AM-MIOInput-Output Expansion InterfaceFor Use With the AM-3, AE-1000, & AE-2000 Access Control Systems
Installation Instructions
PRODUCT DESCRIPTIONThe AM-MIO is an expandable input/output interface designed for use with Linear’s AM-3, AE-1000, & AE-2000 access control systems. Housed in a lockable cabinet, the basic AM-MIO consists of two modules: a power supply module (PSM) and a relay/loop module (RLM). Up to three additional RLM modules can be added to fill the five-position module “rack”. Each RLM module provides six Form “C” (normally open & normally closed) 5-amp relays for outputs and eight supervised loop terminals for inputs. With four RLM modules, the AM-MIO is capable of controlling 24 relay outputs and 32 loop inputs. Each module has a rotary switch to select its unique remote device address. The device address identifies each module to the system. Each module is interconnected to the controller by daisy-chained cables.Pushbuttons on the RLM module are provided for manually triggering each relay for testing. Each relay has a red LED light to show when it’s energized. A two-color red/green LED on the RLM module displays the status of the loop inputs. If all eight loops are “normal” (not shorted or open) the indicator is green. If any of the eight loops are “abnormal” (shorted or open) the indicator is red.The power supply module distributes power to the RLM module(s). An external 16 VAC transformer powers the supply and provides charging current for a 12-volt backup battery (up to 7 amp/hour capacity). Indicators on the power supply module display its status. The green indicator lights when AC power is present and blinks when AC power is absent. The yellow indicator lights when the backup battery is low. Special power circuitry prevents fully discharging the backup battery. The status of the power supply is checked regularly by the controller. The red DATA indicator lights when data transfers. The red TAMPER indicator lights and the controller is signaled when the optional magnetic tamper switch detects that the cabinet has been opened.
CABINET COMPONENTS
MODULE FEATURES KEY LOCK INSTALLATION (OPTIONAL) REMOVING MODULES
MOUNTING CABINET SETTING DEVICE ADDRESSES CONNECTING MODULES
INSTALLING MODULES CONNECTING TAMPER SWITCH (OPTIONAL) CONNECT TO ACCESS CONTROLLER
(760) 438-7000USA & Canada (800) 421-1587 & (800) 392-0123
Toll Free FAX (800) 468-1340www.linearcorp.com
PRINTER’S INSTRUCTIONS:INSTR,INSTL,AM-MIO - LINEAR P/N: 218307 B - INK: BLACK - MATERIAL: 20 LB. MEAD BOND - SIZE: 11.000” X 8.500” - SCALE: 1-1 - SIDE 1 OF 2
POWERSUPPLYMODULE(PSM)
NOTE: ILLUSTRATION SHOWS FOURRELAY/LOOP MODULES, ONLY ONEMODULE IS INCLUDED WITH THE AM-MIO
RELAY/LOOP MODULES (RLM)(FOUR MODULES MAXIMUM)
BACKUP BATTERY12 VOLT 7 AMP/HOURMAXIMUM(NOT INCLUDED)
MODULEMOUNTINGRACKS
CAREFULLY ROUTE THE BATTERYLEADS UNDER MODULE RACKAS SHOWN
1
2SLIDE MODULES OUTOF THE RACK
PSM RLM
1
2
3
PLACE COVER ONCARPET AND PUNCHOUT KEY LOCKKNOCKOUT
INSERT LOCK INTO COVER
TIGHTEN NUT
RELAY/LOOPMODULE (RLM)
POWER SUPPLYMODULE (PSM)
BACKUPBATTERY
LEADS
DEVICEADDRESSSELECTOR
DATA
POWER SUPPLYSTATUS
INDICATORS
TAMPER
LOW BATTERY
AC POWER TAMPERSWITCH
CONNECTOR
MODULECONNECTOR
CONTROLLERCONNECTOR
POWERTERMINALS
AUXILIARYPBUS
TERMINALS
RELAYSTATUS
INDICATORS
LOOP STATUSINDICATOR
DEVICE ADDRESSSELECTOR
MODULECONNECTORS
RELAY TRIGGERPUSHBUTTONS
RELAYOUTPUT
TERMINALS
LOOPINPUT
TERMINALS
USE THE CABINET BOTTOM AS A TEMPLATE TO MARK THE FOUR KEYHOLE MOUNTING HOLES
FOR RECESSED WIRING, MARK WIRING SLOT,THEN CUT OUT HOLEWITH DRYWALL SAW
FOR CONDUIT WIRING,REMOVE ANY CABINETKNOCKOUTS BEFOREMOUNTING THE CABINET
USE THE APPROPRIATEHARDWARE TO MOUNTTHE CABINET
NOTE: PSM DEFAULT ADDRESS IS "5"
NOTE: RLM DEFAULT ADDRESS IS "4"
THE ARROW IN THESELECTOR SWITCHSLOT POINTS TOTHE ADDRESSNUMBER (ADDRESSNUMBERS 1-6 AREVALID)
SET EACH MODULETO A DIFFERENTDEVICE ADDRESS(ONLY REQUIRED IFADDRESS OTHERTHAN DEFAULT ISDESIRED)
RELAY/LOOPMODULE
POWER SUPPLYMODULE
CONNECT POWER SUPPLYTO RELAY/LOOP MODULEWITH THE 10-WIRE CABLE
TO KEEP THE BATTERY LEADSAWAY FROM THE POWER SUPPLYHEAT SINK, ROUTE THE BATTERYLEADS UNDER MODULE RACKAS SHOWN
1
2
3
SLIDE MODULES INTO RACK
PRESS THE MODULES IN UNTILTHEY SNAP INTO PLACE
PSM RLM
1
2
3
REMOVE THE OPTIONAL JUMPER FROM THE TAMPER SWITCHCONNECTOR
INSTALL THE TAMPER SWITCHIN THE BOTTOM CORNER OFCABINET AND CONNECT THEWIRE TO THE TAMPERSWITCH CONNECTOR
ATTACH THE MAGNET TO THE CABINETCOVER SO IT WILL ALIGN WITH THETAMPER SWITCH WHEN THE COVER ISCLOSED
PLUG CABLE FROM AM-MIO PSM CONTROLLERCONNECTOR INTO THE CONTROLLER'S AM-MIOINTERFACE CONNECTOR (MODEL AM-3 CONTROLLER SHOWN)
TO AM-MIO PSM
OPTIONAL: USE THE PSM AUXILIARY PBUS TERMINALS TOCONNECT TO THE CONTROLLER'S AUXILIARY PBUS TERMINALS.REFERENCE THE PSM WIRING DIAGRAM. CABLE TYPE ISBELDEN 9931 (300 FEET MAX. CABLE RUN) OR WEICO 9405(500 FEET MAX. CABLE RUN).
CONNECT RELAY OUTPUTS CONNECT LOOP INPUTS CONNECT AC POWER
CONNECT BACKUP BATTERY TEST RELAYS TEST LOOPS
WIRING DIAGRAM
TEST SYSTEM LINEAR LIMITED WARRANTYThis Linear product is warranted against defects in material and workmanship for twenty four (24) months. The Warranty Expiration Date is labeled on the product. This warranty extends only to wholesale customers who buy direct from Linear or through Linear’s normal distribution channels. Linear does not warrant this product to consumers. Consumers should inquire from their selling dealer as to the nature of the dealer’s warranty, if any. There are no obligations or liabilities on the part of Linear LLC for consequential damages arising out of or in connection with use or performance of this product or other indirect damages with respect to loss of property, revenue, or profit, or cost of removal, installation, or reinstallation. All implied warranties, including implied warranties for merchantability and implied warranties for fitness, are valid only until Warranty Expiration Date as labeled on the product. This Linear LLC Warranty is in lieu of all other warranties express or implied.All products returned for warranty service require a Return Product Authorization Number (RPA#). Contact Linear Technical Service at 1-800-421-1587 for an RPA# and other important details.
IMPORTANT !!!Linear radio controls provide a reliable communications link and fill an important need in portable wireless signalling. However, there are some limitations which must be observed.• For U.S. installations only: The radios are required to comply with FCC
Rules and Regulations as Part 15 devices. As such, they have limited transmitter power and therefore limited range.
• A receiver cannot respond to more than one transmitted signal at a time and may be blocked by radio signals that occur on or near their operating frequencies, regardless of code settings.
• Changes or modifications to the device may void FCC compliance.• Infrequently used radio links should be tested regularly to protect
against undetected interference or fault.• A general knowledge of radio and its vagaries should be gained prior
to acting as a wholesale distributor or dealer, and these facts should be communicated to the ultimate users.
Copyright © 2004 Linear LLC 218307 B
PRINTER’S INSTRUCTIONS:INSTR,INSTL,AM-MIO - LINEAR P/N: 218307 B - INK: BLACK - MATERIAL: 20 LB. MEAD BOND - SIZE: 11.000” X 8.500” - SCALE: 1-1 - SIDE 2 OF 2
N.O.
1
COM
2
N.C.
3
N.O.
4
COM
5
N.C.
6
N.O.
7
COM
8
N.C.
9
N.O.
10
COM
11
N.C.
12
N.O.
13
COM
14
N.C.
15
N.O.
16
COM
17
N.C.
18
CHANNEL 1 CHANNEL 2 CHANNEL 3
CHANNEL 4 CHANNEL 5 CHANNEL 6
CONNECT RELAYOUTPUTS TO THECONTROLLEDDEVICES
RELAY RATING:5 AMPS @14 VDCMAXIMUM
LOOP1
1
COM
2
LOOP2
3
LOOP3
4
COM
5
LOOP4
6
LOOP5
7
COM
8
LOOP6
9
LOOP7
10
COM
11
LOOP8
12
2.2K 2.2K 2.2K 2.2K
2.2K 2.2K 2.2K 2.2K
CONNECT ANY INPUTS TO THELOOP INPUT TERMINALS
EACH LOOP INPUT CAN BETRIGGERED WITH A NORMALLYOPEN OR NORMALLY CLOSEDSWITCH
ALL LOOP INPUTS MUST BETERMINATED WITH A 2.2KEND-OF-LINE RESISTOR
EXAMPLE OF LOOPS 1-4WITH NORMALLYCLOSED SWITCHES
EXAMPLE OF LOOPS 5-8WITH NORMALLYOPEN SWITCHES
ACIN1
ACIN2
EARTHGND
3
DATAGND
4
POWERTERMINALS
16 VAC, 24 VA MIN.POWER
TRANSFORMER
UNIFIEDEARTHGROUND
CONNECT 16 VACPOWER FROM PLUG-INTRANSFORMER TOPOWER TERMINALS1 & 2
CONNECT A GOODEARTH GROUND TOPOWER TERMINAL 3
NOTE: DATA GROUNDTERMINAL IS USED ONLYWHEN CONNECTINGTO THE CONTROLLERTHROUGH THECONTROLLER AUXILIARYPBUS TERMINALS
PLACE THE BACKUPBATTERY IN THE CABINET
CONNECT THE RED LEAD TO BATTERY POSITIVE (+)CONNECT THE BLACK LEAD TO BATTERY NEGATIVE (-)
PRESS THE RELAYTRIGGER BUTTONSTO TEST EACH RELAYCONNECTED
THE RELAY STATUSINDICATOR WILL
LIGHT WHEN THERELAY IS ENERGIZED
CAUTION!DEVICES CONNECTED TO
THE RELAYS WILL ACTIVATE
WATCH THE LOOPSTATUS INDICATORWHILE TESTING THE LOOPS
GREEN = ALL LOOPS NORMALRED = ANY LOOP OPEN OR SHORTED
LOOP1
COM LOOP2
LOOP3
COM LOOP4
2.2K 2.2K 2.2K 2.2K
4 5 61 2 3
LOOP5
COM LOOP6
LOOP7
COM LOOP8
2.2K 2.2K 2.2K 2.2K
10 11 127 8 9
CHANNEL 2 CHANNEL 3
7 8 94 5 6
16 17 1813 14 15
N.O.CHANNEL 1
2 31
11 1210
COM N.C. N.O. COM N.C. N.O. COM N.C.
CHANNEL 5 CHANNEL 6N.O.
CHANNEL 4COM N.C. N.O. COM N.C. N.O. COM N.C.
POWER TERMINALSACIN
ACIN
EARTHGND
DATAGND
DAT1 DAT0 DVAL PCLKAUXILIARY PBUS TERMINALS
RELAY OUTPUT TERMINALS
RELAY OUTPUT TERMINALS
LOOP INPUT TERMINALS
LOOP INPUT TERMINALS
ALL LOOP INPUTS MUST BETERMINATED WITH A 2.2KEND-OF-LINE RESISTOR
CONTROLLED DEVICE "4" CONTROLLED DEVICE "5" CONTROLLED DEVICE "6"
CONTROLLED DEVICE "1" CONTROLLED DEVICE "2" CONTROLLED DEVICE "3"16 VAC, 24 VA
MINIMUMTRANSFORMER EARTH
GROUNDSTAKE
CONTROLLER PBUS TERMINALS
6 7 85
4321
POWER SUPPLYMODULE (PSM)
RELAY/LOOPMODULE (RLM)
AM-MIO RLM WIRING DIAGRAMAM-MIO PSM WIRING DIAGRAM
12 VDCBACKUPBATTERY
+ RE
D W
IRE
- BLA
CK W
IRE
NOTE: OPTIONAL AM-MIO PSM TO CONTROLLER WIRING SHOWN WHEN NOT USING THE INCLUDED CABLE
1. PROGRAM THE ACCESSCONTROL SYSTEM. BESURE TO PROGRAM THESYSTEM FOR THE DEVICEADDRESS OF EACH OF THEAM-MIO MODULES.
2. USE ENTRY CODES ORTRANSMITTERS TO TESTACTIVATE EACH OF THEAM-MIO OUTPUTS
3. TEST TO SEE IF EACH OFTHE AM-MIO LOOP INPUTS(IF USED) ARE RECOGNIZEDBY THE ACCESS CONTROLSYSTEM