RXS-K
Technical DataAir Conditioners
O u t d o o r u n i t - p a i r a p p l i c a t i o n
E E D E N 1 2 - 1 0 0
• Split - Sky Air® • Outdoor Unit 1
• Outdoor Unit • Pair application • RXS-K
TABLE OF CONTENTSRXS-K
1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Nominal Capacity And Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Cooling/Heating Capacity Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6 Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Centre of Gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7 Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Piping Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Wiring Diagrams - Single Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
9 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Sound Pressure Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
10 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Operation Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
• Outdoor Unit • Pair application • RXS-K
11
2
1 Features
door Uni it - Sk -K r applic
Out Spl RXS Pai • Energy efficient units: up to class A energy labels• Seasonal efficiency, optimized for all seasons.
• Seasonal efficiency gives an indication on how efficient an air conditioner operates over an entire heating or cooling season.
• Compact casing (575mm in width and depth) enables unit to fit flush into ceilings and match standard architectural modules, without cutting ceiling tiles
• Modern style decoration panel in white (RAL9010)
• Whisper quiet operation: down to 24.5dBA sound pressure level
• Comfortable vertical auto swing ensures draughtfree operation and prevents ceiling soiling
• Fresh air intake for healthy living
• Since the flaps can move to a 0 degree position, virtually no draught can be experienced
• Possibility to shut 1 or 2 flaps for easy installation in corners
• Easy maintenance: switch box can be reached by simply removing the suction grille
• Standard drain pump with 750mm lift
• No optional adapter needed for DIII-connection: standard plug and play connection with centralised control systems, intelligent touch controller, intelligent manager, ...
• Outdoor units for pair application
• Energy efficient units: full range A class energy labels
• Daikin outdoor units are neat, sturdy and can easily be mounted on a roof or terrace or simply placed against an outside wall
• Energy saving during standby mode: reduces current consumption by about 80% when operating In standby. If no people are detected for more than 20 minutes, the system will automatically switch to the current-saving mode.
• Outdoor unit silent operation: "silent" button on the remote control lowers the operation sound of the outdoor unit by 3dBA to ensure a quiet environment for the neighbourhood.
• Outdoor units are fitted with a swing compressor, renowned for its low noise and high energy efficiency
• Anti-corrosion treated outdoor heat exchanger fin
• Split - Sky Air® • Outdoor Unit
3
12
• Outdoor Unit • Pair application • RXS-K
2 Specifications
Notes (1) Energy label: scale from A (most efficient) to G (less efficient) (2) Annual energy consumption: based on average use of 500 running hours per year at full load (nominal conditions) (3) Cooling: indoor temp. 27ºCDB, 19.0ºCWB; outdoor temp. 35ºCDB, 24ºCWB; equivalent piping length: 5m (4) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m (5) 220V (6) 230V (7) 240V
Notes (1) Energy label: scale from A (most efficient) to G (less efficient) (2) Annual energy consumption: based on average use of 500 running hours per year at full load (nominal conditions) (3) Cooling: indoor temp. 27ºCDB, 19.0ºCWB; outdoor temp. 35ºCDB; equivalent piping length: 5m; level difference: 0m (4) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m; level difference: 0m
2-1 Nominal Capacity And Nominal Input FTXS20K2V1B / RXS20K2V1B FTXS25K2V1B / RXS25K2V1B
Cooling capacity Min. kW 1.3Btu/h 4,400
Nom. kW 2.0 (3) 2.5 (3)Btu/h 6,800 (3) 8,500 (3)
Max. kW 2.8 3.2Btu/h 9,600 10,900
Heating capacity Min. kW 1.3Btu/h 4,400
Nom. kW 2.5 (4) 2.8 (4)Btu/h 8,500 (4) 9,600 (4)
Max. kW 4.3 4.7Btu/h 14,700 16,000
Piping connections Liquid OD mm 6.35Gas OD mm 9.5Drain OD mm 18.0Heat insulation Both liquid and gas pipes
Annual energy consumption kWh 215 285EER 4.65 4.39COP 4.55 4.52Energy label Cooling A
Heating APower input Cooling Min. kW 0.320
Nom. kW 0.430 0.570Max. kW 0.760 1.000
Heating Min. kW 0.310Nom. kW 0.550 0.620Max. kW 1.120 1.410
2-1 Nominal Capacity And Nominal Input FDXS25E7VMB / RXS25K2V1B
Cooling capacity Nom. kW 2.40 (3)Heating capacity Nom. kW 3.20 (4)Annual energy consumption kWh 345EER 3.48COP 3.52Energy label Cooling A
Heating BPower input Cooling Nom. kW 0.69
Heating Nom. kW 0.91
2-1 Nominal Capacity And Nominal Input FLXS25BAVMB / RXS25K2V1B
Cooling capacity Nom. kW 2.50 (3)Heating capacity Nom. kW 3.40 (4)Annual energy consumption kWh 325EER 3.85
• Split - Sky Air® • Outdoor Unit 3
• Outdoor Unit • Pair application • RXS-K
12
4
2 Specifications
Notes (1) Energy label: scale from A (most efficient) to G (less efficient) (2) Annual energy consumption: based on average use of 500 running hours per year at full load (nominal conditions) (3) Cooling: indoor temp. 27ºCDB, 19.0ºCWB; outdoor temp. 35ºCDB; equivalent piping length: 5m; level difference: 0m (4) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m; level difference: 0m
Notes (1) Energy label: scale from A (most efficient) to G (less efficient) (2) Annual energy consumption: based on average use of 500 running hours per year at full load (nominal conditions) (3) Cooling: indoor temp. 27ºCDB, 19.0ºCWB; outdoor temp. 35ºCDB; equivalent piping length: 5m; level difference: 0m (4) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m; level difference: 0m
Notes (1) Energy label: scale from A (most efficient) to G (less efficient) (2) Annual energy consumption: based on average use of 500 running hours per year at full load (nominal conditions) (3) Cooling: indoor temp. 27ºCDB, 19.0ºCWB; outdoor temp. 35ºCDB; equivalent piping length: 5m; level difference: 0m (4) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m; level difference: 0m
COP 3.47Energy label Cooling A
Heating BPower input Cooling Nom. kW 0.65
Heating Nom. kW 0.98
2-1 Nominal Capacity And Nominal Input FVXS25FV1B / RXS25K2V1B
Cooling capacity Nom. kW 2.50 (3)Heating capacity Nom. kW 3.40 (4)Annual energy consumption kWh 285EER 4.39COP 4.30Energy label Cooling A
Heating APower input Cooling Nom. kW 0.57
Heating Nom. kW 0.79
2-1 Nominal Capacity And Nominal Input FFQ25B9V1B / RXS25K2V1B
Cooling capacity Nom. kW 2.50 (3)Heating capacity Nom. kW 3.20 (4)Annual energy consumption kWh 365EER 3.43COP 3.48Energy label Cooling A
Heating BPower input Cooling Nom. kW 0.73
Heating Nom. kW 0.92
2-1 Nominal Capacity And Nominal Input FLXS25BAVMB / RXS25K2V1B
• Split - Sky Air® • Outdoor Unit
3
12
• Outdoor Unit • Pair application • RXS-K
2 Specifications
2-2 Technical Specifications RXS20K RXS25K
Fan Type Propeller fanAir flow rate Cooling High m³/min 33.5
cfm 1,183Low m³/min 30.1
cfm 1,063Super low
m³/min -cfm -
Heating High m³/min 28.3cfm 999
Low m³/min 25.6cfm 904
Super low
m³/min -cfm -
Dimensions Unit Height mm 550Width mm 765Depth mm 285
Packed unit Height mm 612Width mm 906Depth mm 364
Weight Unit kg 34Packed unit kg 38
Piping connections Liquid OD mm 6.35Gas OD mm 9.5Drain ID mm -
OD mm 18.0Piping length OU - IU Max. m 20
System Chargeless m 10Adiitional refrigerant charge kg/m 0.02(for piping length exceeding 10m)Level difference IU - OU Max. m 15Heat insulation Both liquid and gas pipes
Sound pressure level Cooling High dBA 46Silent operation dBA 43
Heating High dBA 47Silent operation dBA 44
Casing Colour Ivory whiteHeat exchanger Length mm 805
Rows Quantity 2Fin pitch mm 1.4Stages Quantity 24Tube type ø7 Hi-XAFin Type Waffle louvered fin
Fan motor Model D23H-28Output W 23Speed Cooling High rpm 860
Super low rpm 780Heating High rpm 860
Super low rpm 740Sound power level Cooling High dBA 61Compressor Model 1YC23AEXDC
Type Hermetically sealed swing compressorOutput W 600
Operation range Cooling Ambient Min. ºCDB -10Max. ºCDB 46
Heating Ambient Min. ºCWB -15Max. ºCWB 18
• Split - Sky Air® • Outdoor Unit 5
• Outdoor Unit • Pair application • RXS-K
12
6
2 Specifications
Notes (1) 220V (2) 230V (3) 240V (4) SL: The silent fan level of the air flow rate setting
Refrigerant Type R-410ACharge kg 1.0
Refrigerant oil Type FVC50KCharged volume l 0.375
2-3 Electrical Specifications RXS20K RXS25K
Power supply Phase 1~Frequency Hz 50Voltage V 220-240
Current Nominal running current (RLA)
Cooling A 2.21 (1) / 2.12 (2) / 2.03 (3) 3.01 (1) / 2.92 (2) / 2.83 (3)Heating A 2.61 (1) / 2.52 (2) / 2.43 (3) 3.11 (1) / 3.02 (2) / 2.93 (3)
Starting current Cooling A 2.8 3.3Heating A 2.8 3.3
Wiring connections For power supply Remark 3 for power supply, 4 for interunit wiring (including earth wiring)
2-2 Technical Specifications RXS20K RXS25K
• Split - Sky Air® • Outdoor Unit
3
13
• Outdoor Unit • Pair application • RXS-K
3 Electrical data
3 - 1 Electrical Data• Split - Sky Air® • Outdoor Unit 7
• Outdoor Unit • Pair application • RXS-K
14
8
4 Capacity tables
4 - 1 Cooling/Heating Capacity Tables• Split - Sky Air® • Outdoor Unit
3
14
• Outdoor Unit • Pair application • RXS-K
4 Capacity tables
4 - 1 Cooling/Heating Capacity Tables• Split - Sky Air® • Outdoor Unit 9
• Outdoor Unit • Pair application • RXS-K
14
10
4 Capacity tables
4 - 1 Cooling/Heating Capacity Tables• Split - Sky Air® • Outdoor Unit
3
14
• Outdoor Unit • Pair application • RXS-K
4 Capacity tables
4 - 1 Cooling/Heating Capacity Tables• Split - Sky Air® • Outdoor Unit 11
• Outdoor Unit • Pair application • RXS-K
14
12
4 Capacity tables
4 - 1 Cooling/Heating Capacity Tables• Split - Sky Air® • Outdoor Unit
3
14
• Outdoor Unit • Pair application • RXS-K
4 Capacity tables
4 - 1 Cooling/Heating Capacity Tables• Split - Sky Air® • Outdoor Unit 13
• Outdoor Unit • Pair application • RXS-K
15
14
5 Dimensional drawings
5 - 1 Dimensional Drawings• Split - Sky Air® • Outdoor Unit
3
16
• Outdoor Unit • Pair application • RXS-K
6 Centre of gravity
6 - 1 Centre of Gravity• Split - Sky Air® • Outdoor Unit 15
• Outdoor Unit • Pair application • RXS-K
17
16
7 Piping diagrams
7 - 1 Piping Diagrams• Split - Sky Air® • Outdoor Unit
3
18
• Outdoor Unit • Pair application • RXS-K
8 Wiring diagrams
8 - 1 Wiring Diagrams - Single Phase• Split - Sky Air® • Outdoor Unit 17
• Outdoor Unit • Pair application • RXS-K
19
18
9 Sound data
9 - 1 Sound Pressure Spectrum∼
∼ ∼
∼
• Split - Sky Air® • Outdoor Unit
3
110
• Outdoor Unit • Pair application • RXS-K
10 Operation range
10 - 1 Operation Range• Split - Sky Air® • Outdoor Unit 19
EEDEN12 - 1 00
Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende
Please fill out the requested informationPlease fill out the requested information
The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V.
Daikin’s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues. For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste.
Daikin Europe N.V. participates in the Eurovent Certification programme for Air conditioners (AC), Liquid Chilling Packages (LCP), Air handling units (AHU) and Fan coil units (FCU), Check ongoing validity of certificate online: www.eurovent-certification.com or using: www.certiflash.com”
Daikin products are distributed by:
EED
EN12
-100
• 01
/12
• Cop
yrig
ht ©
Dai
kin
The
pres
ent
publ
icat
ion
supe
rsed
es E
EDEN
11-1
00Pr
inte
d on
non
-chl
orin
ated
pap
er. P
repa
red
by G
oeki
nt G
raph
ics
NV,
Bel
gium
Resp
onsi
ble
Edito
r: D
aiki
n Eu
rope
N.V
., Za
ndvo
orde
stra
at 3
00, B
-840
0 O
oste
nde
Recommended