View
256
Download
4
Category
Preview:
Citation preview
8/10/2019 Be42 Software Manual v4xx
http://slidepdf.com/reader/full/be42-software-manual-v4xx 1/14
Be-42 V4XX Software User Manual
The information in this document is subject to change without notice.No part of this document may be copied or reproduced in any form or any means without the prior written
consent of Bernini Design company. Bernini Design assumes no responsibility for any errors which mayappear in this instruction manual or in the wiring diagrams. Although Bernini Design has taken all possible steps to ensure that the User Manual is complete, bug freeand up-to-date, we accept that errors may occur. If you encounter problems with this instruction manual, please complete this form and send it back to us.
FAX Message (++39 0386 31657), From:__________________________________
Name: _____________Company: ___________________Tel/Fax: _________________
I would like to report the following error:
______________________________________________________________________ __
Customer Support BERNINI DESIGN SRL ITALY
e-mail: bernini@bernini-design.commobile: ++40 721 241 361. Tel:++39 0386-31445 (fax 31657).
BE-42 software upgrades
Note: some imagines in this Manual may differ according to the software release. The purpouse of thismanual is to provide a general guide for the installation.
Software
Version
Hardware Version Date Description
V4.00 V4.X.XX September 2009 First release
Contents:
1. Overview2. Installing the software3. Connection setup4. How to modify a parameter5. How to store Parameters into Be426. Restore the default parameters7. Save & Load parameters8. Typical wiring diagram9. Contents of the pages
8/10/2019 Be42 Software Manual v4xx
http://slidepdf.com/reader/full/be42-software-manual-v4xx 2/14
- 1.0 - Overview
The software allows full access to the Be42 and features the following components:
For details about the content of the pages see section 9.0.
Tabs for selecting the pages, functions
and parameters
Buttons for opening and
closing the connection
Opens file from a
folder in the PC
Saves parameters
to a file
Loads default
Read parameters
from BE 42
Write parameters
to BE 42
8/10/2019 Be42 Software Manual v4xx
http://slidepdf.com/reader/full/be42-software-manual-v4xx 3/14
- 2.0 - Installing the software:
A) - To install the BE 42 software, unzip the file until the following screen will appear:
B) - Double-click on the BE42 icon; the following screen will appear. Click on 'Next' button
8/10/2019 Be42 Software Manual v4xx
http://slidepdf.com/reader/full/be42-software-manual-v4xx 4/14
C) - Click on the 'Next' button
D) - To complete the task click on the 'Close' button
8/10/2019 Be42 Software Manual v4xx
http://slidepdf.com/reader/full/be42-software-manual-v4xx 5/14
- 3.0 - CONNECTION SETUP
A) - The software will create an icon on the desktop as indicated below.(the code 4 indicatesthe model of the Be42 controller; the code '00' up to '99' indicates the release that you aregoing to install. In this example version of software is '00'). Connect the PC to BE42 (seesection 8.00)
B) - Double Click on the Be424.00 icon (or choose 'Open' by using the mouse); the mainscreen of the software will appear as indicated below. Being not connetcted to the Be42, all
parameters are fitted with defaults (factory programming)
8/10/2019 Be42 Software Manual v4xx
http://slidepdf.com/reader/full/be42-software-manual-v4xx 6/14
C) - Choose a proper Serial connection, select the Be42 address (in other words you have tomatch the node programmed into parameter P49. See section 7.05B of the user manual) and'Password'. If Be42 is not password protected, leave the code 4242 in the box. The followingmessage will indicate the status of the connection:
- 4.0 - How to modify a parameter
The input boxes accept parameters according to a ‘range’ (see user manual ofthe Be42). The parameters can be changed in three ways:
I. Type a new value directly; validation is done when the cursor ismoved outside the textbox
II. Use the Up / Down buttons near to the text box.
There are the following types of parameters:
General purpose Timer. Select the “min” (minutes) or “sec”(seconds) option and then enter the numerical value. You can use the
Up/Down arrows to modify the module of the timer.
Timer module up to 23 hours. The programmingis allowed in Hour + minutes (no seconds), in minutes only or seconds only.
Decimal values. Use Up/Down to modify the timing.
Integer values with off function. When the off check box is
selected, the text box become inactive.
Two state parameters (check the box according toyour needs).
Timer value with off function. When “off”, the timer isinhibited.
Programmable input parameter. From thedrop menu, you can select the function assigned for the input. The twobuttons select the normally open or normally closed mode of the switchconnected to the input.
8/10/2019 Be42 Software Manual v4xx
http://slidepdf.com/reader/full/be42-software-manual-v4xx 7/14
- 5.0 - How to store Parameters into Be-42
a) In order to read parameters from the Be42, push the button. Thiscommand will update all parameters (not only the set of parameters that you areseeing on the display window).
b) You can modify the parameters according to your needs.
c) To write the parameters into Be42, click the button. This functionschecks if the parameters are saved properly. There you are an example ofRead/Write session:
In case of error in the range of the parameters, the following messages will appear:
19:23:42> Write parameters ...
19:23:44> Write fail (check connection or parameters)
- 6.0 - Restoring the default parameters
There is a set of default parameters stored in the software (so called factory
programming). To load the defaults, click the button.
Note: The Default button loads default parameters in the screen window. To write thedefaults into Be42, use the “Write parameter” procedure described in section 5.
- 7.0 - Save / Load parameter
In order to store different set of parameters (for each model of panel forexample) it is possible to save the programming in different files.
Click the SAVE FILE button and choose a name & location to store the file. Clickthe OPEN FILE button to open a file that contains the parameters .
Note:
To write the parameters into Be42 follow the instructions on the section 5.
8/10/2019 Be42 Software Manual v4xx
http://slidepdf.com/reader/full/be42-software-manual-v4xx 8/14
- 8.0 - Typical Application using a RS485 converter
iIn case of use of USB-RS485 converter, consult the converter user manual
T R
A B G N D
R S 4 8 5
Be-XXcontroller
D-SUB9
D-SUB9D-SUB9
D - S U B 9
MALE
MALE
T R A B
G N D
R S 4 8 5
RS232
8
2 7 V d c
÷
P O W E R
R X
T X
P O W E R O N
D - S U B 9
M A L E
FEMALE
F E M A L E
COM port
CABLE 1(max 6 M)
Computer with RS232
Computer with USBadapter
USB toRS232adapter
C A B L E 2
( m a x 5 0 0 M )
4 polesFEMALE
pitch 3.81mm
4 polesFEMALE
pitch 3.81mm
2 polesFEMALE
pitch 5mm
INSTRUCTION OF USE:
1. Connect to using .2. Connect to using .3. Connect4. Turn ON power supply to .5. Turn ON the and start the software. Setup
the parameters acordingly to the User Manual. Green led and red led should blink acordingly to
the received / transmitted data between and .
C232-485 PC CABLE 1
C232-485 BE xxx CABLE 2
POWER SUPPLY.
BE xxx
PC
PC
C232-485
C232-485 to a
Y e l l o w
G r e e n
R e d
8/10/2019 Be42 Software Manual v4xx
http://slidepdf.com/reader/full/be42-software-manual-v4xx 9/14
- 9.0 - Contents of the Pages
9.01: Alarm Status Page iIt indicates the alarms in real time
9.02: Engine Parameters Page iIt contains all parameters of the engine
8/10/2019 Be42 Software Manual v4xx
http://slidepdf.com/reader/full/be42-software-manual-v4xx 10/14
9.03: Generator Parameters Page iIt contains all parameters of the generator
9.04: Measurement Page iIt indicates all measurements
8/10/2019 Be42 Software Manual v4xx
http://slidepdf.com/reader/full/be42-software-manual-v4xx 11/14
9.05: Miscellaneous Parameters Page iIt contains miscellaneous parameters
9.06: Sensors Characteristics Page iIt contains the settings of the sensors
8/10/2019 Be42 Software Manual v4xx
http://slidepdf.com/reader/full/be42-software-manual-v4xx 12/14
9.07: Alarm Setting & Options iIt contains options for the alarms
9.08: Mains Setting & Options iIt contains all parameters of the Mains
8/10/2019 Be42 Software Manual v4xx
http://slidepdf.com/reader/full/be42-software-manual-v4xx 13/14
9.09: Inputs & Outputs options iIt allows you to program the I/O
9.10: Event History iIt displays the memory and the sequence of the events
8/10/2019 Be42 Software Manual v4xx
http://slidepdf.com/reader/full/be42-software-manual-v4xx 14/14
9.11: Control Panel
The control panel is located in the Measurements page (see section 9.04).
You can perform the following operations
- Start engine test - it stats the engine (the Be42 must be in Auto mode)
- Stop engine test - it terminate the engine test
- Start genset test - it starts the engine and transfer the LOAD to generator
- Stop genset test - it terminate the genset test
- Memory init - it cancel the memory and put the factory programming parameters
- Clear events - it cancels the events
- Select a mode of operation. it allows you to select a mode of operation
- Control the contactors - it allows you to open/close the contactor (in Manual mode)
Recommended