Corona effect

Embed Size (px)

Citation preview

Corona Effect in Transmission Lines

Corona Effect

in transmission lines

Presented to Dr. Amlak

1

What is Corona Discharge? Corona discharge is a process by which a current flows in a conductor with a highpotentialinto a neutral fluid, usually air, byionizing that fluid so as to create a region ofplasmaaround the Conductor.The ions generated passchargeto nearby areas of lower potential, or recombine to form neutral gas molecules.When the potential(electric field) is large enough (33 KV =disruptive potential gradient) the air ionizes (1 Cm) and it becomes conductive.

HV

the ionized region continues to grow until it reaches another conductor at a lower potential, a low resistance conductive path between the two will be formed, resulting in anelectric arc, then a faint luminous glow of violet color appears together along with hissing noise. This phenomenon is called corona.

WeldingCircuit breaker arcreal videoApplicationOf electric arc

Problem?!!

Which factors affect Corona? Conductor: Corona Effect is considerably affected by the shape, size and surface conditions of the conductor. Corona Effect decreases with increases in the size of the conductor, this effect is less for the conductors having round conductors compared to flat conductors.

Line Voltage: Corona Discharge effect is not present when the applied line voltages are less. When the Voltage of the system increases corona Effect will be more.

Atmosphere: Breakdown voltage directly proportional to the density of the atmosphere present in between the power conductors. In a stormy weather the ions present around the conductor is higher than normal weather condition.

Spacing between the Conductors: Electro static stresses are reduced with increase in the spacing between the conductors. Corona Discharge Effect takes place at much higher voltage when the distance between the power conductors increases.

How to reduce Corona ?By increasing the spacing between the conductors: Corona Discharge Effect can be reduced by increasing the clearance spacing between the phases of the transmission lines. However increase in the phases results in heavier metal supports. Cost and Space requirement increases.By increasing the diameter of the conductor: Diameter of the conductor can be increased to reduce the corona discharge effect. By using hollow conductors corona discharge effect can be improved.By using Bundled Conductors: By using Bundled Conductors also corona effect can be reduced this is because bundled conductors will have much higher effective diameter compared to the normal conductors.By Using Corona Rings or Grading Rings:Corona Rings or Grading Rings are present on the surge arresters to equally distribute the potential along the Surge Arresters or Lightning Arresters which are present near the Substation and in the Transmission lines.

AdvantagesDue to the corona formation, the air surrounding the conductor becomes conducting and hence the virtual diameter of the conductor is increased , The increased diameter decreases the electro static stresses between the conductors .Corona reduces the effects of transients voltages.

DisadvantagesCorona is accomplished by a loss of energy, This affects the transmission efficiency of the line.Ozone is produced by corona and may cause corrosion of the conductor due to chemical action.The current drawn by the line due to corona is non-sinusoidal and hence non-sinusoidal voltage drop occurs in the line ,This may cause inductive interference with neighboring communication lines.