63
Fire fighting system Summary Part 1 l Purpose l What is a Fire ? l Type of Fire Protection l Type of Fire Detection Part 2 l Fire Equipment Description for RADES l Procedures in Case of Fire

Fire Fighting

Embed Size (px)

DESCRIPTION

yangınla mücadele

Citation preview

Page 1: Fire Fighting

Fire fighting system

SummaryPart 1l Purposel What is a Fire ?l Type of Fire Protectionl Type of Fire Detection

Part 2l Fire Equipment Description for RADESl Procedures in Case of Fire

Page 2: Fire Fighting

Fire fighting system

Why fire fighting system is provided ?

l To protect people against fire

l To save major equipment

l To reduce the damages done by the fire

l To help firemen fight the fire

Purpose

Page 3: Fire Fighting

Fire fighting system

Fire engineering

l Fire Risk Area

l Fire Risk Analysis

l Fire Regulations

l Fire Detection & Protection Systems

Purpose

Page 4: Fire Fighting

Fire fighting system

Fire development

ignition source

oxygen fuel

fire

What is a fire ?

Page 5: Fire Fighting

Fire fighting system

Fire classes (according to NFPA)

l Class A : Paper, wood

l Class B : Oil, gasoline

l Class C : Hydrogen, Methane

l Class D : Special metal

l Class E : Electrical fire

What is a fire ?

Page 6: Fire Fighting

Fire fighting system

Control the Fire

oxygen fuel

no fire

Type of fire protection

Page 7: Fire Fighting

Fire fighting system

Control the fire

fuel

no fire

ignition source

Type of fire protection

Page 8: Fire Fighting

Fire fighting system

Type of extinguishing

l Class A : Water, Foam, Dry powder

l Class B : Dry powder, CO2

l Class C : Dry powder

l Class D : Not applicable

l Class E : Dry powder, CO2

Type of fire protection

Page 9: Fire Fighting

Fire fighting system

Several stages of the fire

l Invisible smoke / Gas

l Visible smoke

l Heat

l Flame

Type of fire detection

Page 10: Fire Fighting

Fire fighting system

Fire alarm control panel

l Detect a Fire

l Give a Visual & Audible Alarm

l Shut off the Air Conditioning (Interlock)

l Actuate the Automatic Extinguishing System

l Inform Firemen

Type of fire detection

Page 11: Fire Fighting

Fire fighting system

Questions ?

l Fire without oxygen is possible YES or NO

l Which is fire class for paper _________

l Which is fire class for hydrogen _________

l Water can extinguish fire class B YES or NO

l Dry powder can be use for all class YES or NO

l Flame is the last stage of the fire YES or NO

Page 12: Fire Fighting

Fire fighting system

ÇAN combined cycle

fire fighting system

Page 13: Fire Fighting

FIRE FIGHTING WATER SUPPLIES (KKS Code SGA)

6. FIRE FIGHTING PUMPING STATION

The fire fighting water pumps are arranged in Raw water PumpStation with a Raw Water Basin partitioned in two different bays of5000 m3 each and accessible from the outside.The fire water Pump station shall be complete of Fire PumpControllers ,Fuel Oil Tank and Air pressure maintenance device.The water pressure within the firewater loop system is maintainedby 2 (one plus stand-by)separate pressure maintenance pump(jockey pump unit).

6.1 JOCKEY PUMPS- Quantity: 2 (one + stand-by)- pump location: Raw water pump house- design flow: 20 m3/hr- design total head: 100 m- Submergence min : 1m*

When the header pressure drops in the fire water main, due toopening hydrants for example, the electrical fire pump (or diesel firepump in case of electric fire pump failure) automatically starts upand supplies the required pressure and water quantity.

6.2 ELECTRICAL DRIVEN FIRE WATER PUMP

- Electrical driven fire water pump: 1 x 100 %- pump location: Raw Water pumphouse- design flow: 264 m3/hr- design total head: 97 m- NFPA 20 Rating: 1250 GPM *- power shaft: 140 kW- Submergence min: 1m

6.3 DIESEL ENGINE DRIVEN FIRE WATER PUMP

- Diesel Engine Driven Fire Water Pump : 1 x 100%- pump location: Raw water Pumphouse- design flow: 264 m3/hr- design total head: 97 m- NFPA 20 Rating: 1250 GPM *- power shaft: 140 kW- Submergence min: 1m

The start-up of the fire pump activates an alarm at the main fire control unitlocated in the Main Fire Alarm Control Panel in control room. When the firepump(s) is no longer needed, it must be manually switched off.

Page 14: Fire Fighting

c:/temp/inps/cnk-jpd001.pid Aug. 06, 2002 14:49:52

Page 15: Fire Fighting
Page 16: Fire Fighting
Page 17: Fire Fighting
Page 18: Fire Fighting
Page 19: Fire Fighting

c:/temp/inps/cnk-jpdpf1.pid Dec. 18, 2002 14:48:51

Page 20: Fire Fighting

Hydrants

General

Hydrants shall be located along the fire main according to the following criteria:• spacing at a maximum distance of 75 mt• Minimum distance from the building:12 mt

Hydrant Cabinets in Defined areas

Hydrant cabinets shall be provided enclosing in loop the following buildings :

• B01 Boiler• B03 Turbine Hall• G17 Auxiliary Boiler• Dike of the Fuel Oil Daily Tank• Dike of the Fuel Oil Storage Tanks:C01 and C02• C03 Fuel oil pumping Station

Page 21: Fire Fighting

9.5

SEE PAGE 9.24 FOR ORDERING INSTRUCTIONS

MUELLER Super Centurion Fire Hydrant Parts

Cat.part#

Description Material Materialstandard

A-1 Operating nut Bronze ASTM B584A-2 Weather cap (not shown; used only on pre-1988 models) Cast iron ASTM A126 CL.BA-3 Hold down nut O-ring Rubber ASTM D2000 BUNA NA-4 Hold down nut (not shown; used only on pre-1988 models) Bronze ASTM B584A-5 Bonnet O-ring Rubber ASTM D2000 BUNA NA-6 Anti-friction washer CelconA-7 Oil plug Brass ASTM B16A-8 Bonnet Cast iron ASTM A126 CL.BA-9 Bonnet bolt and nut Steel ASTM A307 PlatedA-10 Bonnet O-ring (1997 and newer 3-way models; all pre-

1997 models and 1-way and 2-way models have flat gasket)Rubber ASTM D2000 BUNA N

A-11 Upper stem Steel ASTM A576 GR.BA-12 Stem O-ring Rubber ASTM D2000 BUNA NA-13 Nozzle lock Stainless steel ASTM A276A-14 Pumper nozzle Bronze ASTM B584A-15 Pumper nozzle gasket Rubber ASTM D2000 NeopreneA-16 Pumper nozzle O-ring Rubber ASTM D2000 BUNA NA-17 Pumper nozzle cap Cast iron ASTM A126 CL.BA-18 Hose nozzle Bronze ASTM B584A-19 Hose nozzle gasket Rubber ASTM D2000 NeopreneA-20 Hose nozzle O-ring Rubber ASTM D2000 BUNA NA-21 Hose nozzle cap Cast iron ASTM A126 CL.BA-22 Cap chain Steel PlatedA-23 Chain ring Steel PlatedA-24 Upper barrel less nozzles Cast iron ASTM A126 CL.BA-25 Safety coupling Stainless steel ASTM A890A-26 Safety flange bolt and nut Steel ASTM A307 PlatedA-27 Safety flange O-ring (1997 and newer models;

pre-1997 models have flat gasket)Rubber ASTM D2000 BUNA N

A-28 Safety flange Cast iron ASTM A126 CL.BA-29 Cotter pin Stainless steel ASTM A276A-30 Clevis pin Stainless steel ASTM A276A-31 Lower stem Steel ASTM A576 GR.BA-32 Lower barrel Cast iron ASTM A126 CL.BA-33 Stem pin Stainless steel ASTM A276A-34 Drain valve facing PlasticA-35 Drain valve screw Stainless steel ASTM A276A-36 Upper valve plate (includes A-34 and A-35) Bronze ASTM B584A-37 Shoe bolt and nut Steel ASTM A307 PlatedA-38 Drain ring housing O-ring (1997 and newer models;

pre-1997 models have square gasket)Rubber ASTM D2000 BUNA N

A-39 Seat ring top O-ring Rubber ASTM D2000 BUNA NA-40 Drain ring housing Cast iron ASTM A126 CL.BA-41 Drain ring housing bolt and nut (not shown; used only

on pre-1997 model hydrants)Steel ASTM A307 Plated

A-42 Drain ring Bronze ASTM B584A-43 Seat ring Bronze ASTM B584A-44 Seat ring bottom O-ring Rubber ASTM D2000 BUNA NA-45* Reversible main valve (1997 and newer models only; pre-

1997 models use non-reversible main valve and lower valveplate - not shown)

Rubber ASTM D2000

A-46 Lower valve plate (1997 and newer models forreversible main valve; pre-1997 models have non-reversible main valve - not shown)

Cast iron ASTM A126 CL.B

A-47 Cap nut seal Rubber ASTM D2000A-48 Lock washer Stainless steel ASTM A276A-49 Lower valve plate nut Cast iron ASTM A126 CL.BA-50 Shoe** Cast iron ASTM A126 CL. BA-84 Hold down nut Bronze ASTM B584A-85 Weather sealA-51 10.5 oz. hydrant lubricating oil (not shown)

Rubber ASTM D2000

MUELLER® SUPER CENTURION®

FIRE HYDRANT PARTS

* Pre-1997 models may be upgraded to use the reversible main valve by also replacing the lowervalve plate with the 1997 model.

** 6" MJ shoe is Ductile Iron, ASTM A536 Grade 65-45-12.

Rev. 12-01

Page 22: Fire Fighting

7.1 DELUGE WATER SYSTEMS (KKS Code :SGC)

The deluge systems shall adopt "High velocity water spray nozzles".

7.1.1 Main and Unit Transformers

The transformers to be protected shall be:

• No. 2 Main Transformer of 200 MVA each• No. 2 Unit Transformer of 40 MVA each

7.1.2 Coal Mills in the Crusher House

The Coal Mills in the Crusher House to be protected shall be:

• Coal Mill in C52 Primary Crusher house• Coal Mill in C53 Secondary Crusher house• Coal Mill in C54 Tertiary Crusher house

Page 23: Fire Fighting
Page 24: Fire Fighting
Page 25: Fire Fighting

Fire &Security

Wormald

Commessa/Job: 20290Doc. No. : SHSH4236Rev. : 1Fg./Sh. : 16 di/of 53

DV.SGQ 13 - 21.02.00

FIGURE 1

DELUGE VALVE ASSEMBLY

Page 26: Fire Fighting

ential applied through the Clapper Latch which holds the Clapper down in the set position is reduced to below the valve trip point.

NOTE Consult with the Authority Having Jurisdiction regarding installation criteria pertaining to electric actua- tion circuitry.

The Model F470 Multimatic Deluge Valve is a differential latch type valve which depends upon water pressure in the Diaphragm Chamber (Ref. Figure C-l) to hold the Clapper closed against the water supply pressure. The nominal trip ratio is 2.5 to 1, i.e., the F470 Valve operates (opens) when the pressure in the Diaphragm Chamber is reduced to approximately 40 percent of the water supply pressure.

When the F470 Valve is set for service, the Diaphragm Chamber is pressur- ized through the trim connections from the inlet side of the system’s main con- trol valve, for example an O.S.&Y. gate valve or butterfly valve (Ref. Figure G-l, G-2, or G-3). Opening of an actu- ation device, for example the solenoid valve in the Electric Actuation Trim (Ref. Fig. G-3), releases water from the Diaphragm Chamber faster than it can be replenished through the l/8 inch (3,2mm) Restriction in the Dia- phragm Chamber Supply Connection. This results in a rapid pressure drop in the Diaphragm Chamber and the force differential applied through the Clap- per Latch to hold the Clapper down in the set position is reduced to below the valve trip point. The water supply pres- sure then forces the Clapper open per- mitting water to flow into the system piping, as well as through the Alarm Port to actuate the system alarms (Ref. Figure C-2).

When the system main control valve is closed to stop waterflow into the sys- tem, the Clapper will be prevented from resetting by the Clapper Latch until the Rest Knob is pushed inward (Ref. Figure C-3). Pushing the Reset Knob inward will temporarily reposition the Clapper Latch away from the wa- terway and allows the Clapper to drop into the seated position.

TO SYSTEM

WATER SUPPLY

- Set Position - Figure C-l

TO SYSTEM

UP

z

z’ ALARM PORT

WATER ‘SUPPLY

- Open Position (Flowing)- Figure C-2

TO SYSTEM I I

WATER ‘SUPPLY

- Open Position (No Flow)- Figure C-3

FIGURE C MODEL F470 EXTERNAL RESETTING MULTIMATIC DELUGE VALVE

- SET AND OPEN POSITIONS -

-6-

Page 27: Fire Fighting
Page 28: Fire Fighting
Page 29: Fire Fighting
Page 30: Fire Fighting
Page 31: Fire Fighting
Page 32: Fire Fighting

SOLENOID VALVE (FOR ELECTRIC

DIAPHRAGM CHAMBER SUPPLY

Left View Front View

* MINIMUM CLEARANCE,

Nominal Installation Dimensions in Inches and (MM)

B C D E F G H J K

8.69 14.25 13.69 19.00 (220,7) (362,0) (347,7) (462,6) (15&‘) (l%;) (~~~) (lk$, (%?5)

6.69 15.12 14.50 20.00 5.50 7.62 8.88 8.56 6.31 (220,7) (384,0) (368,3) (508,O) (139,7) (193,5) (225,6) (217,4) (160,3)

FIGURE D NOMINAL INSTALLATION DIMENSIONS FOR

WET PILOT ACTUATION TRIM OR ELECTRIC ACTUATION TRIM

ADDITIONAL 2’ (50mm) RECOMMENDED

NOTES Proper operation of the Model F470 Multimatic Deluge Valves depends upon their trim being installed in ac- cordance with the instructions given in this Technical Data Sheet. Failure to follow the appropriate trim dia- gram may prevent the F470 Valve from fintioning properly, as well as void listings, approvals, and the manufacturer$ warranties.

The F470 Valve must be installed in a readily visable and accessible loca- tion.

The F470 Valve, associated trim, and wet pilot lines must be maintained at a minimum temperature of 4O”F/4”C.

Heat tracing of the F470 Valve or its associated trim is not permitted. Heat

tracing can result in the formation of hardened mineral deposits which are capable of preventing proper opera- tion.

The Model F470 Multimatic Deluge Valve is to be installed in accordance with the following criteria:

1 a. Flange mounting fasteners are to be tightened uniformly using a cross- draw sequence. Fastener specifica- tions are to be as required by the authority having jurisdiction. Tight- ening torques are to be as indicated below.

Valve Fastener Torque Size Size Ft. Lbs. (Nm)

4” 5/8” (M16) 40-50 (54-68) 6” 314” (M20) 50-65 (68-81)

lb. All nipples, fittings, and devices must be clean and free of scale and burrs before installation. Use pipe

-7-

thread sealant sparingly on male pipe threads only.

NOTE It is recommended that internally galvanized pipe and cast iron fit- tings be used for wet or dry pilot lines.

2. The F470 Valve must be trimmed in accordance with Figures F-l & F-2.

3. Care must be taken to make sure that check valves, strainers, globe valves, etc. are installed with the flow arrows in the proper direction.

4. Drain tubing to the drip funnel must be installed with smooth bends that will not restrict flow.

5. The main drain and drip funnel drain may be interconnected provided a check valve is located at least 12

Page 33: Fire Fighting

Fire &Security

Wormald

Commessa/Job: 20290Doc. No. : SHSH4236Rev. : 1Fg./Sh. : 17 di/of 53

DV.SGQ 13 - 21.02.00

FIGURE 2

DELUGE VALVE WITH PNEUMATIC DETECTION

Page 34: Fire Fighting
Page 35: Fire Fighting
Page 36: Fire Fighting

Fire &Security

Wormald

Commessa/Job: 20290Doc. No. : SHSH4236Rev. : 1Fg./Sh. : 35 di/of 53

DV.SGQ 13 - 21.02.00

FIGURE 3PREACTION SYSTEM

T O L F C P

AIR

MA

INT

EN

AN

CE

DE

VIC

E

A I R S U P P L Y

L E G E N D :

DRAIN

W A T E R S U P P L Y

V A L V E C L O S E D V A L V E O P E N I N S T R U M E N T W I T H O U T P R E S S U R EI N S T R U M E N T I N P R E S S U R E

D R A I N

Page 37: Fire Fighting

-B

-I

, DRY PILOT ACTUATOR

DIAPHRAGM CHAMBER SUPPL

112” NPT AIR SUPPLY ’ (FROM AbTOMATlC

AIR/NITROGEN MAINTENANCE DEVICE)

2” NPT. DRAIN

Left View Front View

Nominal Installation Dimensions in Inches and (MM)

FIGURE E NOMINAL INSTALLATION DIMENSIONS FOR

DRY PILOT ACTUATION TRIM

* MINIMUM CLEARANCE, ADDITIONAL 2’ (50mm) RECOMMENDED

inches (300 mm) below the drip fun- nel.

6. Suitable provision must be made for disposal of drain water. Drainage water must be directed such that it will not cause accidental damage to property or danger to persons.

7. Connect the Diaphragm Chamber Supply Control Valve to the inlet side of the system’s main control valve in order to facilitate setting of the F470 Valve (Ref. G-l, G-2, or G-3).

8. An Inspector’s Test Connection, as described in the Technical Data sec- tion, must be provided for Wet or Dry Pilot Actuation systems.

9. An Air Maintenance Device, as de- scribed in the Technical Data Sec- tion, must be provided for Dry Pilot Actuation.

10. Adesiccant dryer, when specified for Dry Pilot Actuation, is to be installed between a drip leg and the Air Main- tenance Device.

11. The Low Pressure Alarm Switch for Dry Pilot Actuation is to be adjusted as follows:

. Low pressure alarm setting at approximately 6 psi (0,4 bar) below the minimum pilot line service pressure requirement shown in Graph C.

. Fire alarm setting at approxi- mately 15 psi (1 ,O bar) below the minimum pilot line service pressure requirement shown in Graph C.

-8-

Page 38: Fire Fighting

Fire &Security

Wormald

Commessa/Job: 20290Doc. No. : SHSH4236Rev. : 1Fg./Sh. : 47 di/of 53

DV.SGQ 13 - 21.02.00

2.6.0 FOAM SYSTEM

2.6.1 HAZARDS PROTECTED

The following hazards shall be protected by automatic water-foam(low expansion ) system :

• 09SGF01 Automatic Water Foam Protection on Heavy Fuel Oil Tank C01• 09SGF02 Automatic Water Foam Protection on Light Fuel Oil Tank C02• 09SGF03 Automatic Water Foam Protection on Fuel Oil Pumping Station C03• 09SGF08 Automatic Water Foam Protection on Fuel Oil Pumping Station C03• 09SGF04 Automatic Water Foam Protection on Fuel Oil Unloading Terminal• 09SGF05 Automatic Water Foam Protection on Fuel Oil Daily Tank C01• 09SGF10 Automatic Water spray system of B03 Lube Oil System unit in Turbine

Hall Unit 1• 09SGF11 Automatic Water spray system of B03 Lube Oil System unit in Turbine

Hall Unit 2

The following hazards shall be protected by automatic water-foam(High expansion ) system :

• 09SGF06/07 Automatic Water Foam Protection on B06 Bunker Bay

2.6.2 EQUIPMENT DESCRIPTION

For the number of components see material list sheets 49 - 50

For components features see DATA SHEET doc. CNK09---E30DS201

2.6.3 SYSTEM DESCRIPTION AND OPERATION

For system description and operation see the following document:

P&I DIAGRAM 100CNK09MSGAFD005Block Diagram 150CNK09MCYETD001Typical Logic Diagram 150CNK09MCYELD001Lay out drawings see documents list item 2.1.5

Page 39: Fire Fighting
Page 40: Fire Fighting
Page 41: Fire Fighting

1. ASME Code Pressure Vessel2. Flexible, nylon reinforced elastomeric

concentrate bladder3. Concentrate controller(s) (as required priced

separately)4. Sight gauge5. Vent Valves6. Water inlet7. Fill cup (included with AFFF only)8. Water drain/fill valve9. Concentrate filling/drain valve10. Total discharge pipe11. Thermal relief valve (see instructions)12. Concentrate control valve13. Release line

1

2

10

4

9

8

5

6

5 11

3

7

FLOWCONCENTRATE

WATERSUPPLY

WATERTO TANK

1213

Page 42: Fire Fighting

CCS FILLING SEQUENCE

Before starting the fill procedure, attach the following:

a. 3/4" clear, flexible hose to valve no. 4 and terminate in a 55 gallon (200 liter) barrel

b. Water source to valve no. 6 (garden hose).

Refer to the appropriate concentrate schematic for valve description.

Step 1: Close all valves except No.’s 4, 5, 6, and 7, and fill line master shut-off Valve No. 9, WHICH MUST BE OPEN.

Step 2: Fill the shell with water through Valve No. 6 (do not exceed 25 PSIG water pressure) until a steady full flow occurs from Valve No. 4. DO NOT CLOSE VALVE NO. 4 WITH LINE WATER PRESSURE ON VALVE NO. 6. CLOSE VALVE NO. 6, THEN CLOSE VALVE NO. 4.

Step 3: Check for water at Valve No. 7. If water has appeared, and if water flow continues, consult the CCS supplier before proceeding. If no water appears, proceed to next step.

Step 4: Close Valve No. 7.

TECHNICAL DATA

5

9

3

7

Clear FlexibleHose

55 GallonBarrel

2

41

6

Collapsed Bladder

8

CCS FILLING SEQUENCE

March 4, 1998 Foam 830h

Page 43: Fire Fighting

Step 5: Connect air source to Valve No. 5 (see Figure No. 1 and Figure No. 4) and fill bladder with air (10 PSI maximum) through Valve No. 5 while displacing waterthrough Valve No. 4. Continue until 25% of the water volume (10% for a horizontal unit) has been displaced.

Water volume is to be measured with the 55 gallon (200 liter) drum.

Step 6: When the required water volume has been displaced, close 1/4" shut-off valveon the regulator to trap air inside the bladder, disconnect the air supply, and close Valve No. 4.* Remove the air regulator.

A 10 PSI (0.7 BAR) air bubble has now been formed within the bladder. This liftsthe excess bladder material off the bottom of the vessel, allowing for uniform expansion of the bladder as the concentrate is pumped in.

Step 7: Prime and connect the concentrate pumping apparatus (see Figure No. 2 and 4)and to Valve No. 7, as shown above. Use a Centrifugal Pump or Pneumatic Operated Diaphragm Pump.

Step 8: Remove the water hose from the 55 gallon (200 liter) drum, and terminate to drain.

Step 9: Start the concentrate pump, open Valve No. 4, then Valve No. 7, pumping concentrate into bladder.

*If Valve No. 4 is left open at this point, water will continue to flow out, reducingthe pressure in the bladder.

TECHNICAL DATA CCS FILLING SEQUENCE

March 4, 1998Foam 830i

5

9

3

7

Clear FlexibleHose

55 GallonBarrel

2

41

6

8

Centrifugal Pump(See Schematic

Figure 2)

Page 44: Fire Fighting

The concentrate displaces the shell water. If tank pressure steadily decreases, it will benecessary to partially close Valve No. 4 to slow down the discharge of water. If tankpressure steadily increases, it will be necessary to partially (or fully) open Valve No. 4 toallow the pressure to drop back to 10 PSI (0.7 BAR). Slowing the pump discharge will alsolower the tank pressure.

When approximately 75% of the nominal charge has been attained, (90% for horizontaltanks), shell water will stop flowing and the tank pressure will begin to exceed 10 PSI (0.7BAR).

Step 10: Partially open 1/4" shut off at Valve No. 5 to vent and slowly allow air pressure todrop to 0 PSI while continuing to pump the concentrate to the rated capacity.

IMPORTANT: IF CONCENTRATE OVERFLOWS FROM VALVE NO. 5, DRAIN BACKSEVERAL GALLONS TO ALLOW FOR EXPANSION OF AGENT. FILL ONLY TO RATEDCAPACITY! OVERFILLING MAY DAMAGE THE BLADDER!

Step 11: Close Valve No. 7, shut off the pump, and remove 1/4" valve and gaugeassemble from Valve No. 5.

SIGHT GAUGE PROCEDURE

Step 12: Open Valves No. 3 and No. 9, and allow sight gauge to fill. Mark level for futurereference. Close sight gauge valves No. 3 and No. 9 and drain concentrate fromtube by opening valves No. 7 and No. 3. (Note: Make sure all pressure is ventedoff from valves 4 & 5 before opening sight gauge valve No. 3). After concentrate is completely drained, close valve No.’s 3 and 7.

TECHNICAL DATA

5

9

3

7

Clear FlexibleHose

To Drain

2

41

6

8

CCS FILLING SEQUENCE

March 4, 1998 Foam 830j

Concentrate

Page 45: Fire Fighting

SHELL WATER REFILL PROCEDURE

The installed bladder tank will be either normally pressurized or non-pressurized, dependingupon the type of system (wet or deluge), and the piping design. If pressurized, refer to Steps13-18; if non pressurized, refer to Steps 13 and 19-21.

NOTE: IN MOST INSTALLATIONS, THE PIPING DESIGN REQUIRES THE TANK TOBE NORMALLY PRESSURIZED. IF SO, FOLLOW STEPS 13-18. SHOULD THERE BEQUESTIONS CONCERNING WHEN OR HOW TO PRESSURIZE THE TANK, CONTACTTHE DESIGN ENGINEER OR VIKING.

Step 13: Attach a water supply hose to Valve No. 6 and the clear flexible hose to ValveNo. 5. Terminate the clear hose into a 5 gallon bucket (see Figure No. 6)

TECHNICAL DATA SHELL WATER REFILL PROCEDURE

March 4, 1998Foam 830k

5

3

7

5-GallonBucket

2

41

6

10

Concentrate

WaterSupply

Page 46: Fire Fighting

NORMALLY PRESSURIZED

Step 14: Close all valves except for No. 4 and No. 5.

Step 15: Open Valve No. 6 (allowing water into the shell) until water overflows from ValveNo. 4 and concentrate overflows from Valve No. 5. Close Valve No.’s 4, 5, and 6.

Step 16: Carefully and partially open Valve No. 2 to allow water from the main supply toenter tank and equalize to line pressure. When pressurized, open valve to full.

VERIFY AUTOMATIC VALVE NO. 8 IS CLOSED!

Step 17: Open Valve No. 1. Place all valves in normal position. Install all lock pins inproper locations (refer to "Valve Descriptions" on page V830d)

Step 18: Inspect for piping leaks and correct, as necessary.

NORMALLY UN-PRESSURIZED

Step 19: Close all valves except for Valve No.’s 4 and 5.

Step 20: Open Valve No. 6 (allowing water into shell) until water overflows from ValveNo. 4. Close Valve No. 6, then Valve No.’s 4 and 5.

VERIFY AUTOMATIC VALVE NO. 8 IS CLOSED (IF VALVE NO. 8 IS USED)!

Step 21: Open Valve No.’s 1 and 2.*

*There should be no water pressure on the tank. Lock all valves in proper locations (referto "Valve Descriptions" on page V850f).

TECHNICAL DATASHELL WATER REFILL

PROCEDURE

March 4, 1998 Foam 830l

Page 47: Fire Fighting

CONCENTRATE LEVEL CHECK

AFFF LEVEL CHECK (Refer to Schematic on Page V830d)

Step 1: Close Valve No.’s 1 and 2 to isolate tank.

Step 2: Attach a hose to Valve No. 6 and terminate to drain. Be aware that the tank maybe under pressure.

Step 3: Open Valve No. 6 carefully to relieve pressure. Once pressure is relieved, fullyopen Valve No. 6, draining water from the shell, then slowly vent Valve No.’s 4 and 5.

Step 4: After the water has completely stopped draining, open Valve No.’s 3 and No. 9.Observe sight gauge level (Figure 7).

a. If the level is normal, follow the "Shell Water Refill Procedure" on page V830l..

b. If the level is below normal, add concentrate (per the "Refill Procedure" on page V830l),to the desired level. Again, follow the "Shell Water Refill Procedure" on page V830l.

c. Close Valve No.’s 3 and 9. Drain concentrate from the level gauge by closing Valve No. 9 and open slowly Valves No. 7 and No. 3.

Step 5: After concentrate is completely drained, close valve No.’s 3 and 7.

ATC CONCENTRATE LEVEL CHECK (Refer to Schematic on Page V851f)

Steps 1-3: The same as above.

Step 4: When water has completely stopped draining, open Valve No.’s 9 and 3. Observe the sight gauge level (because of the thick viscosity of ATC, allow time for level to rise).

Step 5: Repeat (a) and (b), as above.

d: Drain concentrate from the level gauge by closing Valve No. 9, then slowly open Valve No.’s 7 and 3 (Figure 7).

Step 6: After concentrate is completely drained, close ValveNo.’s 3 and 7.

NOTE: BECAUSE OF THE THICK VISCOSITY OF ATC FOAM, THE SIGHT GLASS MAY NOT ACCU-RATELY MEASURE THE LEVEL. TO DETERMINE THE AMOUNT OF CONCENTRATE INSIDE THE UNIT,CONTINUE TO FOLLOW THE PROCEDURE ON "CONCENTRATE LEVEL CHECK," BUT MEASURE THEAMOUNT OF WATER DRAINED FROM THE SHELL.

EXAMPLE: THE DESIGNED CAPACITY OF A 6000 HORIZONTAL UNIT IS 6000 LITERS, THE ACTUALCAPACITY IS 6300 LITERS. IF 600 LITERS OF WATER IS DRAINED FROM THE SHELL, 5700 LITERSOF CONCENTRATE REMAIN. CONSULT VIKING FOR ACTUAL CAPACITIES OF TANKS.

TECHNICAL DATA CONCENTRATE LEVELCHECK

March 4, 1998Foam 830m

Figure 7

93

7

Page 48: Fire Fighting

REFILL PROCEDURE - 50% OR MORE DISCHARGED

This method is to be used when the tank has been isolated from the system water drainedfrom the shell and 50% or more of the nominal tank volume has been discharged anddetermined. See page 830m for instructions on concentrate level check.

Refer to page 830g for the schematic on pumping apparatus.

Step 1: Close Valves No. 1, 2, 3, 6 and 7.

Step 2: Fill the tank with water through Valve No. 6 until water flows from Valve No. 4 and/or concentrate from Valve No. 5. Close Valve No.’s 5 and 6.

Step 3: Proceed with "CCS Filling Procedure" on page 830e-f, Steps 5 through 21.

REFILL PROCEDURE - LESS THAN 50% DISCHARGE

This method is to be used when less than 50% of the nominal tank volume has been dischargedand determined. See page 830m for instructions on concentrate level check.

Step 1: Close Valve No.’s 1 and 2, (isolating the tank from the system), and 3.

Step 2: Open Valve No.’s 4, 5, and 6 and fill line master (No. 9).

Refer to page V851c for the schematic on pumping apparatus.

Step 3: Attach a 3/4" clear flexible hose to Valve No. 5 and terminate into a 5 gallon bucket.

Step 4: Prime and connect the pumping apparatus to Valve No. 7. Start the pump, open ValveNo. 7, and pump concentrate to the rated capacity.*

Step 5: Refer to "Sight Gauge Procedure" (page 830m) and "Shell Water Refill Procedure" on page 830k-l.

AFFF FILL CUP PROCEDURE

This method can be used to add small volumes of AFFF concentrate. It is not recommended forinitial filling of the tank or for ATC foams.

Step 1: Close all valves. Slowly open Valve No. 4 to relieve pressure. Open Valve No. 6 to drain.

Step 2: Open Valve No.’s 3, 5 and 9. Observe liquid level in sight gauge.

Step 3: Attach fill cup to valve No. 5. Add concentrate via fill cup to required level.*

Step 4: Close all valves and proceed to "Shell Water Refill Procedure." Drain sight gauge and remove fill cup.

*IMPORTANT! IF CONCENTRATE OVERFLOWS FROM VALVE NO. 5, DRAIN BACKSEVERAL GALLONS TO ALLOW FOR EXPANSION OF AGENT.

FILL ONLY TO RATED CAPACITY!

TECHNICAL DATA REFILL PROCEDURE

March 4, 1998 Foam 830n

Page 49: Fire Fighting
Page 50: Fire Fighting
Page 51: Fire Fighting

8. FIRE DETECTION AND ALARM SYSTEM

8.1 GENERAL (KKS Code CYE)

The primary purpose of the system is to give an early warning of dangerousconditions to occupants enabling them to evacuate the building or area safely.

The equipment provided shall consist of Manual Call Points, Automatic Detectorsand Alarm Sounders.

The system shall be able to raise the alarm both locally, to warn occupants andremotely to allow the designated Fire Brigade, to take appropriate action.

All zone circuits of Manual Call Points, Detectors and Sounders shall beconnected by Hardwiring to the Local Fire Control Panels of area supervised:

• LFCP-1 for Power Block Area• LFCP-2 for Fuel Oil Area• LFCP-3 for Coal Yard Area• LFCP-4 for G01 Area• LFCP-5 for D16 Area

The LFCP's shall be equipped with a number of lines able to connect the expectedfield mounted devices, in order to provide fire detection indication .

The LFCP4 shall be connected by Fiber Optic cable to the DCS Located in B05CCR and from the DCS to the Fire Alarm Control Panel (FACP) located in thesame CCR.

The LFCP-5 shall be connected by hardwiring to the LFCP-3

The LFCP-1,LFCP-2,LFCP-3 shall be connected by Addressable Analoguesystem single Line Control Loop (SLC) to the Fire Alarm Control Station (FACS)located in Fire Station Building (K05) .FACS will supervise all the alarm lines andsupervises the sequence of discharge of fixed extinguishing systems

The FACS shall be connected to the Fire Alarm Control Panel (FACP) evenlocated in Control room

The FACP shall be provided with synoptic panel with LED and mimic showing thetopographical plant layout and reporting by LED the status :

- Fire- Fault- System Discharge

of each fire alarm system of in each area of the Plant or room of the Building

Page 52: Fire Fighting
Page 53: Fire Fighting
Page 54: Fire Fighting

8.3.5 FIRE CONTROL AND ALARM PANELSFire Control and Alarm Panels shall be subdivided in:

8.3.6.1 Local Fire Control Panel (LFCP)

• LFCP-1 for Power Block Area• LFCP-2 for Fuel Oil Area• LFCP-3 for Coal Yard Area• LFCP-4 for G01 Area• LFCP-5 for D16 Area

8.3.6.2 Fire Alarm Control Station (FACS) (Located in Fire Station BuildingK05)

The FACS shall be connected by addressable Single Line Control(SLC)Loop to the LFCP-1;LFCP-2 and LFCP-3.The Function of the FACS shall be:

- Continuous monitoring of the Fire Alarm lines- Continuous supervising of the Fire Alarm lines for fault due to: short

circuit, breaking or earthling leak.- Supervising of automatic actuation release of fixed extinguishing

systems and manual actuation of fixed extinguishing systems release.- Transfer to the Fire Control Panel (FACP)all the signal display of:

• Fire Alarm• Fault• System Released• Fire Pump running

- Receive and Transfer to the FACP hardwired signals of:• Fire Alarm• Fault• System Released• Fire Pump runningcoming from the Logistic Buildings:K09,K05,K01,K02,K03,K16 andK04 )

- Supervise and actuate the HVAC shutdown in case of Fire Alarm

8.3.6.3 Fire Alarm Control Panel (Located in Control Room)

The FACP shall connect by single addressable loop the FACSFACS will transmit all the fire alarms, faults and intervention signals comingfrom the detection system of the area zone supervised by relevant LFCP.

A synoptic mimic mosaic type reproducing in schematic form the area plantshall be connected to the FACP by redundant serial link for a clearunderstanding of the area in alarm

Pump management signals and some general alarms shall be made available asSPDT contacts in the FACP terminal box to be reported by others to DistributedControl System located in Electrical and Control Building.

Page 55: Fire Fighting
Page 56: Fire Fighting

8.3 EQUIPMENT MAIN CHARACTERISTICS

8.3.1 MANUAL CALL STATIONS

Manual call Stations shall be provided to allow the manual initiation of analarm of fire and shall be of the type operated breaking a frangible front.

The stations shall be of cast steel and painted red with lettering "FIREDELUGE" in the English language for the deluge systems and "FIRE" for allthe other systems

Where required, to satisfy the hazardous area classification, explosionand/or flameproof call points shall be provided and the enclosure shall becertified for installation in such area.

8.3.2 OPTICAL SMOKE DETECTORS

Optical smoke detectors shall be used in areas to sense level of smoke andproduct of combustion.

Detector shall have a built -in alarm and indicating lamp flashing when thedetector is in service and a built-in reset switch.

Smoke detectors shall be connected themselves to form a loop andarranged in cross- zone.

8.3.3 POINT TYPE RATE OF RISE HEAT DETECTOR

Heat detector shall be a combination of self-restoring and rate of rise.

Where required, to satisfy the hazardous area classification, an enclosureshall be certified for installation in such area.

Heat detectors shall be connected themselves to form a loop.

8.3.4 ALARM SOUNDER AND SIREN

8.3.4 a Alarm Sounder

The unit is an electronic sounder horn to provide acoustical fire warningsignal to alert the people

The alarm devices shall be provided in different areas of the plant to givewarning of fire to the personnel.

The sounder shall be capable to reach a sound level of 95 dB(A) at 1 m.and shall be distinctive from any other sound produced by other alarmdevices.

8.3.4 b Siren

N°2 Siren shall be provided in the top of the roof of the :- B01 Boiler (CFB)- B05 Common Electrical

The sound level emitted by the siren shall be heard in any point of the plantup to 3 km .

Page 57: Fire Fighting
Page 58: Fire Fighting

9. PORTABLE FIRE EXTINGUISHERS

A range of extinguishers has been provided both portable and mobile. portableextinguishers are hand held to be directed at the bone of the fire. Mobileextinguishers are on a trolley; these are suitable for protecting large industrialrisk.

9.1 WATER-FOAM EXTINGUISHERS WITH TROLLEYWater-Foam Extinguishers with trolley : Suitable for Class A and Class B fires(flammable liquids such as petrol, oil, solvents and paints). AFFF(Aqueous Film Forming Foam) provides “burnback” resistance - givingprotection against re-ignition. Minimum capacity:100 l with Nitrogen cartridge .

9.2 PORTABLE DRY POWDER EXTINGUISHERSPortable Dry Powder Extinguishers: Dry Powder Extinguishers are suitable fora wide range of environments and safe for use on risks involving electricalequipment. Powder Extinguishers give a rapid knock down of the fire. Class A,B and C. Minimum capacity: kg.6

9.3 PORTABLE CO2 EXTINGUISHERSPortable CO2 Extinguishers: The CO2 extinguisher is suitable for fighting ClassB fires as well as fires involving live electrical equipment. Minimumcapacity:Kg5

9.4 PORTABLE BOTTLE CARRIER OF DRY POWDEREXTINGUISHERSN°1 Portable bottle carrier of dry powder extinguisher with capacity of 6 bottles(each bottle of 12 Kg ) shall be provided

Page 59: Fire Fighting

Fire fighting system

Safety rules if fire cannot becontrolled

l Contained room/area

l Evacuate the building

l Call the firemen

Procedures in case of fire

Page 60: Fire Fighting
Page 61: Fire Fighting
Page 62: Fire Fighting
Page 63: Fire Fighting