©2004 Fluke Corporation Introduction to Motor Troubleshooting 1
Introduction to Motor Troubleshooting
©2004 Fluke Corporation Introduction to Motor Troubleshooting 2
Motors are the number one consumer of electrical power
©2004 Fluke Corporation Introduction to Motor Troubleshooting 3
Power consumption based on size
©2004 Fluke Corporation Introduction to Motor Troubleshooting 4
Standard motor operating conditions
©2004 Fluke Corporation Introduction to Motor Troubleshooting 5
Special purpose motor operating conditions
©2004 Fluke Corporation Introduction to Motor Troubleshooting 6
Motor failure
©2004 Fluke Corporation Introduction to Motor Troubleshooting 7
Troubleshooting fuses
©2004 Fluke Corporation Introduction to Motor Troubleshooting 8
Taking motor voltage measurements
©2004 Fluke Corporation Introduction to Motor Troubleshooting 9
Measuring motor voltage unbalance
©2004 Fluke Corporation Introduction to Motor Troubleshooting 10
Measuring motor control circuit transformer
©2004 Fluke Corporation Introduction to Motor Troubleshooting 11
Measuring motor current
©2004 Fluke Corporation Introduction to Motor Troubleshooting 12
Measuring temperature
©2004 Fluke Corporation Introduction to Motor Troubleshooting 13
Measuring motor insulation
©2004 Fluke Corporation Introduction to Motor Troubleshooting 14
Megohmmeter reading interpretation
©2004 Fluke Corporation Introduction to Motor Troubleshooting 15
Motor power measurements
©2004 Fluke Corporation Introduction to Motor Troubleshooting 16
Testing motor capacitors
©2004 Fluke Corporation Introduction to Motor Troubleshooting 17
Electrical measurements on adjustable speed drives
©2004 Fluke Corporation Introduction to Motor Troubleshooting 18
• Voltage ratings
• Category ratings
• Safe practices• De-energize circuits
• Use protective gear
• Do not exceed instrument voltage and category ratings
• Use 3-point test method
• Test known live circuit
• Test target circuit
• Test known live circuit again
• Avoid holding the meter
Measurementcategory
Working voltage(dc or ac-rms to gnd)
Peak impulse transient
(20 repetitions)
Test source(Ohm = V/A)
CAT I 600V 2500V 30 ohm source
CAT I 1000V 4000V 30 ohm source
CAT II 600V 4000V 12 ohm source
CAT II 1000V 6000V 12 ohm source
CAT III 600V 6000V 2 ohm source
CAT III 1000V 8000V 2 ohm source
CAT IV 600V 8000V 2 ohm source
Making safe measurements
©2004 Fluke Corporation Introduction to Motor Troubleshooting 19
Adjustable speed drive – theory
©2004 Fluke Corporation Introduction to Motor Troubleshooting 20
Theory of operation• DC converter section supplies constant DC level
• Rms motor voltage is varied by the width of the PWM pulse
• Motor drive signal frequency is controlled by the modulation frequency
Pulse-width modulated inverter
©2004 Fluke Corporation Introduction to Motor Troubleshooting 21
Motors – measurement 1: Low voltage
Low voltages• Check for voltage drops across connectors, or
• Check for heated connections
Analog meters• Reads the average voltage of the modulation frequency of
the PWM drive
• Meter may not have IEC-61010 safety rating
Digital multimeter• Current DMMS read higher than analog meter on PWM
drives because they responding to the entire frequency spectrum of the drive signal.
• These DMM are not giving inaccurate readings.
• Exception: New DMMs that include low-pass filters
©2004 Fluke Corporation Introduction to Motor Troubleshooting 22
Motors – measurement 1: Low voltage
Using the ASD display 230 volts (calculated)
Using a true-rms meter 247 volts 20 KHz B/W
Using an averaging meter 230 volts @ 5KHz B/W
Using a voltage tester 227 volts @ 400 Hz B/W
Using an oscilloscope 255 (avg) volts @ 20MHz B/W
Using a power 253 (avg) volts @ 20MHz B/Wquality analyzer 243 volts @ 3KHz B/W
226 volts @ 60 Hz
Using an analog meter 223 volts @ 100 Hz
©2004 Fluke Corporation Introduction to Motor Troubleshooting 23
Max. Deviation (V or I)% (V or I) Imbalance = X 100
Average (V or I)
449 470+462 1381
1381 = 460 3
11 X 100 = 2.39 % 460
For example:
Motors - measurement 2:Voltage & current unbalance
• Check for voltage unbalance (< 2 %) first, then
• Check for current unbalance (< 10 %)
1 2 3
©2004 Fluke Corporation Introduction to Motor Troubleshooting 24
Normal PWM waveform
PWM waveform with reflected voltages
Leading edge of normal PWM pulse
Leading edge of PWM pulse with reflected voltage (ringing)
PWM drives – measurement 3:Overvoltage reflections at the motor terminals
©2004 Fluke Corporation Introduction to Motor Troubleshooting 25
PWM drives – measurement 3:Overvoltage reflections at the motor terminals
Overvoltage reflections at the motor terminals.
• Damages the motor windings
• Shorten cable if possible
• If motor is worth repairing, consider rewinding with better insulated wire such as TZ Q (by Phelps Dodge)
• If new motor is required, use one that meets NEMA MG1-1993 Part 31 specifications (can tolerate sustained voltage peaks of 1600 V and rise times >100 ns)
• Use filtering if none of the above is feasible
• Try to mitigate overvoltages to <900 V for standard motors
©2004 Fluke Corporation Introduction to Motor Troubleshooting 26
Possible remedies for overvoltage reflections
PWM drives – measurement 3:Overvoltage reflections at the motor terminals
©2004 Fluke Corporation Introduction to Motor Troubleshooting 27
PWM drives – measurement 4:Motor shaft voltages
Bearing currents: occur when shaft voltagesexceed insulating capability of the grease
• Higher breakdown voltages of 8 -15 V occur due tothe fast edge of the PWM pulse
• First signs of this problem = noise and overheating caused by pitting and loosened metal fragments
• Use an oscilloscope to view shaft voltages measured between the motor shaft and the grounded frame using stranded wire or a carbon brush
©2004 Fluke Corporation Introduction to Motor Troubleshooting 28
Bearing currents: occur when shaft voltagesexceed insulating capability of the grease
• Make the measurement after the motor has heated up
• Simplest solution is to lower the carrier frequency to less than 10 kHz, or down to 4 kHz if possible
• Shaft grounding devices, bearing insulation, faraday shield in the motor, conductive grease or filtering between the ASD and the motor
PWM drives – measurement 4:Motor shaft voltages
©2004 Fluke Corporation Introduction to Motor Troubleshooting 29
Bearing currents: occur when shaft voltagesexceed insulating capability of the grease
• Make the measurement after the motor has heated up
• Simplest solution is to lower the carrier frequency to less than 10 kHz, or down to 4 kHz if possible
• Shaft grounding devices, bearing insulation, faraday shield in the motor, conductive grease or filtering between the ASD and the motor
PWM drives – measurement 4:Motor shaft voltages
©2004 Fluke Corporation Introduction to Motor Troubleshooting 30
PWM drives – measurement 5:Leakage currents (common mode noise)
• Leakage currents flow in capacitive coupling between the stator windings and frame ground. The faster rise times and switching frequencies of the PWM pulse can increase leakage
• Interferes with 4-20 ma control signals and PLC communications
• Increased leakage currents pose potential safety problems and may cause ground fault protection relays to trip
©2004 Fluke Corporation Introduction to Motor Troubleshooting 31
• To measure, place current clamp around all three motor conductors at the inverter output
• Use an oscilloscope to examine the CMN waveform
• Possible solutions: special EMI suppression cables, isolation transformers on the line input, or a common mode choke
PWM drives – measurement 5:Leakage currents (common mode noise)
©2004 Fluke Corporation Introduction to Motor Troubleshooting 32
PWM drives – measurement 6:Testing the IGBT output waveshape
1. Connect the scope common lead to the dc+ bus and measure each of the three phases at the inverter’s motor output terminals.
Check for clean-edged square waves with no visible pulse noise.
Verify that all three phases have the same appearance.
2. Check the negative conducting IGBTs by connecting the common lead to the dc- bus and performing step 1 on each phases at the inverter’s motor output terminals.
©2004 Fluke Corporation Introduction to Motor Troubleshooting 33
PWM drives – measurement 7:Testing the IGBT outputs for leakage
• Measure voltage from earth ground to the inverter’s motor output terminals with the drive powered on and speed set to zero (motor stopped).
• If leaky, the voltage will be elevated 3 or 4 times normal.
• Perform this measurement on a known good drive to determine what is normal for that drive.
©2004 Fluke Corporation Introduction to Motor Troubleshooting 34
PWM drives – measurement 8:ASD “trip” problems – overloading
Cause of overloading = too much motor current
• Verify motor load is not causing the problem
• Check for excessive current unbalance (possible shorted phase windings)
• Verify ASD trip points are set correctly
• Is dc bus voltage being regulated properly? • Leaky capacitors
(too much ripple, too little inrush current)
• Link inductor OK? (waveform different or same on both sides?)
©2004 Fluke Corporation Introduction to Motor Troubleshooting 35
PWM drives – measurement 9:ASD “trip” problems – overvoltage
• Check for high line voltage and/or long term variations
• Check for line transients• Lightening protection in place?
• Proper wiring and grounding?
• Isolation from transient producing loads?
• Verify ASD trip points are set correctly
• Is load regenerative (cranes, elevators)? If so, is dynamic braking installed and working properly?
• Is dc bus voltage being regulated properly?• Leaky capacitors (too much ripple, too little inrush current)
• Link inductor OK? (waveform different or same on both sides?)
©2004 Fluke Corporation Introduction to Motor Troubleshooting 36
Overvoltage transient capture with a power quality analyzer.
PWM drives – measurement 9:ASD “trip” problems – overvoltage
©2004 Fluke Corporation Introduction to Motor Troubleshooting 37
PWM drives – measurement 10:ASD “trip” problems – undervoltage
• Check for low line voltage and/or long term variations
• Verify ASD trip points are set correctly
• Is dc bus voltage being regulated properly (dc link capacitors and/or reactor)
• Check for voltage sags
©2004 Fluke Corporation Introduction to Motor Troubleshooting 38
Check for flat topping of the input voltage
PWM drives – measurement 10:ASD “trip” problems – undervoltage
©2004 Fluke Corporation Introduction to Motor Troubleshooting 39
Check for VTHD < 5 % at the point of common coupling (PCC), not the ASD
Check power factor. Utilities may start charging for distortion power factor.
Check for ITHD < ? % at PCC, not the ASD (% depends on short circuit current ratio of PCC)
PWM drives – bonus measurement:ASDs and IEEE-519 measurements
©2004 Fluke Corporation Introduction to Motor Troubleshooting 40
Series resonant tuned LC shunt filter.
Series resonant tuned LC shunt filter with series line reactor.
PQ troubleshooting: Transformer solutions – Three phase filter traps
©2004 Fluke Corporation Introduction to Motor Troubleshooting 41
• Samples load current for harmonic content
• Generates harmonic frequenciesdemanded by load
• Source supplies 60 Hz only
• Current distortions typically less than 5 %
PQ troubleshooting solutions: Active harmonic compensation devices
©2004 Fluke Corporation Introduction to Motor Troubleshooting 42