Page 1: Variable Speed Heat Pumps

Variable Speed Heat PumpsProvisional UES Proposal Presentation

to the Regional Technical Forum

September 18, 2012

Presentation by Kacie Bedney, Bonneville Power

Elizabeth Daykin, Bonneville PowerBen Larson, Ecotope

Page 2: Variable Speed Heat Pumps

2

Overview

Heat pump measures’ applicability clarified to exclude variable speed heat pumps (VSHP) at May 2012 RTF meeting

83 VSHP systems reported to BPABPA is conducting research to establish

savings for this measure

Page 3: Variable Speed Heat Pumps

3

Measure Summary

• Measure name: Variable Speed Heat Pumps

• Measure Sponsor: BPA

• Measure description:–Installation of high efficiency variable speed air source heat pumps to replace an electric forced air furnace. 12 HSPF / 18 SEER

• Requesting Status: Provisional

Page 4: Variable Speed Heat Pumps

Measure Classification

4

Measure Classification and Properties Upgrades Conversions

Market Sector Residential Residential

Market SegmentSingle Family Homes - New & Existing Construction Single Family Homes - New & Existing Construction

Measure Category HVAC HVAC

Measure Description

Installation of high efficiency variable speed air source heat pumps to replace a single or dual speed air source heat pump.

Installation of high efficiency variable speed air source heat pumps to replace an electric forced air furnace.

Sunset Criteria April 2014 April 2014

Primary Workbook PROPOSED_Res_SF_VSHP_Upgrade_v0.xlsm PROPOSED_Res_SF_VSHP_Upgrade_v0_ed.xlsm

Linked Workbooks No external links No External links

Number of Measures, and UES Components

18 upgrade measures for single-family (new and existing construction) for 3 heating and 3 cooling zones with one UES component each.

36 forced-air furnace conversion measures for single-family (new and existing construction), with and without existing air conditioning, for 3 heating and 3 cooling zones with one UES component each.

Page 5: Variable Speed Heat Pumps

Measure Identifiers

5

Identifier Possible Values Further Explanation and SourcesConstruction Type New or Existing construction

Climate Zone (Heating) Heating zones 1, 2, & 3 Heating zones 1, 2, & 3 are based on the following weightings of SEEM results for 5 citiesZone 1: Portland 20% Seattle 50% Boise 15% Kalispell 0% Spokane 15%Zone 2: Portland 0% Seattle 0% Boise 10% Kalispell 5% Spokane 85%Zone 3: Portland 0% Seattle 0% Boise 0% Kalispell 100% Spokane 0%From: ExistingResidentialSingleFamily_SEEMRuns_03.xlsm

Climate Zone (Cooling) Cooling zones 1, 2, & 3 Cooling zones 1, 2, & 3 are based on the following weightings of SEEM results for 5 citiesZone 1: Portland 5% Seattle 80% Boise 0% Kalispell 15% Spokane 0%Zone 2: Portland 35% Seattle 0% Boise 10% Kalispell 0% Spokane 55%Zone 3: Portland 0% Seattle 0% Boise 100% Kalispell 0% Spokane 0%From: ExistingResidentialSingleFamily_SEEMRuns_03.xlsm

Measure Identifiers

Page 6: Variable Speed Heat Pumps

Baseline Specifications

Two baseline HVAC systems:•Electric Forced Air Furnace - w/ and w/o AC•ASHP - 8.5 HSPF 14.0 SEER−PTCS controls, commissioning, and sizing in base

Three building types (weighted):•1,344 ft2 single-story ranch house (5%)•2,200 ft2 split-level house (67%)•2,688 ft2 house with basement (28%)

6

Page 7: Variable Speed Heat Pumps

Baseline Specifications Cont’d

Last measure in – existing houses weatherized, lighting upgraded• Same characteristics as those used for GSHP analysis• http://www.nwcouncil.org/energy/rtf/measures/res/archive/ResGSHP_v2_1.xlsm 7

House CharacteristicsComponent: New Existing (Fully Wx)Ceiling* R-38 R-38Wall R-21 2"x6" R-13 2"x4"Window U-0.29 U-0.29Floor* R-30 R-30Infiltration 6 ACH50 7 ACH50Supply Duct Leak Fraction 6% 6%Return Duct Leak Fraction 3% 3%Supply Duct R-Val 8 6Return Duct R-Val 8 6Lighting 0.8 W/ft^2 0.8 W/ft^2*Cel ing and fl oors in retrofi t case have s l ightly lower U-va lues than new construction due to larger void spaces in Wx

Page 8: Variable Speed Heat Pumps

VSHP Performance Model: SEEM Ecotope developed based on the Carrier

Corporation 25VNA InfinityTM VSHP • HSPF 12, SEER 18• Product specification sheet provides: input power and

output capacity at 10°F increments for both min & max indoor air handler flow−Min and max inputs and outputs

• Previous work basing performance model from spec sheet data suggests assessment is likely optimistic - field & lab work needed.

8

Page 9: Variable Speed Heat Pumps

Carrier Spec Sheet Data

9

Page 10: Variable Speed Heat Pumps

Curve Fits

Performance curve fitted to spec sheet data using regression techniques

• Input = ƒ(Tout, Trp, CFM)

• Output = ƒ(Tout, Trp, CFM)

Currently, no cooling curve fit. Cooling improvements assumed to occur in proportion to heating improvements.

10

Page 11: Variable Speed Heat Pumps

Variable Capacity Considerations: Controls & Airflow

Assert HP controller follows house load• Assert it is similar to observed DHP behavior• Ex: If VSHP runs for 45 mins at full output for 1 hour, in

the next hour it runs at 75% output for 1 hour.

Airflow is a function of capacity and changes every hour within simulation• Duct losses vary with varied airflow• This model shows ~5% increase in duct losses over a

single speed system

11

Page 12: Variable Speed Heat Pumps

Example Simulation Output

2200ft2 house with UA= 475 Btu/hr-F•Heat pump size = 3 tons

Eugene, OR climate. January 10-11.

12

Page 13: Variable Speed Heat Pumps

13

Page 14: Variable Speed Heat Pumps

14

Higher duct losses for VSHP when operating at lower airflows requires more overall heat output

Higher COP for VSHP system requires less energy input

Capacity changes based on load.Min capacity is ~40%

Page 15: Variable Speed Heat Pumps

Measure Cost Summary

15

Baseline costs for upgrade and conversion rely on air-source heat pump analyses

VSHP costs are from customer invoices•Upgrade $2,851 incremental cost•Conversion incremental cost−FAF w/ CAC $5,616−FAF w/o CAC $6,975

Page 16: Variable Speed Heat Pumps

Measure Life Summary

Measure life of 20 years•Available default EUL

16

• Sunset Criteria:

– Measure shall sunset at the end of 2014, at which time the field work and lab

testing results will inform updated SEEM runs

Page 17: Variable Speed Heat Pumps

Cost Effectiveness

17

Existing Construction

New Construction

Existing Construction

New Construction

Existing Construction

New Construction

1 1 0.70 0.60 2.00 1.50 1.50 1.10

1 2 0.80 0.70 2.00 1.50 1.40 1.00

1 3 0.90 0.70 2.00 1.50 1.30 0.90

2 1 1.10 1.00 2.80 2.10 2.10 1.60

2 2 1.20 1.00 2.80 2.20 2.10 1.60

2 3 1.30 1.10 2.90 2.20 2.00 1.50

3 1 1.60 1.40 3.30 2.50 2.50 1.90

3 2 1.70 1.40 3.30 2.60 2.50 1.90

3 3 1.70 1.50 3.40 2.60 2.40 1.80

Conversion - w/ CACUpgrade Conversion - w/o CAC

HZ CZ

Page 18: Variable Speed Heat Pumps

Checklist

18

1. Introduction and PurposeSponsor(s) Yes Bonneville Power Adminstration

Savings Estimation Method Yes UES

Unit Energy Savings Yes

2. Measure Specification

Measure Identifiers YesSingle family, new and existing construction, for all heating and cooling zones, replacing air-source heat pumps (upgrade) and forced air furnaces (conversion).

Savings Baseline YesCurrent practice: 8.5 HSPF 14 SEER air source heat pump baseline for upgrade measures; conversion from FAF assumes COP = 1.

Implementation Standards Yes Must be installed in accordance with manufacturer specifications.

Product Standards Yes Variable speed compressor and air handler with minimum 12.0 HSPF

Page 19: Variable Speed Heat Pumps

Checklist – cont’d

19

3. Unit Energy SavingsProvisional

Sufficient data collection YesData collection underway with laboratory and analysis studies to be completed by December 2013.

UES adopted ? TDB at September 18, 2012 RTF meeting

Sunset criteria ? TDB at September 18, 2012 RTF meeting

Type of Estimation Procedure Yes Calibrated Engineering

Input Parameters YesAll of the input parameters supporting the baseline and efficient case are documented.

Model Calibration Yes Not calibrated to efficient case house but to various other building UAs

UES Components Yes Space heat and cool

Interactions between Measures Yes Interactions with strip heat and duct losses.

Heating/Cooling Interactions Yes Interactions with strip heat, weatherization, duct losses were all considered.

Reliable Baseline Data ?This measure uses the same baseline as single- and dual-speed air-source heat pumps.

Reliable Efficient-case Data ? The efficient case will be substantiated through data collection.

Model Calibration - Baseline YesNot calibrated to baseline case house but to various other building UAs & heating systems.

Model Calibration - Efficient-Case NoNo measured HVAC and house data to date. Will be collected as part of research plan.

Sound Analyses Used ?

3.2.3 Standard for Reliability

Did RTF determine savings were reliable?

Summary Sheet Completed? Yes

Measure Classification and Properties Yes Residential, single family, HVAC.

Measure Identifiers YesSingle family, new and existing construction, for all heating and cooling zones, replacing air-source heat pumps (upgrade) and forced air furnaces (conversion).

Constant Parameters YesConstant parameters for home size, insulation, infiltration, lighting are detailed in the measure workbook.

Estimation Method, Parameters and Sources Yes Described in Measure Workbook

Costs estimated Yes Described in Measure Workbook

Measure Effective Useful Life (years) Yes 20 year RTF default value available and used

ProCost analysis complete Yes

3.4 Documentation

Standard

3.2 Required Quality of Savings

Estimate

3.1 UES Estimation Procedure

Page 20: Variable Speed Heat Pumps

Plan for Data Collection and Analysis – laboratory testing

Lab testing for performance curves Spring/Summer 2013 2-ton outdoor unit, 2 to 3.5 ton indoor unit AHRI ref # 4618711

Tested at high, intermediate and low compressor speeds

Tested over a range of indoor and outdoor conditions (ODT 17 deg – 62 deg)

AHRI steady state heating tests

20

Page 21: Variable Speed Heat Pumps

Plan for Data Collection and Analysis: field test

BPA-led advisory committee Committee to assist in developing:

• method for evaluating the performance• appropriate M&V plan• what data to collect what & how to measure• duration of the tests• number of sites to test

Combine lab and field testing into SEEM model to determine annual estimated savings

Winter 2013

21

Page 22: Variable Speed Heat Pumps

Contacts

BPAKacie Bedney

[email protected]

503.230.4631

EcotopeBen Larson

[email protected]

206.322.3753 x207

22

Stephanie Vasquez

[email protected]

503.230.3492

Page 23: Variable Speed Heat Pumps

RTF Proposed Motion:

“I _________ move that the RTF approve the Residential VSHP UES Measure as Provisional with Active status.”

23


Recommended