 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
ADH-01 – Electro-Magnetic Door Holder
• Available in 24VDC with 50kg/50N holding force• Release switch on housing• Designed for surface mounted• Adjustable door mounted keeper plate• Separate screw terminals to maintain monitoring integrity• Rear and side cable access
ADH-01 – Electro-Magnetic Door Holder, 50kg/50N holding force 212-0012
ANCILLARIES Electro-Magnetic Door Holders
Operating Voltage 15 to 29 VDCOperating Current 55mA @ 24 VDCHolding Force 50kgHousing White High Temperature ABSOperating Temperature -10° to +55° CDimension (mm) 100h x 100w x 50dIP rating IP 51Weight 750 gApproval C-Tick
H1330 – Magnet
• 50kg/50N holding force• Retains fire doors in the open position• In built residual magnetism release pin• Fail safe operation
H1330 – Magnet, 50kg/50N holding force 212-0002
Voltage 24 VDCQuiescent current 60mA at 24 VDCSize exc anvil 65H x 65W x 35D mmWeight inc anvil 420 grams
AUS / PAGE 112 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
ANCILLARIES Electro-Magnetic Door Holders
H1360 – Surface Mount
• Retains fire doors in the open position• Cover in black ABS• Container in white aluminium• In built residual magnetism release pin• In built manual release switch• Fail safe operation H1360 – Surface Mount, 50kg/50N holding force 212-0003
H1360 – Surface Mount, 100kg/100N holding force 212-0004
Voltage 24 VDCQuiescent current 100mA at 24 VDCSize exc anvil 95H x 95W x 40D mmWeight inc anvil 700 grams
H1368 – Flush Mount
• 50kg/50N holding force• Retains fire doors in the open position• Flush Mount• Cover in aluminium• Housing in galvanised steel• In built residual magnetism release pin• Fail safe operation
H1368 – Flush Mount, 50kg/50N holding force 212-0006
Voltage 24 VDCQuiescent current 100mA at 24 VDCSize exc anvil 120H x 76W x 41D mmWeight inc anvil 650 grams
H1369 – Floor Mount
• 50kg/50N holding force• Retains fire doors in the open position• Black steel bracket, die-cast aluminium mounting• In built residual magnetism release pin• In built manual release switch• Fail safe operation H1369 – Floor Mount, 50kg/50N holding force 212-0001
Voltage 24 VDCQuiescent current 60mA at 24 VDCSize exc anvil 100H x 110W x 80D mmWeight inc anvil 946 grams
AUS / PAGE 113 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
ANCILLARIES Electro-Magnetic Door Holders
H1370 – Floor or Wall Mount
• 50kg/50N holding force• Retains fire doors in the open position• Black steel bracket, aluminium support• In built residual magnetism release pin• In built manual release switch• Fail safe operation
H1370/15 – Floor or Wall Mount – 150mm arm 212-0007H1370/30 – Floor or Wall Mount – 300mm arm 212-0008
Voltage 24 VDCQuiescent current 60mA at 24 VDCSize exc anvil Base 125H x 125W x 15D mmArm 1370/15 40Dia x 150H mmArm 1370/30 40Dia x 300H mmWeight inc anvil 1.277 kg
H1351 – Anvil
• Retains fire doors in the open position• Cushioned magnetic support for 50kg electromagnets• Swivel adjustment
H1351 – Anvil 212-0009
Size 65H x 64W x 48D mmWeight 18 grams
Remote Door Release
• Remotely releases fire doors held open by electro magnetic door holder
Remote Door Release 268-0003
Size 70H x 110W x 10D mmWeight 68 grams
AUS / PAGE 114 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
ANCILLARIES Electro-Magnetic Door Holders
MultiAmp-DH
The MultiAmp-DH 250mA Door Holder Supply (DHS) provides up to 250mA of current at 24 VDC to operate door holders. The unit can operate as an “Automatic Door Release System” (ADRS) or respond to a secondary control.
When configured as an ADRS, conventional detectors are installed and connected directly to the DHS. The detection circuit is monitored for alarm, open, or short circuit conditions. The presence of any one of these conditions will deactivate supply to the door holders and cause doors to be released.
Alternatively doors may be released by a switched VDC input to the DHS, derived normally from a Fire Alarm Control Panel (FACP) or security system. The switched VDC input must be between 8 to 30VDC to release the doors.
• Mains powered 240vAC supply• On board conventional detection zone• Switches off DH power in alarm condition or atlernatively remote
switched input can trigger the door to release
MultiAmp-DH Flush Mount 4510-1100MultiAmp-DH Surface Mount 4510-1101
MechanicalMaterial High Impact ABSFinish WhiteDimension (mm) 91H X 149W x 40D (Recessed) 91H X 149W x 53D (Surface)Weight 400g packed
Power SupplyMains Supply Voltage 230 VAC +/- 10% @ 47-63HzDoor Holder Output Voltage 24 VDC @ 250mAOperating Temperature -5° to +45° CRelative Humidity 25% to 95%
Zone Detection CircuitNo of Zones 1 (one), 2-wire systemZone Monitoring Open and short-circuitZone Current Load 4.8mA maxEOL Value 3k3 ohmNo of detectors/circuit 40 (Max)
InputSwitched VDC Input Inactive state: 0 to 2 VDC Active state: 8 to 30 VDC
AUS / PAGE 115 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
ANCILLARIES DOCUMENT CABINETS
Document Cabinets
AMPAC offers ABS and metal document cabinets designed to complement the range of AMPAC’s fire control panels. The cabinets can hold in excess of 100 A4 sheets of fire and security information relevant to the premises.
The cabinets are fitted with a lockable front door for security and comes complete with an internal key holder bracket to allow easy storage of security keys. Whilst the ABS cabinet is available only in cool grey, thereis a choice of Oyster Grey or Arch White with the metal cabinet option.
• Metal and ABS versions available• Metal version available in Oyster Grey or Arch White• Provides the facility to hold documents i.e. Operation and Maintenance
Manuals• Lockable front door• Internal key holder bracket• Designed to complement the AMPAC range of enclosures
Document Cabinet ABS – Cool Grey 4210-0010Document Cabinet Metal – Oyster Grey 4210-0020Document Cabinet Metal – Arch White 4210-0021
Colour ABS – Cool Grey Metal – Oyster Grey Metal – Arch WhiteDimensions ABS – 300H x 360W x 100Dmm Metal – 295H x 356W x 92DmmIP Rating IP30Weight ABS – 1kg Metal – 3kgKey Type 003 Key
AUS / PAGE 116 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
ANCILLARIES TEST EQUIPMENT
Test Equipment
• Access poles are used with interchangeable heads that fit onto the end of the pole
• The equipment is suitable for use on a wide range of detectors• Poles are telescopic, nonconductive, toughened fibreglass• Light weight and simple to use
Telescopic pole – 6 metre 204-0001Extension pole – 1.3 metre 204-0002 Universal detector removal tool 204-0003 Aerosol Smoke Dispenser 204-0004 Heat detector tester – cordless (head only) 204-0017 Smoke detector test set – 8.2 metre 204-0009 Smoke detector test set – 6.7 metre 204-0010 Smoke & cordless heat test set – 4.5 metre 204-0018 250ml can of smoke (test set use only) 204-0014 150ml can of smoke (hand held) 204-0015 Can of smoke for CO detectors (test set use only) 204-0020 Battery Baton for Cordless Tester 204-0021
Telescopic Pole 204-0001
Aerosol Smoke Dispenser 204-0004 CO Test Can 204-0020250ml Smoke Can 204-0014150ml Smoke Can 204-0015
Cordless Heat Detector 204-0017 Head Removal Tool Smoke & Cordless Heat Test Set
AUS / PAGE 117 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
ANCILLARIES TEST EQUIPMENT
XP95 Test Set (Loop Manager Apollo)
The XP95 Test Set is a self-contained, portable test unit capable of providing a number of useful functions in relation to individual detectors,ancillary devices or complete circuits of analogue addressable devices in the Apollo intelligent ranges. The main function of the test set is to helpthe engineer guarantee correct loop configuration before an active control panel is installed.
• User friendly LCD information display• Speedy commissioning• Option for hard copy of results• No unnecessary site visits• Significant cost reductions
Apollo XP95 Test Set 55000-870EURAmpac XP95 Test Set 204-0016
Discovery Programmer
The Discovery Programmer is a portable test and configuration tool for Discovery smoke and heat detectors.
• Look up the date of manufacture• Check the drift compensation value• Display and change the operating mode• Select/de-select LED flash mode• Tests detectors• Reads approval codes
Discovery Programmer 53832-030
AUS / PAGE 118 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
ANCILLARIES TEST EQUIPMENT
Flame Sensor Test Unit and Case
The Flame Sensor Test Kit is a tool which is designed to test flame detectors without the need of real flames.
• Mimics the characteristics of real flames
Flame Sensor Test Unit and Case 29600-226
AUS / PAGE 119 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
Sealed Rechargeable Lead-Acid Batteries
Ampac sells a comprehensive battery range for all applications requiring a reliable rechargeable power source. The wide range of sizes coupled with good cycling ability make them perfect for critical systems such as fire alarm and emergency warning systems. Designed using VRLA technology, negating the need to add water, these batteries can be applied in many critical systems requiring reliable reserve power. Available as 12V or for very large systems 2 volt cells (x12).
Consideration should be given to the battery space available. If in doubt, consult your local customer service office.
• VRLA technology (Valve Regulated Lead-Acid)• No topping up• Wide capacity range• Can be operated in any position without leakage• Long operating life• Many capacities available• 2 volt cells – very large systems
12 VOLT 1.2 AH SLA 50BP1.212 210-000812 VOLT 3.0 AH 5LA 50BP312 210-000612 VOLT 7AH SLA 50BP712 210-001612 VOLT 12 AH SLA 50BP1212 210-001012 VOLT 17AH SLA 50BP1712 210-000312 VOLT 26AH SLA 50BP2612 210-001212 VOLT 40AH SLA 50BP4012 210-001312 VOLT 65AH 50BP6512 210-0015
12 VOLT 90AH SLA 50BP9012 210-0002BATT 12 VOLT 100AH E12V100 210-000912VOLT 120AH 50BP12012 210-0022
Extra large 12 Volt (consideration of battery cabinet space required)12V 160AH 50BP16012 210-001712 VOLT 230AH SLA 50BP23012 210-0011
Extra large 12 Volt (consideration of battery cabinet space required)2 Volt Cells (12 x Cells are required)210-0018 2VOLT 250AH UPZ 2-250 210-0018210-0019 2VOLT 300AH UXL-330-2 210-0019210-0020 2VOLT 550AH UXL-550-2 210-0020
ANCILLARIES Sealed Rechargeable Lead-Acid Batteries
Voltage (nominal) 12 VDCCapacity VariousOperating temperature – charging -15°C to +50°C (no icing) – discharging -20°C to +60°C (no icing)Life expectancy – standby use 3 to 5 yearsTerminal Quick disconnect or receptacle M5
CONTACT Australia Customer Service Offices
AUS / PAGE 120 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH
WESTERN AUSTRALIA7 Ledgar RoadBalcattaWestern Australia 6021
Telephone: +618 9201 6110Fax: +618 9201 6111Email: info@ampac.netMobile: 0421 129 163
Contact:Joe FusariDavid ThomasLukasz Swietojanski
VICTORIA & TASMANIA422 Johnston StreetAbbotsfordVictoria 3067
Telephone: +613 8459 3300Fax: +613 9416 4227Email: info.vic@ampac.netMobile: 0417 331 473
Contact:Tom StroumosNick VangeliIan Siemonek
NEW SOUTH WALES &AUSTRALIAN CAPITAL TERRITORYUnit B 28-32 Egerton StreetSilverwaterNew South Wales 2128
Telephone: +612 8866 6200Fax: +612 9648 4932Email: info.nsw@ampac.netMobile: 0417 986 847
Contact:David LehnWes McMillanMason Truong
SOUTH AUSTRALIA63 Grange RoadWellandSouth Australia 5032
Telephone: +618 8246 3800Fax: +618 8340 4218Email: info.sa@ampac.netMobile: 0400 835 969
Contact:Lester GaskinPaul Beer
QUEENSLAND1/53 Parramatta Road, Underwood, Queensland 4119
Telephone: +617 3462 5700Fax: +617 3208 9355Email: info.qld@ampac.netMobile: 0409 630 633
Contact:Michael SchusterSam Adams
NORTHERN TERRITORY2/10 Cato St, Winnellie Northern Territory, 0820
Telephone: +618 8911 1260Fax: +618 8911 1261Email: m.cavenagh@ampac.netMobile: 0451 632 965
Contact:Matt Cavenagh
CONTACT Head Office & Administration
HEAD OFFICE & ADMINISTRATION
Ampac Technologies Pty Ltd7 Ledgar RoadBalcattaWestern Australia 6021
Telephone:+618 9201 6100Fax:+618 9201 6101Email:info@ampac.netWeb:www.ampac.net
CLICK HERE TO VIEW CUSTOMER SERVICE OFFICES
As part of Ampac’s commitment to continuous improvement, specifications may change without notice.Version AUS/15-05-2012
Planned, written, designed and produced by Right Angle • www.rightangle.co.uk
AUS / PAGE 121 ZOOM PRINT EXITCONTENTSCONTACT AMPAC HOME SEARCH