The materials included in this compilation are for the use of Dwyer Instruments, Inc. potential customers and current employees as a resource only. They may not be reproduced, published, or transmitted electronically for commercial purposes. Furthermore, the Company’s name, likeness, product names, and logos, included

within these compilations may not be used without specific, written prior permission from Dwyer Instruments, Inc. ©Copyright 2014 Dwyer Instruments, Inc.

Page 2: Universal Handheld Product Family

What is it? Our Model UHH Universal Handheld Base

Unit is a handheld display interface that communicates with probes or modules in order to detect a wide variety of parameters.

Customers for the UHH include Air Balancing Contractors, Building Commissioning Agents, and Building Energy Management Specialist.

Universal Handheld Overview

Page 3: Universal Handheld Product Family

Other Units in the Market

Page 4: Universal Handheld Product Family

What makes it different than our other handhelds or competitors units? The UHH was designed to be the easiest to use and

navigate through the menus.

All probes and modules are available wired and wireless.

Ergonomic Design to fit comfortably in most users hands.

Lowest Price in It’s Class!

UHH vs. other Units in the Market

Page 5: Universal Handheld Product Family

UHH Product Features

Page 6: Universal Handheld Product Family

Series UHH Base Unit Accepts 1 Wired Probe and/or 6

Wireless Probes or Modules

Measures Differential Pressure, Air Velocity, Volumetric Air Flow, Humidity, and Temperature

Internal Memory or External SD Memory Card for Logging Readings

Re-Chargeable Lithium-Ion Battery for Hours of Usage

Full Color OLED Graphical Display Shows Readings as a Meter, Gauge, or Strip Chart

Universal Handheld Features

Page 7: Universal Handheld Product Family

Series UHH Base Unit Menus available in English,

Portuguese, Spanish, German, and Italian

Multiple English and SI engineering units available for each parameter

Ergonomic Shape Fits Most Hands Comfortably

Multi-functional Soft Keys for Easy Navigation

Simple to Use

Universal Handheld Features

Page 8: Universal Handheld Product Family

Languages: English, German, Italian, Portuguese, Spanish.

Temperature Limits: 5 to 125°F (-15 to 51°C); 20 to 125°F (-6 to 51°C) for wireless operation.

Battery Charging Limits: 32 to 113°F (0 to 45°C).

Units Air Velocity: FPM,

MPH, KN, M/H, M/S K/H, FPS.

Units Flow: CFM, M3/HR, M3/S, GPM, GPH, GPD, LPS, LPM, LPH.

Units Temperature: °F, °C.

Resolution: 1 FPM, 0.1 MPS, 0.1 CFM & M3/HR; 0.1°F & °C; RH 0.1%.

Display: OLED, color 240 x 320.

Housing: Thermoplastic elastomer over polycarbonate.

Power Requirements: 3 V BR1225 lithium ion battery.

Wireless Distance: 50' (15 m).

Universal Handheld Specifications

Page 9: Universal Handheld Product Family

Series WDPM Measures Differential

Pressure, Static Pressure, Air Velocity, and Volumetric Air Flow

Fits in Rear Pouch of UHH

Available Magnetic Surface Mount Bracket

Push Button Logging

Differential Pressure Modules

Page 10: Universal Handheld Product Family

Ranges: 0 to 500 Pa up to 0 to 87 Kpa

Service: Non-corrosive dry gases

Wetted Materials: Consult factory

Accuracy: ±0.5% FS span @ 25°C

Temperature Limits: Compensated: 32 to 140°F (0 to 60°C) Process/Ambient: 14 to 140°F (-10 to 60°C).

Thermal Effects: ±0.01% FS/°F (±0.02% FS/°C)

Battery Charging Limits: 32 to 113°F (0 to 45°C)

Power Requirements: 3.7 V lithium ion battery

Wireless Distance: At least 50' (15 m)

Connections: Two barbed connections for use with 1/8" (3.18 mm) or 3/16" (4.76 mm) ID tubing

Differential Pressure Module Specifications

Page 11: Universal Handheld Product Family

Model AP1 (Wired) / AP2 (Wireless) Measures Air Velocity,

Volumetric Air Flow, and Temperature

Probe length is 203 mm (8”) and has Metric and English Insertion Markings

Primarily Used for Lower Flow Detection under m/s (200 FPM)

Push Button to Trigger Logging (AP2 Only)

Thermo-Anemometer Probes

Page 12: Universal Handheld Product Family

Temperature Limits:       Process: -20 to 212°F (-29 to 100°C);      Ambient: 5 to 125°F (-15 to 51°C).

Range: ◦ Air Velocity: 0 to 6000

FPM (0 to 30 m/s);◦ Volumetric Air: 999,999

in selected flow units;◦ Temperature: -20 to

212°F (-29 to 100°C).

Accuracy:       Air Velocity: ±3% FS within temperature range of 40 to 90°F (4 to 32°C);      Temperature: ±0.5°F (±0.28°C).

Response Time: 1 s.

Probe Length: 8" (203 mm) insertion.

Weight: 12.8 oz (378.54 g).

Thermo-Anemomter Probes Specifications

Page 13: Universal Handheld Product Family

Model RP1 / RP2 Thermo-Hygrometer Probe Measures humidity, dew

point, wet bulb temperature, and temperature

Field replaceable 2% accurate sensor and filter

Probe length is 203 mm (8”)

Thermo-Hygrometer Probes

Page 14: Universal Handheld Product Family

Service: Clean air.

Temperature Limits: Process: -40 to 176°F (-40 to 100°C)Ambient: 5 to 125°F (-15 to 51°C)

Range: RH: 0 to 100% (non-condensing)Temperature: -20 to 140°F (-29 to 60°C)

Accuracy: RH: ±2% @ 25°C (10 to 90% RH) ±4% @ 25°C (0 to 10, 90 to 100% RH)Temperature: ±0.54 @ 77°F (±0.3 @ 25°C).

Response Time: 1.5 s Probe Length: 8" (203

mm) insertion

Thermo-Hygrometer Probe Specifications

Page 15: Universal Handheld Product Family

VP1 / VP2 100 mm Vane Thermo-Anemometer Measures air velocity,

volumetric air flow, temperature, and humidity

Probe length is 203 mm (8”)

Used to measure the air flow at supply and return air registers

100mm Vane Thermo-Anemometer Probes

Page 16: Universal Handheld Product Family

Air Velocity: ◦ Range: 40 to 5000 fpm

(0.2 to 25 m/s)◦ Accuracy: ±1.5% of

reading ±20 to 60 fpm (±0.1 to 0.3 m/s) (Reading Dependent)

◦ Response Time: 1 s

Temperature:◦ Range: -4 to 140°F (-20 to

60°C) ◦ Accuracy: ±0.54 @ 77°F

(±0.3 @ 25°C)◦ Response Time: 1.5 s

Relative Humidity: ◦ Range: 0 to 100% RH◦ Accuracy: ±2% @ 77°F (25°C)

(10 to 90% RH); ±4% (0 to 10% and 90 to 100%)

◦ Response Time: 1.5 s

Air Volume:◦ Range: 999,999 in selected

units◦ Response Time: 1 s.

Vane Material: Anondized aluminum.

Probe Length: 8" (203 mm) insertion.

100mm Vane Thermo-Anemometer Probe Specifications

Page 17: Universal Handheld Product Family

UHH Operation

Page 18: Universal Handheld Product Family

Press and release the Enter Key in the center of the directional pad to turn on the UHH

Holding down the Enter Key will turn off the UHH

Wired Probes will power on and off with the base unit

Wireless Probes will be turned on and off with the button on the probe handle

Powering Up UHH

Page 19: Universal Handheld Product Family

Use the Left and Right Directional Arrows to highlight the Probe Menu at the top of the display and press the Enter Key

Use the Down Directional Arrow to select Pairing Mode and press the Enter Key

Turn on the wireless probes to be paired

Highlight the desired probes and press the Enter Key

Pairing Wireless ProbesProbe Menu

Pairing Mode

Page 20: Universal Handheld Product Family

Using the Left Multi-Function Key, select the desired parameter

Except for volumetric flow, the Right Multi-Function Key will cycle through the available engineering units

For volumetric flow, the Right Multi-Function Key will enter the Settings Menu and the engineering units can be selected in the units sub-menu

Changing Engineering Units

Adjust UnitsSelect Parameter

Page 21: Universal Handheld Product Family

Maximum, minimum, and average statistics are available for each parameter

Press the Left Multi-Function Key until Display appears

Press the Center Multi-Function Key to toggle between the current and statistics views

Viewing Statistics

Select DisplayToggle Between Statistics and Current

Page 22: Universal Handheld Product Family

Logging can be set to be over a time duration or can be single value at a time

Logging can start by an event or by manually pushing the button on the UHH or the probe

Press the Left Multi-Function Button until Log is displayed

Press the Center Key to enter the Log Settings or the Right Key to trigger the Log to start

Logging Measurements

Select Log Access Log Settings

Start Log

Page 23: Universal Handheld Product Family

Using the Left Multi-Function Key, select the desired parameter

In order to change between differential pressure, air velocity, and volumetric air flow, press the Center Multifunction Key

Dew point and wet bulb selections are located as humidity engineering units

Changing Mode of Operation

Select Parameter

Select Mode of Operation

Page 24: Universal Handheld Product Family

Parameters can be displayed as a meter, gauge, or strip chart

When gauge is selected, a color band can be added to the display

Use the Left and Right Directional Keys to select the View Menu at the top of the display

Use the View sub-menu to select the display format

Changing Display Formats

Select the Format in the View Sub-Menu

Select View Menu

Page 25: Universal Handheld Product Family

Please contact Dwyer Instruments, Inc. with any questions you may have regarding the Model UHH Universal Handheld Test Instrument or any of our products at:

◦ Website www.dwyer-inst.com◦ E-mail [email protected] ◦ Phone 1.800.872.9141

Questions?