PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
1
tracor
Infrared Thermography
CHILLER ROOM
Prepared for:
PT.SKF Indonesia
Proyek Perluasan Utara Kawasan Industri Pulogadung
Jl.Tipar Cakung, Jakarta 13910
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
2
tracor
CHILLER NO 2 – MCCB 250 A
Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 0.4 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0.2 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 0.2 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 43.4 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 32.0 B:20 °C - 39 °C Perlu Perbaikan ∆ T 11.4 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 37.7°C 1.00 R 40.6
Hot 43.4°C 1.00 S 40.2 Cold 32.0°C 1.00 T 40.4
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
3
tracor
CHILLER NO 3 – MCCB 250 A
Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 4 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0.2 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 4.2 3. (>16oC) Perlu Perbaikan Classification 2
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 62.2 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 35.0 B:20 °C - 39 °C Perlu Perbaikan ∆ T 27.2 C:10 °C - 19 °C Perlu Perhatian Classification B D:≤ 9 °C Baik X Bad Conection B/2 : Perlu dilakukan perbaikan di koneksi
MCCB Fasa R,S,T Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 46.6°C 1.00 R 58.2
Hot 62.2°C 1.00 S 62.2 Cold 35.0°C 1.00 T 58.0
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
4
tracor
CHIL DP – ACB 2000 A
Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 0.1 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 0.1 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 38.6 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 28.6 B:20 °C - 39 °C Perlu Perbaikan ∆ T 10 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 33.6°C 1.00 R 36.1
Hot 38.6°C 1.00 S 36.0 Cold 28.6°C 1.00 T 36.1
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
5
tracor
CHIL PUMP – MCCB 630 A
Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 0 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 1.2 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 1.2 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 46.2 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 35.6 B:20 °C - 39 °C Perlu Perbaikan ∆ T 10.6 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 40.9°C 1.00 R 46.2
Hot 46.2°C 1.00 S 46.2 Cold 35.6°C 1.00 T 45.0
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
6
tracor
CT.PP – MCCB 200 A
Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 0.3 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0.1 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 0.2 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 40.3 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 30.3 B:20 °C - 39 °C Perlu Perbaikan ∆ T 10 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 35.3°C 1.00 R 40.0
Hot 40.3°C 1.00 S 40.3 Cold 30.3°C 1.00 T 40.1
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
7
tracor
ACH.PP – MCCB 80 A
Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 0.2 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0.1 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 0.1 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 39.7 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 29.7 B:20 °C - 39 °C Perlu Perbaikan ∆ T 10 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 34.7°C 1.00 R 37.2
Hot 39.7°C 1.00 S 37.0 Cold 29.7°C 1.00 T 37.1
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
8
tracor
COUPLER – MCCB 1600 A
Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 0.1 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0.3 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 0.2 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 36.5 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 26.5 B:20 °C - 39 °C Perlu Perbaikan ∆ T 10 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 31.5°C 1.00 R 31.5
Hot 36.5°C 1.00 S 31.4 Cold 26.5°C 1.00 T 31.2
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
9
tracor
CHIL 2 – MCCB 1000 A
Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 2 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0.3 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 2.3 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 40.3 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 30.3 B:20 °C - 39 °C Perlu Perbaikan ∆ T 10 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 35.3°C 1.00 R 38.3
Hot 40.3°C 1.00 S 40.3 Cold 30.3°C 1.00 T 38.6
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
10
tracor
CHIL 3 – MCCB 1000 A
Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 0.4 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0.6 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 0.2 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 37.7 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 27.7 B:20 °C - 39 °C Perlu Perbaikan ∆ T 10 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 32.7°C 1.00 R 32.7
Hot 37.7°C 1.00 S 32.3 Cold 27.7°C 1.00 T 32.1
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
11
tracor
CAP BANK CHIL DP (600 KVAR) – FUSE 160 A NO 1
Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 2.3 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0.6 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 3.3 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 45.3 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 31.1 B:20 °C - 39 °C Perlu Perbaikan ∆ T 14.2 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 38.2°C 1.00 R 42.6
Hot 45.3°C 1.00 S 45.3 Cold 31.1°C 1.00 T 42.0
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
12
tracor
CAP BANK CHIL DP (600 KVAR) – KONTAKTOR NO 1
Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 2 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0.1 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 2.1 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 45.3 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 31.0 B:20 °C - 39 °C Perlu Perbaikan ∆ T 14.3 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 38.1°C 1.00 R 43.3
Hot 45.3°C 1.00 S 45.3 Cold 31.0°C 1.00 T 43.2
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
13
tracor
CAP BANK CHIL DP (600 KVAR) – FUSE 160A NO 4
Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 0.2 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0.2 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 0.2 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 49.2 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 31.0 B:20 °C - 39 °C Perlu Perbaikan ∆ T 18.2 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 40.1°C 1.00 R 44.4
Hot 49.2°C 1.00 S 44.6 Cold 31.0°C 1.00 T 44.2
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
14
tracor
CAP BANK CHIL DP (600 KVAR) – KONTAKTOR NO 4
Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 2 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 2.2 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 0.2 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 47.5 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 31.5 B:20 °C - 39 °C Perlu Perbaikan ∆ T 16 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 39.5°C 1.00 R 45.5
Hot 47.5°C 1.00 S 47.5 Cold 31.5°C 1.00 T 47.3
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
15
tracor
PP CHILLER PUMP – MCCB 630 A
Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 0.4 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0.6 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 0.2 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 47.6 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 35.2 B:20 °C - 39 °C Perlu Perbaikan ∆ T 12.4 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 41.4°C 1.00 R 47.6
Hot 47.6°C 1.00 S 47.2 Cold 35.2°C 1.00 T 47.0
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
16
tracor
P CHWP-2 – MCCB 200 A
Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 0.1 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 1.2 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 1.1 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 44.4 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 31.9 B:20 °C - 39 °C Perlu Perbaikan ∆ T 12.5 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 38.2°C 1.00 R 44.4
Hot 44.4°C 1.00 S 44.3 Cold 31.9°C 1.00 T 43.2
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
17
tracor
P CHWP-2 – KONTAKTOR
Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 2.1 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0.2 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 0.1 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 68.5 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 31.4 B:20 °C - 39 °C Perlu Perbaikan ∆ T 37.1 C:10 °C - 19 °C Perlu Perhatian Classification B D:≤ 9 °C Baik X Bad Conection B/1 : Perlu dilakukan perbaikan koneksi di
kontaktor Fasa R,S,T Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 50.0°C 1.00 R 66.6
Hot 68.5°C 1.00 S 68.5 Cold 31.4°C 1.00 T 66.4
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
18
tracor
P CWP 2 – MCCB 160 A
Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 0.2 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 1.3 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 1.1 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 44.4 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 31.9 B:20 °C - 39 °C Perlu Perbaikan ∆ T 12.5 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 38.2°C 1.00 R 44.4
Hot 44.4°C 1.00 S 44.2 Cold 31.9°C 1.00 T 43.1
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
19
tracor
CWP-2 – KONTAKTOR
Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 2.1 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0.1 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 0.2 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 75.1 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 35.3 B:20 °C - 39 °C Perlu Perbaikan ∆ T 39.8 C:10 °C - 19 °C Perlu Perhatian Classification B D:≤ 9 °C Baik X Bad Conection B/1 : Perlu dilakukan perbaikan koneksi di
kontaktor Fasa R,S,T Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 55.2°C 1.00 R 73.4
Hot 75.1°C 1.00 S 75.3 Cold 35.3°C 1.00 T 73.5
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
20
tracor
PP COOLING TOWER – MCCB 200 A Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 3.1 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 3.1 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 0.2 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 46.6 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 34.1 B:20 °C - 39 °C Perlu Perbaikan ∆ T 12.5 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 40.4°C 1.00 R 43.5
Hot 46.6°C 1.00 S 46.6 Cold 34.1°C 1.00 T 46.4
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
21
tracor
PP COOLING TOWER (Q7) – MCCB 25 A Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 0.5 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0.7 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 0.2 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 48.2 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 35.1 B:20 °C - 39 °C Perlu Perbaikan ∆ T 13.1 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 41.7°C 1.00 R 44.9
Hot 48.2°C 1.00 S 44.4 Cold 35.1°C 1.00 T 44.2
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
22
tracor
PP COOLING TOWER (Q8) – MCCB 25 A Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 3.5 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0.1 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 3.6 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 48.6 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 34.6 B:20 °C - 39 °C Perlu Perbaikan ∆ T 14 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 41.6°C 1.00 R 45.1
Hot 48.6°C 1.00 S 48.6 Cold 34.6°C 1.00 T 45.0
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
23
tracor
PP COOLING TOWER (Q9) – MCCB 25 A Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 0.5 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0.3 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 0.2 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 46.8 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 34.5 B:20 °C - 39 °C Perlu Perbaikan ∆ T 12.3 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 40.7°C 1.00 R 43.8
Hot 46.8°C 1.00 S 43.3 Cold 34.5°C 1.00 T 43.5
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
24
tracor
PP COOLING TOWER (Q4) – MCCB 25 A Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 0.1 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0.1 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 0.2 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 47.6 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 35.1 B:20 °C - 39 °C Perlu Perbaikan ∆ T 12.5 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 41.3°C 1.00 R 44.5
Hot 47.6°C 1.00 S 44.4 Cold 35.1°C 1.00 T 44.6
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
25
tracor
PP COOLING TOWER (Q5) – MCCB 25 A Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 3.4 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 3.4 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 47.8 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 34.5 B:20 °C - 39 °C Perlu Perbaikan ∆ T 13.3 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 41.1°C 1.00 R 44.4
Hot 47.8°C 1.00 S 47.8 Cold 34.5°C 1.00 T 44.4
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
26
tracor
PP COOLING TOWER (Q6) – MCCB 25 A Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 0.2 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 0.2 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 47.6 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 34.6 B:20 °C - 39 °C Perlu Perbaikan ∆ T 13.0 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 41.1°C 1.00 R 44.4
Hot 47.6°C 1.00 S 44.2 Cold 34.6°C 1.00 T 44.4
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
27
tracor
CT HT – MCCB 25 A Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 6.7 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0.4 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 7.2 3. (>16oC) Perlu Perbaikan Classification 2
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 61.4 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 34.4 B:20 °C - 39 °C Perlu Perbaikan ∆ T 27.0 C:10 °C - 19 °C Perlu Perhatian Classification B D:≤ 9 °C Baik X Bad Conection B/2 : Perlu penggantian MCB Overload Unbalance Loaded
X Internal Componen/Parts Failur Electromagnetic Induction Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 47.9°C 1.00 R 54.7
Hot 61.4°C 1.00 S 61.4 Cold 34.4°C 1.00 T 54.2
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
28
tracor
AC HPP – MCCB 80 A Visible Light Image
Main Image Markers
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
∆ T - (Phase R dan S) 0.2 1. (1 oC – 3oC) Baik ∆ T - (Phase R dan T) 0.1 2. (4 oC – 15oC) Perlu Perhatian ∆ T - (Phase S dan T) 0.1 3. (>16oC) Perlu Perbaikan Classification 1
Temperatur Data ( °C ) Classification Off Rise In Temperatur ∆ T
Hot Spot 38.4 A: ≥ 40 °C Perlu Perbaikan SegeraTemperatur Refference 28.4 B:20 °C - 39 °C Perlu Perbaikan ∆ T 10 C:10 °C - 19 °C Perlu Perhatian Classification C D:≤ 9 °C Baik
Bad Conection C/1 : Normal Overload Unbalance Loaded Internal Componen/Parts Failur Electromagnetic Induction
X Normal Operating Temperatur
Name Temperature Emissivity Phase Temperatur Centerpoint 33.4°C 1.00 R 38.4
Hot 38.4°C 1.00 S 38.2 Cold 28.4°C 1.00 T 38.3
Probable Causes Comment/Suggestion
Client Supervisors Notes
R S T
R S T
PQA – INFRARED THERMOGHRAPHY PT.SKF INDONESIA
29
tracor
Recommended