Att-1_Cable Selection Chart

Preview:

DESCRIPTION

Att-1_Cable Selection Chart

Citation preview

TFM UTILITIES

DATA 3C(6-10kV)TABLE : 3C-6/10kV3C 6/10kVRFOUNominalResistanceResistanceReactance3CCable(AC) at 90 C(DC) at 20 Cat 50 HzIn airsize45C(mm)(Ohm/km)(Ohm/km)(Ohm/km)(Amp)161.4791.16000.12663250.9360.73400.11984350.6740.52900.114102500.4990.39100.106126700.3440.27000.101158950.2490.19500.0971931200.1960.15400.0932241500.1610.12600.0912561850.1280.10000.0892902400.0970.07620.086345390Note :1. Based on Nexans cables

&C&P of &N

REF DATA_0.6-1kVTABLE : 0.6/1KV0.6/1kVL3RFOU (Normal service)BFOU (Vital service)L4=VSD cableNominalResistanceResistanceReactanceReactance1C2C3C1C2C3C3C+3ECable(AC) at 90 C(DC) at 20 Cat 50 Hzat 50 HzIn airIn airIn airIn airIn airIn airIn airsizeFor multi coreFor 1Core45C45C45C45C45C45C45C(mm)(Ohm/km)(Ohm/km)(Ohm/km)(Ohm/km)(Amp)(Amp)(Amp)(Amp)(Amp)(Amp)(Amp)L3L3L32.59.6397.5600.1030.15630262130262145.9934.7000.0960.14540342840342863.9653.1100.0900.135524436524436102.3461.8400.0850.126726150726150161.4791.1600.0800.117968267968267250.9360.7340.0790.112127108891271088989350.6740.5290.0770.107157133110157133110110500.4990.3910.0760.104196167137196167137137700.3440.2700.0760.101242206169242206169169950.2490.1950.0740.0972932492052932492052051200.1960.1540.0720.0943392882373392882372371500.1610.1260.0720.0933893312723893312722721850.1280.1000.0720.0924443773114443773113112400.0970.0760.0720.0905224443655224443653653000.0770.0610.0710.0896015114216015114214214000.0610.0480.0897196117196115000.0470.0370.0878278276300.0360.0290.087955955Note :1. Based on Nexans cables

&C&P of &NWong Yit Sin (Kuala Lumpur):(refer IEC 61892-4. table 5)Wong Yit Sin (Kuala Lumpur):(refer IEC 61892-4. table 5)Wong Yit Sin (Kuala Lumpur):(refer IEC 61892-4. table 5)Wong Yit Sin (Kuala Lumpur):(refer IEC 61892-4. table 5)Wong Yit Sin (Kuala Lumpur):(refer IEC 61892-4. table 5)Wong Yit Sin (Kuala Lumpur):(refer IEC 61892-4. table 5)Wong Yit Sin (Kuala Lumpur):(refer IEC 61892-4. table 5)Wong Yit Sin (Kuala Lumpur):(refer IEC 61892-4. table 5)

MVMFDPTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)HV MOTOR FEEDER CABLE SELECTION CHART (H1)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters0.9360.6740.4990.3440.2490.196Resistance (Ohms/km) at 90C0.1190.1140.1060.1010.0970.093Reactance (Ohms/km) 50Hz84.0102.0126.0158.0193.0224.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting75.091.0112.5141.0172.3199.9Derated Rating (Amps.)(Amp)cos@sin@(Amp)cos@sin@2535507095120Conductor Size (mm2)3C3C3C3C3C3CNo. of Cable core1320.9514.30.850.5383.10.220.989295**********1600.9517.30.850.53100.50.220.987684**********1800.9519.50.850.53109.10.230.9768389272********2000.9521.60.850.53125.40.230.9761608353********2250.9524.00.860.51132.10.230.97549974639851******2500.9626.90.850.53164.00.220.98495467188859******2800.9630.10.850.53177.70.230.97442359987910******3150.9633.80.850.53199.70.230.973936533770389775****3550.9638.10.850.53224.50.230.973500474662588691****4000.9642.70.850.53252.20.210.983116422555717738****4500.9648.00.850.53278.60.210.9827723759495768859056**5000.9753.30.850.53309.30.200.982498338744666203815994545600.9759.70.850.53352.00.200.982232302739925544729383076300.9765.60.870.49380.30.180.98--271335844994659279047100.9773.80.870.49435.60.180.98--241031844436585569018000.9783.10.870.49473.70.180.98----282839415202634610000.97102.60.880.47595.00.180.98------31784202505212500.97128.00.880.47755.00.180.98--------33693981Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :6600V2) MOTOR DATA IS BASED ON LOHER MOTORSSystem Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :3%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 10000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER AND FULLY LOADED.1.732 x I x (RCos@+XSin@)5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.

&L&"Arial,Regular"&8&F-&A

24VFDR-L1PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)24V DC FEEDER SELECTION CHART (L1)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.0640.0770.0610.0390.031Resistance (Ohms/km) at 90C26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0662.0754.0601.0719.01202.01438.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1590.8672.9536.4641.71072.81283.4Derated Rating (Amps.)(Amp)(Amp)2.546101625355070951201501852x952x1202x1502x1853004002x3002x400Conductor Size (mm2)2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C1C1C1C1CNo. of Cable core43.2081319325180111150218301383466586602765932**974******108.003581320324560871201531862342413063734693904927799841612.802358132028385575961161461511912332932443074876153225.60----246101419273848587375961161461221542443074032.00------35811152230384759607793117971231952465040.00--------4691217243137474861759478981561976350.40--------3571014192430373849597462781241568064.00----------46811151923293038475949619712310080.00------------469121519232431374739497898125100.00--------------57101215191924303831396279160128.00------------------81012151519232924314961200160.00--------------------89121215192319253949250200.00----------------------791012151916203139Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :24V2) CABLE DE-RATING FACTORS ARE AS FOLLOWS :-Steady State Allowable Volt Drop :2%A)Ambient temp at 40C1.05B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x RAND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VFDR-L1 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V FEEDER SELECTION CHART (L1)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.0640.0650.0540.043Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.0720.0370.0360.0360.0360.0240.0240.024Reactance (Ohms/km) 50Hz21.028.036.050.067.089.0110.0137.0169.0205.0237.0272.0311.0410.0474.0544.0622.0711.0816.0933.0Current Rating (Amps.) at 45CCBFLC18.725.032.144.659.879.498.2122.3150.8183.0211.5242.8277.6365.9423.0485.5555.1634.6728.3832.7Derated Rating (Amps.)(Amp)(Amp)Cos@Sin@2.546101625355070951201501852x952x1202x1502x1853x1203x1503x185Conductor Size (mm2)3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3CNo. of Cable core43.200.850.53175281422708********************************108.000.850.5370112169283444690941**************************1612.800.850.534470106177278431588777************************3225.600.850.53------88139216294389543720882******************4032.000.850.53--------111172235311434576706826984**************5040.000.850.53--------89138188249347461565661787921************6350.400.850.53----------109149197276366448524625731896**********8064.000.850.53------------118155217288353413492576706826984******10080.000.850.53--------------124174230282330393461565661787847991**125100.000.850.53----------------139184226264315369452529630678793944160128.000.850.53--------------------176206246288353413492529619738200160.000.850.53----------------------165197230282330393423496590250200.000.850.53--------------------------184226264315339396472300240.000.850.53--------------------------154188220262282330393400320.000.850.53------------------------------165197212248295500400.000.850.53----------------------------------169198236630504.000.850.53------------------------------------157187800640.000.850.53----------------------------------------1000800.000.850.53----------------------------------------12501000.000.850.53----------------------------------------16001280.000.850.53----------------------------------------20001600.000.850.53----------------------------------------25002000.000.850.53----------------------------------------30002400.000.850.53----------------------------------------35002800.000.850.53----------------------------------------Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :400V2) CABLE DERATING FACTORS ARE AS FOLLOWS :-System Frequency :50HzA)Ambient temp at 40C1.05Steady State Allowable Volt Drop :2%B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.C)Safety factor1.158)FORMULA USED FOR DETERMINING LENGTH :3) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHERLENGTH (L) =System Voltage (V) x Volt Drop X 1000AND FULLY LOADED.1.732 x I x (RCos@+XSin@)4) * CABLES WITHIN BRACKETS ARE SINGLE CORE CABLES PER PHASE9)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VFDR-L2 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V FEEDER SELECTION CHART (L2)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.0640.0650.0540.043Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.0720.0370.0360.0360.0360.0240.0240.024Reactance (Ohms/km) 50Hz21.028.036.050.067.089.0110.0137.0169.0205.0237.0272.0311.0410.0474.0544.0622.0711.0816.0933.0Current Rating (Amps.) at 45CCBFLC18.725.032.144.659.879.498.2122.3150.8183.0211.5242.8277.6365.9423.0485.5555.1634.6728.3832.7Derated Rating (Amps.)(Amp)(Amp)Cos@Sin@2.546101625355070951201501852x952x1202x1502x1853x1203x1503x185Conductor Size (mm2)3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3C3CNo. of Cable core43.200.850.53175281422708********************************108.000.850.5370112169283444690941**************************1612.800.850.534470106177278431588777************************3225.600.850.53------88139216294389543720882******************4032.000.850.53--------111172235311434576706826984**************5040.000.850.53--------89138188249347461565661787921************6350.400.850.53----------109149197276366448524625731896**********8064.000.850.53------------118155217288353413492576706826984******10080.000.850.53--------------124174230282330393461565661787847991**125100.000.850.53----------------139184226264315369452529630678793944160128.000.850.53--------------------176206246288353413492529619738200160.000.850.53----------------------165197230282330393423496590250200.000.850.53--------------------------184226264315339396472300240.000.850.53--------------------------154188220262282330393400320.000.850.53------------------------------165197212248295500400.000.850.53----------------------------------169198236630504.000.850.53------------------------------------157187800640.000.850.53----------------------------------------1000800.000.850.53----------------------------------------12501000.000.850.53----------------------------------------16001280.000.850.53----------------------------------------20001600.000.850.53----------------------------------------25002000.000.850.53----------------------------------------30002400.000.850.53----------------------------------------35002800.000.850.53----------------------------------------Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :400V2) CABLE DE-RATING FACTORS ARE AS FOLLOWS :-System Frequency :50HzA)Ambient temp at 40C1.05Steady State Allowable Volt Drop :2%B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.C)Safety factor1.158)FORMULA USED FOR DETERMINING LENGTH :3) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHERLENGTH (L) =System Voltage (V) x Volt Drop X 1000AND FULLY LOADED.1.732 x I x (RCos@+XSin@)4) * CABLES WITHIN BRACKETS ARE SINGLE CORE CABLES PER PHASE9)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VFDR-L3 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V FEEDER SELECTION CHART (L3)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating0.0970.0770.0610.0490.0320.0240.0390.0260.0190.0150.0130.0110.0310.0200.0150.012Resistance (Ohms/km) at 90C0.0900.0890.0890.0450.0300.0230.0450.0300.0220.0180.0150.0130.0450.0300.0220.018Reactance (Ohms/km) 50Hz522.0601.0719.01044.01566.02088.01202.01803.02404.03005.03606.04207.01438.02157.02876.03595.0Current Rating (Amps.) at 45CCBFLC465.9536.4641.7931.81397.71863.51072.81609.22145.62682.03218.43754.71283.41925.12566.83208.5Derated Rating (Amps.)(Amp)(Amp)Cos@Sin@2403004002x(240)*3x(240)*4x(240)*2x(300)*3x(300)*4x(300)*5x(300)*6x(300)*7x(300)*2x(400)*3x(400)*4x(400)*5x(400)*Conductor Size (mm2)1C1C1C1C1C1C1C1C1C1C1C1C1C1C1C1CNo. of Cable core43.200.850.53********************************108.000.850.53********************************1612.800.850.53********************************3225.600.850.53********************************4032.000.850.53********************************5040.000.850.53889******************************6350.400.850.53706816928**************************8064.000.850.53556642731**************************10080.000.850.53445514585889************************125100.000.850.53356411468711****822**********936******160128.000.850.53278321365556834**642964********731******200160.000.850.53222257292445667889514771********585877****250200.000.850.53178206234356534711411617822******468702936**300240.000.850.53148171195296445593343514685857****390585780975400320.000.850.53111128146222333445257385514642771899292439585731500400.000.850.53----117178267356206308411514617720234351468585630504.000.850.53------141212282163245326408490571186278371464800640.000.850.53------1111672221281932573213854501462192923651000800.000.850.53--------133178--15420625730836011717523429212501000.000.850.53----------142--123164206247288--14018723416001280.000.850.53----------111----128161193225--11014618320001600.000.850.53------------------128154180----11714625002000.000.850.53--------------------123144------11730002400.000.850.53----------------------120--------35002800.000.850.53--------------------------------Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :400V2) CABLE DE-RATING FACTORS ARE AS FOLLOWS :-Single coreSystem Frequency :50HzA)Ambient temp at 40C1.05Steady State Allowable Volt Drop :2%B)Grouping (6 and above cables bunching)0.85Total correction factor0.89(single core trefoil formation)7)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.C)Safety factor1.158)FORMULA USED FOR DETERMINING LENGTH :3) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHERLENGTH (L) =System Voltage (V) x Volt Drop X 1000AND FULLY LOADED.1.732 x I x (RCos@+XSin@)4) * CABLES WITHIN BRACKETS ARE SINGLE CORE CABLES PER PHASE5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.

&L&"Arial,Regular"&8&F-&A

400VMTFDR-L1 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V MOTOR FEEDER SELECTION CHART (L1)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.128Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.072Reactance (Ohms/km) 50Hz21.028.036.050.067.089.0110.0137.0169.0205.0237.0272.0311.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting18.725.032.144.659.879.498.2122.3150.8183.0211.5242.8277.6Derated Rating (Amps.)(Amp)cos@sin@(Amp)%cos@sin@2.54610162535507095120150185Conductor Size (mm2)3C3C3C3C3C3C3C3C3C3C3C3C3CNo. of Cable core0.250.660.70.730.683.95200.091.00872************************0.370.711.00.750.665.25200.100.99629************************0.550.751.50.730.687.55200.110.99448717**********************0.750.761.90.760.6511.26000.101.00335536805********************1.10.792.60.780.6315.66000.100.99235376566946******************1.50.813.40.780.6320.76000.100.99177283425711******************2.20.834.80.800.6028.96000.110.99124198298498780****************30.856.20.820.5740.66500.110.9993149224375587909**************40.868.30.810.5953.96500.110.9971113171286448693943************5.50.8710.80.840.5470.36500.110.995284126212332515703928**********7.50.8914.30.850.5393.06500.120.99396394158248386526695971********110.9121.20.820.57163.37700.101.00--4466110173268365481669883******150.9228.40.830.56215.57600.100.99------82128198270357497657803937**18.50.9335.20.820.57257.07300.100.99------67104161220290403532650757898220.9341.80.820.57296.97100.110.99--------88136185244339448547638756300.9455.10.840.54408.07400.110.99----------101138182254336411481572370.9467.90.840.54523.07700.100.99----------82112148206273334390464450.9480.00.860.51592.17400.110.99------------93123173229281330393550.95101.10.830.56697.66900.110.99--------------100139184225263312750.95132.50.860.51914.36900.120.99------------------138170199237900.95156.80.870.491129.37200.120.99------------------1161431682011100.96190.90.870.491336.37000.120.99----------------------1381651320.96228.60.870.491623.17100.120.99------------------------138Notes:1) MOTOR DATA IS BASED ON ABB MOTORS6)System Nominal Voltage :400V2) CABLE DATA IS BASED ON NEXANS CABLES.System Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :2%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER1.732X Full / Starting Current I (fl/st) x (RCos@+XSin@)AND FULLY LOADED.9)* CABLES WITHIN BRACKETS ARE SINGLE CORE CABLES PER PHASE5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.10)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VMTFDR-L2 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V MOTOR FEEDER SELECTION CHART (L2)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.128Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.072Reactance (Ohms/km) 50Hz21.028.036.050.067.089.0110.0137.0169.0205.0237.0272.0311.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting18.725.032.144.659.879.498.2122.3150.8183.0211.5242.8277.6Derated Rating (Amps.)(Amp)cos@sin@(Amp)%cos@sin@2.54610162535507095120150185Conductor Size (mm2)3C3C3C3C3C3C3C3C3C3C3C3C3CNo. of Cable core0.250.660.70.730.683.95200.091.00872************************0.370.711.00.750.665.25200.100.99629************************0.550.751.50.730.687.55200.110.99448717**********************0.750.761.90.760.6511.26000.101.00335536805********************1.10.792.60.780.6315.66000.100.99235376566946******************1.50.813.40.780.6320.76000.100.99177283425711******************2.20.834.80.800.6028.96000.110.99124198298498780****************30.856.20.820.5740.66500.110.9993149224375587909**************40.868.30.810.5953.96500.110.9971113171286448693943************5.50.8710.80.840.5470.36500.110.995284126212332515703928**********7.50.8914.30.850.5393.06500.120.99396394158248386526695971********110.9121.20.820.57163.37700.101.00--4466110173268365481669883******150.9228.40.830.56215.57600.100.99------82128198270357497657803937**18.50.9335.20.820.57257.07300.100.99------67104161220290403532650757898220.9341.80.820.57296.97100.110.99--------88136185244339448547638756300.9455.10.840.54408.07400.110.99----------101138182254336411481572370.9467.90.840.54523.07700.100.99----------82112148206273334390464450.9480.00.860.51592.17400.110.99------------93123173229281330393550.95101.10.830.56697.66900.110.99--------------100139184225263312750.95132.50.860.51914.36900.120.99------------------138170199237900.95156.80.870.491129.37200.120.99------------------1161431682011100.96190.90.870.491336.37000.120.99----------------------1381651320.96228.60.870.491623.17100.120.99------------------------138Notes:1) MOTOR DATA IS BASED ON ABB MOTORS6)System Nominal Voltage :400V2) CABLE DATA IS BASED ON NEXANS CABLES.System Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :2%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER1.732X Full / Starting Current I (fl/st) x (RCos@+XSin@)AND FULLY LOADED.9)* CABLES WITHIN BRACKETS ARE SINGLE CORE CABLES PER PHASE5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.10)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VMTVSD-L4 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V MOTOR FEEDER SELECTION CHART (L4)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters0.9360.6740.4990.3440.2490.1960.1610.128Resistance (Ohms/km) at 90C0.0790.0770.0760.0760.0740.0720.0720.072Reactance (Ohms/km) 50Hz89.0110.0137.0169.0205.0237.0272.0311.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting79.498.2122.3150.8183.0211.5242.8277.6Derated Rating (Amps.)(Amp)cos@sin@(Amp)%cos@sin@2535507095120150185Conductor Size (mm2)3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3ENo. of Cable core0.250.660.70.730.683.95200.091.00****************0.370.711.00.750.665.25200.100.99****************0.550.751.50.730.687.55200.110.99****************0.750.761.90.760.6511.26000.101.00****************1.10.792.60.780.6315.66000.100.99****************1.50.813.40.780.6320.76000.100.99****************2.20.834.80.800.6028.96000.110.99****************30.856.20.820.5740.66500.110.99909**************40.868.30.810.5953.96500.110.99693943************5.50.8710.80.840.5470.36500.110.99515703928**********7.50.8914.30.850.5393.06500.120.99386526695971********110.9121.20.820.57163.37700.101.00268365481669883******150.9228.40.830.56215.57600.100.99198270357497657803937**18.50.9335.20.820.57257.07300.100.99161220290403532650757898220.9341.80.820.57296.97100.110.99136185244339448547638756300.9455.10.840.54408.07400.110.99101138182254336411481572370.9467.90.840.54523.07700.100.9982112148206273334390464450.9480.00.860.51592.17400.110.99--93123173229281330393550.95101.10.830.56697.66900.110.99----100139184225263312750.95132.50.860.51914.36900.120.99--------138170199237900.95156.80.870.491129.37200.120.99--------1161431682011100.96190.90.870.491336.37000.120.99------------1381651320.96228.60.870.491623.17100.120.99--------------138Notes:1) MOTOR DATA IS BASED ON ABB MOTORS6)System Nominal Voltage :400V2) CABLE DATA IS BASED ON NEXANS CABLES.System Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :2%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER1.732X Full / Starting Current I (fl/st) x (RCos@+XSin@)AND FULLY LOADED.9)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VMTFDR-L1 (2.5%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V MOTOR FEEDER SELECTION CHART (L1)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.128Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.072Reactance (Ohms/km) 50Hz21.028.036.050.067.089.0110.0137.0169.0205.0237.0272.0311.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting18.725.032.144.659.879.498.2122.3150.8183.0211.5242.8277.6Derated Rating (Amps.)(Amp)cos@sin@(Amp)%cos@sin@2.54610162535507095120150185Conductor Size (mm2)3C3C3C3C3C3C3C3C3C3C3C3C3CNo. of Cable core0.250.660.70.730.683.95200.091.00**************************0.370.711.00.750.665.25200.100.99787************************0.550.751.50.730.687.55200.110.99560897**********************0.750.761.90.760.6511.26000.101.00418670**********************1.10.792.60.780.6315.66000.100.99294470707********************1.50.813.40.780.6320.76000.100.99221354532889******************2.20.834.80.800.6028.96000.110.99154247372622975****************30.856.20.820.5740.66500.110.99116186280468734****************40.868.30.810.5953.96500.110.9989142213357560866**************5.50.8710.80.840.5470.36500.110.9965105158265415644878************7.50.8914.30.850.5393.06500.120.994978118198311482658869**********110.9121.20.820.57163.37700.101.00--5582138216335456601836********150.9228.40.830.56215.57600.100.99------102160248338446621821******18.50.9335.20.820.57257.07300.100.99------83130202275362504665812947**220.9341.80.820.57296.97100.110.99--------110170231305424560684797912300.9455.10.840.54408.07400.110.99----------126172227317420514601665370.9467.90.840.54523.07700.100.99----------103140185257341417488521450.9480.00.860.51592.17400.110.99------------117154216286352412456550.95101.10.830.56697.66900.110.99--------------125174230282329384750.95132.50.860.51914.36900.120.99------------------173212249292900.95156.80.870.491129.37200.120.99------------------1451792102371100.96190.90.870.491336.37000.120.99----------------------1721991320.96228.60.870.491623.17100.120.99------------------------164Notes:1) MOTOR DATA IS BASED ON ABB MOTORS6)System Nominal Voltage :400V2) CABLE DATA IS BASED ON NEXANS CABLES.System Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :2.5%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER1.732X Full / Starting Current I (fl/st) x (RCos@+XSin@)AND FULLY LOADED.9)* CABLES WITHIN BRACKETS ARE SINGLE CORE CABLES PER PHASE5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.10)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VMTFDR-L2 (2.5%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V MOTOR FEEDER SELECTION CHART (L2)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.128Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.072Reactance (Ohms/km) 50Hz21.028.036.050.067.089.0110.0137.0169.0205.0237.0272.0311.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting18.725.032.144.659.879.498.2122.3150.8183.0211.5242.8277.6Derated Rating (Amps.)(Amp)cos@sin@(Amp)%cos@sin@2.54610162535507095120150185Conductor Size (mm2)3C3C3C3C3C3C3C3C3C3C3C3C3CNo. of Cable core0.250.660.70.730.683.95200.091.00**************************0.370.711.00.750.665.25200.100.99787************************0.550.751.50.730.687.55200.110.99560897**********************0.750.761.90.760.6511.26000.101.00418670**********************1.10.792.60.780.6315.66000.100.99294470707********************1.50.813.40.780.6320.76000.100.99221354532889******************2.20.834.80.800.6028.96000.110.99154247372622975****************30.856.20.820.5740.66500.110.99116186280468734****************40.868.30.810.5953.96500.110.9989142213357560866**************5.50.8710.80.840.5470.36500.110.9965105158265415644878************7.50.8914.30.850.5393.06500.120.994978118198311482658869**********110.9121.20.820.57163.37700.101.00--5582138216335456601836********150.9228.40.830.56215.57600.100.99------102160248338446621821******18.50.9335.20.820.57257.07300.100.99------83130202275362504665812947**220.9341.80.820.57296.97100.110.99--------110170231305424560684797912300.9455.10.840.54408.07400.110.99----------126172227317420514601665370.9467.90.840.54523.07700.100.99----------103140185257341417488521450.9480.00.860.51592.17400.110.99------------117154216286352412456550.95101.10.830.56697.66900.110.99--------------125174230282329384750.95132.50.860.51914.36900.120.99------------------173212249292900.95156.80.870.491129.37200.120.99------------------1451792102371100.96190.90.870.491336.37000.120.99----------------------1721991320.96228.60.870.491623.17100.120.99------------------------164Notes:1) MOTOR DATA IS BASED ON ABB MOTORS6)System Nominal Voltage :400V2) CABLE DATA IS BASED ON NEXANS CABLES.System Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :2.5%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER1.732X Full / Starting Current I (fl/st) x (RCos@+XSin@)AND FULLY LOADED.9)* CABLES WITHIN BRACKETS ARE SINGLE CORE CABLES PER PHASE5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.10)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VMTVSD-L4 (2.5%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V MOTOR FEEDER SELECTION CHART (L4)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters0.9360.6740.4990.3440.2490.1960.1610.128Resistance (Ohms/km) at 90C0.0790.0770.0760.0760.0740.0720.0720.072Reactance (Ohms/km) 50Hz89.0110.0137.0169.0205.0237.0272.0311.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting79.498.2122.3150.8183.0211.5242.8277.6Derated Rating (Amps.)(Amp)cos@sin@(Amp)%cos@sin@2535507095120150185Conductor Size (mm2)3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3ENo. of Cable core0.250.660.70.730.683.95200.091.00****************0.370.711.00.750.665.25200.100.99****************0.550.751.50.730.687.55200.110.99****************0.750.761.90.760.6511.26000.101.00****************1.10.792.60.780.6315.66000.100.99****************1.50.813.40.780.6320.76000.100.99****************2.20.834.80.800.6028.96000.110.99****************30.856.20.820.5740.66500.110.99****************40.868.30.810.5953.96500.110.99866**************5.50.8710.80.840.5470.36500.110.99644878************7.50.8914.30.850.5393.06500.120.99482658869**********110.9121.20.820.57163.37700.101.00335456601836********150.9228.40.830.56215.57600.100.99248338446621821******18.50.9335.20.820.57257.07300.100.99202275362504665812947**220.9341.80.820.57296.97100.110.99170231305424560684797912300.9455.10.840.54408.07400.110.99126172227317420514601665370.9467.90.840.54523.07700.100.99103140185257341417488521450.9480.00.860.51592.17400.110.99--117154216286352412456550.95101.10.830.56697.66900.110.99----125174230282329384750.95132.50.860.51914.36900.120.99--------173212249292900.95156.80.870.491129.37200.120.99--------1451792102371100.96190.90.870.491336.37000.120.99------------1721991320.96228.60.870.491623.17100.120.99--------------164Notes:1) MOTOR DATA IS BASED ON ABB MOTORS6)System Nominal Voltage :400V2) CABLE DATA IS BASED ON NEXANS CABLES.System Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :2.5%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER1.732X Full / Starting Current I (fl/st) x (RCos@+XSin@)AND FULLY LOADED.9)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VMTFDR-L1 (3%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V MOTOR FEEDER SELECTION CHART (L1)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.128Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.072Reactance (Ohms/km) 50Hz21.028.036.050.067.089.0110.0137.0169.0205.0237.0272.0311.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting18.725.032.144.659.879.498.2122.3150.8183.0211.5242.8277.6Derated Rating (Amps.)(Amp)cos@sin@(Amp)%cos@sin@2.54610162535507095120150185Conductor Size (mm2)3C3C3C3C3C3C3C3C3C3C3C3C3CNo. of Cable core0.250.660.70.730.683.95200.091.00**************************0.370.711.00.750.665.25200.100.99944************************0.550.751.50.730.687.55200.110.99672************************0.750.761.90.760.6511.26000.101.00502804**********************1.10.792.60.780.6315.66000.100.99352564848********************1.50.813.40.780.6320.76000.100.99265424638********************2.20.834.80.800.6028.96000.110.99185297446747******************30.856.20.820.5740.66500.110.99139223336562881****************40.868.30.810.5953.96500.110.99106170256429671****************5.50.8710.80.840.5470.36500.110.9979126190318498773**************7.50.8914.30.850.5393.06500.120.995994142237373578789************110.9121.20.820.57163.37700.101.00--6699166260402547722**********150.9228.40.830.56215.57600.100.99------123192298406535745986******18.50.9335.20.820.57257.07300.100.99------100156242330435604798975****220.9341.80.820.57296.97100.110.99--------132204278366509672820876912300.9455.10.840.54408.07400.110.99----------152207273381504613638665370.9467.90.840.54523.07700.100.99----------123168222309409482501521450.9480.00.860.51592.17400.110.99------------140185259344419437456550.95101.10.830.56697.66900.110.99--------------150209276338368384750.95132.50.860.51914.36900.120.99------------------208255279292900.95156.80.870.491129.37200.120.99------------------1752142272371100.96190.90.870.491336.37000.120.99----------------------1911991320.96228.60.870.491623.17100.120.99------------------------164Notes:1) MOTOR DATA IS BASED ON ABB MOTORS6)System Nominal Voltage :400V2) CABLE DATA IS BASED ON NEXANS CABLES.System Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :3%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER1.732X Full / Starting Current I (fl/st) x (RCos@+XSin@)AND FULLY LOADED.9)* CABLES WITHIN BRACKETS ARE SINGLE CORE CABLES PER PHASE5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.10)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VMTFDR-L2 (3%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V MOTOR FEEDER SELECTION CHART (L2)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.128Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.072Reactance (Ohms/km) 50Hz21.028.036.050.067.089.0110.0137.0169.0205.0237.0272.0311.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting18.725.032.144.659.879.498.2122.3150.8183.0211.5242.8277.6Derated Rating (Amps.)(Amp)cos@sin@(Amp)%cos@sin@2.54610162535507095120150185Conductor Size (mm2)3C3C3C3C3C3C3C3C3C3C3C3C3CNo. of Cable core0.250.660.70.730.683.95200.091.00**************************0.370.711.00.750.665.25200.100.99944************************0.550.751.50.730.687.55200.110.99672************************0.750.761.90.760.6511.26000.101.00502804**********************1.10.792.60.780.6315.66000.100.99352564848********************1.50.813.40.780.6320.76000.100.99265424638********************2.20.834.80.800.6028.96000.110.99185297446747******************30.856.20.820.5740.66500.110.99139223336562881****************40.868.30.810.5953.96500.110.99106170256429671****************5.50.8710.80.840.5470.36500.110.9979126190318498773**************7.50.8914.30.850.5393.06500.120.995994142237373578789************110.9121.20.820.57163.37700.101.00--6699166260402547722**********150.9228.40.830.56215.57600.100.99------123192298406535745986******18.50.9335.20.820.57257.07300.100.99------100156242330435604798975****220.9341.80.820.57296.97100.110.99--------132204278366509672820876912300.9455.10.840.54408.07400.110.99----------152207273381504613638665370.9467.90.840.54523.07700.100.99----------123168222309409482501521450.9480.00.860.51592.17400.110.99------------140185259344419437456550.95101.10.830.56697.66900.110.99--------------150209276338368384750.95132.50.860.51914.36900.120.99------------------208255279292900.95156.80.870.491129.37200.120.99------------------1752142272371100.96190.90.870.491336.37000.120.99----------------------1911991320.96228.60.870.491623.17100.120.99------------------------164Notes:1) MOTOR DATA IS BASED ON ABB MOTORS6)System Nominal Voltage :400V2) CABLE DATA IS BASED ON NEXANS CABLES.System Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :3%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER1.732X Full / Starting Current I (fl/st) x (RCos@+XSin@)AND FULLY LOADED.9)* CABLES WITHIN BRACKETS ARE SINGLE CORE CABLES PER PHASE5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.10)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

400VMTVSD-L4 (3%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)400V MOTOR FEEDER SELECTION CHART (L4)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable Parameters0.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.064Resistance (Ohms/km) at 90C0.0790.0770.0760.0760.0740.0720.0720.0720.0370.0360.0360.036Reactance (Ohms/km) 50Hz89.0110.0137.0169.0205.0237.0272.0311.0410.0474.0544.0622.0Current Rating (Amps.) at 45CKWEFFFLCSteady StateLRCStarting79.498.2122.3150.8183.0211.5242.8277.6365.9423.0485.5555.1Derated Rating (Amps.)(Amp)cos@sin@(Amp)%cos@sin@25355070951201501852x952x1202x1502x180Conductor Size (mm2)3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3E3C+3ENo. of Cable core0.250.660.70.730.683.95200.091.00************************0.370.711.00.750.665.25200.100.99************************0.550.751.50.730.687.55200.110.99************************0.750.761.90.760.6511.26000.101.00************************1.10.792.60.780.6315.66000.100.99************************1.50.813.40.780.6320.76000.100.99************************2.20.834.80.800.6028.96000.110.99************************30.856.20.820.5740.66500.110.99************************40.868.30.810.5953.96500.110.99************************5.50.8710.80.840.5470.36500.110.99773**********************7.50.8914.30.850.5393.06500.120.99578789********************110.9121.20.820.57163.37700.101.00402547722******************150.9228.40.830.56215.57600.100.99298406535745986**************18.50.9335.20.820.57257.07300.100.99242330435604798975************220.9341.80.820.57296.97100.110.99204278366509672820876912********300.9455.10.840.54408.07400.110.99152207273381504613638665********370.9467.90.840.54523.07700.100.99123168222309409482501521818964****450.9480.00.860.51592.17400.110.99--140185259344419437456688838874911550.95101.10.830.56697.66900.110.99----150209276338368384553676737769750.95132.50.860.51914.36900.120.99--------208255279292415509558583900.95156.80.870.491129.37200.120.99--------1752142272373494294544741100.96190.90.870.491336.37000.120.99------------1911992873523813991320.96228.60.870.491623.17100.120.99--------------1642392943153291600.96277.10.870.491967.47100.120.99----------------198243260271Notes:1) MOTOR DATA IS BASED ON ABB MOTORS6)System Nominal Voltage :400V2) CABLE DATA IS BASED ON NEXANS CABLES.System Frequency :50Hz3) CABLE DERATING FACTORS ARE AS FOLLOWS :-Steady State Volt Drop :3%A)Ambient temp at 40C1.05Motor Starting Volt Drop :10%B)Grouping (6 and above cables bunching)0.857)-- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.Total correction factor0.898)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10004) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER1.732X Full / Starting Current I (fl/st) x (RCos@+XSin@)AND FULLY LOADED.9)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZEDFOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

230VFDR-L1 (3%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)230V FEEDER SELECTION CHART (L1) - 3% VdropCLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.098Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.0720.0370.036Reactance (Ohms/km) 50Hz26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1Derated Rating (Amps.)(Amp)(Amp)Cos@Sin@2.546101625355070951201501852x952x120Conductor Size (mm2)2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PENo. of Cable core43.200.850.53131210315529830********************108.000.850.535284126212332515703929**************1612.800.850.53335279132207322439581811************3225.600.850.53----3966104161220290405538659771918****4032.000.850.53------5383129176232324430527617735860**5040.000.850.53--------661031411862593444224935886888436350.400.850.53--------53821121472062733353924675466698064.000.850.53----------648811616221526430836743052710080.000.850.53------------7093130172211247294344422125100.000.850.53--------------74104138169197235275337160128.000.850.53------------------108132154184215264200160.000.850.53--------------------105123147172211250200.000.850.53----------------------99118138169300240.000.850.53--------------------------115141Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :230V2) CABLE DERATING FACTORS ARE AS FOLLOWS :-System Frequency :50HzA)Ambient temp at 40C1.05Steady State Allowable Volt Drop :3%B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x (RCos@+XSin@)AND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

230VFDR-L2 (3%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)230V FEEDER SELECTION CHART (L2) - 3% VdropCLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.098Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.0720.0370.036Reactance (Ohms/km) 50Hz26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1Derated Rating (Amps.)(Amp)(Amp)Cos@Sin@2.546101625355070951201501852x952x120Conductor Size (mm2)2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PENo. of Cable core43.200.850.53131210315529830********************108.000.850.535284126212332515703929**************1612.800.850.53335279132207322439581811************3225.600.850.53----3966104161220290405538659771918****4032.000.850.53------5383129176232324430527617735860**5040.000.850.53--------661031411862593444224935886888436350.400.850.53--------53821121472062733353924675466698064.000.850.53----------648811616221526430836743052710080.000.850.53------------7093130172211247294344422125100.000.850.53--------------74104138169197235275337160128.000.850.53------------------108132154184215264200160.000.850.53--------------------105123147172211250200.000.850.53----------------------99118138169300240.000.850.53--------------------------115141Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :230V2) CABLE DERATING FACTORS ARE AS FOLLOWS :-System Frequency :50HzA)Ambient temp at 40C1.05Steady State Allowable Volt Drop :3%B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x (RCos@+XSin@)AND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

230VFDR-L1 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)230V FEEDER SELECTION CHART (L1) - 2% VdropCLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.098Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.0720.0370.036Reactance (Ohms/km) 50Hz26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1Derated Rating (Amps.)(Amp)(Amp)Cos@Sin@2.546101625355070951201501852x952x120Conductor Size (mm2)2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PENo. of Cable core43.200.850.5387140210353553859******************108.000.850.53355684141221343469619865************1612.800.850.5322355388138215293387541717879********3225.600.850.53----2644691071461942703584395146127178794032.000.850.53------3555861171552162873514114905747035040.000.850.53--------4469941241732292813293924595626350.400.850.53--------355574981371822232613113644468064.000.850.53----------43597710814317620624528735110080.000.850.53------------476286115141164196229281125100.000.850.53--------------506992112132157184225160128.000.850.53------------------7288103122143176200160.000.850.53--------------------708298115141250200.000.850.53----------------------667892112300240.000.850.53--------------------------7694Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :230V2) CABLE DERATING FACTORS ARE AS FOLLOWS :-System Frequency :50HzA)Ambient temp at 40C1.05Steady State Allowable Volt Drop :2%B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x (RCos@+XSin@)AND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

230VFDR-L2 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)230V FEEDER SELECTION CHART (L2) - 2% VdropCLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.098Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.0720.0370.036Reactance (Ohms/km) 50Hz26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1Derated Rating (Amps.)(Amp)(Amp)Cos@Sin@2.546101625355070951201501852x952x120Conductor Size (mm2)2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PENo. of Cable core43.200.850.5387140210353553859******************108.000.850.53355684141221343469619865************1612.800.850.5322355388138215293387541717879********3225.600.850.53----2644691071461942703584395146127178794032.000.850.53------3555861171552162873514114905747035040.000.850.53--------4469941241732292813293924595626350.400.850.53--------355574981371822232613113644468064.000.850.53----------43597710814317620624528735110080.000.850.53------------476286115141164196229281125100.000.850.53--------------506992112132157184225160128.000.850.53------------------7288103122143176200160.000.850.53--------------------708298115141250200.000.850.53----------------------667892112300240.000.850.53--------------------------7694Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :230V2) CABLE DERATING FACTORS ARE AS FOLLOWS :-System Frequency :50HzA)Ambient temp at 40C1.05Steady State Allowable Volt Drop :2%B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x (RCos@+XSin@)AND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

230VFDR-L2 (1%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)230V FEEDER SELECTION CHART (L2) - 1% VdropCLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.0640.0830.0650.0540.043Resistance (Ohms/km) at 90C0.1030.0960.0900.0850.0800.0790.0770.0760.0760.0740.0720.0720.0720.0370.0360.0360.0360.0250.0240.0240.024Reactance (Ohms/km) 50Hz26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0662.0754.0747.0864.0993.01131.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1590.8672.9666.7771.1886.31009.4Derated Rating (Amps.)(Amp)(Amp)Cos@Sin@2.546101625355070951201501852x952x1202x1502x1853x953x1203x1503x185Conductor Size (mm2)2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PE2C+PENo. of Cable core43.200.850.534470105176277429586774**************************108.000.850.5317284271111172234310432574703822980****************1612.800.850.531117264469107146194270358439514612717879************3225.600.850.53----1322355473971351792202573063584395146125386597719184032.000.850.53------18284359771081431762062452873514114904305276177355040.000.850.53--------22344762861151411641962292813293923444224935886350.400.850.53--------1827374969911121311561822232613112733353924678064.000.850.53----------21293954728810312214317620624521526430836710080.000.850.53------------23314357708298115141164196172211247294125100.000.850.53--------------25354656667892112132157138169197235160128.000.850.53------------------364451617288103122108132154184200160.000.850.53--------------------3541495770829886105123147250200.000.850.53----------------------333946566678698499118312.5250.000.850.53--------------------------3745536355677994500400.000.850.53------------------------------333934424959625500.000.850.53------------------------------------343947787.5630.000.850.53----------------------------------------37Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :230V2) CABLE DERATING FACTORS ARE AS FOLLOWS :-System Frequency :50HzA)Ambient temp at 40C1.05Steady State Allowable Volt Drop :1%B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x (RCos@+XSin@)AND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

120VFDR-L1 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)120V DC FEEDER SELECTION CHART (L1)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.064Resistance (Ohms/km) at 90C26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0662.0754.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1590.8672.9Derated Rating (Amps.)(Amp)(Amp)2.546101625355070951201501852x952x1202x1502x185Conductor Size (mm2)2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2CNo. of Cable core2016.0081319325180111150218301383466586602765932**108.0016253864101160223301436602765932**********1612.801016244063100139188273377478582732753957****3225.60----1220325070941361882392913663774785827324032.00------16254056751091511912332933013834665865040.00--------20324560871201531862342413063734696350.40--------1625354869961211481861912432963728064.00----------20283855759611614615119123329310080.00------------223044607793117120153186234125100.00--------------24354861759496122149188160128.00------------------384858737596116146200160.00--------------------384759607793117250200.00----------------------374748617594Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :120V2) CABLE DE-RATING FACTORS ARE AS FOLLOWS :-Steady State Allowable Volt Drop :2%A)Ambient temp at 40C1.05B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x RAND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

120VFDR-L2 (2%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)120V DC FEEDER SELECTION CHART (L2)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.064Resistance (Ohms/km) at 90C26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0662.0754.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1590.8672.9Derated Rating (Amps.)(Amp)(Amp)2.546101625355070951201501852x952x1202x1502x185Conductor Size (mm2)2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2CNo. of Cable core43.20396395160254401556752******************108.0016253864101160223301436602765932**********1612.801016244063100139188273377478582732753957****3225.60----1220325070941361882392913663774785827324032.00------16254056751091511912332933013834665865040.00--------20324560871201531862342413063734696350.40--------1625354869961211481861912432963728064.00----------20283855759611614615119123329310080.00------------223044607793117120153186234125100.00--------------24354861759496122149188160128.00------------------384858737596116146200160.00--------------------384759607793117250200.00----------------------374748617594Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :120V2) CABLE DE-RATING FACTORS ARE AS FOLLOWS :-Steady State Allowable Volt Drop :2%A)Ambient temp at 40C1.05B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x RAND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

120VFDR-L2 (1%)PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)120V DC FEEDER SELECTION CHART (L2)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.064Resistance (Ohms/km) at 90C26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0662.0754.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1590.8672.9Derated Rating (Amps.)(Amp)(Amp)2.546101625355070951201501852x952x1202x1502x185Conductor Size (mm2)2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2CNo. of Cable core43.2019314780127200278376545753957************108.0081319325180111150218301383466586602765932**1612.80581220325070941361882392913663774785827323225.60----6101625354768941201461831882392913664032.00------8132028385575961161461511912332935040.00--------10162230446077931171201531862346350.40--------81318243548617493961211481868064.00----------1014192738485873759611614610080.00------------11152230384759607793117125100.00--------------12172431374748617594160128.00------------------1924293738485873200160.00--------------------19232930384759250200.00----------------------192324313747Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :120V2) CABLE DE-RATING FACTORS ARE AS FOLLOWS :-Steady State Allowable Volt Drop :1%A)Ambient temp at 40C1.05B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x RAND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

110VFDR-L1PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)110V DC FEEDER SELECTION CHART (L1)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.064Resistance (Ohms/km) at 90C26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0662.0754.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1590.8672.9Derated Rating (Amps.)(Amp)(Amp)2.546101625355070951201501852x952x1202x1502x185Conductor Size (mm2)2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2CNo. of Cable core43.20365787147232367510689999****************108.001423355993147204276400552702854**********1612.8091422375892128172250345438534671690877****3225.60----1118294664861251732192673363454385346714032.00------15233751691001381752142692763514275375040.00--------19294155801101401712152212813424306350.40--------1523324463881111361711752232713418064.00----------18263450698810713413817521426910080.00------------202840557085107110140171215125100.00--------------22324456688688112137172160128.00------------------354453676988107134200160.00--------------------354354557085107250200.00----------------------344344566886Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :110V2) CABLE DE-RATING FACTORS ARE AS FOLLOWS :-Steady State Allowable Volt Drop :2%A)Ambient temp at 40C1.05B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x RAND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

110VFDR-L2PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)110V DC FEEDER SELECTION CHART (L2)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.064Resistance (Ohms/km) at 90C26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0662.0754.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1590.8672.9Derated Rating (Amps.)(Amp)(Amp)2.546101625355070951201501852x952x1202x1502x185Conductor Size (mm2)2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2CNo. of Cable core43.20365787147232367510689999****************108.001423355993147204276400552702854**********1612.8091422375892128172250345438534671690877****3225.60----1118294664861251732192673363454385346714032.00------15233751691001381752142692763514275375040.00--------19294155801101401712152212813424306350.40--------1523324463881111361711752232713418064.00----------18263450698810713413817521426910080.00------------202840557085107110140171215125100.00--------------22324456688688112137172160128.00------------------354453676988107134200160.00--------------------354354557085107250200.00----------------------344344566886Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :110V2) CABLE DE-RATING FACTORS ARE AS FOLLOWS :-Steady State Allowable Volt Drop :2%A)Ambient temp at 40C1.05B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x RAND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A

24VFDR-L2PTTEP INTERNATIONAL LIMITEDZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)24V DC FEEDER SELECTION CHART (L2)CLIENT:PTTEP INTERNATIONAL LIMITEDPROJECT:ZAWTIKA PHASE 1A DETAIL ENGINEERING (OFFSHORE SCOPE)JOB NO.:402025-00633MAXIMUM CABLE LENGTH (M)Cable ParametersFeeder Rating9.6395.9933.9652.3461.4790.9360.6740.4990.3440.2490.1960.1610.1280.1250.0980.0810.064Resistance (Ohms/km) at 90C26.034.044.061.082.0108.0133.0167.0206.0249.0288.0331.0377.0498.0576.0662.0754.0Current Rating (Amps.) at 45CCBFLC23.230.339.354.473.296.4118.7149.0183.9222.2257.0295.4336.5444.5514.1590.8672.9Derated Rating (Amps.)(Amp)(Amp)2.546101625355070951201501852x952x1202x1502x185Conductor Size (mm2)2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2C2CNo. of Cable core43.2081319325180111150218301383466586602765932**108.003581320324560871201531862342413063734691612.802358132028385575961161461511912332933225.60----246101419273848587375961161464032.00------358111522303847596077931175040.00--------469121724313747486175946350.40--------357101419243037384959748064.00----------46811151923293038475910080.00------------4691215192324313747125100.00--------------571012151919243038160128.00------------------810121515192329200160.00--------------------891212151923250200.00----------------------7910121519Notes:1) CABLE DATA IS BASED ON NEXANS CABLES.6)System Nominal Voltage :24V2) CABLE DE-RATING FACTORS ARE AS FOLLOWS :-Steady State Allowable Volt Drop :2%A)Ambient temp at 40C1.05B)Grouping (6 and above cables bunching)0.85Total correction factor0.897)FORMULA USED FOR DETERMINING LENGTH :C)Safety factor1.15LENGTH (L) =System Voltage (V) x Volt Drop X 10003) IT IS ASSUMED THAT THE CABLES ARE LAID TOUCHING EACH OTHER2 x I x RAND FULLY LOADED.8)REFER TO APPENDIX 4 & 5, THE RFOU & BFOU CABLES, 2 CORES CABLE, HAVE EQUAL CONDUCTOR RESISTANCE,4) -- NOT APPLICABLE, ** FOR CABLE LENGTH MORE THAN 1000 METRES.CONDUCTOR REACTANCE AND CABLE CURRENT RATING. HENCE, THIS CHART CAN BE UTILIZED5) CABLE CURRENT CAPACITY AT 45C AND CONDUCTOR RESISTANCE AT 90C.FOR RFCU & BFCU CABLE SELECTION.

&L&"Arial,Regular"&8&F-&A