Reply to Comments on 11KV KIOSK PANEL
Document ID IKE-KPR-KIOSK-RPL-001 Revision 00
Ref. Doc. Email dated 07.06.12 regarding Comments on 11KV
KIOSK PANEL
Sheet 1 of 1
Project: M/s KPR SUGAR MILL LTD. (30MW COGEN PLANT)
Prepared by: Yusuf S Checked By: Kamlakar D Approved By: ABH 03.07.12
1. As per contract kindly indicate the below specifications in drawing:a. Highest System Voltage: 12 kV
IKE REPLY: Noted & the same has been indicated in revised drawings (attached)
b. One minute Power Frequency Withstand voltage : 35 kV(rms)IKE REPLY: Noted & the same has been indicated in revised drawings (attached)
c. 1.2/50 micro second impulse: 95 kV (peak)IKE REPLY: Noted & the same has been indicated in revised drawings (attached)
d. Operating Duty: O-0.3s-CO-3 min-COIKE REPLY: Noted & the same has been indicated in revised drawings (attached)
e. Dynamic Rating: 100 kA
IKE REPLY: Noted & the same has been indicated in revised drawings (attached)
f. Rated short circuit making capacity: 100 kAIKE REPLY: Noted & the same has been indicated in revised drawings (attached)
g. DC current & Decay: 18.1 kA at specified breaker opening time
IKE REPLY: Please refer the Attached type test report for exact value of close/opening and other particulars. Theabove technical values as per type test report, Megawin will not provide dc decay-18.1KA (% of DC componentat contact separation is 37%)
h. Pole Parting Time in ms: Not less than 75 ms, by providing suitable electronic valve in breaker mechanism.
IKE Reply: Pole part time is not applicable and there is no electronic valve in Megawins type tested design. Allparameters are as per type tested design hence Megawin is not able to change the type test parameters.
Closing time less than 5 Cycles Opening time less than 4 cycles
2. Incoming and outgoing busbar size (3150A) shall be mentioned. Kindly revise.IKE Reply: Noted & the same has been indicated in revised drawings (attached)
3. Bill of materials shall be submitted.IKE Reply: Noted & the same has been indicated in revised drawings (attached)
4. Kindly furnish the type test certificates for its temperature rise and short time rating for CT for our review/records.IKE Reply: Noted & the same has been indicated in revised drawings (attached).
5. Please note that all final inspection tests shall be witnessed by the client/consultant. Kindly take care the same in theQAP.IKE Reply: Noted.
(We are also attaching the email received from Megawin for authenticity of above reply)
7/29/2019 11kv Kiosk 1kpr.doc
2/26
7/29/2019 11kv Kiosk 1kpr.doc
3/26
7/29/2019 11kv Kiosk 1kpr.doc
4/26
7/29/2019 11kv Kiosk 1kpr.doc
5/26
7/29/2019 11kv Kiosk 1kpr.doc
6/26
7/29/2019 11kv Kiosk 1kpr.doc
7/26
7/29/2019 11kv Kiosk 1kpr.doc
8/26
7/29/2019 11kv Kiosk 1kpr.doc
9/26
7/29/2019 11kv Kiosk 1kpr.doc
10/26
7/29/2019 11kv Kiosk 1kpr.doc
11/26
7/29/2019 11kv Kiosk 1kpr.doc
12/26
Megawin
Switchgear-P-Ltd.
BUS BAR SIZING
CALCULATION FOR
CONTINOUS CURRENT
RATING
Ref. No: MWSG / IKE/GR
Issue No: 01, Dt: 15.05.12
Revision No: R0
Page 1 of 1
CUSTOMER: M/s. IKE ELECTRIC, PUNEPROJECT: KPR SUGARS, KARNATAKA
BUSBAR SIZING CALCULATION FOR AMPERE RATING: 3150A
Specified continuous current rating of the bus bars: 3150A
Max. Permissible current density for Aluminum bus bars:1.0A/Sq.mm
Required area of cross section of Aluminum bus bars for the above: 3150A/1.0
= 3150 Sq.mm
Cross section of the Aluminum bus bar selected for the panel: 120mmX10mmX3 Runs
Area of cross section: 3600 Sq mm
Thus, FLAT type of aluminum bus bar 120mmX10mmX3 Runs is adequate for the continuous current
rating of Main Bus Bar.
7/29/2019 11kv Kiosk 1kpr.doc
13/26
Megawin
Switchgear-P-Ltd.
11KV/40KA/3SEC Short
circuit current Calculation
for single Panel VCB switch
board.
Ref. No: MWSG / IKE/GR
Issue No: 01, Dt: 15.05.12
Revision No: R0
Page 1 of 1
CUSTOMER: M/s. IKE ELECTRIC, PUNEPROJECT: KPR SUGARS, KARNATAKA.CALCULATION FOR SHORT CIRCUIT CURRENT CARRYING CAPACITY FOR BUS BARS
Specified short circuit current rating of the bus bars : 40KA
Specified duration of the short circuit current : 3 second
As per IS 3427 - 1997 we calculate the cross section of bare conductor necessary to withstand thethermal stresses due to short circuit currents with specified duration.
S = (I/)))) (t /))))Where,S is the cross section expressed in Sq.mm.
is expressed in A/mm2 (s / K)
and has the following values:
13 For Copper
8.5 For Aluminum
4.5 For Iron
2.5 For Lead
t is the time, expressed in seconds.
is the temperature rise, expressed in Kelvins (K): for bare conductors, it is normally 180K.Calculation for Main Bus bar
Substitute the values S = (40000 / 8.5) (3/180)Reqd. cross section S = 607.5 Sq.mm
Hence the selected cross section is more than the required cross section of main bus bar, which is
3600 Sq mm
7/29/2019 11kv Kiosk 1kpr.doc
14/26
7/29/2019 11kv Kiosk 1kpr.doc
15/26
7/29/2019 11kv Kiosk 1kpr.doc
16/26
7/29/2019 11kv Kiosk 1kpr.doc
17/26
7/29/2019 11kv Kiosk 1kpr.doc
18/26
7/29/2019 11kv Kiosk 1kpr.doc
19/26
7/29/2019 11kv Kiosk 1kpr.doc
20/26
7/29/2019 11kv Kiosk 1kpr.doc
21/26
7/29/2019 11kv Kiosk 1kpr.doc
22/26
7/29/2019 11kv Kiosk 1kpr.doc
23/26
7/29/2019 11kv Kiosk 1kpr.doc
24/26
7/29/2019 11kv Kiosk 1kpr.doc
25/26
7/29/2019 11kv Kiosk 1kpr.doc
26/26
Recommended